0% found this document useful (0 votes)
176 views112 pages

TFP GPC Asia Pacific Middle East 11 19

Uploaded by

Daniel Ctes
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
176 views112 pages

TFP GPC Asia Pacific Middle East 11 19

Uploaded by

Daniel Ctes
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 112

Fire Suppression

General Products Catalog

Automatic Sprinklers
System Valves & Devices
Piping & Electrical Products
Fire Suppression General Products Catalog

FIRE SUPPRESSION
General Products Catalogue
Johnson Controls leads the industry in water-based fire suppression products, offering one of
the broadest product lines globally. Through ongoing, world-class research and development,
we’re continually expanding our capabilities. Our solutions include brands that have led the fire
protection industry for decades — with over 150 years in the industry, we are uniquely qualified
to deliver cost-effective solutions customized to any building configuration and fire protection
application.
The Johnson Controls team is committed to delivering products with dependable performance
that have received independent approvals and certifications from industry agencies globally. Our
state-of-the-art, international manufacturing facilities have all been granted ISO 9000 approvals
and are routinely audited by independent testing agencies for quality and conformance. We also
participate in many committees and several international standards and code-making bodies.
Johnson Controls fire suppression offering includes leading brands from across the fire protection
industry with decades of industry knowledge and expertise. The brands leverage the global reach
of Johnson Controls to bring customers effective solutions for a variety of applications.

TechXchange Academy
The state-of-the-art TechXchange academy offers on-site and online training courses to equip
students with work-relevant training and on-the-job performance. These solutions, when applied
in the workplace, increase the ability of our graduates to better create value for their organization
and their customers.
It offer various training courses such as Sprinkler Systems, WaterMist System and
SprinkCAD Software.
To learn more, please visit www.onlinetechxchange.com

10 Year Limited Warranty


We have the unique distinction of standing behind the fire suppression products we manufacture
by offering a 10 year limited warranty. This exhibits our commitment to product quality
worldwide. Please see the General Terms and Conditions of Sale at www.tyco-fire.com.

Click on the brands to find out more.

2
TABLE OF CONTENTS
AUTOMATIC SPRINKLERS
Standard Spray Sprinklers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 – 9
Extended Coverage Sprinklers . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 – 17
Storage Sprinklers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 – 28
RAPID RESPONSE® Sprinklers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 – 36
Dry Sprinklers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 – 43
Special Purpose Sprinklers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 – 54
Sprinkler Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 – 57
Nozzles & Nozzle Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 – 64

SYSTEM VALVES & DEVICES


Wet System Valves & Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 – 68
Dry System Valves & Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 – 72
Deluge & Preaction Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 – 78
General Purpose Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 – 84
Specialty Items & AQUAMIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 – 90

PIPING & ELECTRICAL PRODUCTS


GRINNELL® Grooved Piping Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 – 96
CPVC Pipe & Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 – 99
Electrical Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 – 107

SprinkCAD
Software Suite Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

Index
Model Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Keyword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 – 111

All metric measurements throughout this catalog are based on U.S. standard-to-metric conversions.
Metric specifications may vary from country to country.

www.tyco-fire.com 3
Standard Spray Sprinklers
Offered in a wide range of standard and quick response options for light and ordinary hazard occupancies.
-- Office Buildings -- Theaters

-- Schools -- Banks

-- Libraries -- Retail

4
www.tyco-fire.com

Standard Spray Sprinklers


TY-B
Upright, Pendent, & Recessed Pendent
K Factor K=2.8 (40,3) • K=5.6 (80,6) • K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT


K=2.8 – UL, C-UL, FM, NYC
Approvals K=5.6 – UL, C-UL, FM, CE, VdS
K=8.0 – UL, C-UL, FM, NYC, LPCB, VdS
57°C (135°F), 68°C (155°F), 79°C (175°F),
Temperature
93°C (200°F), 141°C (286°F), 182°C (360°F), Open

K=5.6 – Style 15, Style 20


Escutcheon
K=8.0 – Style 10, Style 40
Signal White, Pure White, Jet Black, Chrome Plated,
Escutcheon Finish
Natural Brass
Natural Brass, Chrome Plated, Pure White,
Sprinkler Finish Signal White, Jet Black, Poly-Stainless, Lead Coated,
Wax Coated, Wax over Lead Coated
TY1151, TY1251, TY315, TY325, TY4151, TY4251,
SIN
TY4851, TY4951

Wrench Type W-TYPE 6 / W-TYPE 7 (for recessed escutcheons)

Tech Data Sheet K=2.8 & K=8.0 – TFP151 / K=5.6 – TFP152

All hazard • 5 mm bulb • Small frame, narrow profile bulb • Discharges a hemispherical water spray pattern in the area beneath
the sprinkler • Designed for use in light, ordinary, or extra hazard, commercial occupancies such as banks, hotels, shopping malls,
factories, refineries, chemical plants, etc.

Horizontal, Recessed Horizontal Sidewall & Vertical Sidewall


K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, FM, NYC, LPCB

57°C (135°F), 68°C (155°F), 79°C (175°F),


Temperature 93°C (200°F), 141°C (286°F), 182°C (360°F),
Open (HSW TY3351)

Escutcheon Style 10

Signal White, Pure White, Jet Black, Chrome Plated,


Escutcheon Finish
Natural Brass
Natural Brass, Chrome Plated, Pure White,
Sprinkler Finish Signal White, Jet Black, Poly-Stainless, Lead Coated,
Wax Coated, Wax over Lead Coated
SIN TY3351, TY3451

Wrench Type W-TYPE 6 / W-TYPE 7 (for recessed escutcheons)

Tech Data Sheet TFP161

Light hazard/Ordinary hazard • 5 mm bulb • Small frame • Unique deflector design of the horizontal sidewall sprinkler results in
smaller profile • Designed for installation along a wall or the side of a beam just beneath a smooth ceiling • Water discharge is
directed primarily outward and downward in a quarter spherical pattern • Sidewall sprinklers are often used in lieu of standard
pendent or upright sprinklers due to building construction, economic considerations, or aesthetics • Special deflector on the
vertical sidewall sprinkler allows it to be installed in either a pendent or upright position

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 5
Fire Suppression General Products Catalog

Standard Spray Sprinklers


TY-FRB
Upright, Pendent, & Recessed Pendent
K=2.8 (40,3) • K=4.2 (60,5) • K=5.6 (80,6) •
K Factor
K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT

K=2.8 – UL, C-UL, FM, NYC


K=4.2 – UL, C-UL
Approvals
K=5.6 – UL, C-UL, FM, CE, VdS
K=8.0 – UL, C-UL, FM, NYC, LPCB, VdS

57°C (135°F), 68°C (155°F), 79°C (175°F),


Temperature
93°C (200°F), 141°C (286°F)

K=2.8, K=4.2 & K=8.0 – Style 10 • Style 20 •


Escutcheon Style 30 • Style 40
K=5.6 – Style 15 • Style 20

Signal White, Pure White, Jet Black, Chrome Plated,


Escutcheon Finish
Natural Brass

Natural Brass, Chrome Plated, Pure White,


Sprinkler Finish
Signal White, Jet Black, Poly-Stainless, Lead Coated

TY313, TY323, TY1131, TY1231, TY2131, TY2231,


SIN
TY3131, TY3231, TY4131, TY4231, TY4831, TY4931

Wrench Type W-TYPE 6 / W-TYPE 7 (for recessed escutcheons)

Tech Data Sheet K=2.8 thru K=8.0 – TFP171, K=5.6 – TFP172

Light hazard/Ordinary hazard • 3 mm bulb • Small frame and narrow profile bulb enhance appearance • Hemispherical water spray
pattern in the area beneath the sprinkler • Designed for use in commercial occupancies such as banks, hotels, and shopping malls.

Horizontal, Recessed Horizontal Sidewall & Vertical Sidewall


K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, FM, NYC, LPCB

57°C (135°F), 68°C (155°F), 79°C (175°F),


Temperature
93°C (200°F), 141°C (286°F)

Escutcheon Style 10 • Style 20

Signal White, Pure White, Jet Black, Chrome Plated,


Escutcheon Finish
Brass Plated

Natural Brass, Chrome Plated, Pure White,


Sprinkler Finish
Signal White, Jet Black, Poly-Stainless, Lead Coated

SIN TY3331, TY3431

Wrench Type W-TYPE 6 / W-TYPE 7 (for recessed escutcheons)

Tech Data Sheet TFP176

Light hazard/Ordinary hazard • 3 mm bulb • Designed for use in applications where aesthetics must be considered or where building
construction makes the installation of standard pendent or upright sprinklers impractical • Vertical sidewall sprinkler can be
installed in either the pendent or upright position along a wall or the side of a beam and just below a smooth ceiling

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

6
www.tyco-fire.com

Standard Spray Sprinklers


RFII & RFII-MRI
Concealed Pendent
K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

RFII 3mm= UL, C-UL, NYC, VdS


RFII Approvals RFII 5mm = UL, C-UL, FM, NYC, LPCB
RFII-MRI = UL, & C-UL

68°C/155°F - Sprinkler, 59°C/139°F - Cover Plate


Temperature
93°C/200°F - Sprinkler, 74°C/165°F - Cover Plate

Chrome, Brushed Chrome, Brass, Signal White,


Cover Plate Finish
Grey White, Pure White, Jet Black, Custom

RFII: SR-TY3551, QR-TY3531


RFII-MRI SIN
RFII-MRI: SR-TY3550, QR-TY3530

Wrench Type RFII

RFII: TFP181,
Tech Data Sheet
RFII-MRI: TFP182

Light hazard/Ordinary hazard • 5 mm bulb (standard) 3 mm bulb (quick) • Internally threaded closure with 12,7 mm (1 ⁄ 2") of
adjustment • Concealed in an enclosed escutcheon plate with flat cover for use in those applications where aesthetics is a primary
consideration • Separable, two-piece design of the mounting cup and cover plate allows installation of the sprinklers and pressure
testing of the fire protection system prior to installation of a suspended ceiling or application of the finish coating to a fixed
ceiling • Available with optional dust and air seal • RFII-MRI Non-Magnetic Model Concealed Pendent Sprinkler Quick & Standard
Response, Standard Coverage

ILLUSION™
Concealed Standard Coverage Pendent Sprinklers
K Factor K=11.2 (161,3)

Thread Size 3⁄4" NPT

Approvals UL, C-UL

71°C/160°F - Sprinkler - 59°C/139°F - Cover Plate,


Temperature
100°C/212°F - Sprinkler - 74°C/165°F - Cover Plate

Chrome , Brush Chrome, Brass, Signal White,


Cover Plate Finish
Grey White, Pure White, Custom

SIN TY5521

Wrench Type W-TYPE 18

Tech Data Sheet TFP184

Extra large orifice/Special hazard • Coverage per NFPA 13 • Available with optional dust and air seal • The ILLUSION is concealed
in an enclosed escutcheon plate with flat cover for use in those applications where architecturally sensitive areas such as casinos,
hotel lobbies, office buildings, churches and restaurants

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 7
Fire Suppression General Products Catalog

Standard Spray Sprinklers


TY-L
Upright, Pendent, & Recessed Pendent
K Factor K=5.6 (80,6) • K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL, FM, LPCB

Temperature 74°C/165°F, 100°C/212°F, 138°C/280°F

Escutcheon Style 20 • Style 30

Escutcheon Finish Signal White, Chrome Plated, Brass Plated

Natural Brass, Chrome Plated, Lead Coated,


Sprinkler Finish
Wax over Lead Coated, Wax Coated

SIN TY3111, TY3211, TY4111 TY4211, TY4811, TY4911

Wrench Type W-TYPE 9 / W-TYPE 10 (for recessed escutcheons)

Tech Data Sheet TFP110

All hazard • Solder type • Discharges a hemispherical water spray pattern in the area beneath the sprinkler • Designed for use in
light, ordinary, and extra hazard, commercial occupancies such as banks, hotels, shopping malls, factories, refineries, chemical
plants, etc.

Horizontal Sidewall
K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, FM

Temperature 74°C/165°F, 100°C/212°F, 138°C/280°F,

Natural Brass, Chrome Plated, Lead Coated, Wax


Sprinkler Finish
Coated, Wax over Lead Coated

SIN TY3311

Wrench Type W-TYPE 9

Tech Data Sheet TFP120

Light hazard / Ordinary hazard • Solder type • Suited for hotels, nursing homes and hospitals • Design allows piping to be confined
to corridors, closets or service areas • They are designed for installation along a wall or the side of a beam and just beneath a
smooth ceiling.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

8
www.tyco-fire.com

Standard Spray Sprinklers


TY-FRL
Upright, Pendent, & Recessed Pendent
K Factor K=2.8 (40,3) • K=5.6 (80,6) • K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT

2.8 =UL, C-UL, NYC


Approvals 5.6 =UL, C-UL, FM, NYC, LPCB
8.0 = UL, C-UL, FM, NYC

Temperature 74°C/165°F, 100°C/212°F

1⁄2" NPT - Style 20


Escutcheon
3⁄4" NPT - Style 30

Escutcheon Finish White Coated, Chrome Plated, Brass Plated

Sprinkler Finish Natural Brass, Chrome Plated

SIN TY1121, TY1221, TY3121 TY3221, TY4121, TY4221

Wrench Type W-TYPE 9 / W-TYPE 12 (for recessed escutcheons)

Tech Data Sheet TFP130

Light hazard/Ordinary hazard - light hazard K=2.8 (40,3) • Solder type • Typically used in hotels, motels, office buildings and other
commercial and industrial applications

Horizontal Sidewall
K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, FM, NYC

Temperature 74°C/165°F, 100°C/212°F

Sprinkler Finish Natural Brass, Chrome Plated

SIN TY3321

Wrench Type W-TYPE 9

Tech Data Sheet TFP140

Light hazard/Ordinary hazard • Solder type • Designed for compact installation along a wall or on the side of a beam just beneath a
smooth ceiling • Generally used in lieu of pendent or upright sprinklers because of aesthetics, building construction, where piping
across the ceiling is not desirable.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 9
Extended Coverage Sprinklers
Intended for protection of areas larger than those specified in standard installation rules and specific light,
ordinary and extra hazard occupancies.
-- Office Buildings -- Libraries

-- Hotels -- High-Piled Storage

-- Hospitals -- “Big Box” Retailing

10
www.tyco-fire.com

Extended Coverage Sprinklers


EC-25
Upright
K Factor K=25.2 (362,9)

Thread Size 1" NPT or ISO 7-R1

Approvals UL, C-UL, FM, NYC

Temperature 74°C/165°F, 100°C/212°F

Sprinkler Finish Natural Brass

SIN TY9128

Wrench Type W-TYPE 1

Tech Data Sheet TFP213

For use in high density applications such as “big box” retailing, extra hazard, and high-piled storage occupancies • Solder type •
CMDA and CMSA Applications and FM Approved for storage and non-storage applications • Minimum operating pressure of 0,48
bar (7 psi) • The maximum coverage area per sprinkler is 18,2 m² (196 ft.²), which is almost double the area offered by standard
coverage sprinklers used for similar applications.

EC-11 & EC-14


Upright, Pendent & Recessed Pendent
K Factor K=11.2 (161,3) • K=14.0 (201,6)

Thread Size 3⁄4" NPT

Approvals UL, C-UL, FM, NYC

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F, Open

Escutcheon Style 30 • Style 40 • Style 60

Escutcheon Finish White Coated, Chrome Plated, Brass Plated

Natural Brass, Chrome Plated, Signal White,


Sprinkler Finish
Jet Black, Lead Coated

SIN TY5137, TY5237, TY6137, TY6237

Wrench Type W-TYPE 3 / W-TYPE 22 (for recessed escutcheons)

Tech Data Sheet TFP220

Light hazard/Ordinary hazard • 3 mm bulb • Designed for maximum coverage applications of 37,2 m2 (400 ft 2) - 4,3 m x 4,3 m (14' x
14') up to 6,1 m x 6,1 m (20' x 20') • Low profile decorative glass bulb spray sprinklers • Series EC-11 and EC-14 Sprinklers feature
a UL and C-UL Listing that permits their use with unobstructed or non-combustible obstructed ceiling construction as defined and
permitted by NFPA 13, as well as a specific application listing for use under concrete tees.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 11
Fire Suppression General Products Catalog

Extended Coverage Sprinklers


EC-8
Pendent & Recessed Pendent
K Factor K=8.0 (115,2)

Thread Size 3⁄4" NPT

Approvals UL, C-UL, FM, NYC

Temperature 57°C/135°F, 68°C/155°F

Escutcheon Style 30 • Style 40

Escutcheon Finish Natural Brass, Signal White, Chrome Plated

Natural Brass, Signal White Polyester,


Sprinkler Finish
Chrome Plated

SIN TY4232

Wrench Type W-TYPE 3 / W-TYPE 23 (for recessed escutcheons)

Tech Data Sheet TFP223

Light hazard • 3 mm bulb • Covers areas as large as 6,1 m x 6,1 m (20' x 20') • The recessed version of the EC-8, intended for use
in areas with a finished ceiling, uses either the two-piece Recessed Escutcheon • The Series EC-8 Extended Coverage Pendent
Sprinklers are decorative glass bulb sprinklers designed for use in light hazard occupancies.

EC-5
Pendent & Recessed Pendent
K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, FM, NYC

Temperature 57°C/135°F, 68°C/155°F

Escutcheon Style 50

Escutcheon Finish Signal White, Chrome Plated, Brass Plated

Natural Brass, Chrome Plated,


Sprinkler Finish
Signal White Polyester

SIN TY3232

Wrench Type W-TYPE 6 / W-TYPE 7 (for recessed escutcheons)

Tech Data Sheet TFP228

Light hazard • 3 mm bulb • Coverage up to 6,1 m x 6,1 m (20' x 20')

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

12
www.tyco-fire.com

Extended Coverage Sprinklers


EC-5
Horizontal Sidewall & Recessed Horizontal Sidewall
K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, FM, NYC

Temperature 57°C/135°F, 68°C/155°F, 93°C/200°F

Escutcheon Style 50

Escutcheon Finish Signal White, Chrome Plated, Brass Plated

Signal White, Pure White, Natural Brass,


Sprinkler Finish
Chrome Plated

SIN TY3302

Wrench Type W-TYPE 6 / W-TYPE 7 (for recessed escutcheons)

Tech Data Sheet TFP298

Light hazard • 3 mm bulb • Coverage up to 4,9 m x 7,3 m (16' x 24') • Designed for use in hydraulically calculated sprinkler systems
in commercial occupancies such as churches, restaurant seating areas, hotels, educational facilities, offices, etc.

EC-HS
Extended Coverage Horizontal Sidewall Sprinklers
K Factor K=80 (115.2)

Thread Size 1⁄2" NPT

Approvals VdS

Temperature 57°C/135°F, 68°C/155°F, 79°C/174°F

Escutcheon Style 10 or Style 20

Recessed Escutcheon: Brass Plated Pure White,


Escutcheon Finish
or Chrome Plated.

Sprinkler Finish Refer to Table B of TFP288

SIN TY3330

W-Type 6 Wrench, P/N 56-000-6-387


Wrench Type
W-Type 7 Recessed Wrench, P/N 56-850-4-001

Tech Data Sheet TFP288

The Model EC-HS, 80 K-factor, Extended Coverage Horizontal Sidewall Sprinklers are extended coverage, decorative 3 mm glass
bulb type spray sprinklers. • They are to be installed per VdS CEA 4001 under smooth ceilings in Light or Ordinary Hazard 1, as well
as in accordance with Annex E of VdS CEA 4001 (e.g., commercial occupancies such as churches, restaurant seating areas, hotels,
educational facilities, offices, etc.)

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 13
Fire Suppression General Products Catalog

Extended Coverage Sprinklers


TY-FRB
Horizontal Sidewall & Recessed Horizontal Sidewall
K Factor K=5.6 (80,6) • K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL, FM, NYC

Temperature 57°C/135°F, 68°C/155°F, 79°C/175°F

Escutcheon Style 10 • Style 20 • Style 30 • Style 40

Escutcheon Finish White Coated, Chrome Plated, Brass Plated

Natural Brass, Pure White, Signal White, Jet Black,


Sprinkler Finish
Chrome Plated

SIN TY3332, TY4332

Wrench Type W-TYPE 6 / W-TYPE 7 (for recessed escutcheons)

Tech Data Sheet TFP296

Light hazard • 3 mm bulb • Two-piece escutcheon converts sidewall sprinklers into low profile sprinkler assemblies with coverage
areas up to 4,9 m x 6,7 m (16' x 22') for K=5.6 and 4,9 m x 7,3 m (16' x 24') for K=8.0 • Provides 19,1 mm (3 ⁄4" NPT) of horizontal
adjustment from the recessed sidewall position • Quick & Standard Response (see tech data sheet) • Decorative sprinklers designed
for use in hydraulically calculated sprinkler systems in light hazard, commercial occupancies such as churches, restaurant seating
areas, hotels, educational facilities, offices, etc.

TY-FRL
Horizontal Sidewall
K Factor K=5.6 (80,6) • K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL, FM, NYC

Temperature 74°C/165°F

Sprinkler Finish Natural Brass, Chrome Plated

SIN TY3322, TY4322

Wrench Type W-TYPE 9

Tech Data Sheet TFP280

Light hazard • Solder type • Coverage up to 4,9 m (16 ft.) wide by 7,3 m (24 ft.) long, they are designed for installation along a wall
or the side of a beam and just beneath a smooth, flat, horizontal ceiling • Designed for use in commercial occupancies such as
churches, restaurant seating areas, hotels, educational facilities, offices, etc.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

14
www.tyco-fire.com

Extended Coverage Sprinklers


ELO SW-20/SW-24
Horizontal Sidewall
K Factor K=11.2 (161,3)

Thread Size 3⁄4" NPT

Approvals UL, C-UL, NYC

Temperature 68°C/155°F, 93°C/ 200°F

Sprinkler Finish Natural Brass, Chrome Plated, Signal White

SIN TY5332, TY5337

Wrench Type W-TYPE 3

Tech Data Sheet TFP230

Extended Coverage Ordinary Hazard (ECOH) • 3 mm bulb • SW-20 Listed to a 4,9 m (16'-0") wide and a 6,1 m (20'-0") throw
maximum coverage area, SW-24 Listed to a 4,9 m (16'-0") wide and a 7,3 m (24'-0") throw maximum coverage area • Standard
Response, Extended Coverage Ordinary Hazard (ECOH) Horizontal Sidewall Sprinklers are decorative glass bulb sprinklers designed
for use in ordinary hazard occupancies per NFPA 13

ELOC
Extra Large Orifice Concealed Pendent
K Factor K=11.2 (161,3)

Thread Size 3⁄4" NPT

Approvals UL, C-UL, NYC

71°C/160°F – Sprinkler - 59°C/139°F – Cover Plate,


Temperature
100°C/ 212°F – Sprinkler - 74°C/165°F – Cover Plate

Chrome Plated, Brass Plated, Signal White,


Cover Plate Finish
Grey White, Custom

SIN TY5522

Wrench Type W-TYPE 18

Tech Data Sheet TFP250

Light hazard • Extra Large Orifice Concealed (ELOC) Pendent Sprinklers are decorative, fast response solder type sprinklers
featuring a flat cover plate designed to conceal the sprinkler • Covers 37,2 m2 (400 sq. ft.) using less pressure than a standard 12,7
mm (1 ⁄ 2") sprinkler at 20,3 m2 (225 sq. ft.) • Available with optional dust and air seal • Concealed in an enclosed escutcheon plate
with flat cover for use in those applications where aesthetics is a primary consideration.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 15
Fire Suppression General Products Catalog

Extended Coverage Sprinklers


CHEC
Concealed Horizontal Extended Coverage Sidewall
K Factor K=8.0 (115,2)

Thread Size 3⁄4" NPT

Approvals UL, C-UL, NYC

Temperature 68°C/155°F - Sprinkler, 59°C/139°F - Cover Plate

Cover Plate Finish Signal White, Pure White, Chrome, Custom

SIN TY4332

Wrench Type W-TYPE 7

Tech Data Sheet TFP265

Light hazard • 3 mm bulb • Coverage up to 4,9 m x 4,9 m (16' x 16') • Lowest flows & pressures allowed by NFPA 13 • 1 ⁄ 2" adjustment
• 12" maximum deflector distance from ceiling • No “Slots” in cover plate • It is the best choice for architecturally sensitive areas
such as dormitories, hotel rooms, reception areas, office buildings, banquet facilities, conference rooms, and hospitals.

RFII

Concealed Pendent
K Factor K= 5.6 (80.6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, NYC

68°C (155°F) - Sprinkler 59°C (139°F) - Cover Plate,


Temperature
93°C (200°F) - Sprinkler 74°C (165°F) - Cover Plate

Chrome, Brass, Pure White, Signal White,


Cover Plate Finish
Grey White, Jet Black, Custom

SIN TY3532

Wrench Type RFII

Tech Data Sheet TFP260

Light hazard • 3 mm bulb • Maximum 6,1 m x 6,1 m (20' x 20') QR Listing • Internally threaded closure with 12,7 mm (1 ⁄ 2") of
adjustment • Separable, two-piece design of the mounting cup and cover allows installation of the sprinklers and pressure testing
of the fire protection system prior to installation of a suspended ceiling or application of the finish coating to a fixed ceiling •
Concealed in an enclosed escutcheon plate with flat cover for use in those applications where aesthetics is a primary consideration.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

16
www.tyco-fire.com

Extended Coverage Sprinklers

RFII-MRI

Concealed Pendent
K Factor K= 5.6 (80.6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL

68°C (155°F) - Sprinkler 59°C (139°F) - Cover Plate,


Temperature
93°C (200°F) - Sprinkler 74°C (165°F) - Cover Plate

Cover Plate Finish Brass, Signal White, Grey White, Jet Black, Custom

SIN TY3537

Wrench Type RFII

Tech Data Sheet TFP262

Non-magnetic flat-plate concealed sprinkler for MRI room applications • Tested up to 7 Tesla (standard MRI apparatus is typically
3 Tesla) • Concealed in an enclosed escutcheon plate with flat cover • Separable, two-piece design of the mounting cup and cover
allows installation of the sprinklers and pressure testing of the fire protection system prior to installation of a suspended ceiling
or application of the finish coating to a fixed ceiling • Internally threaded closure with 12,7 mm (1/2") of adjustment • Extended
coverage option designed to protect standardized MRI rooms with fewer sprinklers (up to 5 fewer than standard coverage) •
Maximum 20Ft. x 20Ft. (6,1 m x 6,1 m) QR Listing

RFIII
Flat Plate Concealed Horizontal Extended Coverage Sidewall
K Factor K=8.0 (115,2)

Thread Size 3⁄4" NPT

Approvals UL, C-UL

Temperature 71°C/160°F - Sprinkler 59°C/139°F - Cover Plate

Ivory, Beige, Pure White, Signal White, Grey White,


Cover Plate Finish Brown, Black, Brushed Chrome, Brushed Brass,
Custom Paint

SIN TY4522

Wrench Type W-Type 37

Tech Data Sheet TFP270

Light hazard • Decorative, link type, sprinkler featuring a unique flat cover designed to conceal the sprinkler within a wall • The
sprinkler is the best choice for architecturally sensitive areas such as dormitories, hotel rooms, reception areas, office buildings,
banquet facilities, conference rooms, and hospitals • The Model RFIII ECLH Concealed HSW Sprinklers are designed for installation
along a wall or the side of a beam, and beneath a smooth level ceiling.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 17
Storage Sprinklers
Intended for use in specific storage applications and include a broad offering of early suppression
fast response (ESFR) sprinklers.

-- High-Piled Storage -- High Challenge Occupancies

-- Warehouse -- In-Rack Storage

-- Box-In-Box Cold Storage -- Beneath Open Gridded


Catwalks

18
www.tyco-fire.com

Storage Sprinklers
ESFR-25
Pendent
K Factor K=25.2 (362,9)

Thread Size 1" NPT or ISO 7-R1

Approvals UL, C-UL, FM, NYC, LPCB, VdS, CE

Temperature 74°C/165°F, 100°C/212°F

Sprinkler Finish Natural Brass

SIN TY9226

Wrench Type W-TYPE 1

Tech Data Sheet TFP312

Early Suppression, Fast Response (ESFR) • Solder type • The TYCO Model ESFR-25 Pendent Sprinklers are listed by UL for Specific
Applications with a ceiling height greater than 13,7 m (45 ft.) up to and including 14,6 m (48 ft.), and a storage arrangement up
to and including 13,1 m (43 ft.) • Direct attack on burning fuel by improved heavy sprinkler discharge • Patented frame design
substantially reduces the frame shadow effects that often produce non-uniformity in spray pattern, Novel orifice seal and
unique fast response link design are the very latest in sprinkler technology • Suppression-mode sprinklers that are especially
advantageous as a means of eliminating the use of in-rack sprinklers when protecting high-piled storage.

ESFR-22
Pendent
K Factor K=22.4 (320)

Thread Size 1" NPT or ISO 7-R1

Approvals UL, C-UL, FM

Temperature 74°C/ 165°F, 100°C/212°F

Sprinkler Finish Natural Brass

SIN TY8223

Wrench Type W-TYPE 1

Tech Data Sheet TFP321

Early Suppression, Fast Response (ESFR) • Solder type • Suppression-mode sprinklers that are especially advantageous as a means
of eliminating the use of in-rack sprinklers when protecting high-piled storage • Direct attack on burning fuel by improved heavy
sprinkler discharge • The TYCO Model ESFR-22 Pendent Sprinklers are listed by UL and C-UL for Specific Applications with a ceiling
height of 13,7 m (45 ft.) and a storage arrangement up to and including 12,2 m (40 ft.)

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 19
Fire Suppression General Products Catalog

Storage Sprinklers
ESFR-17
Upright
K Factor K=16.8 (241,9)

Thread Size 3⁄4" NPT

Approvals FM, CE

Temperature 74°C/165°F, 100°C/212°F

Sprinkler Finish Natural Brass

SIN TY7126

Wrench Type W-TYPE 21

Tech Data Sheet TFP316

Early Suppression, Fast Response (ESFR) • Solder type • Unique, upright design and large K-Factor overcome many pendent
obstruction problems • Use of this sprinkler is especially advantageous as a means of eliminating the use of in-rack sprinklers when
protecting rack storage arrangements, Primarily designed for use in ceiling only sprinkler systems.

Pendent
K Factor K=16.8 (241,9)

Thread Size 3⁄4" NPT

Approvals UL, C-UL, FM

Temperature 74°C/165°F, 100°C/212°F

Sprinkler Finish Natural Brass

SIN TY7223

Wrench Type W-TYPE 35

Tech Data Sheet TFP317

Early Suppression, Fast Response (ESFR) • Solder type • Primarily designed for use in ceiling only sprinkler systems • Model ESFR-17
Pendent Sprinklers are designed to operate at substantially lower-end head pressures, as compared to ESFR Sprinklers having a
nominal K-factor of 14.0 • They are suppression mode sprinklers that are especially advantageous as a means of eliminating in-rack
sprinklers when protecting high-piled storage.

ESFR-17
Pendent
K Factor K=16.8 (241,9)

Thread Size 3⁄4" NPT or ISO 7-R 3/4

Approvals UL, C-UL, FM

Temperature 68°C/155°F, 93°C/200°F

Sprinkler Finish Natural Brass

SIN TY7236

Wrench Type W-TYPE 35

Tech Data Sheet TFP322

Early Suppression, Fast Response (ESFR) • 3mm bulb type • Primarily designed for use in ceiling only sprinkler systems • Use of
this sprinkler is especially advantageous as a means of eliminating the use of in-rack sprinklers when protecting rack storage
arrangements • Available in two temperature ratings and Listed or Approved accordingly; 155°F (68°C) is UL and C-UL Listed and FM
Approval; and 200°F (93°C) is UL and C-UL Listing only.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

20
www.tyco-fire.com

Storage Sprinklers
ESFR-17
Dry-Type Pendent
K Factor K=16.8 (241,9)

Thread Size 1-1 ⁄4" NPT or ISO 7-R 1-1 ⁄4

2" Standard Cut Grooved per Tech Data Sheet


Grooved End
TFP1898

Approvals UL, FM

Temperature 74°C/ 165°F, 100°C/ 212°F

Sprinkler Finish Natural Brass

SIN TY7229

Wrench Type W-TYPE 26

Tech Data Sheet TFP320

Early Suppression, Fast Response (ESFR) • Solder type • Eliminates in-rack sprinklers for box-in-box applications • Suppression
mode sprinklers that are especially advantageous as a means of eliminating in-rack sprinklers when protecting high-piled box-
in-box refrigerated storage areas • Less costly to install and maintain than pre-action or antifreeze systems • The Model ESFR-
17 Dry Type Pendent Sprinkler is FM Approved and has successfully undergone full-scale fire testing at FM Global, when used
in conformance with applicable FM Global Property Loss Prevention Data Sheets • The Model ESFR-17 Dry Type Sprinklers are
primarily used for ceiling only sprinkler protection and used to protect solid piled, palletized, and rack storage that is subject to
freezing temperatures

ULTRA K-17
Upright, Control Mode Specific Application
K Factor K=16.8 (241,9)

Thread Size 3⁄4" NPT

Approvals UL, C-UL, FM, NYC

Temperature 68°C/155°F, 93°C/200°F

Sprinkler Finish Natural Brass

SIN TY7153

Wrench Type W-TYPE 8

Tech Data Sheet TFP330

5 mm bulb • Approved for storage heights of 7,6 m (25') and building heights to 9,1 m (30') • Full-scale fire testing has shown that
the Ultra K17 can control fires with commodities up to Group A plastics, and eliminate the need for in-rack sprinklers.

Upright, Control Mode Specific Application, 286° F


K Factor K=16.8 (241,9)

Thread Size 3⁄4" NPT

Temperature 141°C/286°F

Sprinkler Finish Natural Brass

Wrench Type W-TYPE 8

Tech Data Sheet Contact Tyco for Details

5 mm bulb • Control mode sprinkler

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 21
Fire Suppression General Products Catalog

Storage Sprinklers
ESFR-14
Pendent
K Factor K=14.0 (201,6)

Thread Size 3⁄4" NPT or ISO 7-1

Approvals UL, C-UL, FM

Temperature 68°C/155°F, 93°C/200°F

Sprinkler Finish Natural Brass

SIN TY6236

Wrench Type W-TYPE 34

Tech Data Sheet TFP319

Early Suppression, Fast Response (ESFR) • 3mm bulb type • Designed for the protection of rack storage • Direct attack on burning
fuel by improved heavy sprinkler discharge • They are suppression-mode sprinklers that are especially advantageous as a means of
eliminating the use of in-rack sprinklers when protecting high-piled storage.

K17-231
Pendent & Upright
K Factor K=16.8 (241,9)

Thread Size 3⁄4" NPT

Upright= UL, C-UL, FM, NYC


Approvals
Pendent= UL, C-UL, NYC

Temperature 68°C/155°F, 93°C/200°F, 141°C/286°F

Sprinkler Finish Natural Brass

SIN TY7151, TY7251

Wrench Type W-TYPE 8

Tech Data Sheet TFP332

5 mm bulb • They are “standard response spray sprinklers” which produce a hemispherical water distribution pattern below the
deflector • Low-pressure requirement (as low as 0.48 bar (7 psi)) can save cost by reducing branch line size, taking advantage of
maximized spacing, and upgrading existing densities • Very large orifice sprinkler for use in high challenge storage occupancies.

ELO-231B
Pendent & Upright
K Factor K=11.2 (161,3)

Thread Size 1 ⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL, FM, NYC

Temperature 68°C/155°F, 93°C/200°F, 141°C/286°F

Brass, Chrome Plated, Lead Coated, Wax Coated,


Sprinkler Finish
Wax over Lead Coated

SIN TY5151, TY5251, TY5851

Wrench Type W-TYPE 3

Tech Data Sheet TFP342

5mm bulb • Extra large orifice sprinklers proven for storage through full-scale fire testing • Can be used as intermediate level
version by adding a guard and shield • Designed to control high challenge fires with relatively low required pressures

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

22
www.tyco-fire.com

Storage Sprinklers
ELO-231 FRB
Pendent & Upright
K Factor K=11.2 (161,3)

Thread Size 1⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL, FM, NYC, VdS,LPCB

Temperature 68°C/155°F, 93°C/200°F, 141°C/286°F

Sprinkler Finish Natural Brass, Chrome Plated

SIN TY5131, TY5231, TY5831

Wrench Type W-TYPE 3

Tech Data Sheet TFP344

3 mm bulb • Extra large orifice sprinklers proven for storage occupancies through full-scale fire testing • Can be used as
intermediate level version by adding a guard and shield • Designed to control high challenge fires with relatively low
required pressures

ELO-231
Pendent & Upright
K Factor K=11.2 (161,3)

Thread Size 1⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL, FM, NYC

Temperature 74°C/165°F, 100°C/212°F, 141°C/286°F

Natural Brass, Chrome Plated, Lead Coated,


Sprinkler Finish
Wax Coated, Wax over Lead Coated

SIN TY5111, TY5211, TY5811

Wrench Type W-TYPE 3

Tech Data Sheet TFP340

Solder type • Extra large orifice sprinklers proven for storage occupancies through full-scale fire testing • Can be used as
intermediate level version by adding a guard and shield • Designed to control high challenge fires with relatively low required
pressures

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 23
Fire Suppression General Products Catalog

Storage Sprinklers
LD "Large Drop"
Upright, Control Mode Specific Application
K Factor K=11.2 (161,3)

Thread Size 3⁄4" NPT

Approvals UL, C-UL, NYC

Temperature 68°C/155°F, 93°C/200°F, 141°C/286°F

Sprinkler Finish Natural Brass

SIN TY5153

Wrench Type W-TYPE 3

Tech Data Sheet TFP335

5 mm bulb • Control mode sprinkler • Can provide a higher level of protection than standard spray sprinklers • Can provide an
advantage by eliminating in-rack sprinklers • Designed for the protection of high-piled storage

TY-B
Pendent & Upright, Intermediate Level
K Factor K=5.6 (80,6) • K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL, FM, NYC

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F, 182°C/360°F

Natural Brass, Lead Coated, Wax Coated, Wax over


Sprinkler Finish
Lead Coated

SIN TY3153, TY3251, TY4153, TY4251

Wrench Type W-TYPE 6

Tech Data Sheet TFP351

5 mm bulb • Intermediate level (in-rack) with shield • Used where sprinkler guards are not required • Factory assembled unit having
an integral water shield • Both the Pendent and Upright Sprinklers produce a hemispherical water distribution pattern below the
deflector.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

24
www.tyco-fire.com

Storage Sprinklers
TY-B
Pendent & Upright, Intermediate Level
K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, FM

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F, 182°C/360°F

Sprinkler Finish Natural Brass

Guard Finish Red or Zinc

SIN TY315, TY325

Wrench Type W-TYPE 6

Tech Data Sheet TFP352

5 mm bulb • Factory assembled unit having an integral water shield • Intermediate Level Sprinklers are primarily designed for use in
rack storage sprinkler systems where their thermally sensitive elements must be shielded from the water spray of higher elevation
sprinklers that could operate earlier during a fire • May also used in other applications such as beneath open gridded catwalks.

TY-FRB
Pendent & Upright, Intermediate Level
K Factor K=5.6 (80,6) • K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL, FM, NYC

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F, 182°C/360°F

Sprinkler Finish Natural Brass, Lead Coated

SIN TY3133, TY3231, TY4133, TY4231

Wrench Type W-TYPE 6

Tech Data Sheet TFP356

3 mm bulb • Intermediate level with shield • Factory assembled unit having an integral water shield • Used where sprinkler guards
are not required

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 25
Fire Suppression General Products Catalog

Storage Sprinklers
TY-FRB
Pendent & Upright, Intermediate Level
K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, FM

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F

Sprinkler Finish Natural Brass

Guard Finish Red or Zinc

SIN TY313, TY323

Wrench Type W-TYPE 6

Tech Data Sheet TFP357

3 mm bulb • Factory assembled unit having an integral water shield • Intermediate Level Sprinklers are primarily designed for use in
rack storage sprinkler systems where their thermally sensitive elements must be shielded from the water spray of higher elevation
sprinklers that could operate earlier during a fire • May also used in other applications such as beneath open gridded catwalks

TY-L
Pendent & Upright, Intermediate Level
K Factor K=5.6 (80,6) • K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL, FM

Temperature 74°C/165°F, 100°C/212°F, 138°C/ 280°F

Sprinkler Finish Natural Brass

SIN TY3113, TY3211, TY4113, TY4211

Wrench Type W-TYPE 9

Tech Data Sheet TFP350

Solder type • Intermediate level with shield • Factory assembled unit having an integral water shield • Used where sprinkler guards
are not required

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

26
www.tyco-fire.com

Storage Sprinklers
TY-FRL
Pendent & Upright, Intermediate Level
K Factor K=5.6 (80,6) • K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL, FM, NYC

Temperature 74°C/165°F

Sprinkler Finish Natural Brass, Chrome Plated

SIN TY3123, TY3221, TY4123, TY4221

Wrench Type W-TYPE 9

Tech Data Sheet TFP355

Solder type • Intermediate level with shield • Factory assembled unit having an integral water shield • Used where sprinkler guards
are not required

Sprinkler Guards
Model G1 & G4 Sprinkler Guards
Model G1/S1 & G4/S3 Guards with Shields
Approvals UL, C-UL, FM

Plain Brass, Red Painted, Chrome Plated,


Guard Finishes
Zinc Coated, Zinc Chromate

Tech Data Sheet TFP780

Designed for use with specific types of Series TY-B, TY-FRB, TY-L, and TY-
FRL Sprinklers that may be located in areas that make them susceptible to
mechanical or physical damage • Rugged guard design to minimize possible
damage to sprinklers • Shields are for use in storage racks or beneath grated
mezzanine, or other areas requiring the sprinklers to be shielded from possible
discharge from sprinklers above • Can be used with either 1 ⁄ 2" or 3 ⁄4" NPT
G1
sprinklers

S1
G4/S3 with Shield G4
G4

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 27
Fire Suppression General Products Catalog

Storage Sprinklers
Sprinkler Guards
Model G2 Sprinkler Guard, Model WS-2 Shield, and
Model WSG-2 Sprinkler Guard with Shield
Approvals UL, C-UL, FM

Guard Finishes Red Painted, Zinc Coated

Tech Data Sheet TFP782

Designed for use with Series ELO-231, ELO-231B, or ELO-231FRB Sprinklers that
may be located in areas that make them susceptible to mechanical or physical
damage • Rugged guard design to minimize possible damage to sprinklers •
Shields are for use in storage racks or beneath grated mezzanine, or other areas
requiring the sprinklers to be shielded from possible discharge from sprinklers
WSG-2 with Shield above • Can be used with either 1 ⁄ 2" or 3 ⁄4" NPT sprinklers

G2 WS-2 Shield

Model EG-25 Sprinkler Guard


for Model ESFR-25 Pendent Sprinkler
Approvals FM

Guard Finishes Red Painted, Zinc Chromate

Tech Data Sheet TFP784

Designed for use with the TYCO Model ESFR-25 Pendent Sprinkler and may be
located in areas that make it susceptible to mechanical or physical damage •
Provides protection from mechanical and/or physical damage, for example, rack
storage sprinkler installations • Welded assembly fabricated from carbon steel

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

28
RAPID RESPONSE® Residential Sprinkler Systems
Offer optimum design and flow characteristics for all residential applications.
-- Townhomes -- Assisted Living

-- Multi-family -- Student Housing

-- Single-family -- Beam and sloped ceilings

-- Hotel / motel

Custom paint options available


We offer custom paint cover plates for sprinklers with this icon.
Learn more at www.tyco-fire.com/custompaint.

29
Fire Suppression General Products Catalog

Rapid Response® Sprinklers


LFII
Pendent & Recessed Pendent
K Factor K=4.9 (70,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, NSF/ANSI 61

Temperature 68°C/155°F, 79°C/175°F

Escutcheon Style 20

Pure White, Signal White, Chrome Plated,


Sprinkler Finish
Natural Brass

SIN TY2234

Wrench Type W-TYPE 6, W-Type 7 (For recessed escutcheons)

Tech Data Sheet TFP400

3 mm bulb type • Approved for special applications with beamed ceilings


Intended for use in wet & dry pipe scenarios:
- residential sprinkler systems for one/two-family dwellings and mobile homes per NFPA 13D
- residential occupancies up to and including four stories in height per NFPA 13R
- sprinkler systems for the residential portions of any occupancy per NFPA 13

Pendent & Recessed Pendent


K Factor K=5.8 (83,5)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, NSF/ANSI 61

Temperature 68°C/155°F, 79°C/175°F

Escutcheon Style 20

Signal White, Chrome Plated, Natural Brass,


Sprinkler Finish
Jet Black, Pure White

SIN TY3934

Wrench Type W-TYPE 6, W-Type 7 (For recessed escutcheons)

Tech Data Sheet TFP401

3 mm bulb type
Intended for use in these wet pipe scenarios:
- residential sprinkler systems for one/two-family dwellings and mobile homes per NFPA 13D
- residential occupancies up to and including four stories in height per NFPA 13R
- sprinkler systems for the residential portions of any occupancy per NFPA 13

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

30
www.tyco-fire.com

Rapid Response® Sprinklers


LFII
Pendent & Recessed Pendent
K Factor K=3.0 (43,2)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, NSF/ANSI 61

Temperature 68°C/155°F, 79°C/175°F

Escutcheon Style 20

Sprinkler Finish Signal White, Chrome Plated, Natural Brass

SIN TY1234

Wrench Type W-TYPE 6, W-Type 7 (For recessed escutcheons)

Tech Data Sheet TFP402

3 mm bulb type • Decorative, fast response, frangible bulb sprinklers designed for use in residential occupancies such as homes,
apartments, dormitories, and hotels.
Intended for use in these wet pipe scenarios:
- residential sprinkler systems for one/two-family dwellings and mobile homes per NFPA 13D
- residential occupancies up to and including four stories in height per NFPA 13R
- sprinkler systems for the residential portions of any occupancy per NFPA 13

Horizontal & Recessed Horizontal Sidewall


K Factor K=4.4 (63,4)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, NSF/ANSI 61

Temperature 68°C/155°F, 79°C/175°F

Escutcheon Style 20

Sprinkler Finish Signal White, Chrome Plated, Natural Brass

SIN TY2334

Wrench Type W-TYPE 6, W-Type 7 (For recessed escutcheons)

Tech Data Sheet TFP412

3 mm bulb type
Intended for use in these wet pipe scenarios:
- residential sprinkler systems for one/two-family dwellings and mobile homes per NFPA 13D
- residential occupancies up to and including four stories in height per NFPA 13R
- sprinkler systems for the residential portions of any occupancy per NFPA 13

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 31
Fire Suppression General Products Catalog

Rapid Response® Sprinklers


LFII
Horizontal & Recessed Horizontal Sidewall
K Factor K=4.2 (60,5)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, NYC, NSF/ANSI 61

Temperature 68°C/155°F, 79°C/175°F

Escutcheon Style 20

Pure White, Signal White, Chrome Plated,


Sprinkler Finish
Natural Brass

SIN TY1334

Wrench Type W-TYPE 6, W-Type 7 (For recessed escutcheons)

Tech Data Sheet TFP410

3 mm bulb type • Approved for special applications with beamed ceilings


Intended for use in the following scenarios:
- wet and dry pipe residential sprinkler systems for one/two-family dwellings and mobile homes per NFPA 13D
- wet and dry pipe residential occupancies up to and including four stories in height per NFPA 13R
- wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

Flat Plate Concealed Pendent


K Factor K=4.9 (70,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, NYC, NSF/ANSI 61

71°C/160°F - Sprinkler, 59°C/139°F - Cover Plate


Temperature
100°C/212°F - Sprinkler, 74°C/165°F - Cover Plate

Ivory, Beige, Pure White, Signal White, Grey White,


Cover Plate Finish Brown, Black, Brushed Brass, Brushed Chrome,
Bright Chrome, Custom Paint

SIN TY3596

Wrench Type W-TYPE 18

Tech Data Sheet TFP442

Solder type • Provides 12,7 mm (1 ⁄ 2") vertical adjustment. This adjustment provides flexibility when cutting fixed sprinkler drops •
Cover plate conceals sprinkler components above the ceiling
Intended for use in the following scenarios:
- wet and dry pipe residential sprinkler systems for one/two-family dwellings and mobile homes per NFPA 13D
- wet and dry pipe residential occupancies up to and including four stories in height per NFPA 13R
- wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

32
www.tyco-fire.com

Rapid Response® Sprinklers


LFII
Domed Plate Concealed Pendent
K Factor K=4.9 (70,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, NYC

Temperature 68°C/155°F - Sprinkler, 59°C/139°F - Cover Plate

Cover Plate Finish Pure White, Signal White, Chrome, Custom

SIN TY2234

Wrench Type W-TYPE 7

Tech Data Sheet TFP450

3 mm bulb type • Can be used for horizontal and sloped ceilings • Cover plate conceals sprinkler components above the ceiling
Intended for use in the following scenarios:
- wet and dry pipe residential sprinkler systems for one/two-family dwellings and mobile homes per NFPA 13D
- wet and dry pipe residential occupancies up to and including four stories in height per NFPA 13R
- wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

LFII
Cover Plate & Protective Cap Utility Tool for Concealed Sprinklers

Used with the


TY2524, TY3531, TY3532, TY3551, TY3596
following Sprinklers

Tech Data Sheet Tyco for details

Install and remove cover plates for LFII, RFII, and RFIII concealed sprinklers • Also used for removing protective caps before cover
plate installation

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 33
Fire Suppression General Products Catalog

Rapid Response® Sprinklers


LFII
Dry Type Recessed Pendent
K Factor K=4.9 (70,6)

Thread Size 1" NPT or ISO 7-R1

Approvals UL, NSF/ANSI 61

Temperature 68°C/155°F, 79°C/175°F (wet pipe only)

Escutcheon Finish Signal White, Chrome Plated, Natural Brass

Sprinkler Finish Signal White, Chrome Plated, Natural Brass

SIN TY2235

Wrench Type W-TYPE 7

Tech Data Sheet TFP460

3 mm bulb type • Where sprinklers are required on dry pipe systems that are exposed to freezing temperatures, or where sprinklers
are seasonally drained to avoid freezing • Offer the features of non-water filled pipe in addition to not having to increase the
number of design sprinklers (hydraulic design area) for systems designed to NFPA 13, 13D, or 13R
Intended for use in the following residential sprinkler systems scenarios:
- one/two-family dwellings and mobile homes per NFPA 13D
- residential occupancies up to and including four stories in height per NFPA 13R
- the residential portions of any occupancy per NFPA 13

Dry Type Recessed Horizontal Sidewall


K Factor K=4.4 (63,4)

Thread Size 1" NPT or ISO 7-R1

Approvals UL, NSF/ANSI 61

Temperature 68°C/155°F

Escutcheon Finish Signal White, Chrome Plated, Natural Brass

Sprinkler Finish Signal White, Chrome Plated, Natural Brass

SIN TY2335

Wrench Type W-TYPE 6, W-Type 7 (For recessed escutcheons)

Tech Data Sheet TFP461

3 mm bulb type • The Series LFII Dry Type Residential Horizontal Sidewall Sprinklers are typically used where sprinklers and/ or a
portion of the connecting piping are exposed to freezing temperatures • Offer the features of non-water filled pipe in addition to
not having to increase the number of design sprinklers (hydraulic design area) for systems designed to NFPA 13, 13D, or 13R
Intended for use in the following residential sprinkler systems scenarios:
- one/two-family dwellings and mobile homes per NFPA 13D
- residential occupancies up to and including four stories in height per NFPA 13R
- the residential portions of any occupancy per NFPA 13

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

34
www.tyco-fire.com

Rapid Response® Sprinklers

LFII • NFPA 13 Optimized Sprinklers


The large orifice 6.9 K, 5.8 K and 5.6 K sprinklers are primarily intended for residential use where there is a 0.1 gpm/sq. ft. density NFPA 13
design requirement, and are generally used for installations in excess of four stories. They are optimized for residential applications where
this higher water-flow demand is required, and can meet those requirements with less pressure and smaller pipe sizes.

Pendent, Recessed Pendent & Domed Concealed


K Factor K=6.9 (99,4)

Thread Size 3⁄4" NPT

Approvals UL, C-UL, FM, NYC, NSF/ANSI 61

Temperature 68°C/155°F, 79°C/175°F, 59°C/139°F - Cover Plate

Escutcheon Style 30

Escutcheon & Natural Brass, Chrome Plated,


Sprinkler Finish Pure White, Signal White

Cover Plate Finish Pure White, Signal White, Chrome, Custom

SIN TY4234

Wrench Type W-TYPE 6, W-Type 7 (For recessed escutcheons)

Tech Data Sheet TFP408

3 mm bulb type
Intended for use in the following scenarios:
- wet pipe residential sprinkler systems for one/two-family dwellings and mobile homes per NFPA 13D
- wet pipe residential occupancies up to and including four stories in height per NFPA 13R
- wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

Horizontal & Recessed Horizontal Sidewall Sprinklers


K Factor K=5.8 (83,5)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, FM, NSF/ANSI 61

Temperature 68°C/155°F, 79°C/175°F

Escutcheon Style 20

Sprinkler Finish Signal White, Chrome Plated, Natural Brass

SIN TY4334

Wrench Type W-TYPE 6, W-Type 7 (For recessed escutcheons)

Tech Data Sheet TFP417

3 mm bulb type • Can be used for horizontal and sloped ceilings


Intended for use in the following scenarios:
- wet pipe residential sprinkler systems for one/two-family dwellings and mobile homes per NFPA 13D
- wet pipe residential occupancies up to and including four stories in height per NFPA 13R
- wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 35
Fire Suppression General Products Catalog

Rapid Response® Sprinklers

LFII • NFPA 13 Optimized Sprinklers


The large orifice 6.9 K, 5.8 K and 5.6 K sprinklers are primarily intended for residential use where there is a 0.1 gpm/sq. ft. density NFPA 13
design requirement, and are generally used for installations in excess of four stories. They are optimized for residential applications where
this higher water-flow demand is required, and can meet those requirements with less pressure and smaller pipe sizes.

Horizontal & Recessed Horizontal Sidewall Sprinklers


K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, NSF/ANSI 61

Temperature 68°C/155°F, 79°C/175°F

Escutcheon Style 20

Natural Brass, Chrome Plated, Pure White,


Sprinkler Finish
Signal White

SIN T Y3334

Wrench Type W-TYPE 6, W-Type 7 (For recessed escutcheons)

Tech Data Sheet TFP415

3 mm bulb type • Can be used for horizontal and sloped ceilings


Intended for use in the following scenarios:
- wet pipe residential sprinkler systems for one/two-family dwellings and mobile homes per NFPA 13D
- wet pipe residential occupancies up to and including four stories in height per NFPA 13R
- wet pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

RCP-1
Residential Control Panel

Size Range DN25 or DN40 (1" or 11 ⁄ 2")

Approvals UL Listed

Maximum Water
20,7 bar (300 psi)
Pressure

Air Pressure 0,7 bar (10 psi) to 4,5 bar (65 psi)

For use in residential dry pipe fire protection


System
systems

Tech Data Sheet TFP480

Model RCP-1 Residential Control Panel is an integrated valve manifold, air pressure, and electronic control package for controlling
the release of water into residential dry pipe sprinkler systems • Pre-wired assembly containing pre-programmed control panel,
system performance gauges, and an enclosed compressor • Supervised system valve system • Pre-engineered riser design • 48-
hour battery backup

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

36
Dry Sprinklers
Specifically designed for areas where sprinklers may be subjected to freezing conditions.

-- Unheated Warehouses -- Covered Exterior Platforms

-- Loading Docks

37
Fire Suppression General Products Catalog

Dry Sprinklers
DS-1
Pendent, Upright & Horizontal Sidewall
K Factor K=5.6 (80,6)

Thread Size 1" NPT (Standard Order) ISO 7-R1

Upright=UL, C-UL, FM, NYC, CE


Approvals
Pendent & HSW= UL, C-UL,CE, FM, NYC, LPCB, VdS

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F, 182°C/360°F

Escutcheon Finish Signal White, Chrome Plated, Brass Plated

Sprinkler Finish Natural Brass, Chrome Plated, Signal White

SIN TY3255, TY3155, TY3355

Wrench Type W-Type 7

Tech Data Sheet TFP500

Standard coverage • All hazards (light hazards, horizontal sidewall) • 5 mm bulb • Lengths up to 1220 mm (48") • Designed for use in
applications where sprinklers and/or connecting piping may be exposed to freezing conditions, or the sprinkler system is seasonally
drained • Special assembly provides a seal at the main pipe to prevent water from entering the assembly until the sprinkler
operates • Designed for use in applications requiring dry sprinklers, or where building construction or aesthetic considerations
make the installation of dry horizontal sidewall sprinklers more desirable than the dry pendent type

Pendent, Upright & Horizontal Sidewall


K Factor K=5.6 (80,6)
3
Thread Size  ⁄4" or 1" NPT (Std. Order) ISO 7-R1
3
⁄4"= UL, C-UL
Approvals
1"= UL, C-UL, FM, NYC

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F

Escutcheon Finish Signal White, Chrome Plated, Brass Plated

Sprinkler Finish Natural Brass, Chrome Plated, Signal White

SIN TY3235, TY3135, TY3335 TY3935, TY3735

Wrench Type W-Type 7

Tech Data Sheet TFP510

Light hazard/Ordinary hazard • 3 mm bulb • Designed for use in applications where sprinklers and/or connecting piping may be
exposed to freezing conditions, or the sprinkler system is seasonally drained • Special assembly provides a seal at the main pipe to
prevent water from entering the assembly until the sprinkler operates • Designed for use in applications requiring dry sprinklers, or
where building construction or aesthetic considerations make the installation of dry horizontal sidewall sprinklers more desirable
than the dry pendent type

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

38
www.tyco-fire.com

Dry Sprinklers
DS-1
Extended Coverage Horizontal Sidewall
K Factor K=5.6 (80,6)

Thread Size 1" NPT (Standard Order) ISO 7-R1

Approvals UL, C-UL, NYC

Temperature 57°C/135°F, 68°C/155°F

Escutcheon Finish Signal White, Chrome Plated, Brass Plated

Sprinkler Finish Natural Brass, Chrome Plated, Signal White

SIN TY3338, TY3358

Wrench Type W-Type 7

Tech Data Sheet TFP520

EC light hazard • 3mm and 5mm Glass Bulb • Lengths up to 1220 mm (48") • Designed for use in light hazard occupancy applications
requiring a dry sprinkler to cover areas up to: 4,9 m x 6,1 m (16’ x 20’) or 5,5 m x 4,9 m (18’ x 16’) • Special assembly provides a
seal at the main pipe to prevent water from entering the assembly until the sprinkler operates

DS-1 Stainless Steel


Pendent
K Factor K=5.6 (80,6)

Thread Size 1" NPT (Standard Order) ISO 7-R1

Approvals UL, C-UL, LPCB, CE

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F, 182°C/360°F

Escutcheon Finish Stainless Steel

Sprinkler Finish Stainless Steel

SIN TY3230, TY3250

Wrench Type W-Type 7

Tech Data Sheet TFP560

3mm and 5mm Glass Bulb • Quick and Standard Response • The stainless-steel construction of these sprinklers extends the life of
a sprinkler beyond that of traditional copper alloy sprinklers exposed to corrosive atmospheres • Wet-pipe, dry-pipe, or preaction
installations • Designed for use in applications where sprinklers and/or connecting piping may be exposed to freezing conditions, or
the sprinkler system is seasonally drained • Special assembly provides a seal at the main pipe to prevent water from entering the
assembly until the sprinkler operates.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 39
Fire Suppression General Products Catalog

Dry Sprinklers
DS-1 Stainless Steel
Horizontal Sidewall, and Extended Coverage Horizontal Sidewall
K Factor K=5.6 (80,6)

Thread Size 1" NPT (Standard Order) ISO 7-R1

Approvals UL, C-UL

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F, 182°C/360°F

Escutcheon Finish Stainless Steel

Sprinkler Finish Stainless Steel

SIN TY3337, TY3357, TY3339

Wrench Type W-Type 7

Tech Data Sheet TFP560

3mm and 5mm Glass Bulb • Quick and Standard Response • The stainless-steel construction of these sprinklers extends the life of
a sprinkler beyond that of traditional copper alloy sprinklers exposed to corrosive atmospheres • Wet-pipe, dry-pipe, or preaction
installations • Extended coverages protecting areas up to 4,9 x 6,1m (16' x 20’) • Designed for use in applications where sprinklers
and/or connecting piping may be exposed to freezing conditions, or the sprinkler system is seasonally drained • Special assembly
provides a seal at the main pipe to prevent water from entering the assembly until the sprinkler operates.

DS-2
Pendent
K Factor K=11.2 (161,3)

Thread Size 1" NPT (Standard Order) ISO 7-R1

Approvals UL, C-UL, NYC

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F

Escutcheon Finish Signal White, Chrome Plated, Brass Plated

Sprinkler Finish Natural Brass, Chrome Plated, Signal White

SIN TY5255, TY5235

Wrench Type W-Type 17

Tech Data Sheet TFP530

Standard coverage • All hazard (standard response) • Light hazard/Ordinary hazard (quick response) • 3 mm and 5 mm bulb • Extra
large orifice • Lengths to 1220 mm (48") • Designed for use in applications where sprinklers and/or connecting piping may be
exposed to freezing conditions, or the sprinkler system is seasonally drained • Special assembly provides a seal at the main pipe to
prevent water from entering the sprinkler assembly until the sprinkler operates

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

40
www.tyco-fire.com

Dry Sprinklers
DS-2
Extended Coverage Pendent
K Factor K=11.2 (161,3)

Thread Size 1" NPT (Standard Order) ISO 7-R1

Approvals UL, C-UL, NYC

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F

Escutcheon Finish Signal White, Chrome Plated, Brass Plated

Sprinkler Finish Natural Brass, Chrome Plated, Signal White

SIN TY5238

Wrench Type W-Type 17

Tech Data Sheet TFP540

EC light hazard & ordinary hazard • 3 mm bulb • Extra large orifice • Lengths to 1220 mm (48") • Designed for use in applications
where sprinklers and/or connecting piping may be exposed to freezing conditions, or the sprinkler system is seasonally drained •
Special assembly provides a seal at the main pipe to prevent water from entering the assembly until the sprinkler operates

DS-C
Concealed Pendent
K Factor K=5.6 (80,6)

Thread Size 1" NPT (Standard Order) ISO 7-R1

Approvals UL, C-UL, NYC

68°C/155°F - Sprinkler, 59°C/139°F - Cover Plate,


Temperature
93°C/200°F - Sprinkler, 74°C/165°F - Cover Plate

Grey White, Brass, Pure White, Signal White,


Cover Plate Finish
Jet Black, Chrome, Custom

SIN TY3535, TY3555

Wrench Type RFII

Tech Data Sheet TFP515

Standard coverage • All hazard (standard response) • Light hazard/ordinary hazard (quick response) • 3 mm and 5 mm bulb •
Lengths to 1220 mm (48") • Designed for use in applications where sprinklers and/or connecting piping may be exposed to freezing
conditions, or the sprinkler system is seasonally drained • Special assembly provides a seal at the main pipe to prevent water from
entering the sprinkler assembly until the sprinkler operates.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 41
Fire Suppression General Products Catalog

Dry Sprinklers
DS-ECC

Extended Coverage Concealed Pendent


K Factor K=5.6 (80,6)

Thread Size 1" NPT (Standard Order) ISO 7-R1

Approvals UL, C-UL, NYC

68°C/155°F - Sprinkler, 59°C/139°F - Cover Plate,


Temperature
93°C/200°F - Sprinkler, 74°C/165°F - Cover Plate

Grey White, Brass, Pure White, Signal White, Jet


Cover Plate Finish
Black, Chrome, Custom

SIN TY3539

Wrench Type RFII

Tech Data Sheet TFP518

EC light hazard/EC ordinary hazard • 3 mm bulb • Lengths to 1220 mm (48") • Designed for use in applications where sprinklers
and/or connecting piping may be exposed to freezing conditions, or the sprinkler system is seasonally drained • Special assembly
provides a seal at the main pipe to prevent water from entering the sprinkler assembly until the sprinkler operates

DS-3
Extended Coverage Horizontal Sidewall
K Factor K=11.2 (161,3)

Thread Size 1" NPT (Standard Order) ISO 7-R1

Approvals UL, C-UL, NYC

Temperature 68°C/155°F, 93°C/200°F

Escutcheon Finish Signal White, Chrome Plated, Brass Plated

Sprinkler Finish Natural Brass, Chrome Plated, Signal White

SIN TY5339

Wrench Type W-Type 8

Tech Data Sheet TFP550

EC ordinary hazard • 3 mm bulb • Lengths to 1220 mm (48") • Designed for use in applications where sprinklers and/or connecting
piping may be exposed to freezing conditions, or the sprinkler system is seasonally drained • Ideal for Exterior Loading Docks and
Covered Areas and can eliminate the need for dry or anti-freeze systems.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

42
www.tyco-fire.com

Dry Sprinklers
DSB-2
Dry Sprinkler Boot (For Use With TFP Dry Type Sprinklers)

1 Boot, 2 Strap Ties, and


1/3 oz. of Adhesive
Includes
(quantity of adhesive is sufficient for
installing 1 Boot)

Tech Data Sheet TFP591

Helps to close the air gap created by the clearance hole through a wall or ceiling through which the dry type sprinkler has
penetrated • Helps to stop the air exchange between the inside and outside of the freezer (or any other type of similar
construction) to help prevent transfer of moist air into the freezer space

G5
DS-1 Dry Sprinkler Guards

Approvals UL

Finish Zinc Chromate

Tech Data Sheet TFP783

The TYCO Model G5 Sprinkler Guards are designed to be used in areas that make the sprinklers susceptible to mechanical or
physical damage • For use with Series DS-1 Dry Sprinklers standard, deep and no escutcheons

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 43
Special Application Sprinklers
Intended for specific applications such as combustible concealed spaces and areas subject to corrosion.
-- Attic Spaces -- Corrosive Environments

-- High Security Institutions -- Window Protection

44
www.tyco-fire.com

Special Application Sprinklers


Attic
BB (Back-to-Back), SD (Single Directional), HIP, & AP (Attic Plus)
K Factor K=4.2 (60,5), K=5.6 (80,6), K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL

93°C/200°F for BB (K4.2 and K8.0), HIP, AP


Temperature
100°C/212°F for BB (K5.6), SD

Sprinkler Finish Natural Brass


Back-To-Back
TY4180, TY4181, TY4182 TY3180, TY3181, TY3182
SIN TY2180, TY2181, TY2182 TY3183, TY3184, TY3185
TY3187, TY3190, TY2190

Wrench Type W-TYPE 3, W-TYPE 6, W-TYPE 20

Tech Data Sheet TFP610

“Specific Application Sprinklers for Protecting Attics” • 3 mm bulb or solder type


• Wet or dry pipe systems • Provides a tested method of protecting an attic •
Hip Provides a specific cost advantage by reducing the amount of piping required
• Cover attics to 60’-0" wide with a single line of piping, eliminating the need
for as many as five branch lines • Saves up to 80% of the piping that would be
required with standard sprinklers while providing a higher level of protection.

Spray Patterns
Back-To-Back Hip Application Single Directional
Application Application
Single
Directional

BB SD
Attic Plus
(AP)

HIP AP

AREA 2 AREA 1 AREA 3


WITH AP WITH BB WITH AP
SPRINKLERS SPRINKLERS SPRINKLERS

STAGGERED
SPACING WHEN
MORE THAN
ONE ROW

MINIMUM
SEPARATION
15'-0" (4,6 m)

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 45
Fire Suppression General Products Catalog

Special Application Sprinklers


RAVEN Studio Sprinkler
Pendent & Horizontal Sidewall Sprinklers
K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL

Temperature 74°C/165°F

Sprinkler Finish White, Grey, Custom

White, Grey, Chrome/Electropolish, Custom,


Escutcheon Finish
Primed White or Grey (for paint-in-place)

Standard Coverage:
TY1281 - Pendent, TY1381 - HSW
SIN
Extended Coverage:
TY1282 - Pendent, TY1382 - HSW

Wrench Type W-Type 25

Tech Data Sheet TFP658

TYCO RAVEN Studio Sprinklers 5.6K Pendent and Horizontal Sidewall (HSW) Quick Response, Standard Coverage for Light and
Ordinary Hazard applications and Extended Coverage for Light Hazard applications only, are intended for use in areas as designed
per NFPA 13 • The flush design is made aesthetically appealing by concealing the deflector and other operating parts behind the
link assembly. • Additionally, RAVEN Studio is the only sprinkler UL Listed with a paint-in-place escutcheon. Both the sprinkler and
escutcheon are also available in a range of factory-painted custom colors.

RAVEN
Institutional Pendent & Horizontal Sidewall
K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL

Temperature 74°C/165°F

Escutcheon Material Carbon Steel, or Stainless Steel

Escutcheon Finish Grey, Chrome, White, or Electropolished (SS only)

Sprinkler Finish Grey or White

SIN TY3281, TY3282, TY3381, TY3382

Wrench Type W-Type 25

Tech Data Sheet TFP651

Quick Response • Standard and Extended Coverage • Designed for use in areas such as correctional, detention, and mental health
care facilities as well as other commercial buildings • Both the pendent and horizontal sidewall styles are available for standard or
extended coverage applications • Tamper-resistant features • 12,1 bar (175 psi).

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

46
www.tyco-fire.com

Special Application Sprinklers


TFP PH2
Institutional Pendent Sprinklers
K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, NYC

Temperature 74°C/165°F, 100°C/212°F

Sprinkler Finish Chrome Plated

Escutcheon Finish Chrome Plated

SIN TY3290

Wrench Type Model 1509-3

Tech Data Sheet TFP650

The Tyco Model TFP PH2, 5.6 K-factor, Institutional Pendent Sprinklers are standard response standard coverage, fusible solder type
spray sprinklers designed for use in areas such as correctional, detention, and mental health care facilities. • The unique features
of the Model TFP PH2 provide a tamper resistant sprinkler design that helps eliminate the opportunity for individuals to injure
themselves or others with the components of a fire sprinkler. • At the same time, the Model TFP PH2 optimizes an aesthetically
appealing flush design that conceals most of the operating parts.

TFP PH5
Institutional Horizontal Sidewall Sprinklers
K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, NYC

Temperature 74°C/165°F

Sprinkler Finish Chrome Plated

Escutcheon Finish Chrome Plated

SIN TY3390

Wrench Type Model 1509-3

Tech Data Sheet TFP650

The Tyco Model TFP PH5, 5.6 K-factor, Institutional Horizontal Sidewall Sprinklers are standard-response, standard-coverage spray
sprinklers designed for use in areas such as correctional, detention, and mental health care facilities. • The unique features of the
Model TFP PH5 provide a tamper-resistant sprinkler design that helps eliminate the opportunity for individuals to injure themselves
or others with components of a fire sprinkler. • The Model TFP PH5 optimizes an aesthetically appealing flush design that conceals
most of the operating parts.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 47
Fire Suppression General Products Catalog

Special Application Sprinklers


WS™
Window Sprinklers, Horizontal & Pendent Vertical Sidewall
K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, ULC, NYC, ICC

Temperature 68°C/155°F, 93°C/200°F

Signal White Polyester, Chrome Plated,


Sprinkler Finish
Natural Brass, Jet Black

SIN TY3388, TY3488

Wrench Type W-Type 20

Tech Data Sheet TFP620

3 mm bulb • Only UL tested sprinklers that can protect glazing in a wall or window and allow it to maintain its mechanical
equivalent rating up to two hours • First sprinklers to be UL/C-UL Listed, ICC-ES, and ULC Listed & Approved for maintaining a rated
assembly • Pendent allows installation farther away from the glass than the sidewall • Sidewall permits the window mullion to act
as a baffle, allowing the sprinklers to be spaced closely together, if necessary • Provides the only UL tested option when seeking
wall fire ratings when using heat strengthened, tempered, or ceramic glass.

CC1
Combustible Concealed Space Sprinklers™, Upright
K Factor K=2.8 (40,3)

Thread Size 1⁄2" NPT

Approvals UL

Temperature 79°C/175°F

Sprinkler Finish Natural Brass

SIN TY1189

Wrench Type W-Type 20

Tech Data Sheet TFP630

3 mm bulb • Sprinklers are fast response, specific application sprinklers designed to provide protection of light hazard
combustible, as well as non-combustible, concealed spaces • Meets NFPA® Requirements for Specialty Listed Sprinklers in
Combustible Concealed Spaces • Allows the use of BlazeMaster® CPVC pipe with the benefit of superior sprinkler protection
for Wood truss spaces.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

48
www.tyco-fire.com

Special Application Sprinklers


CC2
Combustible Concealed Space Sprinklers™, Upright
K Factor K=4.2 (60,5), K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL

Temperature 79°C/175°F

Sprinkler Finish Natural Brass

SIN TY2189, TY3189

Wrench Type W-Type 6

Tech Data Sheet TFP632

3 mm bulb • Specific application sprinklers • Provides protection of specific light hazard combustible, as well as non-combustible,
concealed spaces requiring sprinkler protection • The CC2 Sprinklers comply with the criterion for the protection of combustible
concealed spaces as described in NFPA 13 • Allows the use of BlazeMaster® CPVC pipe in combustible concealed areas with the
benefit of superior sprinkler protection for Wood truss spaces • Can be used on steel dry pipe sprinkler systems • Increased spacing
from 3,1 m (10 ft.) to 3,7 m (12 ft.) • Increased coverage area from 9,3 m2 (100 ft 2) to 13,4 m2 (144 ft 2)

CC3
Combustible Concealed Space Sprinklers™, Upright
K Factor K=4.2 (60,5), K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL

Temperature 93°C/200°F

Sprinkler Finish Natural Brass

SIN TY2199 - 4.2K, TY3199 - 5.6K

Wrench Type W-Type 6

Tech Data Sheet TFP633

3 mm bulb • The CC3 Combustible Concealed Sprinklers are quick response, upright, specific application sprinklers designed to
provide protection of specific light hazard combustible, as well as non-combustible, concealed spaces requiring protection • The
Model CC3 Sprinklers comply with the criteria for the protection of combustible concealed spaces as described in NFPA 13 • The
Model CC3 are designed for installation on BlazeMaster CPVC wet pipe systems and steel wet pipe or dry pipe sprinkler systems.

Combustible Concealed Standard Spray


Sprinkler Discharge Pattern Sprinkler Discharge Pattern

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 49
Fire Suppression General Products Catalog

Special Application Sprinklers


Issue D Quartzoid®
High Temperature, Upright & Pendent
K Factor K=5.6 (80,6), K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL, FM, LPCB

204°C/400°F, 260°C/500°F,
Temperature
343°C/650°F (K=5.6 only)

Sprinkler Finish Natural Brass, Chrome Plated, Lead Coated

SIN TY3191, TY3296, TY4191 , TY4292

Wrench Type W-Type 11

Tech Data Sheet TFP690

Standard coverage • All hazard • 11 mm bulb • Extra-high and ultra-high temperature ratings and corrosion resistant coatings •
Temperature Ratings to 343°C (650°F) available.

TY-B
Conventional (Old Style)
K Factor K=5.6 (80,6) , K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL, LPCB, VdS, NYC

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F, 182°C/360°F, Open

Natural Brass, Chrome Plated, Pure White,


Sprinkler Finish Signal White, Wax Coated, Lead Coated,
Wax Over Lead Coated

SIN TY3651, TY4651

Wrench Type W-Type 6

Tech Data Sheet TFP661

Ordinary and Extra High Hazard • 5 mm bulb • These sprinklers are intended to be installed either pendent or upright, and in
either position, they produce a spherical water discharge pattern with approximately 50% of the discharge directed upwards and
approximately 50% of the discharge directed downwards. • The NFPA permits the use of “Old Style Sprinklers” where special
construction features require a unique water distribution.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

50
www.tyco-fire.com

Special Application Sprinklers


TY-B
Conventional (Old Style)
K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, VdS, LPCB (TY3650 Only)

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F, 182°C/360°F

Natural Brass, Chrome Plated, Pure White,


Sprinkler Finish
Signal White

SIN TY365, TY3650

Wrench Type W-Type 6

Tech Data Sheet TFP662

Ordinary and Extra High Hazard • 5 mm bulb • These sprinklers are intended to be installed either pendent or upright, and in
either position, they produce a spherical water discharge pattern with approximately 50% of the discharge directed upwards and
approximately 50% of the discharge directed downwards.

TY-FRB
Conventional (Old Style)
K Factor K=5.6 (80,6) , K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL, LPCB, VdS, NYC

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F

Natural Brass, Chrome Plated, Pure White,


Sprinkler Finish
Signal White, Jet Black

SIN TY3631, TY4631

Wrench Type W-Type 6

Tech Data Sheet TFP666

Ordinary and Extra High Hazard • 3 mm bulb • These sprinklers are intended to be installed either pendent or upright, and in
either position, they produce a spherical water discharge pattern with approximately 50% of the discharge directed upwards and
approximately 50% of the discharge directed downwards.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 51
Fire Suppression General Products Catalog

Special Application Sprinklers


TY-FRB
Conventional (Old Style)
K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, VdS, LPCB (TY3630 Only)

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F

Natural Brass, Chrome Plated, Pure White,


Sprinkler Finish
Signal White

SIN TY363, TY3630

Wrench Type W-Type 6

Tech Data Sheet TFP667

Ordinary and Extra High Hazard • The TYCO Series TY-FRB, Conventional Sprinklers, are quick response, standard coverage,
decorative 3 mm glass bulb type spray sprinklers • These sprinklers are intended to be installed either pendent or upright, and in
either position, they produce a spherical water discharge pattern with approximately 50% of the discharge directed upwards and
approximately 50% of the discharge directed downwards.

FTR-1
Fixed Temperature Release
K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL

Temperature 57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F

Natural Brass, White Polyester Coated,


Sprinkler Finish
Gray Teflon® Coated

SIN TY3030

Wrench Type W-Type 6

Tech Data Sheet TFP1388

3 mm bulb • Fixed-temperature, heat detector intended for wet or dry pilot release service • Maximum 40 ft. x 40 ft. spacing • Can
be used for pilot line service, instead of standard sprinklers, to activate deluge and preaction systems equipped with either wet or
dry pilot line detection • Corrosion resistant assembly option for outdoor applications (Teflon® coated)

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

52
www.tyco-fire.com

Special Application Sprinklers


TY-B & TY-FRB (Alternate Materials Of Construction)
Upright & Pendent Sprinklers
K Factor K=5.6 (80,6) • K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL, LPCB, Lloyds

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F, 182°C/360°F

Escutcheon Style Style 10 • Style 40

Sprinkler Finish Stainless Steel, SMO, Titanium

SIN Refer to Tech Data Sheet for SIN Numbers

Wrench Type W-TYPE 6, W-Type 7 (For recessed escutcheons)

Tech Data Sheet TFP680

TY-B: 5 mm diameter heat sensitive glass bulb, standard response • TY-FRB: 3 mm diameter heat sensitive glass bulb, quick
response • Corrosion resistant, standard coverage spray sprinklers designed for use in commercial occupancies where corrosive
atmospheres may exist • Alternate materials of construction (Stainless Steel, SMO, or Titanium) are utilized to extend the life of
a sprinkler beyond that which might be expected of copper alloy sprinklers exposed to corrosive atmospheres, (SMO = stainless-
molybdenum alloyed)

Vertical, Horizontal & Recessed Horizontal Sidewall Sprinklers


K Factor K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, LPCB

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F, 182°C/360°F

Escutcheon Style Style 10

Sprinkler Finish Stainless Steel, SMO, Titanium

SIN Refer to Tech Data Sheet for SIN Numbers

Wrench Type W-TYPE 6, W-Type 7 (For recessed escutcheons)

Tech Data Sheet TFP680

TY-B: 5 mm diameter heat sensitive glass bulb, standard response • TY-FRB: 3 mm diameter heat sensitive glass bulb, quick
response • Corrosion resistant, standard coverage spray sprinklers designed for use in commercial occupancies where corrosive
atmospheres may exist • Alternate materials of construction (Stainless Steel, SMO, or Titanium) are utilized to extend the life of
a sprinkler beyond that which might be expected of copper alloy sprinklers exposed to corrosive atmospheres (SMO = stainless-
molybdenum alloyed)

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 53
Fire Suppression General Products Catalog

Special Application Sprinklers


TY-B & TY-FRB (Poly-Stainless)
Upright, Pendent & Horizontal Sidewall Sprinklers
K Factor K=5.6 (80,6) • K=8.0 (115,2)

Thread Size 1⁄2" NPT • 3⁄4" NPT

Approvals UL, C-UL, LPCB, Lloyds

57°C/135°F, 68°C/155°F, 79°C/175°F, 93°C/200°F,


Temperature
141°C/286°F, 182°C/360°F

Escutcheon Style Style 10 • Style 40

Sprinkler Finish Poly-Stainless

SIN Refer to Tech Data Sheet for SIN Numbers

Wrench Type W-TYPE 6, W-Type 7 (For recessed escutcheons)

Tech Data Sheet TFP682

TY-B: 5 mm diameter heat sensitive glass bulb, standard response • TY-FRB: 3 mm diameter heat sensitive glass bulb, quick
response • Corrosion resistant, standard coverage spray sprinklers designed for use in commercial occupancies where corrosive
atmospheres may exist • Corrosive environments can wreak havoc on standard sprinkler heads. The TYCO Poly-Stainless sprinklers
are here to maintain the aesthetics of a sprinkler in a wide range of corrosive locations.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

54
Sprinkler Accessories
For use with the sprinklers and nozzles described in this catalog.

-- Improve Appearance -- Protection From Damage

-- Conceal Clearance Holes -- Onsite Emergency


Storage Supply

55
Fire Suppression General Products Catalog

Sprinkler Accessories
Escutcheon Plates
Recessed Escutcheons and Protective Paint Caps

1⁄2" NPT - Styles 10, 15, 20, & 50


Thread Size 3⁄8" NPT - Styles 70
3⁄4" NPT - Styles 30, & 40

Escutcheon Styles Styles 10, 15, 20, 30, 40, 50, & 70

Pure White, Signal White, Jet Black, Chrome Plated,


Finishes
Brass Plated, Plain

Tech Data Sheet TFP770

Consists of a mounting plate and closure for finished appearance in ceilings or soffits • Intended for use in areas with finished
ceilings or walls, and the adjustment provided by these escutcheons reduces the accuracy to which fixed piping to the sprinklers
must be cut, while providing a decorative recessed sprinkler installation • Primarily designed for use with standard spray, quick
response sprinklers and the Designer residential sidewall sprinklers • Maximum 1 ⁄ 2" to 3 ⁄4" adjustment

Style 65, One-Piece Flat Escutcheon


Style 401, Two-Piece Adjustable Escutcheon

Thread Size 1⁄2" NPT • 3⁄4" NPT

Escutcheon Styles Styles 65, 401

Finishes Chrome, Signal White, or Brass


Style 401
Style 65 Tech Data Sheet TFP777

Used to improve the overall appearance of the sprinkler installation by concealing the clearance holes required for wall or ceiling
installation • Deep, two-piece, adjustable • Available for 1 ⁄ 2" and 3 ⁄4" NPT

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

56
www.tyco-fire.com

Sprinkler Accessories
Escutcheon Plates
Style 60, Two-Piece Flush Escutcheon

Thread Size 3⁄4" NPT

Approvals UL, FM

Escutcheon Styles Styles 60

Finishes Chrome, Signal White, or Brass

Tech Data Sheet TFP778

Used to improve the overall appearance of the sprinkler installation by concealing the clearance holes required for wall or ceiling
installation • Deep, two-piece, adjustable • 3 ⁄4" total adjustment

Sprinkler Head Cabinet


3, 6 or 12 Capacity

Thread Size 1⁄2" NPT • 3⁄4" NPT • 1" NPT

Tech Data Sheet TFP785

Provides storage for spare sprinklers and sprinkler wrench • Spare sprinklers facilitate the prompt replacement of operated or
damaged sprinklers and return of fire protection system to service as soon as possible

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 57
Nozzle & Nozzle Accessories
Designed for use in a variety of special hazard application – may be required to provide a
properly designed special hazard fire protection system.
-- Flammable Liquid Ranks -- Industrial Process Equipment
& Operations
-- Computer Rooms
-- Flammable Liquid Storage
-- Clean Rooms
-- Offshore Platforms

58
www.tyco-fire.com

Nozzles and Accessories


D3
Protectospray Directional Spray Nozzle
K Factor K=1.2 (17,3) to 7.2 (103,7)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, FM

Spray Angles 65°, 80°, 95°, 110°, 125°, 140°, 160°, and 180°

Bronze: Natural Finish, Teflon Coated, Lead Coated,


Nozzle Finish
Chrome, or Natural Stainless Steel

Wrench Type W-Type 11

Tech Data Sheet TFP802, Blow-off Plugs TFP890

Designed for use in water spray fixed systems for fire protection applications • Open orifice type for use in deluge systems •
Nozzles are external deflector types that discharge a uniformly filled cone of medium velocity water droplets • Blow-Off Plugs are
available and designed for both indoor or outdoor use.

D3S
Protectospray Directional Spray Nozzle
K Factor K=1.1 (15,8) to 2.8 (40,3)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, FM

Nozzle Finish Bronze, Stainless Steel

Wrench Type W-Type 11

Tech Data Sheet TFP804

The D3S Nozzles that are typically used in non-NFPA installations feature an integral strainer for use when the Authority Having
Jurisdiction requires the use of individual strainers • The D3S Nozzles are external deflector type nozzles that discharge a uniformly
filled cone of medium velocity water droplets.

HV ”High Velocity”
Directional Spray Nozzle
K=1.6 (23,0) • K=1.8 (25,9) • K=2.8 (40,3) • K=4.6 (66,2)
K Factor
K=5.5 (79,2) • K=6.4 (92,2)

Thread Size 1" NPT 1-1⁄4" (only K=6.4)

Approvals UL, C-UL, FM

Nozzle Finish Natural Brass or Stainless Steel

Wrench Type Common Adjustable Wrench

Tech Data Sheet TFP815

Open, directional spray nozzles • Designed for use in fixed water spray fire protection systems where a high velocity water
application is needed, such as the protection of flammable liquids, electrical transformers, circuit breakers, oil-fired boilers and
lube oil systems • Available in six different orifice sizes and six angle spray patterns • Produces a solid conical spray pattern

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 59
Fire Suppression General Products Catalog

Nozzles and Accessories


EA-1
Automatic Protectospray Directional Spray Nozzle
K Factor K=1.4 (20,2), K=2.8 (40,3), K=5.6 (80,6)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, FM


57°C/135°F, 79°C/175°F, 121°C/250°F, 163°C/325°F,
Temperature
204°C/400°F, 260°C/500°F
Spray Angles 65°, 80°, 95°, 110°, 125°, 140°, 160°, and 180°
Natural Finish Bronze, Lead Coated Bronze,
Sprinkler Finish
Chrome Plated, Wax Coated Bronze
Wrench Type W-TYPE 11

Tech Data Sheet TFP800

Medium velocity, Bulb type frangible element for use in closed head systems • Discharges a filled cone of water droplets at
relatively low velocity • The Type EA-1 Nozzles are also especially effective for area coverage and are sometimes used in lieu of
standard sprinklers where directional spray is considered more appropriate.

TN-25
Horizontal Spray Nozzle, Open
K Factor K=25.2 (362,9)

Thread Size 1" NPT or ISO 7-R 1

Approvals UL, C-UL

Nozzle Finish Natural Brass

Wrench Type W-Type 1

Tech Data Sheet TFP850

The TYCO Model TN-25 Horizontal Spray Nozzle is a specialized open nozzle for use in tunnel fire protection deluge systems,
providing an improved alternative to traditional designs • Model TN-25 Nozzle allows for a single pipe to run the length of a tunnel,
compared to traditional designs that use multiple pipes in order to provide sufficient coverage.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

60
www.tyco-fire.com

Nozzles and Accessories

TN-17
Horizontal Spray Nozzle, Open
K Factor K=16.8 (241,9)

Thread Size 3/4" NPT or ISO 7-R 3/4

Approvals UL, C-UL

Nozzle Finish Natural Brass

Wrench Type W-Type 21

Tech Data Sheet TFP852

The TYCO Model TN-17 Horizontal Spray Nozzle having a 16.8 (K240) K-factor is a specialized open nozzle for use in tunnel fire
protection deluge systems, providing an improved alternative to traditional designs • With its ability to provide extended coverage,
the Model TN-17 Nozzle allows for a single pipe to run the length of a tunnel, compared to traditional designs that use multiple
pipes in order to provide sufficient coverage • The Model TN-17 Nozzle is an open nozzle designed to be integrated into a deluge
fire protection system.

D4a
Directional Spray Nozzles, Open, Medium Velocity
K=1.2 (17,3) • K=1.8 (25,9) • K=2.3 (33,1) • K=3.0 (43,2)
K Factor
K=4.1 (59,0) • K=5.6 (80,6) • K=7.2 (103,7)

Thread Size 1⁄2" NPT

Approvals UL, C-UL

Spray Angles 65°, 80°, 95°, 110°, 125°, 140°, 160°, and 180°

Nozzle Finish Natural Finish Bronze, Teflon Coated Bronze

Wrench Type Common Adjustable Wrench

Tech Data Sheet TFP806

Nozzles are external deflector types that discharge a uniformly filled cone of medium velocity water droplets • The Type D4a
Nozzles feature a four arm body design that helps assist against mechanical or physical damage • Open orifice design type for use
in deluge systems

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 61
Fire Suppression General Products Catalog

Nozzles and Accessories


F822 thru F834 Mulsifyre®
Directional Spray Nozzles, Open, High Velocity
K=2.0 (28,8) • K=2.3 (33,1) • K=2.7 (38,9)
K Factor
K=2.6 (37,4) • K=4.6 (66,2) • K=5.1 (73,4)

Thread Size 3⁄4" NPT

Approvals UL, ULC

Nozzle Finish Brass

Wrench Type Common Adjustable Wrench

Tech Data Sheet TFP810

Two configurations: basic Mulsifyre Nozzle & Mulsifyre Nozzle with Model F880 Dust Cap, • Available in six different models provide
a wide range of orifice sizes and water distribution characteristics • Air aspirating foam-water nozzles, for use with all types of
foam (required for Non-AFFF type foams) • Designed for use in water spray fixed systems for fire protection applications where a
high velocity water application may be required, Pendent & upright designs, Open nozzle for use on deluge systems.

F822S thru F834S Mulsifyre®


Directional Spray Nozzles, Open, With Strainers, High Velocity
K=2.0 (28,8) • K=2.3 (33,1) • K=2.7 (38,9)
K Factor
K=2.6 (37,4) • K=4.6 (66,2) • K=5.1 (73,4)

Thread Size 3⁄4" NPT

Approvals FM

Nozzle Finish Brass

Wrench Type Common Adjustable Wrench

Tech Data Sheet TFP811

Two configurations: basic Mulsifyre Nozzle & Mulsifyre Nozzle with Model F880 Dust Cap, • Available in six different models provide
a wide range of orifice sizes and water distribution characteristics • Air aspirating foam-water nozzles, for use with all types of
foam (required for Non-AFFF type foams) • Designed for use in water spray fixed systems for fire protection applications where a
high velocity water application may be required, Pendent & upright designs, Open nozzle for use on deluge systems.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

62
www.tyco-fire.com

Nozzles and Accessories


Cooling Tower Nozzle
Type 1 and 2
K Factor K=2.9 (42,0)

Thread Size 3⁄4" NPT

Approvals UL, FM

Nozzle Finish Bronze or Stainless Steel

Wrench Type W-Type 11

Tech Data Sheet TFP830

Intended for use in fire protection systems for cross flow cooling towers with combustible fill sections • Open nozzle design for use
in water spray deluge system • Installed under the distribution basin, they discharge water in a relatively narrow, elongated spray
pattern • Type 1 has a waterway designed for use in towers with diffusion decks, Type 2 for those without diffusion decks

B-1
Upright & Pendent Foam-Water Sprinkler
K Factor K=3.0 (43,2)

Thread Size 1⁄2" NPT

Approvals UL, C-UL, Military

Nozzle Finish Natural Bronze

Wrench Type Common Adjustable Wrench

Tech Data Sheet TFP840

Air aspirating foam-water nozzles • Pendent & upright styles • Open nozzle for use in NFPA 16 foam-water sprinkler systems

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 63
Fire Suppression General Products Catalog

Nozzles and Accessories


Type DN-5
Corrosion Resistant Duct Nozzle, Open, Medium Velocity
K Factor K=6.0 (86,5)

Thread Size 1⁄2" NPT

Approvals FM

Nozzle Coating HALAR (ECTFE)

Tech Data Sheet TFP808

The TYCO Type DN-5 Corrosion Resistant Duct Nozzle is an open (non-automatic) directional spray nozzle designed for use in
water spray fixed systems for fire protection applications in extremely corrosive duct environments. • It is an external deflector
type nozzle that discharges medium velocity water droplets. • The Type DN-5 Corrosion Resistant Duct Nozzle is effective in
discharging water to vertical, horizontal, curved, and irregular shaped surfaces within a duct to achieve fire suppression and
potential extinguishment.

DDS Duct Deluge System


For The Protection of Ventilation Ductwork Handling Corrosive Gases

Approvals FM

- Steel Manufacturing,
- Copper Mineral Processing,
- Lead Mineral Processing,
Corrosive
- Zinc Mineral Processing,
Environments
- Coal Power Generation,
- Semiconductor Fabrication,
- Pulp & Paper Facilities

Tech Data Sheet TFP870

The TYCO DDS Duct Deluge System is designed specifically for the protection of ventilation ductwork handling corrosive gases,
including extremely corrosive gases as defined in FM Property Loss Prevention Data Sheet 7-78. • The DDS System features the
TYCO DN-5 Corrosion Resistant Duct Nozzle, which is an open (non automatic) directional spray nozzle, and also includes the
TYCO Red-E Cabinet, Protectowire linear heat detection, and FlexHead duct mounting hardware. • Ventilation ductwork handling
extremely corrosive environments in industrial settings.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

64
Wet Pipe Sprinkler Systems
Designed for use in wet pipe sprinkler systems.

-- Heated Warehouses -- Apartment or Condominium


Complexes
-- Factories
-- Single Family Residences
-- Hospitals

-- Shopping Centers

65
Fire Suppression General Products Catalog

Wet System Valves & Devices

AV-1 Alarm Valve

BFV-300 Butterfly Valve


to Control Water Supply
to System

Water Supply

AV-1-300
Alarm Valve
Size Range DN65 thru DN200 (21 ⁄ 2" thru 8")

Approvals UL, C-UL Listed & FM Approved

Working Water
1,4 to 20,7 bar (20 to 300 psi)
Pressure

For use in wet pipe (automatic sprinkler) fire


System
protection systems

End Connection Groove x Groove, Flange x Flange, Flange x Groove

Flange Drilling ANSI, ISO, AS, & JIS

Tech Data Sheet TFP910

AV-1 Alarm Valves may be installed vertically or horizontally • Alarm Valves are divided seat ring, rubber-faced clapper, check
type, water flow alarm valves • Automatically actuates electrically and/or hydraulically operated alarms when there is a steady
flow equivalent to the discharge rate for one or more sprinklers • Optional Retard Chamber used in installations subject to variable
pressure (generally associated with public water supplies) to help prevent false alarms • Available pre-assembled with modular trim
to provide a quick and convenient method for trimming valve risers. Contact TFP for details

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

66
www.tyco-fire.com

Wet System Valves & Devices


RC-1
Retard Chamber
UL, ULC, & FM for use with: Model AV-1-300 Alarm
Check Valves
Approvals UL, ULC, FM, VdS, & LPCB for use with the following
Alarm Check Valves: Model AV-1-175,
Gem Model F20/F200/F2001, Gem Model A,
Star Model S30/S300/S3001

Maximum Working
20,7 bar (300 psi)
Pressure

System Use in a wet type automatic sprinkler system riser

Tech Data Sheet TFP920

The Model RC-1 Retard Chamber is required in installations that will be subject to pressure variations, as are generally associated
with public water supplies, in order to help prevent false alarms

CV-1FR
Riser Check Valve
Size Range DN50 thru DN300 (2" thru 12")

Approvals UL, C-UL Listed & FM Approved

Maximum Working
20,7 bar (300 psi)
Pressure

System Use in a wet type automatic sprinkler system riser

End Connection Groove x Groove

Tech Data Sheet TFP950

Can be installed using GRINNELL Grooved Couplings or GRINNELL Figure 71 Flange Adapters • Designed with a removable cover for
ease of field maintenance • Standard seal is grade “E" EPDM

RM-1
Riser Manifolds
NFPA 13 - DN40 thru DN150 (1-1 ⁄ 2" thru 6")
Size Range NFPA 13D - DN25 (1")
NFPA 13R - DN40 thru DN50 (1-1 ⁄ 2" thru 2")

UL, C-UL Listed & FM Approved


Approvals
Listed by California State Fire Marshall

Maximum Working
20,7 bar (300 psi)
Pressure

System Use in commercial or residential sprinkler systems

End Connection Thread x Thread, Groove x Groove

Tech Data Sheet TFP963

Riser Manifolds may be installed either horizontally or vertically orientation, for both single sprinkler rises and floor control in
high-rises. • Optional Pressure Relief Kits feature a 12,1 bar (175 psi) pressure relief valve and trim components for convenient
integration into commercial and residential riser manifold assemblies.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 67
Fire Suppression General Products Catalog

Wet System Valves & Devices


RSV-1
Residential Shutoff Valve
NFPA 13D - DN25 (1")
Size Range
NFPA 13R or NFPA 12D - DN50 (2")

Approvals UL, C-UL, & NSF-61

Maximum Working
12,1 bar (175 psi)
Pressure

System For use in residential sprinkler systems

End Connection Thread x Thread

Tech Data Sheet TFP980

During the design of a residential sprinkler system, domestic water use should be taken into consideration unless the domestic
supply can be stopped when a sprinkler operates • When a sprinkler operates, water supply is automatically diverted from the
domestic system to the sprinkler system • Eliminates the need for pumps, pressurized storage tanks, or electrically operated
domestic shutoff valves • Valve automatically resets after the fire protection system is returned to normal service

Resi-Riser
Residential
Size Range DN25 thru DN50 (1" thru 2")

Maximum Working
12,1 bar (175 psi)
Pressure

System For use in residential sprinkler systems

End Connection Thread x Thread

Tech Data Sheet Contact Tyco for details

Compact, pre-assembled, ready to install sprinkler riser • Brass construction for use in potable water supply • Integral test and
drain assembly, flow switch with retard mechanism, 20,7 bar (300 psi) gauge, and check valve • Compact size allows for easy
installation between 50-100 mm (2" x 4") studs • Molded mounting points allow for fast and easy left or right hand installation •
Available with or without pressure relief valve or flow switch retard mechanism features

WMA-1
Water Motor Alarm
NFPA 13D - DN25 (1")
Size Range
NFPA 13R or NFPA 12D - DN50 (2")

Approvals UL, ULC Listed & FM, VdS, & LPCB Approved

Maximum Working
20,7 bar (300 psi)
Pressure
For use in a wet type automatic sprinkler system
System
riser
Tech Data Sheet TFP921

Hydraulically operated outdoor alarm for use with appropriate fire protection system valves (alarm, dry, deluge) • Supplied by
dedicated outlet in valve trim line or retard chamber • Uses energy-efficient lightweight impeller design capable of producing very
high sound level • Corrosion-resistant aluminum alloy gong, gong-mount, and water motor housing • Furnished with approved
20mm (3 ⁄4") Y-strainer for use in alarm line

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

68
Dry Pipe Sprinkler Systems
Designed for use in dry pipe sprinkler systems where piping and sprinklers are subjected
to freezing temperatures.

-- Unheated Warehouses -- Attic Spaces

-- Parking Garages -- Loading Docks

-- Store Windows

69
Fire Suppression General Products Catalog

Dry System Valves & Devices

Air DPV-1 Dry Pipe Valve

BFV-300 Butterfly Valve


to Control Water
Supply to System

Water Supply

DPV-1
Dry Pipe Valve
Size Range DN65 thru DN150 (2-1 ⁄ 2" thru 6")

Approvals UL, C-UL Listed & FM Approved

Maximum Service
17,2 bar (250 psi)
Pressure

System For use in dry pipe fire protection systems

End Connection Groove x Groove, Flange x Flange, Flange x Groove

Flange Drilling ANSI, ISO, AS, & JIS

Tech Data Sheet TFP1020

External reset differential dry pipe valves • Unique offset single clapper design enabling a simple compact valve to minimize
installation labor • Used to supply sprinkler installations in which sprinklers are subjected to freezing conditions (4˚C / 40˚F or less)
• Ductile iron construction to ensure a lightweight valve to minimize shipping cost. • Compact, Pre-Trimmed, and Semi-Assembled,
easy to operate valve trim. • Simple reset procedure through the elimination of priming water.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

70
www.tyco-fire.com

Dry System Valves & Devices


ACC-1
Dry Pipe Valve Accelerator
Approvals UL, C-UL Listed & FM, LPCB Approved

Maximum Working
4,8 bar (70 psi)
Air Pressure

System For use in dry pipe fire protection systems

End Connection Threaded

Tech Data Sheet TFP1112

Model ACC-1 Accelerator reduces the time for valve operation following the operation of one or more automatic sprinklers. •
Automatically adjusts to small or slow changes in system pressure but trips upon a rapid and steady drop in pressure • Designed
to trip when system air pressure drops at a rate exceeding approximately 0.07 bar/min (1 psi/minute) • Upon tripping, it transmits
system air pressure to the intermediate chamber of the dry pipe valve, which neutralizes the differential pressure holding the valve
closed and opens the waterway clapper • Rated for use at a maximum water supply pressure of 17,2 bar (250 psi) and a maximum
system air (or nitrogen) pressure of 4,8 bar (70 psi)

QRS
Electronic Accelerator
Approvals UL Listed & FM Approved

Maximum Working
4,8 bar (70 psi)
Air Pressure

System For use in dry pipe fire protection systems

End Connection Threaded

Tech Data Sheet TFP1100

Quick opening device intended to reduce the time for dry pipe valve operation following the operation of one or more automatic
sprinklers. • Automatically adjusts to both small and slow changes in system pressure, but trips with a steady drop in pressure (as
in the case of sprinkler operation) • Can be used to retro-fit existing mechanical accelerators • Fully assembled package includes
switch, solenoid, control panel, and accelerator trim pipe and fittings • Built-in low and high pressure alarm supervision • Proven
electronic release technology as used for electrically operated deluge and preaction systems • Battery back-up in the event of
primary power failure • Eliminates re-setting problems often incurred with traditional mechanical accelerators

VIZOR
Electronic Dry Pipe Accelerator
Approvals UL, C-UL Listed & FM Approved

Max. Water Pressure 20,7 bar (300 psi)

Air Pressure 0,7 bar (10 psi) to 4,5 bar (65 psi)

System For use in dry pipe fire protection systems

End Connection Threaded

Tech Data Sheet TFP1105

Direct mounting to the riser • Installation consistent with the installation of mechanical devices • Easy test-and-reset function,
as compared to mechanical accelerators • Battery back-up in the event of primary power failure • Electronically self-supervising
technology, similar to that used in typical alarm panels for alarm and detection systems • Built-in low-pressure and high pressure
alarm supervision

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 71
Fire Suppression General Products Catalog

Dry System Valves & Devices


AMD-1
Air Maintenance Device, Pressure Reducing Type
UL, C-UL Listed & FM Approved &
Approvals
NYC Approved under MEA 206-02-E

Field-Adjustable
0,4 to 4,8 bar (5 to 70 psi)
Outlet Pressure Range

Maximum Inlet Air


13,8 bar (200 psi)
Supply Pressure

System For use in dry pipe fire protection systems

Tech Data Sheet TFP1221

Field adjustable • Used in systems where compressed air source is available • Used in systems in which the air supply is at a higher
pressure than is desired for a sprinkler system or dry pilot line system

AMD-2
Air Maintenance Device, Compressor Control Type
UL, C-UL Listed & FM Approved &
Approvals
NYC Approved under MEA 206-02-E

Field-Adjustable Minimum Cut-In (On) 1,0 bar (14 psi)


Pressures Maximum Cut-Out (Off) 4,1 bar (60 psi)

The housing of the Pressure Switch meets


NEMA Rating
NEMA 1 requirements.

System For use in dry pipe fire protection systems

Tech Data Sheet TFP1231

Field adjustable • Used in conjunction with a small, non-tank-mounted air compressor • Monitors sprinkler system or dry pilot line
detection for deluge system air pressure and automatically cycles the compressor to maintain system pressure within preset limits

AMD-3
Nitrogen Maintenance Device, High Pressure (Cylinder) Reducing Type
UL, C-UL Listed & FM Approved &
Approvals
NYC Approved under MEA 206-02-E

Field-Adjustable
Outlet Pressures 0,4 to 4,1 bar (4 to 60 psi)
Range

Maximum Inlet
Nitrogen Supply 200 bar (3000 psi)
Pressure

System For use in dry pipe fire protection systems

Tech Data Sheet TFP1241

Field adjustable • Used in conjunction with a cylinder of high pressure nitrogen to control the nitrogen pressure in a sprinkler
system or a dry pilot line detection for deluge systems

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

72
Deluge & Preaction Systems
For use in deluge and preaction fire sprinkler systems.

-- Aircraft Hangars -- High-Hazard Installations Using


Water as Extinguishing Agent
-- Refrigerated Areas
-- Archives
-- Flammable Liquid Handling
-- Libraries

73
Fire Suppression General Products Catalog

Deluge & Preaction Systems


DV-5A

Deluge Valve, External Resetting Diaphragm Style – DN40 thru DN200 (11/2" thru 8")

The TYCO DV-5A Automatic Water Control Valves are


diaphragm type valves that can be used in deluge fire
protection systems. When properly trimmed, the double
seat design of the DV-5A Valve also provides actuation of
fire alarms upon system operation.

The diaphragm style design of the DV-5A Valve allows


external resetting, providing for easy resetting of a deluge
system without having to open a valve handhole cover to
manually reposition a clapper and/or latch mechanism.
Simply re-pressurizing the diaphragm chamber resets the
valve.

The DV-5A features internal and external coating of


the valve to provide corrosion resistance. The external
corrosion resistance of the epoxy coating permits the use
of the DV-5A in corrosive atmospheres associated with
many types of industrial processing plants and outdoor
installations.

Size Range DN40 thru DN200 (11 ⁄ 2" thru 8")

Approvals UL, C-UL Listed & FM, VdS & LPCB Approved

Maximum Service
1,4 bar (20 psi) to 20,7 bar (300 psi)
Pressure

Deluge Systems: (TFP1306 & TFP1325)


- Wet Pilot Actuation
- Dry Pilot Actuation
- Electric Actuation
Single Interlock Preaction Systems: (TFP1425)
Types of System - Wet Pilot Actuation
- Dry Pilot Actuation
- Electric Actuation
Double Interlock Preaction Systems: (TFP1450)
- Electric/Pneumatic Actuation
- Electric/Electric Actuation

Thread x Thread, Groove x Groove,


End Connection
Flange x Flange, Flange x Groove

Flange Drilling ANSI, ISO, AS, & JIS

Tech Data Sheet TFP1306

Vertical installation • One internal working part, Diaphragm operation • No linkage or clapper assembly • Light weight ductile
iron body • Available with deluge and single & double interlock preaction trim • Internally & externally coated • Features external
resetting • For deluge, preaction & foam systems

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

74
www.tyco-fire.com

Deluge & Preaction Systems


Deluge Systems
Wet Pilot, Dry Pilot, or Electric Actuation, Remote Resetting, or
Remote Resetting Pressure Reducing

Deluge fire protection systems are normally


used in special hazard installations where
an entire area application of water or foam
is required for protection. Applications may
include flammable liquid handling and
storage areas, aircraft hangars, and other
high-hazard installations where water is
the most effective extinguishing agent.
Deluge systems employ open sprinklers or
spray nozzles attached to a piping system.
The system is connected to a water supply
through the deluge valve. This valve is
opened by the operation of a fire detection
system installed in the same areas as the
open sprinklers or nozzles. Deluge systems
may be activated by wet or dry pilot
sprinklers, or electric detectors. When the
deluge valve opens, water flows into the
piping system and discharges from all open
sprinklers and nozzles.

(Electric Actuation Trim Shown)

DV-5A Size Range DN40 thru DN200 (11 ⁄ 2" thru 8")

Approvals UL, C-UL Listed & FM, VdS & LPCB Approved

Wet Pilot Actuation: 20,7 bar (300 psi)


Maximum Service
Dry Pilot Actuation: 17,2 bar (250 psi)
Pressure
Electric Actuation: Per Solenoid, see TFP2180

Thread x Thread, Groove x Groove,


End Connection
Flange x Flange, Flange x Groove

Flange Drilling ANSI, ISO, AS, & JIS


(Remote
Resetting TFP1306 - DV-5A
Trim Shown) TFP1325 - DV-5A Remote Resetting
Tech Data Sheet
TFP1326 - DV-5A Remote Resetting, Pressure
Reducing

Vertical installation • One internal working part, Diaphragm operation • No linkage or clapper assembly • Light weight ductile
iron body • Available with deluge and single & double interlock preaction trim • Internally & externally coated • Features external
resetting • For deluge, preaction & foam systems

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 75
Fire Suppression General Products Catalog

Deluge & Preaction Systems


Single Interlock Preaction Systems

Wet Pilot, Dry Pilot, or Electric Actuation

The DV-5A Supervised single interlock preaction systems


are used to protect areas where there is danger of
serious water damage that might result from damaged
automatic sprinklers or piping. Typically, such areas
include computer rooms, storage areas for valuable
artifacts, libraries and archives. Also, preaction systems
are effectively used to protect properties where a
prealarm of a possible fire condition may allow time for
fire extinguishment by alternate suppression means,
prior to a sprinkler discharge. In the event the fire cannot
be extinguished, the preaction sprinkler system will then
perform as the primary fire protection system.
Single interlock preaction systems employ automatic
sprinklers attached to a piping system containing 10
psi (0,7 bar) supervisory pressure, with a supplemental
electric fire detection system installed in the same area
as the sprinklers. Preaction systems with 10 psi (0,7 bar)
supervisory pressure may also be activated by either
wet or dry pilot sprinklers instead of electric detectors.
Actuation of the fire detection system from a fire
opens the deluge valve, allowing water to flow into the
sprinkler piping system and to be discharged only from
those sprinklers that have been operated by heat over
the fire. Loss of supervisory pressure from the system
piping as a result of damaged sprinklers or broken piping
will activate a trouble alarm to indicate impairment of
the system. The deluge valve will not open due to loss of
supervisory pressure.

DV-5A Size Range DN40 thru DN200 (11 ⁄ 2" thru 8")

Approvals UL, C-UL Listed & FM Approved

Maximum Service Wet Pilot Actuation: 20,7 bar (300 psi)


Pressure Preaction Dry Pilot Actuation: 17,2 bar (250 psi)
Single Interlock Trim Electric Actuation: Per Solenoid, see TFP2180

Thread x Thread, Groove x Groove,


End Connection
Flange x Flange, Flange x Groove

Flange Drilling ANSI, ISO, AS, & JIS

Tech Data Sheet TFP1425

Vertical installation • One internal working part, Diaphragm operation • No linkage or clapper assembly • Light weight ductile iron
body • Internally & externally coated • Features external resetting • For deluge, preaction & foam systems

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

76
www.tyco-fire.com

Deluge & Preaction Systems


Double Interlock Preaction Systems

Electric/Electric or Electric/Pneumatic Actuation

The DV-5A Double Interlock Preaction Systems are


designed for applications such as refrigerated areas
that require the maximum degree of protection against
inadvertent flooding of the sprinkler system piping.
The double interlock system consists of a deluge valve
and swing check valve with releasing trim featuring
both a solenoid valve and a dry pilot actuator in a series
configuration. The swing check valve isolates the body of
the deluge valve from the system air or nitrogen pressure
that holds the dry pilot actuator closed. The solenoid valve
remains closed until it is electrically energized by a deluge
releasing panel that responds to the operation of a fire
detection device.
In order to actuate the double interlock preaction system,
two independent events, caused by a fire condition, must
occur. The sprinkler system piping must lose air or nitrogen
pressure due to the operation of one or more sprinklers,
and the deluge releasing panel must energize and open
the solenoid valve upon the operation of a fire detection
device.
The double interlock system will operate only when both
the dry pilot actuator and the solenoid valve are open at
the same time. Opening of the dry pilot actuator only (for
example: a forklift truck accidentally dislodges a sprinkler)
or of the solenoid valve only (for example: accidental
operation of an electric manual pull station) will cause an
alarm, and will not trip the system or flood the sprinkler
system piping.

DV-5A Size Range DN40 thru DN200 (11 ⁄ 2" thru 8")

Approvals UL, C-UL Listed & FM Approved

Preaction Double Electric/Electric Actuation,


Interlock Trim Electric/Pneumatic Actuation

Thread x Thread, Groove x Groove,


End Connection
Flange x Flange, Flange x Groove

Flange Drilling ANSI, ISO, AS, & JIS

Tech Data Sheet TFP1450

Vertical installation • One internal working part, Diaphragm operation • No linkage or clapper assembly • Light weight ductile iron
body • Internally & externally coated • Features external resetting • For deluge, preaction & foam systems

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 77
Fire Suppression General Products Catalog

Deluge & Preaction Systems


RED-E-Cabinet®

Integrated Fire Protection Packages


The TYCO DV-5A Red-E Cabinet is a pre-assembled fire protection valve package enclosed
within a free-standing cabinet designed to occupy minimal floor space and to provide an
aesthetically pleasing enclosure for a fire protection valve riser. The entire package is pre-
wired and the water inlet and outlets to the valve riser are grooved to provide minimal
installation time. The valve package includes the system (manual) shut-off control valve,
automatic water control valve, and waterflow/supervisory switches. When dry pilot actuation
is utilized, a built-in air compressor with associated controls provides an automatic air supply
for the dry pilot lines.
Integral to the DV-5A Red-E Cabinet is a control panel and back-up batteries for providing
electrical alarm, supervisory, and trouble functions. All switches within the cabinet are pre-
wired to the control panel, making the electrical connections for power, detection circuits (as
applicable), and alarms the only remaining connections to complete the system.
In addition to the control panel being integral to the DV-5A Red-E Cabinet, windows have
been provided in the door for viewing the releasing panel functions and essential system
pressure gauges. A lock for the control panel access door is standard, and a lock for the
cabinet door is optional.

Size Range DN40 thru DN200 (11 ⁄ 2" thru 8") valve risers

Approvals UL, C-UL Listed & FM Approved

Maximum Service
20.7 bar (300 psi)
Pressure

Deluge Systems: TFP1301


- Wet Pilot Actuation
- Dry Pilot Actuation
- Electric Actuation
- Remote Reset
- Remote Reset Pressure Reducing
Types of System Single Interlock Preaction Systems: TFP1401
- Wet Pilot Actuation
- Dry Pilot Actuation
- Electric Actuation
Double Interlock Preaction Systems: TFP1401
- Electric/Pneumatic Actuation
- Electric/Electric Actuation

End Connection Groove x Groove


TFP1301 – Deluge Systems Cabinet
TFP1401 – Preaction Systems Cabinet

DV-5A Deluge Valve Tech Data Sheets


Deluge Wet / Dry /Electric - TFP1306
Tech Data Sheet
Remote Reset - TFP1325
Remote Reset Pressure Reducing - TFP1326
Single Interlock Wet / Dry / Electric - TFP1425
Double Interlock E/E E/P - TFP1450
Type A - TFP1485

Aesthetically pleasing appearance • Professionally assembled • Minimal installation time • Internally wired • Custom manufactured
• Model DV-5A deluge valve (standard) • All gauges and panel display are externally visible

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

78
General Purpose Valves
Designed for use in wet pipe sprinkler systems.

-- Prevention of Reverse Flow -- Closure of Fire Protection


After Operation
-- System Shut-off
-- Facilitation of System Testing
-- Sectional Control

79
Fire Suppression General Products Catalog

General Purpose Valves


PRV-1
Pressure Regulating Valve
Sizes DN50 thru DN200 (2" thru 8")

Approvals UL, C-UL Listed & FM Approved

Maximum Inlet
17,2 bar (250 psi)
Pressure

Field Outlet “Set 80 to 225 psi (5,5 to 15,5 bar) per FM Approval, or
Pressure” Range 80 to 150 psi (5,5 to 10,3 bar) per UL Listing

End Connection Thread x Thread, Groove x Groove, Flange x Flange

Tech Data Sheet TFP1580

The PRV-1 is intended to automatically maintain the outlet “set pressure” (static and residual) within a close range, regardless of
fluctuations in the higher pressure inlet line or varying flow rates. • Can be installed either vertically or horizontally • One piece,
one moving part diaphragm • In-line service (for maintenance) • Factory outlet “set pressure” of 8,6 bar (125 psi)

RV-1
Pressure Relief Valve
Sizes DN50 thru DN200 (2" thru 8")

Approvals UL Listed & FM Approved

Maximum Inlet
17,2 bar (250 psi)
Pressure

Field Relief “Set


2,1 to 17,2 bar (30 to 250 psi)
Pressure” Range

Temperature Range 10°C to 80°C (50°F to 175°F)

Body Style Globe or Angle Pattern

End Connection Thread x Thread or Flange x Flange

Flange Drilling ANSI, ISO, AS, & JIS

Tech Data Sheet TFP1585

Installation in any orientation • One-piece, one-moving-part diaphragm • Ceramic enamel-coated interior • Standard nylon-coated
exterior • Accurate pressure control • In-line service • No need to bleed trapped air from the diaphragm chamber

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

80
www.tyco-fire.com

General Purpose Valves


Model TJR Series Resilient-Seated Gate Valves
Outside Screw and Yoke

Sizes DN50 thru DN400 (2" thru 16")

Approvals UL & C-UL Listed & FM Approved

Maximum Working UL - 20,7 bar (300 psi) up to DN300 (12")


Pressure FM - 16,0 bar (232 psi) up to DN300 (12")

End Connection Flange x Flange, Flange x Groove, Groove x Groove

Flange Drilling ANSI, PN, AS

Tech Data Sheet TFP1541

TYCO TJ Series Resilient-Seated Gate Valves are offered in multiple end connection configurations including: Flange by Flange,
Flange by Groove, and Groove by Groove • Tapping bossed for up and downstream connection to valve trims • Ductile iron wedge
gate, fully encapsulated with EPDM rubber • Corrosion-resistant components

Model TJP Series Resilient-Seated Gate Valves

Non-Rising Stem, Cross Wall Indicator Post, Vertical Indicator Post


Valves: DN50 thru DN600 (2" thru 24")
Sizes Wall Post: DN50 thru DN300 (2" thru 12")
Vertical Post: DN50 thru DN400 (2" thru 16")

Approvals UL & C-UL Listed & FM Approved

Maximum Working UL - 20,7 bar (300 psi)


Pressure FM - 16,0 bar (232 psi)

End Connection Flange x Flange, Flange x Groove, Groove x Groove

Flange Drilling ANSI & ISO

Tech Data Sheet TFP1546

TYCO TJ Series Resilient-Seated Gate Valves are offered in multiple end


connection configurations including: Flange by Flange, Flange by Groove, and
Groove by Groove • Ductile iron wedge gate, fully encapsulated with EPDM
rubber • Corrosion-resistant components • Indicators provide external visual
indication of the open or shut valve condition as well as a locking mechanism to
secure a particular wedge position.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 81
Fire Suppression General Products Catalog

General Purpose Valves


BFV-300
Grooved Butterfly Valve
Sizes DN50 thru DN300 (2" thru 12")

UL Listed, FM Approved, CE Certified


VdS Approved, Russian Fire Certificate
Approvals
CNPP R1 Listed – APSAD
Listed by California State Fire Marshall
UL/FM Maximum Working Pressure
DN50 – DN200 (2" – 8") 20,7 bar (300 psi)
DN250 – DN300 (10" – 12") 12,1 bar (175 psi)
Maximum Working
Pressure VdS Maximum Working Pressure
DN50 – DN200 (2" – 8") 20,7 bar (300 psi)
DN250 (10") 16,0 bar (232 psi)
DN300 (12") 12,1 bar (175 psi)
Maximum Working
100°C (212°F) in accordance with UL 1091
Temperature

End Connection Groove x Groove

Tech Data Sheet TFP1511

BFV-300 (Normally Open) and BFV-300C (Normally Closed) • Indicating type valves provide visual indication of whether the valve is
open or closed • Suitable for use with grooved pipe couplings that are listed or approved for fire protection service

Wafer Style Butterfly Valve


Sizes DN50 thru DN300 (2" thru 12")

UL Listed, FM Approved, CE Certified


VdS Approved, Russian Fire Certificate
Approvals
CNPP R1 Listed – APSAD
Listed by California State Fire Marshall
UL/FM Maximum Working Pressure
DN50 – DN200 (2" – 8") 20,7 bar (300 psi)
DN250 – DN300 (10" – 12") 12,1 bar (175 psi)
Maximum Working
Pressure VdS Maximum Working Pressure
DN50 – DN200 (2" – 8") 20,7 bar (300 psi)
DN250 (10") 16,0 bar (232 psi)
DN300 (12") 12,1 bar (175 psi)
Maximum Working
100°C (212°F) in accordance with UL 1091
Temperature

End Connection Wafer

Tech Data Sheet TFP1516

Suitable for use installation between ANSI Class 125 or 150 flanges or PN10/16 flanges without the need for flange gaskets •
Indicating type valves provide visual indication of whether the valve is open or closed

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

82
www.tyco-fire.com

General Purpose Valves


CV-1F
Grooved Check Valve
Sizes DN50 thru DN250 (2" thru 10")

UL, C-UL Listed & FM & VdS Approved


Approvals Compliance with CE Pressure Equipment Directive
(PED) and Standards of Engineering Practice

Maximum Working UL/FM - 20,7 bar (300 psi)


Pressure VdS - 16 bar

End Connection Groove x Groove, Flange x Flange, Flange x Groove

Tech Data Sheet TFP1550

Can be installed either vertically or horizontally • Cut groove inlet and outlet connections • Suitable for use with grooved pipe
couplings that are listed or approved for fire protection service

CV-300B
Grooved End Swing Check Valve
Sizes DN100 (4")

Approvals UL, C-UL Listed & FM Approved

Maximum Working
20,7 bar (300 psi)
Pressure

End Connection Groove x Groove

Tech Data Sheet TFP1552

The TYCO Model CV-300B Grooved End Swing Check Valves are compact and rugged swing-type units that allow water flow in one
direction and prevent flow in the opposite direction • The Model CV-300B Check Valves are designed to minimize water hammer
caused by flow reversal • A resilient elastomer seal facing on the spring-loaded clapper ensures a leaktight seal and non-sticking
operation.

Lansdale Powerball 300


Bronze Butterfly Valve
1" - 2-1 ⁄ 2" NPT
Sizes
1-1 ⁄4" - 2-1 ⁄ 2" Grooved

Approvals UL Listed & FM Approved

Maximum Service
20.7 bar (300psi)
Pressure

Tech Data Sheet Contact Tyco for details

Bronze body butterfly valves are designed specifically for fire protection applications • Feature slow closure that substantially
minimizes water hammer • May be used as sectional or small system control valves where a distinct visual indication of the valve
status is required • Complete with Position Indicator and Integral Tamper Switch

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 83
Fire Suppression General Products Catalog

General Purpose Valves

Trim Valves

Tech Data Sheet Contact Tyco for details

For general service such as shut-off, throttling, or drain valves • Provide positive shut-off under normal operating conditions

DP-1
Dry Pilot Actuator
Approvals UL, C-UL Listed & FM, LPCB Approved
Maximum Water
17,2 bar (250 psi)
Supply Pressure
Maximum System Air
3,4 bar (50 psi)
(Nitrogen) Pressure
Tech Data Sheet TFP1380

Dry Pilot Actuator is an auxiliary releasing device • When the Model DP-1 actuates, it permits water pressure to be released from
the deluge or preaction valve differential chamber, thereby allowing the deluge or preaction valve to open • Designed for Preaction
Valves having double interlock electric/pneumatic release

ASV-1
Automatic Shut-Off Valve, Trim Component
Approvals UL, C-UL Listed & FM Approved

Maximum Working
17,2 bar (250 psi)
Water Pressure

Tech Data Sheet TFP1384

Intended for use with the DV-5 Deluge Valve in deluge and preaction systems • Prevents inadvertent resetting of the DV-5 Valve
after the DV-5 Valve initial operation • Provided as part of the DV-5 Valve trim arrangements, it is installed in the diaphragm
chamber supply connections

FSV-1
Fail-Safe Valve, Trim Component
Approvals UL, C-UL Listed & FM Approved

Maximum Working
17,2 bar (250 psi)
Water Pressure

Tech Data Sheet TFP1386

Intended for use with the Model DV-5 Deluge Valve in certain types of trim arrangements for deluge and preaction systems •
Prevents inadvertent resetting of the DV-5 after initial operation of the DV-5 Valve

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

84
Specialty Items & Antifreeze
Complement the system components used in fire protection systems.

-- UL Certified Antifreeze for -- Automatic Actuation of


Fire Sprinkler Systems Electric &/or Hydraulic Alarms

-- Automatic Quarterly Flow -- Eliminate Expelled Water


Switch Tests
-- Reduce Accidental Manual
Shut-Off

85
Fire Suppression General Products Catalog

Specialty Items
DD-1 (Drum Drip)
Wiliag™ Condensate Drain
Overall Length 615 mm (24")

Turning radius 64 mm (2.5")

Tech Data Sheet Contact Tyco for details

Ready to install • No power machine required for cutting pipe and making fittings • No power machine for repair • Eliminates
potential leaks • Eliminates labor of fabrication • Classic look of a professional job • Net weight only 6.25 lbs.

FL-1
Fusible Links

Approvals UL, C-UL Listed & FM Approved

Load Rating 2,3 to 22,7kg (5 to 50 lbs). Continuous Load

74°C (165°F), 100°C (212°F), 141°C (286°F),


Temperature Rating
162°C (360°F), 260°C (500°F)

Tech Data Sheet TFP1610

Heat-activated releasing device designed for installation in mechanically operated systems requiring a positive acting release
mechanism • Used extensively as releasing devices in restaurants and industrial fire protection systems, as well as in heat-activated
counterbalanced systems such as fire doors, dampers and kitchen chemical systems • Consists of fusible alloy sealed in the center
of a bronze tube by a stainless steel ball • When the alloy melts, the fusible assembly compresses, allowing it to eject from between
the two-piece strut, strut assembly separates, activating the intended fire protection system or device

MC-1
Manual Control Station

Approvals UL, C-UL Listed & FM Approved

Working Water
1,4 to 20,7 bar (20 to 300 psi)
Pressure

Minimum Ambient Dry Pilot Lines: -46°C (-50°F)


Temperature Wet Pilot Lines: 4°C (40°F)

Tech Data Sheet TFP1382

Provides a tamper resistant means for emergency release • Interconnection with the valves may be direct via hydraulic (wet) pilot
line or indirect via pneumatic (dry) pilot line to a Model DP-1 Dry Pilot Actuator

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

86
www.tyco-fire.com

Specialty Items
Model A
Pipe Line Strainers
Sizes DN80 thru DN250 (3" thru 10")

Approvals UL, C-UL Listed & FM Approved

Maximum Working
12,1 bar (175 psi)
Pressure

3,2 mm (1 ⁄ 8") diameter holes spaced to provide


Strainer Basket Screen
40 percent open area.

Tech Data Sheet TFP1640

Model A Pipe Line Strainers are designed for installation in the water supply connection to automatic sprinkler, water spray deluge,
foam-water deluge, or standpipe fire protection systems.

Model B-1
Pipe Line Strainers
Sizes DN80 thru DN150 (3" thru 6")

Approvals UL, C-UL Listed & FM Approved

Maximum Working
12,1 bar (175 psi)
Pressure

3,2 mm (1 ⁄ 8") diameter holes spaced to provide


Strainer Basket Screen
40 percent open area.

Tech Data Sheet TFP1642

The Model B-1 Pipe Line Strainers are designed for installation in the water supply connection to automatic sprinkler, water spray
deluge, foam-water deluge, or standpipe fire protection systems.

Model C
Pipe Line Strainers
DN150 x DN150 (6" x 6"),
Sizes
DN200 x DN200 (8" x 8")

Approvals UL, C-UL Listed & FM Approved

Maximum Working
7,2 bar (250 psi)
Pressure

3,2 mm (1 ⁄ 8") diameter holes spaced to provide


Strainer Basket Screen
40 percent open area.

Tech Data Sheet TFP1644

Compact lightweight welded hot dipped galvanized assembly with flanged inlet, outlet and flushing connection • Corrosion resistant
Type 304 stainless steel screen especially designed for low pressure loss

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 87
Fire Suppression General Products Catalog

Specialty Items
Signs
Identification Signs
229 x 178mm (9" x 7"), 152 x 51mm (6" x 2"),
Sizes 127 x 178mm (5" x 7"),
Round: 184mm Dia. (7-1 ⁄4" Dia.)
AIR CONTROL
AIR LINE
ALARM TEST
ANTIFREEZE SYSTEM
AUXILIARY DRAIN
CONTROL VALVE
Signs DRAIN
DRAIN VALVE
FIRE ALARM
HYDRAULIC CALCULATION
INSPECTORS TEST
MAIN CONTROL
MAIN DRAIN

Tech Data Sheet TFP1615

Designed to provide information to the end user about the sprinkler system and its components • Available with a variety of
wording combinations to meet the signage requirements of NFPA 13

SF-1
Sight Flow Connection
Sizes DN25 and DN50 (1" and 2")

Approvals UL Listed & FM Approved

Maximum Working
12,1 bar (175 psi)
Pressure

Tech Data Sheet TFP1635

Designed for use in fire protection systems as a means for visibly checking that water is flowing and filling the pipe at that point •
May be installed vertically or horizontally

Fire Department Connections


Straight & 90° Fire Department Connections

90° Side Outlet Pattern


Pattern
Straight -Through Siamese Pattern

Tech Data Sheet Contact Tyco for details

Designed for fire department use to increase water pressure and volume to automatic sprinkler system or standard-pipe system

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

88
www.tyco-fire.com

Specialty Items
AD-1
Automatic Drain Valve
The Model AD-1 Automatic Drain Valve forms a
part of the overall approvals given in the applicable
Approvals
technical data sheets for the TYCO Dry Pipe, Deluge,
or Preaction Valves.

Maximum Working
17,2 bar (250 psi)
Pressure

Tech Data Sheet TFP1630

Designed for use with Tyco Dry Pipe, Deluge, and Preaction Valves • Provided as a trim component for these valves, the Model
AD-1 Automatic Drain Valve is used to automatically drain the normally dry alarm lines

AD-2
Automatic Drain Valve
Approvals UL Listed & FM Approved

Maximum Working
12,1 bar (175 psi)
Pressure

Tech Data Sheet TFP1632

Designed to automatically drain water from fire protection equipment supply connections that are to be maintained normally dry •
Installed vertically and utilized with an open drain

Hangers
Pipe Hangers

Tech Data Sheet Contact Tyco for details

A full-line of pipe hangers for every fire protection need • Manufactured to meet the quality standards that the industry demands •
Meet the requirements of NFPA 13

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 89
Fire Suppression General Products Catalog

Specialty Items
The AQUAMIST System

AM4 Non-Automatic Open Type AM24 Automatic Type Mist Nozzle


4.7 lpm/bar 1/2, 0.33
K Factor
K Factor K=0.24 (3,5) gpm/psi 0.5

Approvals UL
Tech Data Sheet TFP2204
Tech Data
Tyco for details
Sheet
Open, directional mist nozzles • They are intermediate
Listed and Approved for Marine Type Approved by Lloyds,
pressure nozzles which utilize a single fluid jet impinging on
USCG, DNV, American Bureau of Shipping, MCA, Germanischer
a diffuser to produce a spray having a range of water droplet
Lloyd, Bureau Veritas • Intended Applications –  IMO
sizes suitable for the extinguishment of Class B fires, as well
Mandated Local Application System for Protection of Class A
as incidental Class A fires • Maximum utilization of water for
Machinery Spaces • Nozzle pressure: 12,1 to 17,2 bar.
flammable liquid fire protection.

AM10 & AM10B Non-Automatic AQUAMIST Mist Control Center (MCC)


Open Type Pump Skid Unit

K Factor K=0.24 (3,5)


Approvals FM

Tech Data Sheet TFP2210

Tech Data
TFP2270
Open mist nozzles • Designed for use in water “low pressure” Sheet
mist protection systems protecting flammable liquids and
turbine bearings • Minimal water demand • Min. operating
pressure is 11,6 bar (170 psi) The “MCC" Pump Skid Package is the self-contained control
center of the AQUAMIST System. The compact skid unit
has been professionally designed and assembled to ease
system installation and to meet the most stringent project
requirements. • Power must be provided for the control
cabinet and pump controller • Detection circuits must be
installed and wired to the control cabinet. • An adequate
water supply must be piped to the pump supply piping inlet.

How the AQUAMIST System Works

1 2
• Evaporation (heat extraction) is a • Water converts to vapor expanding by
function of surface area of droplets a factor of 1650 times
• Reducing droplet size increases • Oxygen is displaced and diluted,
OXYGEN
HEAT surface area thereby blocking it from the fuel
• Increase in surface area allows for
VAPOR source
larger cooling effect for a given flow • Higher heat level causes a faster
vaporization

3 4
• Fire extinguishment is improved with • Small water droplets tend to remain
LARGER DROPS direct contact of water droplets BLOCKS RADIANT
HEAT AND
suspended
PENETRATE TO
BURNING SURFACE • This type of extinguishment is COOLS GASSES • The expanding mist will expand
normally associated with and cool the gases and other fuels
standard sprinklers in the area
• Important part of operation if • Blocks the transfer of radiant heat
ventilation is a factor and Class A to the adjacent combustibles and
combustibles are present pre-wets them

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

90
Grooved Piping Products
Designed for use in fire protection systems.

-- Easy One-Bolt Coupling -- Quickly Join Steel Pipe


for Fast Install without Welding

-- Rigid Connections for Long -- Dampening Noise & Vibration


Runs & Risers Transmission

91
Fire Suppression General Products Catalog

Grooved Piping Products


Figure 579
One-Bolt Rigid Coupling
Sizes DN50 thru DN200 (2" thru 8")

Approvals UL, ULC Listed & FM Approved

Maximum Working
Up to 25,2 bar (365 psi)
Pressure

Grade “A” EPDM


Pre-Lubricate Gasket -34°C to 66°C (-30°F to 150°F)
Temperature

Tech Data Sheet TFP1856

For use in fire protection systems, the GRINNELL G-Fire Figure 579 Grooved Rigid Coupling is designed to make joining pipe faster
and easier than ever before. • Arriving pre-assembled and pre-lubricated, this One-Bolt Coupling is ready to install right out of the
box. • The unique design consists of a three-piece housing, a center-stop gasket, and just one bolt to tighten. • The center-stop
gasket ensures proper positioning on the pipe and enables easy push-on installation in both horizontal and vertical applications
across wet, dry and freezer systems. • The unique, one-bolt design eliminates alternate tightening for a faster, more efficient
installation. • It is capable of pressures up to 25,2 bar (365 psi) depending on pipe size and wall thickness when used in fire
protection services.

Figure 577
Rigid Coupling
Sizes DN25 thru DN300 (1" thru 12")

Approvals UL, ULC Listed & FM, VdS, & LPCB Approved

Maximum Working
24, 1 bar (350 psi)
Pressure

Grade “A” EPDM


Pre-Lubricate Gasket -34°C to 66°C (-30°F to 150°F)
Temperature

Tech Data Sheet TFP1854

For use in fire protection systems, the GRINNELL G-FIRE Figure 577 Grooved Rigid Coupling provides a rigid joint by firmly gripping
along the full circumference of the pipe grooves. Figure 577 Grooved Rigid Couplings are a proven dependable method of joining
pipe and are an economical alternative to welding, threading, or using flanges. • It is capable of pressures up to 24, 1 bar (350 psi)
depending on pipe size and wall thickness when used in fire protection services • Also available with tri-seal Grade “E” EPDM
gasket for dry pipe fire protection systems, vacuum systems, and freezer applications

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

92
www.tyco-fire.com

Grooved Piping Products


Figure 705
Grooved Flexible Coupling
Sizes DN25 thru DN300 (1" thru 12")

Approvals UL, ULC Listed & FM, VdS, & LPCB Approved

Maximum Working
20,7 bar (300 psi)
Pressure

Grade “E” EPDM


-34°C to 110°C (-30°F to 230°F)
Gasket Temperature

Tech Data Sheet TFP1820

The GRINNELL G-FIRE Figure 705 Flexible Coupling is capable of pressures up to 20,7 bar (300 psi) depending on pipe size and wall
thickness when used in fire protection services. It provides a dependable method of joining pipe and is suitable for use in a variety
of applications. • Provides the needed flexibility to accommodate differential movement • Also available with tri-seal Grade E EPDM
gasket for dry pipe fire protection systems, vacuum systems, and freezer applications

Figure 707
Flexible Coupling
Sizes DN32 x DN300 (1-1 ⁄4" x 12" )

Approvals UL, ULC Listed & FM, VdS, & LPCB Approved

Maximum Working
34,5 bar (500 psi)
Pressure

Grade “E” EPDM


-34°C to 110°C (-30°F to 230°F)
Gasket Temperature

Tech Data Sheet TFP1840

he GRINNELL 707 Flexible Coupling provides a dependable method ofjoining pipe and is suitable for use in a variety of applications
• Capable of pressures up to 34,5 bar (500 psi) depending on pipe size and wall thickness • Also available with tri-seal Grade “E”
EPDM gasket for dry pipe fire protection systems, vacuum systems, and freezer applications

Figure 716
Flexible Reducing Coupling
DN50 x DN40 (2" x 1-1 ⁄ 2") through
Sizes
DN200 x DN150 (8" x 6")

Approvals UL, ULC Listed & FM, VdS, & LPCB Approved

Maximum Working
24,1 bar (350 psi)
Pressure

Grade “E” EPDM


-34°C to 110°C (-30°F to 230°F)
Gasket Temperature

Tech Data Sheet TFP1830

The GRINNELL G-FIRE 716 Reducing Coupling allows easy transition between two different pipe sizes and replaces two
couplings and a reducing fitting • It is capable of pressures up to 24,1 bar (350 psi) depending on pipe size and wall thickness.
A flexible reducing coupling is not recommended for low-temperature applications. • Faster and easier than threading, welding
or using flanges

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 93
Fire Suppression General Products Catalog

Grooved Piping Products


Figure 71
Flange Adapter
Sizes DN50 x DN300 (2" x 12")

Approvals UL, ULC Listed & FM, VdS, & LPCB Approved

Maximum Working
17,2 bar (250 psi)
Pressure

Grade “E” EPDM


-34°C to 110°C (-30°F to 230°F)
Gasket Temperature

Flange Drilling ANSI Class 125 and 150, or PN16 standards

Tech Data Sheet TFP1880

The GRINNELL 71 Flange Adapter allows for a direct transition from flanged components to a grooved piping system • Capable of
pressures up to 17,2 bar (250 psi) depending on pipe size and wall thickness

Figure 730
Mechanical Tees & Crosses

Run Sizes DN50 x DN200 (2" x 8")

Branch Sizes DN15 to DN100 outlets (1 ⁄ 2" to 4" )

Approvals UL, ULC Listed & FM, VdS, & LPCB Approved

Maximum Working
20,7 bar (300 psi)
Pressure

Grade “E” EPDM


-34°C to 110°C (-30°F to 230°F)
Gasket Temperature

Tech Data Sheet TFP1860

The GRINNELL 730 Mechanical Tees & Crosses come with threaded or grooved outlets and can be used for any tee connection
where a threaded or grooved outlet is needed. • It can be used in place of a tee, a cross connection, or a welded outlet where a
threaded or grooved outlet is needed. • The Mechanical Tee is ideal for use in retrofit or equipment hookup installations as it can be
positioned along the pipe at the proper location in the field, ensuring exact lineup of the branch outlet connection.

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

94
www.tyco-fire.com

Grooved Piping Products


Grooved Fittings
Elbows, Tees, Reducers, Caps, Crosses and Flange Adapters
Sizes Range DN25 x DN300 (1" x 12" )

Approvals UL, ULC Listed & FM, VdS, & LPCB Approved

Maximum Working
20,7 bar (300 psi)
Pressure

Tech Data Sheet TFP1815

Provide an economical and efficient method of changing direction, adding an outlet, reducing or capping grooved piping systems •
Cast grooved fittings provide full flow characteristics • Full back stop behind the groove to ensure proper coupling engagement and
rigidity • 90° elbows and tees are also available in the “short pattern" style • Available painted or galvanized finish

Figure 510S Figures 221 & 321


Short Pattern 90° Cast Elbows Reducing Tees
Sizes DN50 – DN200 (2" thru 8") Sizes DN32 x DN25 thru DN300 x DN250
(1-1 ⁄4" x 1" thru 12" x 10")

Figure 323
Figure 510
Groove x Groove x Male Thread
90° Cast Elbows
Reducing Tees
Sizes DN25 – DN300 (1" thru 12")
Sizes DN50 x DN20 thru DN300 x DN250
(2" x 3 ⁄4" thru 12" x 10")

Figure 510DE Figures 391, 392, & 393


90° Drain Elbows Adaptor Nipples
Sizes DN50 – DN200 (2" thru 8") Sizes DN32 – DN300 (1-1 ⁄4" thru 12")

Figure 501 Figure 372


45° Cast Elbows Reducers, Small End Threaded (Male)
Sizes DN25 – DN300 (1" thru 12") Sizes DN40 x DN25 thru DN150 x DN125
(1-1 ⁄ 2" x 1" thru 6" x 5")

Figures 512 & 312


22-1/2° Elbows Figures 250, 550 & 350
Sizes DN32 – DN300 (1-1 ⁄4" thru 12") Concentric Reducers
Sizes DN32 x DN25 thru DN300 x DN250
(1-1 ⁄4" x 1" thru 12" x 10")
Figures 511 & 311
11-1 ⁄4° Elbows
Sizes DN32 – DN300 (1-1 ⁄4" thru 12")
Figures 327 Fabricated
Crosses
Figure 519S Sizes DN25 – DN300 (1" thru 12")
Short Pattern Tee
Sizes DN50 – DN200 (2" thru 8")

Figures 260 & 360


Figure 519
End Caps
Tees
Sizes DN25 – DN300 (1" thru 12")
Sizes DN25 – DN300 (1" thru 12")

Figure 320 Figure 341 & 342


Groove x Groove x Male Thread Flange Adapters
Reducing Tees Sizes DN25 – DN300 (1" thru 12")
Sizes DN25 – DN300 (1" thru 12")

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 95
Fire Suppression General Products Catalog

Grooved Piping Products


40-5
Strap Outlets
Pipe Run Sizes DN32 to DN65 Outlets (1-1 ⁄4" to 2-1 ⁄ 2")
1
Outlet Thread Sizes ⁄ 2" to 1" NPT Outlet

Approvals UL, ULC Listed & FM Approved

Maximum Working
12,1 bar (175 psi)
Pressure

Grade “E” EPDM


-34°C to 110°C (-30°F to 230°F)
Gasket Temperature

Tech Data Sheet TFP1720

The Figure 40-5 Strap is an economical alternative to welded pipe outlets on steel pipe. • Can be used with full lengths of pipe and
eliminates threading and welding, decreasing waste and installation time. • Can be used in wet, dry pipe, and deluge systems

ADACAP®
End of Line Sprinkler Fitting
Pipe Run Sizes DN40 to DN65 Outlets (1-1 ⁄ 2" to 2-1 ⁄ 2")
1
Outlet Thread Sizes ⁄ 2" to 1" NPT Outlet

Approvals UL, ULC Listed & FM, VdS, & LPCB Approved

Rated Pressure 20,7 bar (300 psi)

Tech Data Sheet TFP1815

Used to install the last sprinkler on grooved branch line piping or as a drain fitting • End-of-the-line sprinkler fittings eliminate the
need for an end cap and female outlet • Can be turned down for end of line drain

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

96
Tyco CPVC Pipe & Fittings
Manufactured with BlazeMaster® compound.

-- Light Hazard & Residential -- Connections to Copper


Occupancies & Steel Piping

-- Unfinished basements -- Resistance of Sweating,


Condensation, & MIC
-- Underground Water
Pressure Service

97
Fire Suppression General Products Catalog

CPVC Pipe & Threaded Fittings


CPVC Pipe
Sprinkler Pipe
Sizes DN20 thru DN80 (3 ⁄4" thru 3")
Pipe Length 10’ and 15’ Lengths
Approvals UL, C-UL Listed & FM,MEA, NSF, & LPCB Approved
Rated Pressure 12,1 bar (175 psi)
Maximum
65°C (150°F).
Temperature Rating
TFP1915 and
Tech Data Sheet
Installation Handbook - IH-1900

Manufactured with Lubrizol's BLAZEMASTER® compound • Produced from BlazeMaster® thermoplastic compound, RAPID
RESPONSE CPVC pipe is designed exclusively for use in wet and dry pipe automatic fire sprinkler systems. • Our CPVC pipe is easier
to install than traditional steel components, while providing superior heat resistance and strength compared to traditional CPVC
and PVC piping materials. • TYCO CPVC sprinkler pipe conforms to the requirements of ASTM F442 and is produced to SDR 13.5.
SDR (Standard Dimension Ratio) is the ratio of the outside pipe diameter to the wall thickness of the pipe.

Fittings
Sizes DN20 thru DN80 (3 ⁄4" thru 3")

Approvals UL, C-UL Listed & FM,MEA, NSF, & LPCB Approved

Rated Pressure 12,1 bar (175 psi)


Maximum
65°C (150°F).
Temperature Rating
TFP1915 and
Tech Data Sheet
Installation Handbook - IH-1900

Manufactured with Lubrizol's BLAZEMASTER® compound • Produced from BlazeMaster® thermoplastic compound, RAPID
RESPONSE CPVC fittings are designed exclusively for use in wet and dry pipe automatic fire sprinkler systems. • Our CPVC is easier
to install than traditional steel components, while providing superior heat resistance and strength compared to traditional CPVC
and PVC fitting materials. • Tees, Crosses, Reducing Tees & Crosses, 90° Elbows, 45° Elbows, Couplings, Bushings, Caps, Sprinkler
Head Adapters, Grooved Coupling Adapters, Female and Male Adapters, Sprinkler Adapter Tees, etc...

Rapid Seal Adapter (RSA) Fittings


Sizes DN20 thru DN25 (3 ⁄4" thru 1")

Pipe Thread 1
/2" NPS
Connection
UL, C-UL Listed & FM, & LPCB Approved
Approvals
Certified to all requirements of NSF/ANSI 61, Annex G

Rated Pressure 12,1 bar (175 psi)

Maximum
65°C (150°F).
Temperature Rating
TFP1925 and
Tech Data Sheet
Installation Handbook - IH-1900

Rapid Seal Adapter (RSA) Fittings are intended for use in fire protection sprinkler systems comprised of CPVC pipe and fittings.
A gasket housed within the fitting eliminates the need to apply sealant to sprinkler threads and reduces the effort necessary to
complete a leak-free installation. • No need for thread tape or sealant • No brass, no lead, no dezincification • Thanks to its brass-
free design, Rapid Seal is not prone to dezincification in hard water environments and also complies with growing state and federal
low-lead requirements for sprinkler and plumbing systems. • 90° Elbow, Straight Adapter, Spigot

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

98
www.tyco-fire.com

CPVC Pipe & Threaded Fittings


CPVC
Back-to-Back Fittings
Sizes DN20 thru DN80 (3 ⁄4" thru 3")

Approvals UL, C-UL Listed & FM,MEA, NSF, & LPCB Approved

Rated Pressure 12,1 bar (175 psi)


Maximum
65°C (150°F).
Temperature Rating
TFP1915 and
Tech Data Sheet
Installation Handbook - IH-1900

Included in the Tyco line of BLAZEMASTER® CPVC products • Allows two sidewall sprinklers to be piped from one fitting • Ideal
when the CPVC piping is located in a 3-1 ⁄ 2" (2" x 4") vertical wall, eliminating the need for extra nipples, fittings and sprinkler head
adapters typically associated with supplying two rooms with the same pipe • Specially designed and dimensioned to enable the
sidewall sprinklers to be recessed with 1 ⁄ 2" or 5 ⁄ 8" sheet-rock wall covering

CPVC to Copper Fitting


Sizes DN20 thru DN50 (3 ⁄4" thru 2" )

Approvals UL, C-UL Listed & FM,MEA, NSF, & LPCB Approved

Rated Pressure 12,1 bar (175 psi)


Maximum
65°C (150°F).
Temperature Rating
TFP1915 and
Tech Data Sheet
Installation Handbook - IH-1900

Transition to BLAZEMASTER pipe from traditional copper tube for plumbing services • Transition to steel or BLAZEMASTER
CPVC Fire Sprinkler System piping from traditional copper tube for plumbing services is fast, easy, and readily available in the most
complete fire sprinkler package in the industry

CPVC Hangers & SHB1 Head Set


3
Sizes ⁄4" thru 1" NPT

Approvals UL Listed

Material Galvanized aluminum, 20 gauge


TFP1920 and
Tech Data Sheet
Installation Handbook - IH-1900

“No Block Hanger" is a two hole strap that eliminates blocking to the beam when hanging CPVC pipe • The TYCO CPVC Hanger
Head Set Model SHB1 offers a time saving installation method for proper placement of an automatic sprinkler before the ceiling
is installed. • Positions the face of the pipe 1-1 ⁄ 2" off the face of the joist • Provides vertical restraint, eliminating need for
additional hangers

CPVC Supplies

TFP-600 One Step Solvent Cement (TFP1994)


Tech Data Sheet
and CPVC Installation Handbook (IH-1900)

One-Step CPVC Cement specifically formulated for use with BlazeMaster® pipe and fittings • BLAZEMASTER Caulk and
Walk® Firestop

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 99
Electrical Devices
Allow fire protection systems to be interfaced with alarm systems.

-- Battery Back-up in the Event -- Electric Release Technology


of Power Failure
-- Easier to Install, Set, &
-- Built-in High & Low Pressure Maintain than Mechanical
Alarm Supervision Accelerators

100
www.tyco-fire.com

Electrical Devices
VSR Waterflow Alarm Switch
Flow & Pressure Switch

Sizes DN50 thru DN200 (2" thru 8")

Tech Data Sheet Contact Tyco for details

Vane type waterflow switch for use on wet sprinkler systems • Actuated with a minimum flow of 10 gallons per minute • Retard
delay is an adjustable feature that can be set from 0 to 90 seconds • Flow condition must exist for the period of time necessary to
overcome the selected delay period

VSR Waterflow Alarm Switch for Small Pipe


Flow & Pressure Switch

Sizes DN25 thru DN50 (1" thru 2")

Tech Data Sheet Contact Tyco for details

Vane type waterflow switch for use on wet sprinkler systems • May also be used as a sectional water flow detector on large
systems • Installs directly into a threaded tee

Model PS10/PS40 Pressure alarm Switch


Flow & Pressure Switch

Tech Data Sheet Contact Tyco for details

Designed to detect a pressure increase or decrease in fire sprinkler systems • PS40 switches are primarily used to monitor low air
pressure conditions in dry systems • PS10 switch is appropriate for water flow detection

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 101
Fire Suppression General Products Catalog

Electrical Devices
PCVS Control Valve Supervisory Switch
Tamper & Alarm Switch

Tech Data Sheet Contact Tyco for details

Weather proof and tamper resistant switch for monitoring the open position of post indicator, butterfly and other types of fire
sprinkler/control valves

OSY-SU
Tamper & Alarm Switch

Tech Data Sheet Contact Tyco for details

Used to monitor the open position of an OS&Y (outside screw and yoke) type gate valve • Mounts conveniently to most OS&Y
valves ranging in size from DN50 to DN300 (2" to 12") • Can be used on some valves as small as 1 ⁄ 2" • Models include options for one
or two sets of SPDT (Form C) contacts.

Solenoid Valve
For Releasing Service

Sizes DN15 (1 ⁄ 2")

Approvals UL Listed, FM Approved & CE Certified

Working Pressure 1,4 - 17,2 bar (20 thru 250 psi)

Tech Data Sheet TFP2180

Used in conjunction with an electric releasing panel that is listed or approved (as appropriate) for fire protection releasing service,
and where the releasing panel is operated by listed or approved (as appropriate) electric fire detectors • Available in a variety of
voltages for both normal and hazardous locations

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

102
www.tyco-fire.com

Electrical Devices

4410-RC
Releasing Panel

Approvals UL Listed & FM Approved

Tech Data Sheet Contact Tyco for details

Provides the interface between detection system, deluge or single or double interlocked preaction valve, and signaling circuit and
devices in electrically actuated fire protection systems • Separate supervisory zone provided for electronic supervision of valve
position, low pressure, and other critical fire protection functions • Can be used in single zone, cross zone, sequential or cross/
sequential electric deduction systems • Has programming capability

Tank Mounted Air Compressor


For Dry Pipe Sprinkler Systems

Tech Data Sheet Contact Tyco for details

Designed for the same high-performance as base mounted units • Compressor is mounted on an air tank to offer further ease of
installation and availability • Automatic and safety features are built into the unit, reducing installation costs • Multiple dry systems
may be supplied from a single compressor tank that is a constant source of air • This is the recommended air supply method for all
dry pipe sprinkler systems

Base Mounted Air Compressor


For Dry Pipe Sprinkler Systems

Sizes DN25 thru DN50 (1" thru 2")

Tech Data Sheet Contact Tyco for details

Designed for high volume (cubic feet of air per minute) at the moderate pressures required for the system • Sized properly, these
will fill the system to 2.76 bar (40 psi) of air pressure in approximately 30 minutes as required in NFPA 13

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 103
Fire Suppression General Products Catalog

Electrical Devices

Riser Mounted Air Compressor


Fully Automatic

Tech Data Sheet Contact Tyco for details

Fully automatic and are designed for easy installation • Special mounting kits are available to facilitate riser mounting • Sized
properly, these compressors will fill a system to 2.76 bar (40 psi) within 30 minutes as required in NFPA 13

Model G16AC812
Automatic Supervisory Air Supply

Approvals UL Listed & CSA Certified

Nominal Supervisory
0,7 bar (10 psi)
Air Pressure

Tech Data Sheet TFP1620

Supplies and maintains air in single interlock preaction fire protection systems • Can be mounted on the floor, on a wall, or to the
system riser using optional brackets

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

104
www.tyco-fire.com

Electrical Devices

DAP Series
Dry Air Pac™

General’s DAP Series Dry Air Pac™ is an FM Approved, twin tower regenerative
dryer / compressor package. This turnkey system is designed to provide the
sprinkler system with moisture free air to a -40°F Dew Point. The air compressor
is designed to fill the sprinkler system in accordance with NFPA 13 standards,
as well as provide the higher pressure needed to allow the twin tower
regenerative dryer to function properly.
Prior to entering the regenerative air dryer, an air cooled aftercooler cools the
compressor’s hot discharge air to a maximum 100°F. A coalescing prefilter with
differential pressure gauge removes oil vapor and other contaminants that can
destroy the desiccant in the dryer towers. A combination particulate filter and
regulator prevents downstream migration of desiccant dust while regulating
air pressure to the sprinkler system.

The Dry Air Pac™ is controlled by one integrated control


panel complete with flow diagram display, 120 volt
control circuit with indicating lights for tower drying,
drain valve activation and compressor operation, along
with panel mounted hour meter, separate drain valve
duration and interval controls, drain valve on/off switch
and panel control on/off switch. Four panel-mounted
pressure gauges are provided for receiver, outlet and
drying tower pressures. Purge set pressure gauge is
separately mounted and conveniently located at the
purge valve for ease of setting the purge flow.
All components are pre-piped, pre-tested, and pre-
wired
for ease of mechanical and electrical installation on
site. Each unit includes a UL Listed, FM Approved Air
Maintenance Device. -100°F dew point is achievable -
consult factory for details.
Applications for the Dry Air Pac™ include, but are not
limited to Freezer Rooms, Cold Storage Warehouses,
Attic Spaces and Parking Garages.

Approvals FM Approved

Tech Data Sheet Contact Tyco for details

Combination afterfilter and regulator • A separate port is provided for attachment of a dewpoint-monitoring device • Oversized
mufflers • Fully integrated control panel • Compact air cooled after cooler • Prefilter with differential pressure • Vibration pads
• The Dry Air Pac™ comes fully charged with desiccant so that no on-site desiccant installation is required at startup • Separate
desiccant fill and drain ports are provided to allow re-charging of the dryer tanks without disassembly of the dryer component
piping • A coalescing filter, with integral differential pressure gauge, removes oil and water droplets prior to entry to into the
desiccant dryer • The single stage compressor allows for maximum efficiency. Standard equipment includes intercooler, oil fill/
breather, oil sight glass and easily removable drain plug

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 105
Fire Suppression General Products Catalog

Electrical Devices

Nitrogen Generators
Potter IntelliGen® Nitrogen Generators

Potter’s IntelliGen® Series of Nitrogen Generators are


specifically designed to generate on-site, 98%+ purity
nitrogen for use in fire protection sprinkler systems. When
used as a supervisory gas in fire sprinkler systems, nitrogen
slows corrosion, improves the life of your system, and
lowers maintenance costs.

The Potter IntelliGen® Series utilizes nitrogen membrane


technology for gas separation. Nitrogen membranes are
highly effective and a cost-conscious way of producing on-
site nitrogen. Acting as a gas filter, the nitrogen membrane
separates the oxygen and water vapor molecules in the air
from the nitrogen molecules. The high-purity nitrogen gas
is then piped through the air maintenance device and into
the fire protection system. As the system fills with nitrogen,
the remaining oxygen molecules in the fire protection
system are exhausted through a separate purge valve.

All systems are ready to be connected to a new or


existing fire sprinkler system, and include an integrated
air compressor, nitrogen membrane, all air filtration
equipment, tanks and the patent-pending Potter IntelliGen®
Controller. Each unit is designed to be turned on and
walk away. The built-in monitoring capabilities will make
corrections and alert the user to any necessary changes.
Alerts and notifications can be viewed locally or online via
the Potter IntelliView™ website.

Tech Data Sheet Contact Tyco for details

Potter’s IntelliGen Controller (Patent Pending) •


Fully automates the air and nitrogen fill procedure
• Advanced leak rate detection • Integrated Bypass
alarm • Web Enabled – system can be monitored
anywhere there is internet connectivity • Automatically
emails trouble alerts and maintenance reminders •
Includes all air compressors, tanks, filters, relief valves,
coolers, automatic drains, and gauges

* Largest ** Max
Unit Type Compressor Air Tank Nitrogen Tank
Model # Riser Fill Total System
(Shipping) Type/HP (Gal.) (Gal.)
(gal) Capacity (gal)
Wall Mount INS-100 160 675 Oil-Less, 1/4 HP -- 10
(1 Pallet) INS-250 300 1000 Oil-Less, 1/2 HP -- 10
Integrated INS-500 500 1850 Oil-Less, 1 HP 20 20
(1 Pallet) INS-1000 1000 3400 Oil-Less, 2 HP 20 20
INS-1500 2000 6200 Lubricated, 7.5 HP 80 60
Modular
INS-2000 2400 12000 Lubricated, 7.5 HP 80 60
(3 Pallets)
INS-2500 2400 24000 Lubricated, 7.5 HP 80 120
* At 40 PSI
** Assuming new system leak rate of 1.5 PSI per 24 hours

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

106
www.tyco-fire.com

Electrical Devices

LHD
Linear Heat Detection Cable

The Linear Heat Detection (LHD) cable is a combination of


advanced polymer and digital technologies which can be used
on any panel, and can detect heat anywhere along its entire
length.

At the core of the LHD cable is a twisted pair of extremely low


resistance, tri-metallic conductors, sheathed in new advanced
thermal polymers. These polymers are chemically engineered
to break down at specific fixed temperatures allowing the
twisted conductors to make contact and initiate an alarm. The
polymer used for the protective outer coating of LHD cable is
chemical resistant and UV protected. This allows the LHD cable
be used in a wide variety of installations and special hazard
applications.
Junction Box Cable Strain Relief Connectors
Spot
Detection Alarm/Release Thermo Cable®

Loop Cable Ties


Leader Wires or other approved fastener
Min. 18 AWG 18,000 ft. LHD Cable Secured to the Sprinkler Pipe
Releasing by Cable Ties Every 3 - 5 ft.
10 ft.
Ultra K17
Maximum 10,000 Feet of LHD Cable Per Zone
Upright Sprinkler
Spaced 10 ft. Apart
Sollenoid 10 ft.
Valve

J-Box or
ELR-Box

Potter® Electronic
Series PFC-4410-RC DV-5 Cable Strain Relief Connectors
Releasing Panel Deluge/Preaction Valve
3-5 ft.
Linear Heat Detection Cable allows a Quell designed fire
sprinkler system to be more efficient by quickly recognizing 3-5 ft.
LHD Cable Secured
the fire, and conveying the information back to the fire to the Sprinkler Pipe with
alarm panel. Guide Wire Every 3-5 ft. 3-5 ft.

Approvals UL, C-UL Listed & FM Approved


Tri-Metallic Core:
Steel provides tensile strength
68°C (155° F) (typical temperature)
Copper Increase conductivity Temperature
Tin for corrosion resistance 78°C (172° F), 88°C (190° F)
Range
105°C (220° F)
Advanced Polymer Thermal
Reactant Sheathing
Available
No Protective Tape Required Polyproplene, PVC, Nylon
Jacket Material

Resistance 0.05 ohms/ft Resistance per Twisted Pair


Chemical and UV Resistant
Polymer Outer Covering
RF Tested Up to 10,000 linear ft.

Wire O.D. 1⁄8” Tech Data Sheet Contact Tyco for details

Ideal for double interlock preaction detection • Install up to 10,000 linear feet per zone • Compatible with any conventional
releasing panel listed for fire • Can detect heat anywhere along the entire length of cable • Multiple alarm temperatures can be
incorporated in the same zone • Easy to add a module • Lower material & installation cost

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 107
Advanced Software for the Fire Protection Professional
SprinkCAD™ 3D
Users can design in full-3D using fast, accurate drawing and editing tools

SprinkCODE™ Connect
This web-based, interactive code guide includes multiple editions of NFPA
and EN codes

SprinkCALC
Perform hydraulic calculations and easily share them with an approving authority

SprinkFDT
This tool is the only UL Listed software for calculating fluid delivery time to
optimize dry system design

SprinkSLIC
Users can create and interpret pipe fabrication schedules utilizing this standalone
stocklisting software

REVIT® Tools for SprinkCAD


Optional add-on tools for use with SprinkCAD 3D™ or Classic help simplify
Revit® design

108
www.tyco-fire.com

Index
Model #. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page Model #. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
40-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 Figure 707. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
4410-RC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 Figure 71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
ACC-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Figure 716. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
AD-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 Figure 730. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
AD-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 FL-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
ADACAP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 FSV-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
AM10 and AM10B AQUAMIST. . . . . . . . . . . . . . . . . . 61, 90 FTR-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
AM24 AQUAMIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62, 90 G1, G3, G4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
AM4 AQUAMIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61, 90 G2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
AMD-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 G5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
AMD-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Grooved Fittings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
AMD-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Guards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 - 28
AP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Hangers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
AQUAMIST. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 HIP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
ASV-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 HV ”High Velocity”. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Attic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 ILLUSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
AV-1-300 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Issue D Quartzoid. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
B-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 K17-231. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
BB. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Lansdale Powerball 300. . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
BFV-300. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 LD "Large Drop" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
CC1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 LHD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
CC2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 LFII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 - 36
CC3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 MC-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
CHEC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 MCC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Cooling Tower. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Model A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
CPVC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 Model B-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
CPVC Pipe. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 Model C. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
CV-1F. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Model G16AC812. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
CV-1FR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 OSY-SU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
CV-300B. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 PCVS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
D3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 PRV-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
D3S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 PS10, PS40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
D4a. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 QRS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
DAP Series. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 RAVEN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
DD-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 RC-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
DDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 RCP-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
DP-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 RED-E-Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
DPV-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 Resi-Riser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
DS-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 - 40 RFII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 16
DS-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 - 41 RFII-MRI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 17
DS-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 RFIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
DS-C. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 RM-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
DS-ECC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 RSV-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
DSB-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 RV-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
DV-5A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 SD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
EA-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60 SF-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
EC-11 & EC-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 SHB1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
EC-25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Signs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
EC-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 - 13 TFP PH2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
EC-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 TFP PH5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
EC-HS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 TN-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
ELO SW-20/SW-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 TN-25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
ELO-231. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 TY-B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5, 24, 25, 50 - 53
ELO-231 FRB. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 TY-FRB. . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 14, 25, 26, 51 - 54
ELO-231B. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 TY-FRL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9, 14, 27
ELOC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 TY-L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 26
ESFR-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 TYCO LFP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
ESFR-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 - 21 Type DN-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
ESFR-22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 ULTRA K-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
ESFR-25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 VIZOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
F822 thru F834 Mulsifyre. . . . . . . . . . . . . . . . . . . . . . . . . . 62 VSR. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
F822S thru F834S Mulsifyre. . . . . . . . . . . . . . . . . . . . . . . . 62 WMA-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Figure 577. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 WS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Figure 579. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 WS-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 705. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 WSG-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 109
Fire Suppression General Products Catalog

Index
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
Air Compressor, Tank Mounted . . . . . . . . . . . . . . . . . . . . 103 Dry Pipe Valve Accelerator . . . . . . . . . . . . . . . . . . . . . . . . . 71
Air Maintenance Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Dry Sprinkler Boot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Alarm Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 - 102 Dry Type Recessed Horizontal Sidewall . . . . . . . . . . . . . 34
Alarm Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Dry Type Recessed Pendent . . . . . . . . . . . . . . . . . . . . . . . . 34
Attic Plus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Dry-Type Pendent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Automatic Drain Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 DS-1 Dry Sprinkler Guards. . . . . . . . . . . . . . . . . . . . . . . . . . 43
Automatic Protectospray Directional Spray Nozzle . . . 60 DS-1 Stainless Steel. . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 - 40
Automatic Shut-Off Valve, Trim Component. . . . . . . . . . 84 Duct Deluge System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Automatic Supervisory Air Supply. . . . . . . . . . . . . . . . . . 104 Elbows, Tees, Reducers, Caps, Crosses and .
Automatic Type Mist Nozzle. . . . . . . . . . . . . . . . . . . . . . . . 62 Flange Adapters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

Back-to-Back . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Electronic Accelerator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

Back-to-Back Fittings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 Electronic Dry Pipe Accelerator . . . . . . . . . . . . . . . . . . . . . 71

Base Mounted Air Compressor. . . . . . . . . . . . . . . . . . . . . 103 End of Line Sprinkler Fitting. . . . . . . . . . . . . . . . . . . . . . . . . 96

Bronze Butterfly Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Escutcheon Plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 - 57

Cap Utility Tool for Concealed Sprinklers. . . . . . . . . . . . . 33 Escutcheons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 - 57

Caps. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 Extended Coverage Concealed Pendent . . . . . . . . . . . . . 42

Combustible Concealed Space Sprinklers. . . . . . . . 48 - 49 Extended Coverage Horizontal Sidewall . . . . . . 39, 40, 42

Compressor Control Type Air Maintenance Device . . . 72 Extended Coverage Pendent. . . . . . . . . . . . . . . . . . . . . . . . 41

Concealed Horizontal Extended Coverage Sidewall. . . 16 Extra Large Orifice Concealed Pendent . . . . . . . . . . . . . . 15

Concealed Pendent. . . . . . . . . . . . . . . . . . . . . . . 7, 16, 17, 41 Fail-Safe Valve, Trim Component. . . . . . . . . . . . . . . . . . . . 84

Concealed Standard Coverage Pendent Sprinklers. . . . . . 7 Fire Department Connections. . . . . . . . . . . . . . . . . . . . . . . 88

Conventional (Old Style). . . . . . . . . . . . . . . . . . . . . . . . 50 - 52 Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

Cooling Tower Nozzle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Fixed Temperature Release. . . . . . . . . . . . . . . . . . . . . . . . . 52

Corrosion Resistant Duct Nozzle, Open, . Flange Adapter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94


Medium Velocity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Flange Adapters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Cover Plate & Protective Cap Utility Tool for . Flat Plate Concealed Extended Coverage .
Concealed Sprinklers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Horizontal Sidewall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
CPVC Hangers & SHB1 Head Set. . . . . . . . . . . . . . . . . . . . 99 Flat Plate Concealed Pendent . . . . . . . . . . . . . . . . . . . . . . 32
CPVC Supplies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 Flexible Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
CPVC to Copper Fitting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 Flexible Reducing Coupling. . . . . . . . . . . . . . . . . . . . . . . . . 93
Crosses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 Flow & Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Deluge Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Flush Escutcheon. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Deluge Valve, External Resetting Diaphragm Style. . . . 74 For Dry Pipe Sprinkler Systems. . . . . . . . . . . . . . . . . . . . . 103
Directional Spray Nozzle. . . . . . . . . . . . . . . . . . . . . . . . 59 - 60 For Releasing Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Directional Spray Nozzles, Open, High Velocity. . . . . . . 62 For The Protection of Ventilation Ductwork .
Directional Spray Nozzles, Open, Medium Velocity . . . 61 Handling Corrosive Gases . . . . . . . . . . . . . . . . . . . . . . . . . . 64

Directional Spray Nozzles, Open, With Strainers, . Fully Automatic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104


High Velocity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Fusible Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Domed Plate Concealed Pendent. . . . . . . . . . . . . . . . . . . .33 Grooved Butterfly Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Double Interlock Preaction Systems. . . . . . . . . . . . . . . . . 77 Grooved Check Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Drum Drip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 Grooved End Swing Check Valve. . . . . . . . . . . . . . . . . . . . 83
Dry Air Pac. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Grooved Fittings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Dry Pilot Actuator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Grooved Flexible Coupling. . . . . . . . . . . . . . . . . . . . . . . . . . 93
Dry Pipe Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 High Temperature, Upright & Pendent. . . . . . . . . . . . . . . 50

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

110
www.tyco-fire.com

Index
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
High Velocity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Releasing Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Horizontal & Recessed . Residential. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Horizontal Sidewall . . . . . . 8, 9, 13, 14, 31, 32, 35, 36, 40 Residential Control Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Horizontal Spray Nozzle, Open. . . . . . . . . . . . . . . . . . . . . . 60 Residential Shutoff Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Horizontal, Recessed Horizontal Sidewall & . Resilient-Seated Gate Valves. . . . . . . . . . . . . . . . . . . . . . . . 81
Vertical Sidewall. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5, 6
Retard Chamber. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Identification Signs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Rigid Coupling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Institutional Horizontal Sidewall Sprinklers. . . . . . . . . . . 47
Riser Check Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Institutional Pendent & Horizontal Sidewall . . . . . . . . . . 46
Riser Manifolds. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Institutional Sprinklers . . . . . . . . . . . . . . . . . . . . . . . . . . 46, 47
Riser Mounted Air Compressor. . . . . . . . . . . . . . . . . . . . . 104
Integrated Fire Protection Packages. . . . . . . . . . . . . . . . . 78
Sight Flow Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Large Drop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Single Directional. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Linear Heat Detection Cable. . . . . . . . . . . . . . . . . . . . . . . 107
Single Interlock Preaction Systems. . . . . . . . . . . . . . . . . . 76
Manual Control Station. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Solenoid Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Mechanical Tees & Crosses. . . . . . . . . . . . . . . . . . . . . . . . . 94
Sprinkler Guards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 - 28
Model PS10/PS40 Pressure alarm Switch. . . . . . . . . . 101
Sprinkler Guards with Shield. . . . . . . . . . . . . . . . . . . . . . . . 28
NFPA 13 Optimized Sprinklers . . . . . . . . . . . . . . . . . 35 - 36
Sprinkler Head Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Nitrogen Generators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Sprinkler Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Nitrogen Maintenance Device . . . . . . . . . . . . . . . . . . . . . . 72
Straight & 90° Fire Department Connections . . . . . . . . 88
Non-Automatic Open Type. . . . . . . . . . . . . . . . . . . . . . . . . .61
Strap Outlets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
One-Bolt Rigid Coupling. . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Tamper Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Outside Screw and Yoke. . . . . . . . . . . . . . . . . . . . . . . . . . . .81
Tank Mounted Air Compressor. . . . . . . . . . . . . . . . . . . . . 103
PCVS Control Valve Supervisory Switch . . . . . . . . . . . . 102
Tees. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Pendent. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 - 21, 39, 40
Trim Valves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Pendent & Horizontal Sidewall Sprinklers. . . . . . . . . . . . 46
Type 1 and 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Pendent & Recessed Pendent. . . . . . . . . . . . . . . . 12, 30, 31
Upright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11, 19-21 48, 49
Pendent & Upright. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 - 23
Upright & Pendent Foam-Water Sprinkler. . . . . . . . . . . . 63
Pendent & Upright, Intermediate Level . . . . . . . . . . 24 - 27
Upright & Pendent Sprinklers. . . . . . . . . . . . . . . . . . . . . . . 53
Pendent, Recessed Pendent & Domed Concealed . . . . 35
Upright, Control Mode Specific Application. . . . . . . 21, 24
Pendent, Upright & Horizontal Sidewall. . . . . . . . . . . . . . 38
Upright, Pendent & Horizontal Sidewall Sprinklers . . . 54
Pipe Hangers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Upright, Pendent & Recessed Pendent. . . . . . 5, 6, 8, 9, 11
Pipe Line Strainers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Vertical or Cross Wall Post Indicator . . . . . . . . . . . . . . . . 81
Potter IntelliGen Nitrogen Generators. . . . . . . . . . . . . . . 106
Vertical, Horizontal & Recessed .
Pressure alarm Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 Horizontal Sidewall Sprinklers . . . . . . . . . . . . . . 5, 6, 48, 53
Pressure Reducing Type Air Maintenance Device. . . . . 72 Wafer Style Butterfly Valve . . . . . . . . . . . . . . . . . . . . . . . . . 82
Pressure Regulating Valve. . . . . . . . . . . . . . . . . . . . . . . . . . 80 Water Motor Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Pressure Relief Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Wet Pilot, Dry Pilot, or Electric Actuation. . . . . . . . . 75 - 77
Protectospray Directional Spray Nozzle. . . . . . . . . . 59 - 60 Wiliag Condensate Drain. . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Rapid Seal Adapter (RSA) Fittings. . . . . . . . . . . . . . . . . . . 98 Window Sprinklers, Horizontal &.
RAVEN Studio Sprinkler. . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Pendent Vertical Sidewall . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Recessed Escutcheons and Protective Paint Caps . . . . 56
Reducing Coupling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93

Always refer to the product’s Technical Data Sheet for a complete description of all Listing and Approval criteria, design parameters, installation instructions, care and maintenance guidelines, and our limited warranty.

www.tyco-fire.com 111
About Johnson Controls:
At Johnson Controls, we transform the environments where people live, work, learn and play. From optimizing
building performance to improving safety and enhancing comfort, we drive the outcomes that matter most.
We deliver our promise in industries such as healthcare, education, data centers, and manufacturing. With
a global team of 105,000 experts in more than 150 countries and over 130 years of innovation , we are the
power behind our customers’ mission. Our leading portfolio of building technology and solutions includes
some of the most trusted names in the industry, such as Tyco®, ANSUL®, YORK®, Metasys®, Ruskin®, Titus®,
Frick®, PENN®, Sabroe®, Simplex® and Grinnell®. For more information, visit www.johnsoncontrols.com or
follow us @johnsoncontrols on Twitter

Australia & New Zealand Singapore & Southeast Asia


Tel: +61 3 9313 9700 Tel: +65 6577 4360

India Region South Korea


+91 22 6628 6628 Tel: +82 31 737 3881

Middle East Taiwan, China; Hong Kong, SAR, China;


Tel: +971 4 455 0700 Macau, SAR, China
Tel: +886 2 2698 3559

Products displayed are for visual representation only. Actual products may vary. The information provided in this
brochure is provided for informational purposes only. The materials are general in nature; they are not offered as
advice on a particular matter and should not be relied on as such. The materials contained in this brochure are the
copyrighted property of Johnson Controls unless a separate copyright notice is placed on the material.

www.tyco-fire.com

© 2019 Johnson Controls. All rights reserved. FSP2019024  Rev. 10-2019

You might also like