Alpha Lubricator Manual 140809
Alpha Lubricator Manual 140809
Table of Contents
1. General Information 9
1.1 Main components 9
1.2 Working principle 12
1.3 Guidance values automation 13
Table of Contents
Alpha Lubricator System
Page
4. Configuration of BCU 39
4.1 Injection rate with BCU in control 39
4.2 Detection rate (BCU take over from MCU) 39
4.3 Number of cylinders for the engine 40
4.4 BCU board revision 40
4.5 Slow down output 40
4.6 Number of lubricators 41
4.7 Upload of BCU basic program 41
Table of Contents
Appendix 1
Function of the LEDs in the Intermediate Box 65
Appendix 2
Control Unit Cylinder Lubrication - Logic Diagram 66
Appendix 3
Replacement of MCU, BCU, SBU Boards 75
Appendix 4
Cylinder oil feed rate during running-in 77
Appendix 5
3045-0110-0001.1
Appendix 6
Back-up Control Unit 88
List of Abbreviations:
AC Alternating Current
DC Direct Current
IC Integrated Circuit
1. General Information
The Alpha Lubricator System Layout is shown in the diagram below: Alpha Lu-
bricator System Layout
TANK
LUBRICATOR
3045-0110-0001.1
HMI
2008-12-12
ALCU
Description
PUMP
STATION Pipe System
Electrical Connection
Lubricator units
707X03 40C 01
lator on the outlet side of each lubricator,
with nitrogen pre-pressure of 1.5 bar.
XZ707.40A
XZ707.40A 03 03
XZ707.40A02
2008-12-12
The three main electronic components for controlling the lubricating oil are com-
prised in one steel cabinet -the so-called ALCU unit.
Description
SBU
BCU
707-X01 40C 11
The 24 V DC power is supplied from two individual power sources, from different
breakers in the UPS unit. Please note that some installations might be connected
differently by the shipyard.
Load transmitter
3045-0110-0001.1
2008-12-12
Description
XZ707.40A 05
Backup trigger system
XZ707.40A05
The backup trigger system comprises two
tacho pickups in a box at the turning wheel,
thereby transmitting the engine rpm to the
BCU. The backup pickups are also connect-
ed to the MCU for surveillance purposes.
"#5æINæ#TRL
æ
%NGINEæSPEED
æ
)NDEX
,UBRICATION
ª# RPM
K.M
)NDEXæFAILURE
-ARKTRIGæFAIL
&EEDBACKæFAIL
#OMMONæALARM
2008-12-12
• The pump station supplies the Alpha Lubricators with 40-50 bar oil pres-
sure.
• The MCU controls the oil injection by activating a solenoid valve situated
on the relevant lubricator.
• A feedback signal from each lubricator indicates that oil injection has
• Timing is based on two signals from the angle encoder, a TDC cyl. 1
marker and a crankshaft position trigger. The Alpha Lubricator system is
normally timed to inject cyl. oil into the piston ring pack during the com-
pression stroke.
• The injection frequency is calculated from index and speed, and is nor-
mally proportional to the engine MEP. However, a power Mode or RPM
Mode is possible.
• The basic cylinder oil feed rate at MCR (100%) is calculated as a correla-
tion between a number of injections / rpm and the stroke of the lubrica-
tors.
• On the HMI panel, adjustment of lubrication feed rate for individual cylin-
ders is possible between 60% and 200%. Default value is 100%.
• During normal operation the system is controlled by the MCU. If any fail-
ures are detected in the system, a common alarm is activated in the con-
trol room. The detailed alarm reference is displayed on the HMI panel.
• The BCU is based on random timing and RPM Mode. The injection fre-
quency is adjustable on the BCU and is normally, as minimum, set to the
basic cylinder oil feed rate for the engine, plus 50%.
1. As standard, the HMI panel (for description, see Section 3), a three-posi-
tion mode switch, and an indicator lamp are mounted in the engine con-
trol room.
one of the pump station starter panels. In this case a local/remote switch
has to be installed.
2.2 Control buttons and indicator lamps on pump station starter panels
Each starter panel contains the following switches, buttons and lamps:
1. To fill the pump station with cylinder oil, open the valves for the cylinder
oil supply line and the venting cock (if installed). Close the venting cock
when cylinder oil flows out into the venting line.
2008-12-12
4. Check that the pressure differential indicator on the pump station filter is
green, when one pump is operating.
Description
XZ707.40A 08
6. Press [esc] and [prelub] at the
same time on the HMI panel to
activate the test sequence, and
check that all lubricators are
operating correctly by watching
the LEDs (feedback signals) on
the intermediate boxes for each
lubricator.
At commissioning or after
overhaul of the system, check
visually from the scavenge
air receiver that all non-return
valves inject cylinder oil into the
cylinder liners.
7. Stop the pumps manually, and switch to “Remote” on the starter panels.
The Alpha Lubricator System is now ready for normal operation.
1. Upon start of the engine’s auxiliary blowers, the Alpha Lubricator Sys-
tem is programmed to carry out automatic prelubrication. The pump sta-
tion will automatically stop if the engine is not started shortly after.
2. Check that the pump station automatically starts up when the engine is
started, and that the cyl. oil pressure builds up to 40-50 bar.
3. Check that all the green LEDs flash on the intermediate boxes for each
3045-0110-0001.1
lubricator.
2008-12-12
4. Check that no alarm is detected in the control room and on the HMI
Description
panel.
In order to prevent this, the circulation of the cylinder oil in the main
Alpha Lubricator System
This by-pass valve is only introduced on engines with two lubricators per
cylinder.
On engines with one lubricator per cylinder, the valve on the cylinder
block intended for emptying the accumulator at overhaul can also be
used as a by-pass valve.
The main purpose of the new by-pass valve is to heat up the pipes by
circulating the cylinder oil in the main pipes with open by-pass valve be-
fore engine start. The valve is to be closed just before engine start.
2. Inspect the local oil pressure gauge on the pump station. Normal service
value = 40-50 bar.
Bar graphs
The two upper bar graphs display relative values in percent of engine speed and
fuel index (≈ mep%), respectively. The range is from 0 to 120 percent, where 100
percent corresponds to the physical values at MCR. The third upper bar graph
displays oil pressure in the range of 0 to 100 bar.
Five LEDs for indication of fault category are placed below the numerical display,
3045-0110-0001.1
as follows:
2008-12-12
• Marker/Trigger failure
• Feedback failure
Buttons
[ q ] Move down in the HMI panel menu structure. See item 3.2.9.
[esc] + [prelub] Starts test sequence of 1000 pre lubrications. The test se-
quence is stopped by pressing [prelub] again.
This section describes the menu system in the HMI-panel numerical display. Six
of the most common manoeuvres are described below and the complete struc-
ture and parameters are shown in items 3.2.9 and 3.2.10.
3.2.1 Navigation HMI panel menu system is a hierarchic menu system. The following four buttons
principle are used to navigate through the menu system.
[ q ] Move down in the HMI panel menu structure. See item 3.2.9.
2008-12-12
[esc] Move to the left in the HMI panel menu structure. See item 3.2.9.
Description
[enter] Move to the right in the HMI panel menu structure. See item 3.2.9.
3.2.2 Reading of Press [ p ] or [ q ] until rXXX is shown in the display (Note that this value is an
Alpha Lubricator System
4. Press [esc] to return to main menu (one press [esc] = one step back-
wards).
The value of Str.lo represents the five rightmost figures and the value of
Str.hi the five leftmost figures.
Example:
Str. hi Str. lo
707-X10 40C 3235
Total number
of strokes = 12345 67890 =1234567890
The total stroke amount is used to calculate the amount of cylinder lube oil used
within a specified amount of time. The following formula can be used:
active alarms [AL- For explanation of the alarm code see the alarm list in Section 5.
RXX]
2. To clear a logged alarm, press [enter] when the alarm is shown in the dis-
2008-12-12
play. To clear all logged alarms, press [enter] for 5 seconds while an LALxx
is shown in the display.
Description
For systems with Alpha ACC (Adaptive Cylinder oil Control) the feed rate is set
proportionally to the sulphur content in the fuel oil. The feed rate setting percent-
age can be obtained from the regulation plates.
Reference is made to all time latest service letter concerning cylinder condition.
An example is given in appendix 4.
4. Press [enter] and the current feed rate is shown. Please note that if SEt.
Al was selected the value shown is the last value saved in SEt.Al, and
this value is not true if any cylinder has been individually adjusted since.
6. Press [enter] - The value is stored in the computer memory, and the main
3045-0110-0001.1
change of operat-
ing pumps (master 2. Press [esc] + [pump 1] or [pump 2] (pump not running).
pump)
3. New master pump is now chosen and running.
3.2.9 Menu struc- The following pages show how to navigate in the HMI-panel menu structure.
ture
3045-0110-0001.1
2008-12-12
Description
up = [?
] down = [?
] right = [ENTER] left = [ESC]
tEcH SoFt
(technical parameters, advanced (MCU software revision number)
parameters)
FPgA
(FPGA software revision number)
Connt Par.Ch
(connection test (MCU program parameter check sum)
menu)
SEtuP Par
(setup menu) (read out of all setup parameters)
(MBD Service)
of solenoid valves)
.. value
Co.ALr Lub. 1
2008-12-12
A activation
(manuel
(manual activation of MCU common
alarm output - MCU J32 terminal 1,2)
oFF / on
Description
XXX [°]
toil [°C]
(norm 40-60 °C)
(alarm 70 °C)
in.hi [%]
r XXX (index high, theoretical index
(total stroke/min) % at 20mA)
FE.AD int.
(feed rate regulation Menu navigation (internal, LCD controlled
parameter adjustment) internally)
press "?
? " to select
press "ENTER" to SAVE
n.PrL on
(number of pre-lubrications) Po. underneath (permanent on)
(For Test Only)
(power proportional feed rate
calculation)
r.run oFF
(rpm run adjustment) rPnn (permanent off)
(rpm proportional feed rate
calculation)
Ang.dE
(angle deviation limit bet. nnep
MCU and BCU tacho)
(MEP, mean efficient pressure
prop. feed rate calc..)
Pu
3045-0110-0001.1
Str.hi
(total lubricator stroke counter
Description
adjustment)
Str.Lo
(total lubricator stroke counter
adjustment, )
Par
('raw' adjustment out of all
setup parameters)
diSP n.PrL
(display menu) (number of pre-lubrications)
(norm. 12)
Auto
(change master with interval
of Pu.int )
bacup
(backup mode, fixed master
pump)
Pu.dEF
(default pump selection, pump
1 or 2)(norm. 1)
Str.hi
(total lubricator stroke counter Pu.int [hour] XXX
adjustment) (pump interval time) press "?
? " to change
(norm. 12) press "ENTER" to SAVE
Str.Lo
(total lubricator stroke counter
adjustment, )
Par XXX
3045-0110-0001.1
Description
Caution !
Adjusting of the values in the "Par" menu may cause damage to the
engine and should be done by authorised personnel only
The specific crank angles for oil injection for each lubricator. Normally it is the
crank angle at the point where No. 1 piston ring passes the oil quills on the up-
ward stroke of the piston.
The number consists of an online measurement of the angle for the first flank of
the feedback signal plus the angle corresponding to the hydraulic delay time.
Only active when engine is running ahead. Normal value for cylinder one is around
270 to 310°.
Example:
0.1;inj / rev=
1 1
rE.inj = 4 revolutions => basic frequency 0.25 ;inj / rev =
rE .inJ 4
Code number for active alarms, where the number ‘XX’ represents the alarm
code. For explanation of the alarm code see the alarm list in Section 5.
The Maximum allowable angle difference between the marker signal (TDC signal)
2008-12-12
from the encoder (or trigger ring) and the marker signal from the BCU pickups.
Only valid when engine is running ahead. Normal value is 2 degrees.
Description
Indication of actual crank angle from the shaft encoder. Blocked when the engine
is running. Only valid when continuously turned in same direction by turning gear
and after having passed TDC cyl. 1. The indication is sensitive to rocking motion
and should therefore only be used as an indication.
Display menu. Values and parameters are displayed, but cannot be changed
from diSP menu.
Feed rate setting high limit. The maximum possible feed rate setting on the HMI
panel. The value is a percentage of the basic recommended feed rate setting.
Normal value is 200 %.
Feed rate setting low limit. The minimum possible feed rate setting on the HMI
panel. The value is a percentage of the basic recommended feed rate setting.
Normal value is 50%.
Feed rate setting adjustment. The feed rate can be adjusted individually for each
cylinder or for all cylinders at one time with the SEt.Al function. Please note that
the value shown when entering the SEt.Al menu is the last value saved in the
SEt.Al menu. Thus if the cylinders have been adjusted individually since, the value
shown when entering the SEt.Al function is no longer true for all cylinders.
100 % feed rate setting normally corresponds to basic setting. (Reference is ma
de to the guidelines for cylinder lubrication)
Feed rate increase in case of scuffing. Input for each cylinder on the MCU board
can receive signal from a cylinder liner temperature monitoring system. If begin-
ning scuffing is detected, a signal can be given and extra lubrication activated.
Please contact MAN B&W if this function is needed. Normal value is 200 %
FPGA software revision number. The IC (Integrated Circuit) (u33) contains the
program for the FPGA. If the FPGA code is updated, a new IC will have to be
installed. The current FPGA software revision is 7.
Load transmitter calibration menu for generator curve running. When the engine
is running 50 % load and 100 % load (with reference to testbed results), enter the
menu by pressing [enter] and choose the correct engine load (50 % or 100 %)
followed by pressing [enter]. The program will respond with donE.
Hydraulic delay (time offset value). The value is inserted to compensate for the
time-delay from the first flank of the feedback signal, until the oil enters the cylin-
der through the cylinder liner non-return valves. The longer the hydraulic delay -
the earlier the solenoid valve is activated. The Hydraulic delay is calculated in the
design process and is confirmed by measurements on prototype engines. A good
estimate of the value is 1 ms for each meter pipe length from the lubricator to the
cylinder liner. The value cannot be adjusted individually for each cylinder, but is
common for all cylinders. Normally values are from 1 to 6 ms.
Read out of the index transmitter current. The mA signal from the index trans-
mitter without scaling. Used for mechanical adjustment of the index transmitter
during commissioning. The index transmitter is adjusted to 4.5 mA at mechanical
minimum index and to 19.5 mA at mechanical maximum index. The adjustment
is made on testbed before initial start up.
Index transmitter raw calibration value. The index transmitter calibration values
are given as an index low (in.Lo) value and an index high (in.hi) value. These
values are the theoretical index percentages when the pickup gives respectively
3045-0110-0001.1
4 and 20mA. Estimated values are pre-programmed from MAN B&W, and the
2008-12-12
system is calibrated by means of the (ProP) or (gEn) menus on testbed. The raw
values should only be changed if the automatic calibration in the ProP and gEn
Description
The values are normally around -30 to -10 for [in.Lo] and around 125 to 140 for
[in.hi].
Injection amount algorithm menu. Injection rate calculation can be chosen in pro-
portion to mean efficient pressure (nneP), rpm (rPnn) or power (Po.). Normal mode
is power Po proportional.
Injection offset. Angle offset inserted to compensate for small deviations between
the injection angle determined in the design process and the actual crank angle
for injection. The actual crank angle for injection is normally when the first piston
ring passes the oil quill during the upward stroke of the piston. inJ.oF can be
adjusted within +/– 5 °.
The value cannot be adjusted individually for each cylinder, but is common for
all cylinders.
Normal value is 0.
Logged alarms where the number ‘XX’ represents the alarm code. When an alarm
is activated, it will appear as both ALRXX and LALXX. The LALXX will remain
after the alarm is gone. For explanation of the alarm code see the alarm list in Sec-
tion 5.
To clear a logged alarm press [enter] while the alarm code is displayed. To clear
all logged alarms press [enter] for 5 seconds while one of the alarm codes is
displayed.
Load change dependent extra lubrication status. X indicates the status. When
LCD is active, i.e. when a load change situation occurs, the status changes from
0 (=off) to 1 (=on). The normal hold time is 30 min.
Load change dependent extra lubrication parameter adjustment menu. Six pa-
rameters, P1 to P6, can be adjusted. For further explanation see P1 to P6.
Mean effective pressure percentage (equal to torque percentage and index per-
3045-0110-0001.1
centage). Scaled read out of the index transmitter input. The value is used for the
2008-12-12
amount regulation. When generator curve running the value is equal to the load
percentage. When ideal propeller curve running normal values are: 25 % load =
Description
Engine speed.
MEP relative limit. Only used when inJ.AL is set to nnep. Minimum relative re-
duction percentage for the MEP dependent amount regulation. The parameter
is used for defining the level where the algorithm changes from MEP dependent
regulation to RPM dependent regulation. The parameter is relative i.e. the load
point of change is independent of the feed rate setting.
Normal high limit. Upper limit for automatic extra lubrication (LCD).
Example: If the feed rate setting is set to 145 % and nor.hi is set to 150 %, the
3045-0110-0001.1
LCD function can only increase the feed rate from 145 % to 150 %.
2008-12-12
LCD deviation percentage. Used only when P.1 is set to int. or tELE.P. To activate
LCD, the index (or telegraph position in case of tELE.P mode) must change more
than the LCD deviation percentage (P.2) within the reset time (P.3).
Average time or more correct: reset time. Used only when P.1 is set to int. or
tELE.P. To activate LCD, the index (or telegraph position in case of tELE.P mode)
must change more than LCD deviation percentage (P.2) within the reset time
(P.3).
Normal value is 10 sec.
Holding time. Used only when P.1 is set to int., E.Sig, or tELE.P. When the LCD
function is activated, it will remain active for a period of the holding time (P.4).
Normal value is 30 min.
3045-0110-0001.1
2008-12-12
Description
LCD factor. When LCD is active the feed rate setting for each cylinder multiplied
by the LCD factor (P.5). When the LCD function is active, the injection algorithm
(inJ.AL) is set to RPM (rPnn).
Normal value is 125 %.
Telegraph signal scale (used in tELE.P mode only). Scale factor for the mA input
to terminals ALCU/X1:33, ALCU/X1:34 (MCU/J40:1, MCU/J40:3).
Examples:
1) If 4-20 mA corresponds to 0-100 % RPM, the value of P.6 should be 100 %.
2) If 4-20 mA corresponds to -100 to 100 % RPM, the value of P.6 should be
200%:
Normal value is 100 %.
Par (abbr. of parameter) (in diSP menu) (for MAN B&W service engineers)
‘Raw’ read out of all setup parameter values. The parameters are numbered 1
through 176. Please contact MAN B&W for further information.
Par (abbr. of parameter) (in SEtuP menu) (for MAN B&W service engineers)
Adjusting the values in the “Par” menu may cause damage to the engine
CAUTION and should be done by authorised personnel only.
1. Navigate through the SEtuP menu until Par is displayed on the HMI panel.
Password required. The menu you wish to enter is password protected to prevent
Description
access.
The password for the SEtuP menu is = [p] [p] [esc] [enter]
The password for the Par sub menu in the SEtuP menu is = [esc] [p] [q] [enter]
Normal value is 40 %.
Propeller curve index adjustment menu. Used for calibrating the index transmitter
during propeller curve running. Please note that load conditions must be similar
to testbed.
Pu (abbr. of pump)
Description
Default pump selection. Used only when Pu.SEt is set to backup mode. If e.g. P1
is chosen, pump no. 2 will only start in case of low pressure alarm. The default
pump can also be chosen by “short cut” from the HMI panel by pressing [esc]
and [pump1] or [pump2] simultaneously.
Pump interval time. Used only when Pu.SEt is set to Auto mode. After an interval
of Pu.int the master pump is automatically changed from pump 1 to 2 and vice
versa.
Normal value is 12.
Pump mode setup. backup or Auto mode can be chosen. In backup mode the
master pump is selected manually by the operator by pressing [esc] and [pump X]
on the HMI panel. In Auto mode the master pump changes automatically after
an interval of Pu.int.
Normal value is backup.
Strokes per minute. Read out of total number of lubricator strokes per minute for
the whole engine. The number is the average over one minute. The instant feed
rate can be calculated based on total strokes per minute:
Example:
3
Lubricator volume (compensated for volumetric efficiency 0.97) = 1.8 cm
(The value can be found on page 2 of the setup document enclosed with the
ALCU unit)
oil density = 0.94 kg/l
power = 70000 kw
r XXX = strokes per minute = 462
Please note that a much more accurate calculation can be made using
2008-12-12
Rpm run. Engine run detection limit. When the engines rpm is above r.run, lubri-
cation will start and when rpm is below r.run lubrication will stop.
Please note that the parameter influences the alarm delays for the tacho system
and should therefore not be changed without consideration. Normal value is 8
rpm.
Feed rate setting max. normal service. Only used when inJ.AL is set to nneP
or Po. If the feed rate is set above Ser.hi - the feed rate is set over the limit for
normal service lubrication. A feed rate setting over the limit for normal service
lubrication is per definition “manual extra lubrication”, i.e. used for breaking-in
new liners and rings. The feed rate calculation algorithm is therefore changed to
RPM dependent, disregarding the setting of inJ.AL. (Reference is made to the
guidelines for cylinder lubrication and service letters).
Normal value is 199 %.
Setup menu. Values and parameters can be changed in the SEtuP menu. The
menu is password protected to prevent access.
1. Navigate through the outer menu level until SEtuP is shown in the display.
Solenoid valve test - Manual activation of solenoid valves. Blocked when the
engine is running.
2. Choose the lubricator number by pressing the [p] and [q] key.
4. Press [p] to set lubricator on, press [q] to set lubricator off.
Total lubricator stroke counter. The total number of solenoid valve activations
during the lifetime of the engine. The Str.hi menu shows the values from 105 to
109. The Str.Lo shows the values from 1 to 105.
The feed rate can be calculated based on the change of Str.Lo and Str.hi over
a period of time.
Example:
3
Lubricator volume (compensated for volumetric efficiency.) = 1.8 cm
(The value can be found on page 2 of the setup document enclosed with the
ALCU unit)
oil density = 0.94 kg/l
power = 70000 kw
Total lubricator stroke counter. Adjustment of total stroke counter in case of i.e.
Description
Activation delay time. On line measurement of the time from activation of solenoid
valve to the first flank of the feedback signal, used for automatic compensation
of timing of the solenoid valve activation.
The delay can also be used for trouble shooting by observing if the delay time
deviates on a lubricator.
Technical parameters. Sub menu in diSP menu containing the menu items, which
are not used for normal operation.
For explanation of their functionality see SoFt, FPgA, Par.Ch and Par.
Telegraph position raw value. Used with mechanical governor. Read out of the
4-20 mA signal from governor to ALCU/X1:33, ALCU/X1:34 (MCU/J40:1, MCU/
J40:3).
XXX
Display of a number.
3.3.1 Dip switch- Three double 4-position dip switches are available on the MCU board, SW 1, SW2
2008-12-12
es for MCU and SW 3. The dip switches represent binary values of 1, 2, 4 and 8, respectively,
when counting from the left. A switch is ON in the “up-position” and OFF in the
Description
“down-position”.
SW1 positions 1 and 2 are used to define the Baud rate at which the MCU com-
Alpha Lubricator System
16
4) OFF (MCU Null-series)
4)
2008-12-12
ON
4) ON
Description
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
SW
ON
SW 3
3
1 2 3 4 5 6 7 8 SW 3
OFF
OFF
1 2 4 8 2 4 8 16
1 2 4 8 2 4 8 16
OFF
1 2 4 8 2 4 8 16
5)
5)
ON
36 (90) 5) 3045-0110-0001.1
Doc-ID: ON
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
SW
ON
SW 1
1
MAN Diesel 3045-0110-0001.1
3.3.2 Upload of A VT100 terminal is part of the standard Windows software on a PC, and the
If the MCU main led (positioned in the upper left corner) is flashing red/
NOTE green, the MCU only contains production test software. In this case the
baud rate must be set to 38,400. When the main program has been
uploaded to the MCU, set the baud rate to 19,200 before uploading the
set-up file.
- Data bits: 8
- Parity: None
- Stop bits: 1
- Flow control: None
Press [Space] on the PC keyboard and the screen will display a menu as fol-
lows:
[R] Reset
The PC is connected to the MCU by means of the RS 232 serial cable, and the
VT100 terminal is started.
From the Alpha Lubricator menu, press [R] followed by [Y], [ASD and [Ctrl-U].
Send / transfer the latest version from ASD of the E-prompt file called *.epr from
3045-0110-0001.1
the PC to the MCU by means of menus in the VT100 terminal program. Make sure
2008-12-12
to use Xmodem protocol. When the file is transmitted to the MCU, press [Ctrl-P]
after confirming that calculated and read check sums are equal. Now the basic
Description
If a new basic program is uploaded to a MCU in service, the original set-up file
is deleted and a default set-up file is loaded in the MCU. Consequently, a new
setup file must be uploaded to the MCU in this case.
3.3.3 Upload MCU The PC is connected to the MCU by means of the RS 232 serial cable, and the
Alpha Lubricator System
From the Alpha Lubricator menu, press [1] (Transfer of setup data), followed by [1]
(Upload setup file). A capital C will start moving from left to right, indicating the
time remaining for uploading of set-up file. If the file is not uploaded successfully
the first time, just try again. This is not critical.
In the VT100 terminal, select menu item [Transfer] followed by [Send File], then
browse until you have found the correct setup file on your PC. Select the file and
press [Send].
When the file is transferred, ignore the command “Type password”, which is
displayed for a few seconds. Press [Y]. Now the new configuration parameters
are uploaded.
Interrupt the 24DC volt power supply. The green light will turn on and the MCU
is ready for operation.
If the MCU set-up file generated by the set-up program does not match the basic
MCU program, the VT100 terminal will display an error message and the MCU
will load the default set-up file.
The remedy for this is to download the default set-up file from the MCU to your
PC and manually change the displayed parameters for this specific file to match
the originally generated parameters. Save the new set-up file on your PC and
upload it to the MCU.
If the MCU is not able to receive the set-up file, turn to the VT100 menu 9 (MBD
Development menu) in order to reset RAM.
3.3.4 MCU LED On the MCU a main LED is positioned in the upper left corner. The status of the
information unit is given as follows:
Red/green flashing: The MCU basic program file is not loaded. Green flashing:
MCU set-up file is not loaded. Green light: Normal condition. Red light: Alarm
condition
3.3.5 Read-out of The HMI panel facilitates a menu that enables the use of read-out of all set-up
raw parameters in parameters. This feature might be helpful when troubleshooting the system.
HMI Panel
To read-out the raw parameter, follow the instruction below:
diSP
2008-12-12
Description
tEcH
Par
1 2 3 4 5 6 7 8 SW 3
9)
MAN Diesel OFF 3045-0110-0001.1
1 2 4 8 2 4 8 16
3 rev / inj 1 2 3 4 5 6 7 8 SW 1
OFF
1 2 4 8 2 4 8 16
The lowest injection rate the MCU can perform before the BCU takes over, is set
on the dip switches SW1 positions 5-8, as a binary value.
Examples:
If SW1.6 and SW1.8 are ON and SW1.5 and SW1.7 are OFF, the lowest injection
rate is 20 rev/injection for the MCU before BCU will take over control.
) Example: 38400 Baud 6)
ON ON
1 2 3 4 5 6 7 8 SW 1 20 rev / inj 1 2 3 4 5 6 7 8 SW 1
OFF OFF
1 2 4 8 2 4 8 16 1 2 4 8 2 4 8 16
3045-0110-0001.1
) 7)
2008-12-12
ON ON
Description
1 2 3 4 5 6 7 8 SW 1 1 2 3 4 5 6 7 8 SW 2
OFF OFF
1 2 4 8 2 4 8 16 1 2 4 8 2 4 8 16
ON
8)
1 2 3 4 5 6 7 8 SW 2 Doc-ID: 3045-0110-0001.1 ON 39 (90)
OFF 1 2 3 4 5 6 7 8 SW 2
1 2 4 8 2 4 8 16
1) Example: 38400 Baud 6)
1) Example: 38400 Baud
ON 6) ON
3045-0110-0001.1 ON MAN
ON Diesel
1 2 3 4 5 6 7 8 SW 1 1 2 3 4 5 6 7 8 SW 1
1 2 3 4 5 6 7 8 SW 1 1 2 3 4 5 6 7 8 SW 1
OFF for the engine
4.3 Number of cylinders OFF
Alpha Lubricator System
1 2 4 8 2 4 8 16 OFF 1 2 4 8 2 4 8 16 OFF
1 2 4 8 2 4 8 16 The number of cylinders for the specific
1 2engine
4 8 is 2set4on 8SW2
16 positions 1-4, as
a binary value.
2) 7)
2)
1) Example: 38400 Baud ON 7)
6) ON
ON
ON ON
ON
1 2 3 4 5 6 7 8 SW1 e.g. 7 cyl. 1 2 3 4 5 6 7 8 SW 2
1
1 2
2 3
3 4
4 5
5 6
6 7
7 8
8 SW 1 1
1 2
2 3
3 4
4 5
5 6
6 7
7 8
8 SW 2
1
OFF OFF
1 2 4 8 2 4 8 16 OFF 1 2 4 8 2 4 8 16 OFF
OFF OFF
1 2
1 2 44 8 2
8 2 44 88 16
16 1 2
1 2 4 4 88 2 2 4 4 88 16
16
4.4 BCU board revision
ON
ON 8)
The revision number of the printed circuit board is set on SW2.6.
2) 1 2 3 4 5 6 7 8 SW 2 7)
8) ON
1 2 3 4 5 6 7 8 ON SW 2 ON
OFF 1 2 3 4 5 6 7 8 SW 2
1
1 2
2 4
3 8
4 2
5 46 87 16 SW 1
8 OFF 1 2 3 4
1 2 3 4 5 6 7 85 6 7 8 SW 2
1 2 4 8 2 4 8 16 OFF
ON
OFF 1 2 4 8 2 4 8 16 OFF
1 2 4 8 2 4 8 16 ON 1 2 4 8 2 4 8 16 2.6
1 2 3 4 5 6 7 8 SW 3 2.6
1 2 3 4 5 6 7 SW 3
ON8 9)
OFF
For
8)
9) ON
1
1 2
2 4
3 8
4 25 46 8
7 16 SWinstallations
8 OFF 2 with revision B, SW2.6 must be OFF.
ON
For other installations SW2.6 must be ON.
1 2 4 8 2 4 8 16 1 2 3 4 5 6 7 8
The revision is printed on top of the board below the MAN B&W logo,SW 2
OFF 1 2 3 4 5 6 7 8
as “BCU-250-X” where X is the revision. SW 2
1 2 4 8 2 4 8 16 OFF
3) 4.5 Slow down output 1 2 4 8 2 4 8 16 OFF
3) ON 1 2 4 8 2 4 8 16 2.7
The slow down output switch (BCU terminal J8.3, 4) is 2.6
2.7 closed) if
NC(normally
1 2 3 4 5 6 7 8
ON
SW 3is ON and NO (normally
SW2.7 10) open) if SW2.7 is OFF.
1 2 3 4 5 6 7 8 SW 3 10)
9) ON
OFF ON
ON
1 2 4 8 2 4 8 16 OFF 1 2 3 4 5 6 7 8 SW 2
1 2 4 8 2 4 8 16 1 2 3 4 5
1 2 3 4 5 6 7 8 6 7 8 SW
SW 2 2
OFF
4) 1 2 4 8 2 4 8 16 OFF
OFF2.8
4)
3) ON 1
1 2 2 44 8 8 22 4 4 8 8 16
16
ON 2.8
2.7
1 2 3 4 5 6 7 8 ON SW 3
1
1
2
2
3
3
4
4
5
5
6
6
SW
7
The
7
OFF
8
83 is connected in 10)
3
SWoutput parrallel with slow-down output from MCU. The MCU
slow-down output is non-configurable, always NO. Consequently ONthe BCU slow-
1 2 4 8 2 4 8 16 OFF
down output must also be NO, i.e. SW2.7 OFF.
3045-0110-0001.1
OFF
1
1 2
2 4
4 8
8 2
2 4
4 8
8 16
16 1 2 3 4 5 6 7 8 SW 2
2008-12-12
5)
5)
Description
ON OFF
4) 1 2 4 8 2 4 8 16
ON 2.8
1 2 3 4 5 6 7 8 SW
ON 1
1 2 3 4 5 6 7 8 SW 1
1 2 3 4 5 6 7 8 SW 3
OFF
1 2 4 8 2 4 8 16 OFF
1 2 4 8 2 4 8 16 OFF
1 2 4 8 2 4 8 16
40 (90) Doc-ID: 3045-0110-0001.1
5)
ON
OFF
ON 1 2 4 8 2 4 8 16
2.6
1 2 3 4 5 6 7 8 SW 3
9)
MAN Diesel OFF
ON 3045-0110-0001.1
1 2 4 8 2 4 8 16
1 2 3 4 5 6 7 8 SW 2
4.6 Number of lubricators
1 2 4.7
3 4 Upload
5 6 of
7 BCU SW program
8 basic 3
OFF
To identify the component, see Document: ASD244-4090.
1 2 4 8 2 4 8 16
1. Connect a NULL-MODEM cable between the PC and BCU (J27)]
) 2. Connect the BCU to a suitable power supply (24V and minimum 2A)
ON
3. Set Switch (SW3) on the BCU in position “Program Mode”
1 2 3 4 5 6 7 8 SW 1
4. Press [RESET] button (SW4) on the BCU (the LED D50 located in the upper
OFF left corner of the PCB will turn off)
1 2 4 8 2 4 8 16
5. The device is now in programming mode (ISP mode)
into the device, or press the [BROWSE] button to choose the file.
Description
10. In the FlashMagic program window part 4 - key in the following data:
12. In the FlashMagic status line, the following information should appear:
Erasing Device
Programming Device
Verifying
Finished
The BCU has now been programmed
13. When the uploading is completed, set switch SW3 on the BCU back in po-
sition [NORMAL] and interrupt the power supply.
14. Verification
When the power supply is reconnected, the diode D50 in upper left cor-
ner will initially lit constantly green. This verifies that the unit is now pro-
grammed with application software. The diode may change to constantly
red if e.g. external signals are not present.
The [reset] button (SW 4) must not be pressed during normal opera-
CAUTION tion. This will cause “Internal Failure” (Alarm LED #8).
If, by mistake, the [reset] button has been activated and the LED #8 is lit, the error
message can be removed by interrupting the 24V power as follows:
2008-12-12
Description
5.1 Fuses
5.2 External alarm signals
5.3 MCU - alarm handling and trouble shooting
5.4 BCU alarms
5.5 Emergency running without external trigger signals
5.6 Sequence diagram for alarm handling
5.1 Fuses
5.1.1 MCU-Unit Normally, a fuse does not blow without reason. It is therefore important to locate
and correct the problem before normal operation can be restored.
There are two different fuse ratings: 12 Amp and 3 Amp. It is very important to
replace a fuse with one of the correct rating and type.
3045-0110-0001.1
2008-12-12
Description
MCU fuses
Alpha Lubricator System
The MCU unit has three fuses located on the filter board, as indicated in the
drawing below.
MCU board
FBU board
XZ707.40C 01
F1 Main fuse
Fuse F1 is rated 12 Amp and is the main fuse for the MCU unit.
If this fuse is blown, a consumer connected to plugs FJ8, FJ9, FJ11, FJ12, FJ13,
FJ14 may be suspected of overloading the fuse.
Check for shorts by removing the fuse. Connect a multimeter to the right fuse
holder and measure the resistance to the negative terminal of FJ1
3045-0110-0001.1
2008-12-12
Description
FBU board
XZ707.40C 02
If the short can be located by this method, continue investigating the problem in
the circuit connected to the suspected plug.
If the reason for the short cannot be found by the procedure described above,
an internal MCU failure may be suspected.
F2 and F3
Fuse F2 is rated at 3 Amp and is the main fuse for the SBU unit when running
MCU mode.
This fuse supplies control power (pump running signal) to the pump station via
the SBU unit when running in MCU mode as well as power to the feedback sen-
sors.
If this fuse is blown, a fault in the pump station wiring or in the connections to the
cylinder intermediate boxes may be suspected.
3045-0110-0001.1
2008-12-12
Description
In order to check whether the problem is in the pump station or the intermediate
Alpha Lubricator System
Remove fuse F2. Connect a multimeter to the right fuse holder clip, and measure
the resistance to the negative terminal of FJ1 (right terminal). A measurement
below 10 ohm is defined as a short.
If the measurement indicates a short, disconnect plug FJ5 on the MCU filter
board (disconnecting the supply to the pump station) and observe the meter
reading. If the short is still present, disconnect the plugs L1 to L14 in the SBU
one by one until the short is located. Investigate the problem further by discon-
necting the plug J1 in the intermediate box and reconnect the suspected plug in
the SBU. If the problem disappears, the short is located in the intermediate box
or the lubricator units.
Fuse F3 is rated at 3 Amp, and is the main fuse for the shaft encoder. If this fuse
is blown, a fault in the encoder connections may be suspected.
3045-0110-0001.1
2008-12-12
Description
5.1.2 BCU-Unit There are two different fuse ratings 12 Amp and 3 Amp. It is very important to
BCU fuses
The BCU unit has three fuses located on the filter board as indicated in the draw-
ing below.
FBU board
XZ707.40C 03
F1 Main fuse
Fuse F1 is rated at 12 Amp and is the main fuse for the BCU unit.
If this fuse is blown, a consumer connected to the plugs FJ8, FJ9, FJ11, FJ12,
FJ13, FJ14 may be suspected of overloading the fuse.
3045-0110-0001.1
2008-12-12
Check for shorts by removing the fuse. Connect a multimeter to the right fuse
holder, and measure the resistance to the negative terminal of FJ1.
Description
Alarm Led
Alpha Lubricator System
BCU board
FBU board
XZ707.40C 04
If the short can be located by this method, continue investigating the problem in
the circuit connected to the suspected plug.
F2 and F3
The fuse F2 is rated at 3 Amp and is the main fuse for the SBU unit when running
BCU mode. This fuse supplies power to the feedback sensors in BCU mode as
well as power to the pump station.
If this fuse is blown, a fault in the pump station wiring or in the connections to the
cylinder intermediate boxes might be suspected.
Remove fuse F2. Connect a multimeter to the right fuse holder clip, and measure
the resistance to the negative terminal of FJ1 (right terminal). A measurement
below 10 ohm is defined as a short.
3045-0110-0001.1
If the measurement indicates a short, disconnect plug FJ5 on the BCU filter board
2008-12-12
(disconnecting the supply to the pump station) and observe the meter reading.
If the short is still present, disconnect the plugs L1 to L14 in the SBU one by one
Description
until the short is located. Investigate the problem further by disconnecting the
plug J1 in the intermediate box and reconnect the suspected plug in the SBU.
If the problem disappears, the short is located in the intermediate box or the
lubricator units.
Fuse F3 is rated at 3 Amp, and is the main fuse for the BCU pickups. If this fuse
State indicator:
- BCU in control
Please note that some installations might have some alarm signals connected in
serial to save alarm channels in the alarm system.
5.2.1 Common The common alarm is a normally closed contact. In case the MCU system detects
alarm a fault, the alarm will be released. Information about the cause of the alarm can
be read of the number in the HMI panel.
To solve the problem, read the information related to the alarm number found in
the HMI panel.
5.2.2 MCU power The MCU power failure alarm is a normally closed contact.
failure In case the power to the MCU system is interrupted the alarm will be released.
Start by checking the breaker and fuse in the UPS cabinet. If no problem can be
found in the UPS, check that 24 V is present at terminal X1 PWR A in the ALCU
box. Continue by checking the fuse F2 on the MCU filter board (see page 41).
3045-0110-0001.1
2008-12-12
Description
5.2.3 BCU power The BCU power failure alarm is a normally closed contact.
Alpha Lubricator System
failure In case the power to the BCU system is interrupted, the alarm will be released.
Start by checking the breaker and fuse in the UPS cabinet. If no problem can be
found in the UPS, check that 24 V is present at terminal X1 PWR B in the ALCU
box. Continue by checking the fuse F2 on the BCU filter board (see page 44).
5.2.4 MCU failure The MCU failure alarm is a normally closed contact.
The BCU system has detected that the MCU system program execution has
halted.
If the Power supply is OK interrupt the power to the MCU for 5 secs. in order to
reset the MCU. If the MCU failure alarm is still active, the MCU itself might be
damaged and has to be replaced.
Note that if the power to the BCU is interrupted, the MCU failure will be activated
eventhough the MCU system is working well.
5.2.5 BCU failure The BCU failure alarm is a normally closed contact.
The BCU system has detected a fault in the BCU system.
Check the LED on the BCU board and read the instruction in item 5.4.
The BCU is not connected to the HMI panel and, consequently, no alarms from
the BCU will be displayed.
Check for other alarms in the HMI panel and follow the recommendations stat-
ed.
If the BCU system is able to re-establish the lubrication, the lubricators are work-
ing properly. The problem is to be found in the MCU system. Check for other
alarms and read the alarm codes on the HMI panel and follow the recommenda-
tions stated.
3045-0110-0001.1
2008-12-12
Description
If the alarm stated in the HMI panel is a logged alarm (the alarm has disappeared
again) the alarm will be displayed as LAL XX
The alarm code in the HMI panel provides information about which lubricator is
suspected to fail. (Alr 2 in the HMI panel indicates that lubricator 2 on cylinder 1
is failing.)
Note that in case of one lubricator per cylinder (engines with a bore below 0,60 m),
the alarm will only read uneven numbers e.g. 1, 3, 5, 7 for cylinder 1, 2, 3, 4.
as follows:
Lubricator 1 Lubricator 2
To verify that the problem is in the lubricator, disconnect the plug for the lu-
bricator and observe the indicator light on the intermediate box. If the light
turns off after the plug is removed, the problem is located in the lubricator.
The lubricator must be replaced and overhauled (instruction 903-2).
Alternatively, if the light in the intermediate box remains lit after the plug to
the lubricator has been removed, the fault is not in the lubricator. Check the
cable and plugs from the intermediate box to the lubricator for shorts.
Description
XZ707.40C 06
If no light flashes in the solenoid plug,
remove the plug from the solenoid and
check again if the light starts flashing.
If yes, the solenoids coil may have an
internal short, which can be confirmed by measuring the coil resistance. The
normal resistance is 15 to 22 ohm for a new solenoid.
If the red light flashes in the solenoid plug, but no feedback is observed, check
the connections in the lubricator plugs, mounted on the cable from the intermedi-
ate box, for loose connections or shorts.
sensor)).
+1 –2
5.3.2 Alarm 29 - The Marker signal (one pulse per revolution) is abnormal. The system will change
Marker signal fail- to random lubrication based on the remaining good signals. First check the elec-
ure from encoder trical connections in the encoder terminal box as well as the connections to the
ALCU control box.
If no problems are found in the wiring or fuse, replace the encoder.
3045-0110-0001.1
5.3.3 Alarm 30 - The two marker pickups mounted on the flywheel side of the engine gives one
Alarm number 30 indicates that BCU pickup # 1 is abnormal and alarm number
43 indicates that BCU pickup # 2 is abnormal.
If the Alpha lubricator system is running in BCU mode due to a MCU unit failure
the alarms for pickup failure can be found by observing the LED on the BCU pcb
(see picture below).
Alarm Led
S903-21 10B
The BCU system can be operated with only one pickup signal present.
Failure of one sensor is not critical and can be replaced when convenient.
3045-0110-0001.1
2008-12-12
Description
EN905-7.1 203 05
BCU terminal box. If power is present
at terminal 1 and 2 disconnect the
sensor wire connected to terminal # 3
(sensor # 1) or terminal # 6 (sensor # 2)
and observe if the light starts flashing.
If yes the wiring from the sensor to the ALCU box is shorted. If the indicator light
still does not flash, replace the pickup.
5.3.4 Alarm 31 - The trigger signals (1024 pulses per revolution) are abnormal. The system will
Trigger signal fail- change to random lubrication based on the remaining good signals. First check
ure from encoder for loose connection and shorts in the encoder terminal box, as well as the wiring
to the ALCU control box.
5.3.5 Alarm 33 - Engine stop signal failure will be released if the engine stop signal is detected as
Engine stop signal abnormal by the MCU.
failure
There are two cases that will trigger the stop signal alarm.
1. The engine is running above 8 r/min and engine stop signal is present at the
MCU input for more than 20 minutes.
Check the engine stop signal circuit in the bridge control system.
2. The engine is stopped (detection is only active for 30 seconds after stop)
but there is no engine stop signal present at the MCU input.
3045-0110-0001.1
2008-12-12
Check the engine stop signal circuit in the bridge control system.
Description
5.3.6 Alarm 34 - The MCU has detected that the external LCD signal has been continuously ON
5.3.7 Alarm 35 - The MCU has detected that the BCU is abnormal.
BCU alive signal
missing Start checking if there are other alarms from the system. Power fail from the BCU
will give this alarm.
Check the wiring in MCU plug J52 terminal 4 and 5 as well as BCU plug J7 termi-
nal 3 and 4. (BCU alive signal connections) The alive signal is a pulse signal with
a frequency of approximately 1 Hz. An oscilloscope or a multimeter, capable of
measuring frequency, must be used to measure this signal.
If none of the above problems are found, try to interrupt the power to the BCU
unit for 5 sec. If the problem is still present, the BCU is probably damaged and
must be replaced. However, the engine can be operated in MCU mode until a
new BCU unit can be obtained.
5.3.8 Alarm 36 - The MCU unit has detected that the astern signal has been ON for more than 24
Astern signal ab- hours.
normal
The engine can be operated with this alarm present, however the lubrication
amount is increased.
5.3.9 Alarm 37 - The MCU has detected that the prelubrication signal is ON and the index is higher
Prelubrication sig- than 80%.
nal abnormal This fault is not critical.
5.3.10 Alarm 38 - The oil temperature has exceeded the alarm level normally adjusted to 70°C.
Oil temperature
high Check the oil temperature sensor (Pt-100 type) by disconnecting the plug from
the sensor and measure the sensor resistance.
If the readings do not correspond the values stated above, the sensor is damaged
and must be replaced. This fault is not critical and the sensor can be replaced
Description
when convenient.
5.3.11 Alarm 39 - The oil pressure is below the normal alarm level of 35 bar.
Alpha Lubricator System
Both pumps will run continuously due to the detected fault. This fault is cleared
by manually pressing one of the PUMP-buttons on the HMI panel.
Check if the pumps are running. Check for leaks in the high-pressure supply
lines.
Check the oil pressure sensor (4-20 mA type) by measuring the sensor current
and comparing it with the pressure.
5.3.12 Alarm 40 - The MCU has detected that one or more of the four speed measurements are
Speed deviation abnormal.
alarm
Check the alarm list in the HMI panel to see which sensor is abnormal (BCU
pickups or the angle encoder) alarm 29, 30, 31 and 43 and read the chapter
concerning the alarm.
5.3.13 Alarm 41 - The index level does not correspond to the engine rpm.
Index transmitter
abnormal Fuel index is internally set to a fixed value of 100 percent due to the detected fault.
The fault is cleared by activation of engine stop signal.
5.3.14 Alarm 42 - The index transmitter cable is interrupted or the index transmitter is damaged.
Cable failure index Correct the cable failure or replace the index transmitter.
transmitter
If the index transmitter is replaced, readjustment is needed. Follow the index
adjustment instruction S903-25.
2008-12-12
Description
°C rpm
Find the cause for the BCU takeover. Deg. %
707 40C 09
5.3.17 Alarm 45 Electric motor # 1 or 2 is tripped by thermal overload.
and 46- Thermal
overload electric Check the thermal trip breaker in the pump station control box.
motor
Press the reset button on the thermal overload breaker to reactivate the pump
motor and check the current at the ammeter local side.
Check that the voltage on all three phases is OK. If not, check the fuses in the
feeder panel. Also verify that the motor windings are OK by measuring the resist-
ance of the individual windings.
If no electrical fault can be found check the oil pump for mechanical damage.
5.3.18 Alarm 47 - This alarm indicates that the MCU computer has lost its configuration file or that
MCU parameter it is missing.
list not loaded
Change to forced BCU operation by using the mode switch and replace the MCU
with a spare when possible.
5.3.19 Alarm 48 - The angle difference between the TDC marker from the angle encoder and the
Angle deviation TDC markers from the BCU pickups exceeds the alarm level.
fail
Check the Initial adjustment of the angle encoder and adjust as necessary. The
adjustment procedure can be found in Procedure 905-8.
Also check the flexible coupling between the engine and angle encoder for good
condition.
5.3.20 Alarm 49 - The stand-by pump has been activated either by the user or automatically due to
Stand-by pump is a low-pressure alarm. See alarm 39.
3045-0110-0001.1
running
2008-12-12
Description
FBU board
XZ707.40C 10
An internal failure in the BCU is detected. Check that the small switch SW3 on
the BCU board is in the normal position.
Reboot the BCU computer by interrupting the power supply for 5 sec. (Plug
FJ 1).
If the alarm comes on again, the BCU board might be damaged and must be
replaced.
3045-0110-0001.1
2008-12-12
The engine stop signal has been on for more than 20 minutes with the engine
running. The engine stop signal is off and the engine is not running (only for 30
seconds). Check the stop signal wiring and the engine control system for correct
operation.
Start checking if there are other alarms from the system. Power failure from the
MCU will give this alarm as well as a common alarm.
Check the wiring in MCU plug J52 terminal 2 and 3 as well as BCU plug J7 ter-
minal 1 and 2. (MCU alive signal connections).
The alive signal is a pulse signal with a frequency of approx. 0,5 Hz. An oscil-
loscope must be used to measure this signal.
If no problems, as described above, are found try to interrupt the power to the
MCU unit for 5 sec. If the problem is still present the MCU unit is probably dam-
aged and must be replaced. However, the engine can be operated in BCU mode
until a new MCU unit can be obtained.
If, for any reason, a feedback signal from a lubricator is measured as abnormal
by the BCU, an alarm will be given (BCU fail alarm).
Note that if the system is running in BCU mode due to a MCU failure, the MCU
might not be able to show any alarm codes in the HMI panel. The defect lubri-
cators are to be found by observing the feedback signal indicator lights at the
intermediate boxes at the engine.
First check if the fault is concerning more than one cylinder. If more than one
cylinder is affected, check the oil supply system. The oil pressure might be low
or the oil supply from the gravity tank has stopped. Check for leaks on the oil
supply lines.
If the problem can be isolated to only one cylinder, check the feedback wiring
from the defect cylinders intermediate box to the control box (ALCU). The inter-
mediate PCB (Printed Circuit Board) itself might be damaged.
To check if the BCU board is damaged, the plug for the defect cylinder can be
removed from the BCU and a plug from a working cylinder can temporally be
mounted instead. If this cylinder that previously worked well is now faulty, the
BCU board is probably damaged.
3045-0110-0001.1
2008-12-12
The BCU computer can be rebooted by interrupting the main power supply for
5 sec. (Remove plug FJ1 on the BCU filter board).)
If, for any reason, a feedback signal from a lubricator is measured as abnormal
by the BCU, an alarm will be given (BCU fail alarm).
Note that if the system is running in BCU mode due to a MCU failure, the MCU
might not be able to show any alarm codes on the HMI panel. The defective lu-
bricators are to be found by observing the feedback signal indicator lights at the
intermediate boxes on the engine.
For further information, see chapter covering MCU feedback fail alarms.
The two marker pickups mounted on the turning wheel end of the engine give
one pulse every engine revolution. These signals are used by the BCU system
to determine the engine speed. The signals are also used by the MCU system to
monitor the signals and release an alarm in case of signal failure.
Note that if the system is running in BCU mode due to a MCU failure, the MCU
may not be able to show any alarm codes on the HMI panel.
This case needs prompt attention. The lubrication will stop, and a slowdown
command will be activated.
Check the sensors and the trigger-bracket on the flywheel for mechanical dam-
age. Sensor gap is 3.0 mm. (Regarding distance: always refer to manufacturer’s
recommendation).
Check that there is 24 volt on terminals 1 and 2 in the BCU terminal box. If there
is no power present on terminals 1 and 2, investigate further for short-circuited
wiring to the BCU pickup system.
Failure of one pickup is not critical and it can be replaced when convenient.
The BCU pickups have a built-in indicator which flashes once for each engine
3045-0110-0001.1
revolution.
2008-12-12
Description
EN905-7.1 203 05
from the pickup to the ALCU box is
shorted. If the indicator light still does
not flash, replace the pickup.
In the event that all trigger signals to the lubricator system fails (angle encoder
and pickups for the BCU system), it is possible to maintain a certain level of lubri-
cation by means of an internal stroke generator on the MCU or BCU card.
This stroke generator emits one pulse per second, i.e. approx. 60 rpm.
3045-0110-0001.1
2008-12-12
Description
MCU board
XZ707.40C 13
The system now starts lubricating regardless of whether the engine is running
or stopped.
However, feedback alarms will still function and indicate whether all cylinders are
being lubricated. When running in this mode, the BCU system is not active.
2008-12-12
Description
No
Two lubricator Automatic
BCU in Control Startning two (2)
on one Cyl. Yes change over
Alr 44 Booster pumps
failure to BCU
No
Com. alarm
MCU Automatic Running
MCU Power fail
power Yes change over continuously
BCU in Control
failure to BCU Untimed
MCU fail
No
No No
No No
No No
MCU Running Com. Alarm BCU BCU Fail
BCU Pickup #1 Yes continuously + Pickup signals Yes Alarm Slow down
missing Timed Alr 30 missing LED 2
No No
MCU Running Com. Alarm MCU BCU Fail
BCU Pickup #2 Yes continuously + alive signal Yes Alarm
missing Timed Alr 43 missing LED 3
No No
Com. Alarm
MCU Running Com. Alarm BCU
MCU fail
BCU Pickup signals Yes continuously + power Yes Slow down
BCU fail
missing Timed Alr 30+43 failure
BCU power fail
No No
MCU Automatic BCU in Control
Failure Encoder Yes change over Com. Alarm OK
BCU Failure Pickups to BCU Alr 44
No
Low Start Two lubricator
booster oil Yes stand-by fails on one unit HMI Panel Alarm list
pressure pump BCU in Control
Appendix 1
D7 D17
Error FB-signal output
FB-signal input A
D5 FB-signal input B
D6
J2
J4
J1
The two green LEDs D5 and D6 (FB-signal input A and FB-signal input B) light
when there is an input from one of the feedback sensors.
FB-signal output is also a green LED D17, which flashes every time a feedback
signal is sent to the Switch Board Unit. There has to be a flash at FB-signal output
every time, shortly after there is an input on one of the two FB-signal input.
The Error LED D7 indicates with a red light, if there is an error on the cable from
the FB-signal output, or if the input at the Switch Board Unit has an error.
If there is an error, remove the plug from J1 and see if the LED still indicates error.
If it does then change the circuit board, if this does not remove the indicated error,
then look for any damage on the cable. If the cable is damaged, then change it or,
if possible, repair the damage. If there is not any damage on the cable, then the
source of the error could be the input channel at the Switch Board Unit.
3045-0110-0001.1
2008-12-12
Description
Appendix 2
Alpha Lubricator System
2008-12-12
Description
MAN Diesel
Doc-ID: 3045-0110-0001.1
Description Alpha Lubricator System
3045-0110-0001.1
3045-0110-0001.1
67 (90)
3045-0110-0001.1 MAN Diesel
Alpha Lubricator System
3045-0110-0001.1
2008-12-12
Description
MAN Diesel
Doc-ID: 3045-0110-0001.1
Description Alpha Lubricator System
3045-0110-0001.1
3045-0110-0001.1
69 (90)
3045-0110-0001.1 MAN Diesel
Alpha Lubricator System
3045-0110-0001.1
2008-12-12
Description
MAN Diesel
Doc-ID: 3045-0110-0001.1
Description Alpha Lubricator System
3045-0110-0001.1
3045-0110-0001.1
71 (90)
3045-0110-0001.1 MAN Diesel
Alpha Lubricator System
3045-0110-0001.1
2008-12-12
Description
MAN Diesel
Doc-ID: 3045-0110-0001.1
Description Alpha Lubricator System
3045-0110-0001.1
3045-0110-0001.1
73 (90)
3045-0110-0001.1 MAN Diesel
Alpha Lubricator System
3045-0110-0001.1
2008-12-12
Description
Appendix 3
Before removing any plugs from the PCB ensure that the plugs are numbered in
order to remount them in the correct place.
The SBU unit does not need any programming or setup. This board can be re-
placed directly with a spare.
MCU replacement
Note that a new MCU unit is adjusted to a feed rate of 200% (factory setting).
1. Read out the feed rate setting for the individual cylinders on the old MCU in
order to adjust the new MCU to the same setting
2. Start the prelubrication sequence and check that all cylinders are lubricat-
ed by observing that all LEDs on the intermediate boxes flash. Also check
that no feedback alarms are present in the HMI panel.
3. With the engine running, check the injection angles in the HMI panel and
compare these with the angles stated in the test sheet supplied with the
ALCU box.
4. Adjust the lubrication feed rate according to the settings the engine had
before this replacement.
Description
BCU replacement
Alpha Lubricator System
1. Check that the DIP switch settings on the new board are corresponding to
the settings of the old board.
2. With the engine running, switch to forced BCU operation and check that
all cylinders are lubricated by observing that all LEDs on the intermediate
boxes flash. Switch back to auto mode.
4. If the SBU unit has been replaced, check the function by carrying out the
checks stated under both MCU and BCU replacements.
3045-0110-0001.1
2008-12-12
Description
Cylinder Lubrication
Since our last Service Letter SL05-455 concerning Cylinder Lubrication, the de-
fault feed rate sulphur proportional factor has been in the range of 0.34 to 0.26 g/
kWh x S%, with an absolute minimum at 0.70 - 0.60 g/kWh.
However, many engines have followed the lowest level in the range, and evalua-
tions of the results regarding wear, scuffing resistance and TBO show that this
dosage is superior to higher levels. Therefore, we now recommend a fixed sched-
ule for navigating from the upper level to the lower level in the range, within a
2,000-hour period.
Consequently, the recommended basic feed rate after running-in is 0.26 g/kWh x
S%, with the absolute lower limit at 0.60 g/kWh.
Alpha ACC is the default lubrication mode for modern MAN B&W two-stroke
engines, i.e. lube oil is dosed at a feed rate proportional to the engine load and
proportional to the sulphur content in the fuel oil. This ensures that the alkali ad-
ditives in the cylinder oil are applied proportionally with the amount of sulphur
entering into the combustion chamber. The build up of a safe oil film is ensured
at any time by the lower limit of 0.60 g/kWh. 3045-0110-0001.1
2008-12-12
Description
Running-in
Alpha Lubricator System
During the first running-in, we recommend a relatively high fixed dosage: 1.5 g/
kWh for the first 250 hours succeeded by 1.2 g/kWh for another 250 hours. After
these 500 hours of initial running-in, where ample oil is used for flushing away
wear particles from the sliding surfaces, ACC running with the factor 0.34 g/
kWh x S% should be introduced.
The next 2,000 hours should be used for a gradual reduction towards the basic
setting, i.e. the ACC factor 0.26 g/kWh x S%, see the feed rate chart below.
Regulating from the upper ACC factor 0.34 g/kWh x S% to the basic setting at
0.26 g/kWh x S% should take place stepwise over a 2,000-hour period. The size
of the steps may depend on the evaluation of the actual lubricating and deposit
condition appearing from scavenge port inspections.
Due to the sulphur dependency, the average Cylinder Oil Consumption depends
on the sulphur content in fuel bunkers. According to DNV, worldwide deliveries
in 2006 have been recorded as shown in Fig. 2 below.
3045-0110-0001.1
2008-12-12
Description
About 40% of all fuel bunkers have a sulphur content below 2.3%, and conse-
quently call for the minimum dosage of 0.60 g/kWh. About 60% of ail fuel bunkers
call for the sulphur dependent lube control, i.e. 0.26 g/kWh x S%. On average,
this results in a yearly absolute Cylinder Oil Dosage of 0.70 g/kWh.
At sulphur ievels below 2.2%, the minimum dosages at 0.6 g/kWh should be
maintained. Consequently, when using a normal BN70 cylinder oil, there will be
a surplus of alkali additives. Unused alkali additives have a negative influence
on the cylinder condition due to accumulation on the piston top land and due to
lack of refreshment of the liner surface by corrosion. This negative influence is
naturally time based and becomes more and more severe the lower the sulphur
content gets. As a rule of thumb, we recommend to change to a lower BN cylinder
oil when operating on sulphur levels below 1.5% for more than 1 to 2 weeks.
Description
th
HRR 6 February 2007
2008-12-12
Description
3045-0110-0001.1
2008-12-12
Description
MAN Diesel
1.8 0.52
0.50
1.6 Scavenge port insp. Fixed running-in dosage (g/kWh) 0.48
*
0.46
1.4 Feed rate factor reduction curve(g/kWh/S%)
0.44
Scavenge port insp.
* 0.42
1.2
0.40
1 0.38
0.36
Doc-ID: 3045-0110-0001.1
* Scavenge port insp.
Scavenge port insp. * 0.32
0.6 Scavenge port insp. 0.30
*
Scavenge port insp.
0.28
0.4 *
0.26
0.24
0.2
Running-in Change to ACC 0.22
period with
0 fixed 0.20
lubrication ACC optimisation phase Optimum ACC setting 0.18
ACC feed rate factor (g/kWh/S%)
-0.2 0.16
0 500 1000 1500 2000 2500 3000 3500 4000
HRJ 2300, 11 October 2006 Hours
83 (90)
3045-0110-0001.1 MAN Diesel
Appendix 5
Alpha Lubricator System
2008-12-12
Description
MAN Diesel
Doc-ID: 3045-0110-0001.1
Description Alpha Lubricator System
3045-0110-0001.1
3045-0110-0001.1
85 (90)
3045-0110-0001.1 MAN Diesel
Alpha Lubricator System
3045-0110-0001.1
2008-12-12
Description
MAN Diesel
Doc-ID: 3045-0110-0001.1
Description Alpha Lubricator System
3045-0110-0001.1
3045-0110-0001.1
87 (90)
3045-0110-0001.1 MAN Diesel
Appendix 6
Alpha Lubricator System
2008-12-12
Description
MAN Diesel
Doc-ID: 3045-0110-0001.1
Description Alpha Lubricator System
3045-0110-0001.1
3045-0110-0001.1
89 (90)
3045-0110-0001.1 MAN Diesel
Alpha Lubricator System
3045-0110-0001.1
2008-12-12
Description
Commissioning
Maintenance
Components
Electrical Wiring
Blank
Commissioning
Table of Contents
See
1. N2 Charging Maintenance 903-2.1, page 2-3 and 103-2
2. Flushing S903-24
1. Preparation
1.1 Connect a 440 V power supply to the two pump starter cabinets, and start the two
pumps locally for a brief period to check that they run in the correct direction of
rotation.
1.2 Check, and if necessary adjust, the current limits on the two motor-start relays so
that they comply with the rating plate on the motor.
1.3 Connect and activate the heating element in the suction tank.
1.4 Dismount the inlet and outlet pipes to the lubricator blocks and mount U-pipes
with shut-off cocks instead (bypass the blocks).
Remember to seal off the free pipe connections on the lubricator block to prevent the in-
gress of dirt.
Mount an extra full-flow filter (15 to 35 m) in the return pipe from the engine to the pump
station.
1.5 Mount a U-pipe with shut-off cock on the end of the oil supply main pipe.
1.6 Close all shut-off cocks on the U-pipes at the lubricator blocks and open the cock
at the end of the main pipe.
1.7 Fill the suction tank on the pump station with hydraulic oil.
1.10 Adjust the pressure regulator on the pump station to maximum pressure.
1.12 Check the oil level in the suction tank and, if necessary, top up until the level is
stable.
1.14 Start pump No. 2 and check that it can maintain a pressure level similar to pump
No. 1.
1.16 Regularly check the oil level in the suction tank and top up as necessary.
1.17 Regularly check that the pressure drop across the suction filters and in the full-
flow filter in the pressure outlet do not exceed the maximum level. Replace the fil-
ters if clogged.
When referring to this page, please quote Procedure S903-24 Page 1 (3)
MAN B&W Diesel A/S, Copenhagen, Denmark
Flushing of Pipe System on
S903-24
Alpha Lubricators
2. Flushing
The following flushing procedure is to be carried out before starting up on the testbed:
2.1 After five hours’ flushing, open one half of the shut-off cocks on the U-pipes on
the lubricator blocks, and close the cock at the end of the main pipe.
2.3 After five hours’ flushing, open the other half of the shut-off cocks on the U-pipes
and close the half that were open.
2.5 Close the inlet and outlet cocks on the pump station, and drain the oil from the
suction tank.
2.6 Switch-off the 440 V power supply to the pumps and tank heater via the main
switch on the starter cabinets.
2.7 Remove the inspection cover on the suction tank and clean the inside of the tank
so that it is completely free of any oil or dirt.
2.8 Dismount all U-pipes and re-install all the original pipe connections.
2.9 Open all relevant cocks on the pumps and open for the supply of cylinder oil from
the service tank (gravity tank).
2.10 Start a pump from the pertaining start button on the starter cabinet and adjust the
pressure regulator to 45 bar.
2.11 Check that there are no leaks in the pipe system or lubricators.
2.12 Check and, if necessary, adjust the thermostat to 45o C, after dismounting the
cover on the heater.
Page 2 (3) When referring to this page, please quote Procedurer S903-24
MAN B&W Diesel A/S, Copenhagen, Denmark
Flushing of Pipe System on
S903-24
Alpha Lubricators
Return line
Extra
full float 15-30 m
flushing filter
Pump station
Supply line
Group #1 Group #2
#1 #2
When referring to this page, please quote Procedure S903-24 Page 3 (3)
MAN B&W Diesel A/S, Copenhagen, Denmark
Blank
Cylinder Lubrication S903-21
Testbed Commissioning Procedure
Cylinder Lubrication
21
Testbed Commissioning Procedure
S903-21
1.
ALCU – Testbed Procedure
S903-21 01
2.
TB x 1 V
Alcu Box
24 V DC
Main B
Main A
S903-21 02
3.
V
V
24 V DC
S903-21 03
When referring to this page, please quote Procedure S903-21 Page 1 (8)
0$1% :'LHVHO$6 2003-01-28
S903-21 Cylinder Lubrication
Testbed Commissioning Procedure
S90321-4
diSP in.A XXX [mA]
Page 2 (8) When referring to this page, please quote Procedure S903-21
2003-01-28 0$1% :'LHVHO$6
Cylinder Lubrication S903-21
Testbed Commissioning Procedure
120
Index
6B.
Lubrication
°C rpm
Deg. %
Auto MCU BCU Min. bar
Oil pressure low
Index failure
Mark/trig failure
Feedback failure
Common alarm
S903-21 06A
7.
S903-21 06B
Lub.XX oFF/on
S903-21 07
PRESS
S90321-7
When referring to this page, please quote Procedure S903-21 Page 3 (8)
0$1% :'LHVHO$6 2003-01-28
S903-21 Cylinder Lubrication
Testbed Commissioning Procedure
9A. 9B.
MCU Board
TDC Cyl. 1
350°
0°
S903-21 09A
S903-21 09B
Page 4 (8) When referring to this page, please quote Procedure S903-21
2003-01-28 0$1% :'LHVHO$6
Cylinder Lubrication S903-21
Testbed Commissioning Procedure
10A.
S903-21 10A
MCU Board
When referring to this page, please quote Procedure S903-21 Page 5 (8)
0$1% :'LHVHO$6 2003-01-28
S903-21 Cylinder Lubrication
Testbed Commissioning Procedure
S90321-11
Connt. Co.ALr oFF/on
Common Alarm
12. Check the timing adjustment as described
in Procedure S903-20.
S903-21 11
12.
Cyl. 1: 270
Cyl. 2:
Cyl. 3:
S903-20 04
Page 6 (8) When referring to this page, please quote Procedure S903-21
2003-01-28 0$1% :'LHVHO$6
Cylinder Lubrication S903-21
Testbed Commissioning Procedure
Function to be Alarm number Com- MCU BCU BCU in MCU BCU Slow- Checked
Test
tested: Test by displayed on Action mon power power control fail fail down
No.
HMI panel alarm fail fail
4 Engine stop sig- Simulating Stop signal MCU LED D80 above
nal plug J30 lights Simulate engine stop signal from engine control system
BCU LED D49 above
plug J5 lights
X1 1+2 3+6
X1 7+8
°C rpm
Deg. %
Min. bar
Oil pressure low
Index failure
Common alarm
When referring to this page, please quote Procedure S903-21 Page 7 (8)
0$1% :'LHVHO$6 2003-01-28
S903-21 Cylinder Lubrication
Testbed Commissioning Procedure
14a. Password
ESC ENTER
50%
Prop 100%
Gen
SETUP PASS in.AdJ Value
S903-21 22
(Password)
15.
120
Engine speed
120
Index
100 bar
Oil pressure
°C rpm
Deg. %
Min. bar
Oil pressure low
Index failure
Common alarm
Page 8 (8) When referring to this page, please quote Procedure S903-21
2003-01-28 0$1% :'LHVHO$6
Cylinder Lubrication S903-20
Check of Injection Timing
Cylinder Lubrication
S50MC
20
Check of Injection Timing
S903-20
Injection timing 2.
S903-20 02
ahead until the upper edge of the top piston
ring becomes visible.
3.
Note!
Cyl. 1: 270
Cyl. 2:
Cyl. 3:
S903-20 04
When referring to this page, please quote Procedure S903-20 Page 1 (2)
0$1% :'LHVHO$6
S903-20 Cylinder Lubrication
Check of Injection Timing
7.
S903-20 07
8.
S903-20 08
Page 2 (2) When referring to this page, please quote Procedure S903-20
0$1% :'LHVHO$6
Alpha lubricator testbed trail test scheme Alarm outputs to be activated
Simulate common alarm from HMI panel Common alarm turns ON in alarm
1 Common alarm output
menu system
MCU LED D80 above plug J30 light
2 Engine stop signal Simulating Stop signal Simulate engine stop signal from engine control system
BCU LED D49 above plug J5 light
3 Standby pump Switch master pump OFF local side (39) + 49 Standby pump starts X
BCU take-over, standby pump Disconnect Plugs on both lubricatores Change over to BCU control and
4 Varius X X X X
start and slowdown output one cylinder standby pump start, slowdown
Valid for ALCU system and MCU software Rev 1.6X X1 1 and 2 3 and 6
X1 9 and 12 13 and 14 15 and 16 17 and 18
X1 7 and 8
* Note that the control switch must be in AUTO position during the test
* All tests can be made with Engine running low load or with trigger simulator without engine running
* After every test the logged alarms must be deleted in the HMI panel
* After test 4 the control switch must be changed to MCU and back to AUTO mode
Basic Standards (MBD SB) & Suppl. Drawing No.: EN21C Surf. roughness Material / Blank:
EN21F-m Tolerances
Mass (kg) Final User Matrial:
This drawing is the property of MAN B&W Diesel A/S and is to be treated as confidential by the party to whom it has been submitted by 3 02 023 INSTRUCTION 0788812-9
MAN B&W Diesel A/S and is not to be disclosed to any third party without the specific prior written permission of MAN B&W Diesel A/S Final User Info No. Final User Description Final User Ident. No.
Blank
Cylinder Lubrication S903-0039
MAN B&W Dock Trial Commissioning Procedure
ALCU –
1.
Dock Trial Commissioning Procedure
S9030039,01
2.
+
TB x 1 V
Alcu Box
24V DC
L+
L Main B
S9030039,02
L+
L Main A
3.
+
24V DC
S9030039,03
When referring to this page, please quote S-Instruction S903 Edition 0039 Page 1 (5)
S903-0039 Cylinder Lubrication
Dock Trial Commissioning Procedure MAN B&W
PRESS
6.
PRESS
S9030039,06
Page 2 (5) When referring to this page, please quote S-Instruction S903 Edition 0039
Cylinder Lubrication S903-0039
MAN B&W Dock Trial Commissioning Procedure
S9030039,07A
7B.
MCU Board
S9030039,07B
When referring to this page, please quote S-Instruction S903 Edition 0039 Page 3 (5)
S903-0039 Cylinder Lubrication
Dock Trial Commissioning Procedure MAN B&W
Scaling:
8B.
4 mA zero load
PASS
PASS 20 mA max. handle position (overload)
Password=
Password= esc enter
The signal may be generated by the remote
control system as:
in.Adj Pitch set % * RPM set % if convenient.
SEtuP Lcd P.1 TELE.P See Figs. 8A and 8B and also section
S9030039,08B
Page 4 (5) When referring to this page, please quote S-Instruction S903 Edition 0039
Cylinder Lubrication S903-0039
MAN B&W Dock Trial Commissioning Procedure
Test Function to be Test by Alarm number Com- MCU BCU BCU in MCU BCU Slow- Checked
No. tested: displayed on Action mon power power control fail fail down
HMI panel alarm fail fail
4 Ahead/Astern Simulating Astern MCU LED D78 above Simulate Astern signal from engine control system
signal signal plug J30 light
5 Pre-lubrication Simulating pre. Lub. Pre lubrication Simulate pre-lubrication signal from engine control system
signal signal sequence start
X1 1+2 3+6
X1 7+8
When referring to this page, please quote S-Instruction S903 Edition 0039 Page 5 (5)
Blank
Alpha lubricator dock trail test scheme Activated alarm outputs
Alarm number Checked
Function to be Common MCU BCU BCU in Slow
Test Nr Test by displayed in HMI Action MCU fail BCU fail
tested: alarm power fali power fali ctrl. down
panel
External alarm signals
1 Disconnect X1 - PWR A – L+ Change over to BCU control
to AMS X X X X
External alarm signals
2 Disconnect X1 - PWR B – L+ 30+35+43 BCU power fail alarm
to AMS X X X X
MCU LED D80 above plug J30 light
3 Engine stop signal Simulating Stop signal Simulate engine stop signal from engine control system
BCU LED D49 above plug J5 light
4 Ah/As signal Simulating Astern signal MCU LED D78 Above plug J30 light Simulate Astern signal from engine control system
5 Prelubrication signal Simulating pre. Lub. signal Prelubrication sequence start Simulate prelubrication signal from engine control system
Valid for ALCU system and MCU software Rev 1.6X X1 1 and 2 3 and 6
Basic Standards (MBD SB) & Suppl. Drawing No.: EN21C Surf. roughness Material / Blank:
EN21F-m Tolerances
Mass (kg) Final User Matrial:
This drawing is the property of MAN B&W Diesel A/S and is to be treated as confidential by the party to whom it has been submitted by 3 02 023 INSTRUCTION 0788811-7
MAN B&W Diesel A/S and is not to be disclosed to any third party without the specific prior written permission of MAN B&W Diesel A/S Final User Info No. Final User Description Final User Ident. No.
Blank
Index
Operation
Commissioning
Maintenance
Components
Electrical Wiring
Blank
Cylinder Lubricators 103-2
Data
X Stopped engine
X Block the starting mechanism
X Shut off starting air supply
X Engage turning gear
Shut off cooling water
Shut off fuel oil
Shut off lubrication oil
Lock turbocharger rotors
Data
Ref. Description Value Unit
0-10 bar
When referring to this page, please quote Data D10302 Edition 0020 Page 1 (2)
MAN B&W Diesel A/S
103-2 Cylinder Lubricators
Data
Spare Parts
Page 2 (2) When referring to this page, please quote Data D10302 Edition 0020
MAN B&W Diesel A/S
Cylinder Lubricators 903-2.1
Checking
0236
Cylinder Lubricators
S42MC
Checking
903-2.1
1.
Check of Oil Injection:
When referring to this page, please quote Procedure M90302 Edition 0236 Page 1 (10)
0$1% :'LHVHO$6
903-2.1 Cylinder Lubricators
Checking
3. Check of Accumulators:
Page 2 (10) When referring to this page, please quote Procedure M90302 Edition 0236
0$1% :'LHVHO$6
Cylinder Lubricators 903-2.1
Checking
6. C
7. Before mounting the filling valve on the ac-
cumulator, check that the accumulator top
is clean. A
D03-13
E
Mount the filling valve on the relevant accu- F
mulator with the union nut. Check that
valves C and F are closed.
NA903-2.1 222 06
gauge on the filling valve.
When referring to this page, please quote Procedure M90302 Edition 0236 Page 3 (10)
0$1% :'LHVHO$6
903-2.2 Cylinder Lubricators
Dismantling
Dismantling
903-2.2
1. Dismantling of lubricators:
Special running
Page 4 (10) When referring to this page, please quote Procedure M90302 Edition 0236
0$1% :'LHVHO$6
Cylinder Lubricators 903-2.2
Dismantling
Dismantling of accumulators: 4.
Note!
EN903-2.2 219 04
remain in the accumulator.
When referring to this page, please quote Procedure M90302 Edition 0236 Page 5 (10)
0$1% :'LHVHO$6
903-2.3 Cylinder Lubricators
Overhaul
Overhaul
903-2.3
3.
EN903-2.3 219 03
Page 6 (10) When referring to this page, please quote Procedure M90302 Edition 0236
0$1% :'LHVHO$6
Cylinder Lubricators 903-2.3
Overhaul
EN903-2.3 221 04
Clean the housing with diesel oil or kero-
sene and dry with a non-fluffy cloth.
When referring to this page, please quote Procedure M90302 Edition 0236 Page 7 (10)
0$1% :'LHVHO$6
903-2.3 Cylinder Lubricators
Overhaul
1 1
EN903-2.3 219 06
2 Solenoid valve
7. Fit the cylinder block with new O-rings.
2
3 BN (brown)
4 BK (black) Feedback sensor Assemble the non-return valves in the cyl-
5 BU (blue) inder block.
3 2
6 5 1
4
5V
+1
wn
B ro
e OV al
Blu ign
F B-s
ck
Bla
707-40C-7A
7.
EN903-2.3 219 07
Page 8 (10) When referring to this page, please quote Procedure M90302 Edition 0236
0$1% :'LHVHO$6
Cylinder Lubricators 903-2.3
Overhaul
EN903-2.3 219 08
Mount the screws and tighten the block to
the housing.
10.
EN903-2.3 219 01
When referring to this page, please quote Procedure M90302 Edition 0236 Page 9 (10)
0$1% :'LHVHO$6
903-2.4 Cylinder Lubricators
Mounting
Mounting
903-2.4
3.
EN903-2.4 219 03
Page 10 (10) When referring to this page, please quote Procedure M90302 Edition 0236
0$1% :'LHVHO$6
Cylinder Lubricators 903-2.1
MAN B&W Diesel Checking
3.
M903020245C02
When referring to this page, please quote Procedure M90302 Edition 0249 Page 1 (12)
903-2.1 Cylinder Lubricators
Checking MAN B&W Diesel
Check of Accumulators:
Page 2 (12) When referring to this page, please quote Procedure M90302 Edition 0249
Cylinder Lubricators 903-2.1
MAN B&W Diesel Checking
M903020247C07
Mount the filling valve on the relevant accu-
mulator with the union nut. Check that
valves C and F are closed.
When referring to this page, please quote Procedure M90302 Edition 0249 Page 3 (12)
903-2.2 Cylinder Lubricators
Dismantling MAN B&W Diesel
Dismantling of lubricators:
1.
The engine must be stopped and blocked be-
fore dismounting a lubricator. Stop the cylinder
Inlet oil pump station.
Special running
Page 4 (12) When referring to this page, please quote Procedure M90302 Edition 0249
Cylinder Lubricators 903-2.2
MAN B&W Diesel Dismantling
Dismantling of accumulators:
5.
4. The engine must be stopped and blocked
before the accumulator is dismounted.
Inlet
Stop the cylinder oil pump station.
Note!
When the oil pressure is released, a ni-
M903020249D04
trogen pre-pressure of 25-30 bar will re-
main in the accumulator.
When referring to this page, please quote Procedure M90302 Edition 0249 Page 5 (12)
903-2.3 Cylinder Lubricators
Overhaul MAN B&W Diesel
3.
M903020247O03
Page 6 (12) When referring to this page, please quote Procedure M90302 Edition 0249
Cylinder Lubricators 903-2.3
MAN B&W Diesel Overhaul
M903020247O04
5.
M903020247O05
6.
M903020247O06
When referring to this page, please quote Procedure M90302 Edition 0249 Page 7 (12)
903-2.3 Cylinder Lubricators
Overhaul MAN B&W Diesel
Page 8 (12) When referring to this page, please quote Procedure M90302 Edition 0249
Cylinder Lubricators 903-2.3
MAN B&W Diesel Overhaul
M903020247O08
Unscrew the solenoid valve.
10.
M903020244O12
When referring to this page, please quote Procedure M90302 Edition 0249 Page 9 (12)
903-2.3 Cylinder Lubricators
Overhaul MAN B&W Diesel
1 1
2 2 Solenoid valve 11. Connect the wires and mount the cover on
3 BN (brown) the terminal box.
BK (black)
4
BU (blue) Feedback sensor
5 13. Mount the solenoid valve fitted with new
O-rings. Coat the O-rings with a little
12. grease to keep the rings in place during
LED
mounting.
2
Brown+15
Blue OV
Black FBsignal
M903020242O08
13.
M903020247O13
Page 10 (12) When referring to this page, please quote Procedure M90302 Edition 0249
Cylinder Lubricators 903-2.3
MAN B&W Diesel Overhaul
M903020247O14
Mount the oil accumulator.
When referring to this page, please quote Procedure M90302 Edition 0249 Page 11 (12)
903-2.4 Cylinder Lubricators
Mounting MAN B&W Diesel
3.
Inlet
M903020249M03
Page 12 (12) When referring to this page, please quote Procedure M90302 Edition 0249
Cylinder Lubricators 903-2.1
Checking
0237
Cylinder Lubricators
K98MC
Checking
903-2.1
1.
Check of Oil Injection:
When referring to this page, please quote Procedure M90302 Edition 0237 Page 1 (10)
0$1% :'LHVHO$6
903-2.1 Cylinder Lubricators
Checking
4. Check of Accumulators:
Page 2 (10) When referring to this page, please quote Procedure M90302 Edition 0237
0$1% :'LHVHO$6
Cylinder Lubricators 903-2.1
Checking
7. C
7. Before mounting the filling valve on the ac-
cumulator, check that the accumulator top
is clean. A E
Mount the filling valve on the relevant accu- D-3 F
mulator with the union nut. Check that
valves C and F are closed.
NA903-2.1 222 06
gauge on the filling valve.
When referring to this page, please quote Procedure M90302 Edition 0237 Page 3 (10)
0$1% :'LHVHO$6
903-2.2 Cylinder Lubricators
Dismantling
Dismantling
903-2.2
1. Dismantling of lubricators:
Dismantling of accumulators:
4. Inlet Accumulator
Close the valve that connects the accumu-
lator to the distributor block.
Page 4 (10) When referring to this page, please quote Procedure M90302 Edition 0237
0$1% :'LHVHO$6
Cylinder Lubricators 903-2.2
Dismantling
5. Outlet Accumulator 4.
Close the supply valve for the accumulator
concerned, using the special tool. The out-
er valve is for accumulator marked A and
the inner valve is for accumulator marked
B. A B
NA903-2.2 222 05
dismounted, see Step 1 .
When referring to this page, please quote Procedure M90302 Edition 0237 Page 5 (10)
0$1% :'LHVHO$6
903-2.3 Cylinder Lubricators
Overhaul
Overhaul
903-2.3
3.
NA903-2.3 222 03
Page 6 (10) When referring to this page, please quote Procedure M90302 Edition 0237
0$1% :'LHVHO$6
Cylinder Lubricators 903-2.3
Overhaul
NA903-2.3 222 04
Clean the housing with diesel oil or kero-
sene and dry with a non-fluffy cloth.
When referring to this page, please quote Procedure M90302 Edition 0237 Page 7 (10)
0$1% :'LHVHO$6
903-2.3 Cylinder Lubricators
Overhaul
2 2 Solenoid valve
7. Fit the cylinder block with new O-rings.
3 BN (brown)
4 BK (black) Feedback sensor
5 BU (blue) Assemble the non-return valves in the cyl-
inder block.
6a.
Mount the cover with the three inner
LED
screws.
5V
+1
wn
B ro
e OV al
Blu ign
F B-s
ck
Bla
707-40C-7A
7.
EN903-2.3 219 07
Page 8 (10) When referring to this page, please quote Procedure M90302 Edition 0237
0$1% :'LHVHO$6
Cylinder Lubricators 903-2.3
Overhaul
EN903-2.3 219 08
Check that the spring pin engages correctly
with the cylinder block assembly.
10.
EN903-2.3 219 01
When referring to this page, please quote Procedure M90302 Edition 0237 Page 9 (10)
0$1% :'LHVHO$6
903-2.4 Cylinder Lubricators
Mounting
Mounting
903-2.4
1. Mounting of Lubricators
3.
NA903-2.4 222 03
Page 10 (10) When referring to this page, please quote Procedure M90302 Edition 0237
0$1% :'LHVHO$6
Cylinder Lubricators 903-2.1
When referring to this page, please quote Procedure M90302 Edition 0256 Page 1 (13)
903-2.1 Cylinder Lubricators
Checking MAN B&W
Check of Accumulators:
4.
D03-10 4. Check of Inlet Accumulator
Checking the inlet accumulator can be
done with running engine.
Page 2 (13) When referring to this page, please quote Procedure M90302 Edition 0256
Cylinder Lubricators 903-2.1
M903020247C07
8. If the accumulator needs to be refilled with
nitrogen, open valve A and increase the
outlet pressure from valve C on spindle
B to 12 bar above the pressure stated in
Data.
When referring to this page, please quote Procedure M90302 Edition 0256 Page 3 (13)
903-2.2 Cylinder Lubricators
Dismantling MAN B&W
Dismantling of lubricators:
1.
Both lubricators can be dismounted with run-
A B ning engine, one at a time. If the engine is
running when a lubricator is dismounted, it is
important to check that the other lubricator is
doubling injection frequency.
Page 4 (13) When referring to this page, please quote Procedure M90302 Edition 0256
Cylinder Lubricators 903-2.2
Dismantling of accumulators:
4.
4. Inlet Accumulator
Close the valve that connects the accumu-
lator to the distributor block.
Mount the special hose on the minimess
coupling and drain the oil out of the accu-
mulator.
Unscrew the accumulator. If the engine is
running, a new or checked accumulator
should be mounted at once.
5. Outlet Accumulator
M903020256D04
Close the supply valve for the accumulator
concerned, using the special tool. The out-
er valve is for accumulator marked A and
the inner valve is for accumulator marked
B.
5.
Let the lubricator inject oil until the feed-
back LED stops flashing.
A B
When referring to this page, please quote Procedure M90302 Edition 0256 Page 5 (13)
903-2.3 Cylinder Lubricators
Overhaul MAN B&W
plungers.
3.
M903020247O03
Page 6 (13) When referring to this page, please quote Procedure M90302 Edition 0256
Cylinder Lubricators 903-2.3
M903020247O04
5.
M903020247O05
6.
M903020247O06
When referring to this page, please quote Procedure M90302 Edition 0256 Page 7 (13)
903-2.3 Cylinder Lubricators
Overhaul MAN B&W
8.
M903020247O08
Page 8 (13) When referring to this page, please quote Procedure M90302 Edition 0256
Cylinder Lubricators 903-2.3
M903020247O09
Lubricate the slide with oil and check that
the slide can move lightly with a good fit in
the housing.
11.
M903020245O10
1 1
2 2 Solenoid valve
3 BN (brown)
BK (black)
4
BU (blue) Feedback sensor
5
When referring to this page, please quote Procedure M90302 Edition 0256 Page 9 (13)
903-2.3 Cylinder Lubricators
Overhaul MAN B&W
13.
M903020247O13
14.
M903020247O14
Page 10 (13) When referring to this page, please quote Procedure M90302 Edition 0256
Cylinder Lubricators 903-2.3
M903020247O01
When referring to this page, please quote Procedure M90302 Edition 0256 Page 11 (13)
903-2.4 Cylinder Lubricators
Mounting MAN B&W
Mounting of Lubricators
1.
1. Mount new Orings on the hydraulic block
and on the cover with pipes.
2.
A B
M903020256M02
Page 12 (13) When referring to this page, please quote Procedure M90302 Edition 0256
Cylinder Lubricators 903-2.4
Mounting of Accumulator
3.
3. Mount the accumulator. Remove the drain
hose from the minimess coupling. Open the
valve that connects the accumulator to the
distributor block.
M903020256M03
When referring to this page, please quote Procedure M90302 Edition 0256 Page 13 (13)
Blank
Tacho Pick-Ups 105-7
MAN B&W Data
Data
D05-42 50 ±2 mm
D05-43 10 ±2 mm
When referring to this page, please quote Data D10507 Edition 0006 Page 1 (2)
105-7 Tacho Pick-Ups
Data MAN B&W
The task-specific tools used in this procedure are shown on the plates at the end of this chapter or in
the chapters indicated by the first three digits in the plate number, e.g. P90951 refers to chapter 909.
Page 2 (2) When referring to this page, please quote Data D10507 Edition 0006
Tacho Pick-Ups 905-7.1
MAN B&W Checking
2.
D05-40
Turning wheel
M90507-0205C02
When referring to this page, please quote Procedure M90507 Edition 0205 Page 1 (3)
905-7.1 Tacho Pick-Ups
Checking MAN B&W
5.
D05-41
M90507-0205C05
50 ± 2mm
Page 2 (3) When referring to this page, please quote Procedure M90507 Edition 0205
Tacho Pick-Ups 905-7.1
MAN B&W Checking
M90501-0205C06
10 ± 2mm
When referring to this page, please quote Procedure M90507 Edition 0205 Page 3 (3)
Blank
Angle Encoder 105-8
Data
SAFETY PRECAUTIONS
Special Edition
MC
D10508
105-8 Data 0007 Angle Encoder
X Stopped engine
X Block the starting mechanism
X Shut off starting air supply
X Engage turning gear
Shut off cooling water
Shut off fuel oil
X Shut off lubricating oil
Lock turbocharger rotors
Data
Ref. Description Value Unit
When referring to this page, please quote Data D10508 Edition 0007 Page 1 (2)
MAN B&W Diesel A/S
105-8 Angle Encoder
Data
The task-specific tools used in this procedure are shown on the plates at the end of this chapter or in the
chapters indicated by the first three digits in the plate number, e.g. P90951 refers to chapter 909.
Page 2 (2) When referring to this page, please quote Data D10508 Edition 0007
MAN B&W Diesel A/S
Angle Encoder 905-8.1
MAN B&W Checking
M90508-0206C01
Check that the rubber damper is intact.
3.
M90508-0206C03
When referring to this page, please quote Procedure M90508 Edition 0206 Page 1 (4)
905-8.2 Angle Encoder
Dismantling MAN B&W
2.
M90508-0206D02
3.
M90508-0206D03
Page 2 (4) When referring to this page, please quote Procedure M90508 Edition 0206
Angle Encoder 905-5.3
MAN B&W Adjustment
Note!
Before using the pin gauge, check the
measurement from tip to tip with the val-
ue stamped on the pin gauge, and/or the
check-marks stamped on the fore end of
M90508-0206O01
the cylinder frame.
2.
M90508-0206O03
When referring to this page, please quote Procedure M90508 Edition 0206 Page 3 (4)
905-8.4 Angle Encoder
Mounting MAN B&W
Note!
M90508-0206M01
3.
M90508-0206M03
Page 4 (4) When referring to this page, please quote Procedure M90508 Edition 0206
Alpha Lubricator System S903-0040
MAN B&W Check and Adjustment of Index Transmitter
The following guidelines are relevant for the adjustment or replacement of the index transmitter
on engines in service.
Deg. %
Min. bar
Navigate, via the HMI panel, to the Index Oil pressure low
Index failure
Adjust menu.
Mark/trig failure
Choose either the generator curve or the Feedback failure
propeller curve, depending on the measure- Common alarm
S90321-0021
These settings are only 100% valid when running on diesel oil. When running on heavy fuel
there can be a minor offset, which can be compensated for by adjusting the mechanical con-
nection from the fuel rack to the index transmitter.
When referring to this page, please quote S-Instruction S903 Edition 0040 Page 1 (1)
Blank
Index
Operation
Commissioning
Maintenance
Components
Electrical Wiring
Blank
Cylinder Lubricator Assy Plate
P90307-0008
3
&\OLQGHU/XEULFDWRU$VV\
When referring to this page, please quote Plate P90307 Edition 0008 Page 1 (2)
MAN B&W Diesel A/S
Plate Cylinder Lubricator Assy
P90307-0008
Item Item
Item Description Item Description
No. No.
700 Screw
018 Accumulator membrane
031 Shim
043 Distributor block
055 Studs
067 Nut
079 Coupling, minimess
114 Ball valve
126 Coupling
138 Distributor block
151 Stud
175 Spring pin
199 Lubricator
209 Screw
222 Accumulator membrane
234 Shim
258 Distributor block
271 Plug screw
295 O-ring
317 Non-return valve
329 Disc
330 Circlip
342 Plug screw
366 Terminal box, complete
378 Screw
391 Cable
401 O-ring
413 Inductive sensor, complete
437 Steel ball
449 Spring
462 Screw
474 O-ring
498 Coupling
508 Adjustment screw
521 Spacer
533 Cover
545 Cylinder block
557 Cover
569 Cylinder block
570 O-ring
582 Spring
594 O-ring
616 Screw
628 Screw
653 Plunger
665 Cylinder housing
677 Actuator piston
690 Solenoid valve, complete
Page 2 (2) When referring to this page, please quote Plate P90307 Edition 0008
MAN B&W Diesel A/S
Cylinder Lubricator Assy Plate
P90307-0011
3
&\OLQGHU/XEULFDWRU$VV\
C
A
A-A
When referring to this page, please quote Plate P90307 Edition 0011 Page 1 (2)
MAN B&W Diesel A/S
Plate Cylinder Lubricator Assy
P90307-0011
Item Item
Item Description Item Description
No. No.
Page 2 (2) When referring to this page, please quote Plate P90307 Edition 0011
MAN B&W Diesel A/S
Cylinder Lubricator Unit Plate
MAN B&W P90307-0036
When referring to this page, please qoute Plate P90307 Edition 0036 Page 1 (2)
Plate Cylinder Lubricator Unit
P90307-0036 MAN B&W
Note:
*
Page 2 (2) When referring to this page, please qoute Plate P90307 Edition 0036
Cylinder Lubricator Unit Plate
MAN B&W P90307-0045
When referring to this page, please quote Plate P90307 Edition 0045 Page 1 (2)
Plate
Cylinder Lubricator Unit
P90307-0045 MAN B&W
Page 2 (2) When referring to this page, please quote Plate P90307 Edition 0045
Cylinder Lubricator - Intermediate Box Plate
P90308-0010
3
&\OLQGHU/XEULFDWRU,QWHUPHGLDWH%R[
A A
A A
When referring to this page, please quote Plate P90308 Edition 0010 Page 1 (2)
MAN B&W Diesel A/S
Plate Cylinder Lubricator - Intermediate Box
P90308-0010
Item Item
Item Description Item Description
No. No.
Page 2 (2) When referring to this page, please quote Plate P90308 Edition 0010
MAN B&W Diesel A/S
Arrangement of Angle Decoder Plate
P90503-0017
3
$UUDQJHPHQWRI$QJOH'HFRGHU
A-A
When referring to this page, please quote Plate P90503 Edition 0017 Page 1 (2)
MAN B&W Diesel A/S
Plate Arrangement of Angle Decoder
P90503-0017
Item Item
Item Description Item Description
No. No.
Page 2 (2) When referring to this page, please quote Plate P90503 Edition 0017
MAN B&W Diesel A/S
Index
Operation
Commissioning
Maintenance
Components
Electrical Wiring
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank