ST7cc TIM S7-1500 S7-1200 ET 200SP DOC en V10
ST7cc TIM S7-1500 S7-1200 ET 200SP DOC en V10
an S7-1200 RTU,
an S7-1500 and
an ET 200SP RTU
to a ST7cc central
station
Siemens
ST7cc / TIA Portal V15 / WinCC V7.4 / TeleControl Industry
Online
https://support.industry.siemens.com/cs/ww/en/view/109761107 Support
Legal information
Legal information
Use of application examples
Application examples illustrate the solution of automation tasks through an interaction of several
components in the form of text, graphics and/or software modules. The application examples are
a free service by Siemens AG and/or a subsidiary of Siemens AG (“Siemens”). They are non-
binding and make no claim to completeness or functionality regarding configuration and
equipment. The application examples merely offer help with typical tasks; they do not constitute
customer-specific solutions. You yourself are responsible for the proper and safe operation of the
products in accordance with applicable regulations and must also check the function of the
respective application example and customize it for your system.
Siemens grants you the non-exclusive, non-sublicensable and non-transferable right to have the
application examples used by technically trained personnel. Any change to the application
examples is your responsibility. Sharing the application examples with third parties or copying the
application examples or excerpts thereof is permitted only in combination with your own products.
The application examples are not required to undergo the customary tests and quality inspections
of a chargeable product; they may have functional and performance defects as well as errors. It is
your responsibility to use them in such a manner that any malfunctions that may occur do not
result in property damage or injury to persons.
Disclaimer of liability
Siemens shall not assume any liability, for any legal reason whatsoever, including, without
limitation, liability for the usability, availability, completeness and freedom from defects of the
application examples as well as for related information, configuration and performance data and
any damage caused thereby. This shall not apply in cases of mandatory liability, for example
under the German Product Liability Act, or in cases of intent, gross negligence, or culpable loss of
life, bodily injury or damage to health, non-compliance with a guarantee, fraudulent
non-disclosure of a defect, or culpable breach of material contractual obligations. Claims for
damages arising from a breach of material contractual obligations shall however be limited to the
© Siemens AG 2019 All rights reserved
foreseeable damage typical of the type of agreement, unless liability arises from intent or gross
negligence or is based on loss of life, bodily injury or damage to health. The foregoing provisions
do not imply any change in the burden of proof to your detriment. You shall indemnify Siemens
against existing or future claims of third parties in this connection except where Siemens is
mandatorily liable.
By using the application examples you acknowledge that Siemens cannot be held liable for any
damage beyond the liability provisions described.
Other information
Siemens reserves the right to make changes to the application examples at any time without
notice. In case of discrepancies between the suggestions in the application examples and other
Siemens publications such as catalogs, the content of the other documentation shall have
precedence.
The Siemens terms of use (https://support.industry.siemens.com) shall also apply.
Security information
Siemens provides products and solutions with industrial security functions that support the secure
operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept.
Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems, machines
and networks. Such systems, machines and components should only be connected to an
enterprise network or the Internet if and to the extent such a connection is necessary and only
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
at: https://www.siemens.com/industrialsecurity.
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 2
Table of contents
Table of contents
Legal information ......................................................................................................... 2
1 Introduction ........................................................................................................ 4
1.1 Overview............................................................................................... 4
1.2 Principle of operation............................................................................ 7
1.3 Components used ................................................................................ 7
2 Engineering ........................................................................................................ 8
2.1 Installing and commissioning ............................................................... 8
2.1.1 Installation and loading......................................................................... 8
2.1.2 Configuring the PC station ................................................................... 9
2.2 Configuring ST7cc and WinCC servers ............................................. 12
2.2.1 Assigning a computer name in WinCC Explorer ................................ 12
2.2.2 Configuring ST7cc Config .................................................................. 13
2.2.3 Start ST7cc and WinCC Runtime ....................................................... 16
2.3 Operation ............................................................................................ 17
2.3.1 Operating WinCC startup screen ....................................................... 17
2.3.2 Operate "RTU based on XXX" screens .............................................. 20
2.3.3 Ending WinCC and ST7cc Runtime ................................................... 21
3 Useful Information ........................................................................................... 23
3.1 Configure modules in STEP 7 ............................................................ 23
3.2 Configuring WinCC and ST7cc Config ............................................... 27
© Siemens AG 2019 All rights reserved
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 3
1 Introduction
1 Introduction
1.1 Overview
With the integration of the SINAUT project planning in the TIA Portal (from V14
SP1 Upd2), the complete communication configuration takes place in one tool.
The TeleControl portfolio has been expanded with the TIM 1531 IRC, which can be
connected to the central control station as a stand-alone device.
This means that one or more RTUs can be used as substations in existing
TeleControl systems or in new systems with the SINAUT ST7 protocol.
In this application example, an RTU based on SIMATIC S7-1500, a
SIMATIC S7-1200 using the CP 1243-8 IRC and a SIMATIC ET 200SP using the
CP 1542SP-1 IRC are each configured in a new system with TIA Portal.
The following graphic shows the configuration scenario that is implemented in this
example.
© Siemens AG 2019 All rights reserved
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 4
1 Introduction
Figure 1-1
SINAUT ST7cc
WinCC
SCALANCE M816-1
Central TIM
TIM 1531 IRC
© Siemens AG 2019 All rights reserved
SCALANCE SCALANCE
M816-1 M874-3
RTU based on PROFINET / IE
VPN tunnel
S7-1500
SCALANCE
M816-1
Station TIM
TIM 1531 IRC
Note The core of this scenario is the TeleControl configuration. To keep the
documentation clear, the RTU is directly connected to the central control station
via Ethernet (see Figure 1-2).
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 5
1 Introduction
Figure 1-2
SINAUT ST7cc
WinCC
Central TIM
TIM 1531 IRC
S7-1500
Station TIM
TIM 1531 IRC
Delimitation
• For the WinCC configuration, only the communication-relevant settings are
described.
• The configuration of the VPN tunnel and the SCALANCE M devices is not
described in this documentation. The possible remote network configurations
are described in the link \3\.
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 6
1 Introduction
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 7
2 Engineering
2 Engineering
This application example supports you in the creation of the communication
configuration. It enables a quick functional test of the hardware and software
interfaces between the products described here.
The application example shows the basic interaction of the TeleControl modules.
However, it itself does not represent a real application in the sense of a
technological problem solution with definable properties.
CP 1512SP-1 PN
S7-1511-1 PN Port 1 192.168.1.31 TIM of the S7-1500 RTU
with Port 2 192.168.0.31
TIM 1531 IRC
Port 3 192.168.2.31
1. Install the hardware and software components (Table 1-1) according to the
description in the operating instructions of the respective components
(chapter 4.2).
2. Connect the hardware components as shown in Figure 1-2.
Note During the creation of this example, one computer was used simultaneously as a
programming computer and as a central control station.
If you use separate computers, the following software must be installed on the
central control station:
• SIMATIC WinCC Runtime
• SINAUT ST7cc
• SIMATIC NET PC software
Note Note that the S7-1200 CPs are mounted to the left of the CPU. The CPs for the
ET 200SP are mounted on the right side of the CPU.
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 8
2 Engineering
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 9
2 Engineering
© Siemens AG 2019 All rights reserved
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 10
2 Engineering
Note If the components are not started immediately without errors, restart the
computer.
Note Importing is possible only when the imported configuration matches the existing
local configuration. Make sure that the IP address of the PC/PG matches the
configuration in the TIA Portal.
Incorrect components are marked.
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 11
2 Engineering
6. Now enter the name of your computer under "Computer name" and accept the
entry with "OK".
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 12
2 Engineering
1. Start the program "ST7cc Config" via the corresponding desktop icon and then
open the project " ST7cc_TIM_S7-1500_S7-1200_ET_200SP_WinCC > ST7cc
> ST7_PROJEKT.XML" via "File > Open".
2. Open the "Project settings" window via "Edit" and adjust the paths for the
project. Confirm your settings with "OK".
Note You can look up the files to be selected in manual \7\ in chapter 3.3.2.
List of files to be selected:
1. "st7_project_english.txt"
2. "st7_typicals_english.txt"
3. "st7_project.mmf"
4. "st7_project_local.mmf"
5. "st7_project_remote.mmf".
© Siemens AG 2019 All rights reserved
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 13
2 Engineering
Click on "Add server information to system" to activate the settings you have
made.
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 14
2 Engineering
6. Check whether all messages end with "... OK" and confirm the settings with
"OK".
© Siemens AG 2019 All rights reserved
7. Go to the "Project" tab and click "Activate current project for ST7cc Runtime"
(1).
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 15
2 Engineering
Among other things, the log window of the SINAUT server shows the
connection setup with the SINAUT subscribers and that the general queries of
these subscribers, which were started automatically when the system was
started, were terminated without errors.
3. Wait until the ST7cc server is running. This is the case when the "ST7CC
Server" window appears.
© Siemens AG 2019 All rights reserved
4. After the ST7cc server has been started, start the WinCC Runtime in the
WinCC Explorer.
After the ST7cc and WinCC runtime have been started, the SINAUT demo
project is active and the start screen of the WinCC Runtime appears.
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 16
2 Engineering
2.3 Operation
In the following chapter we will introduce you to the operation of the demo project
as well as the test and diagnostic options provided by the components used. The
prerequisite for operation is that the installation and configuration has taken place
in accordance with chapter 2.1 and 2.2.
The WinCC start screen displays the faceplates with status information for all
TeleControl stations. These faceplates can be generated by SINAUT ST7cc Config
Tool and integrated into a project.
1. Click with the left mouse button on the respective faceplate to open the list with
the details.
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 17
2 Engineering
Besides the number of existing ST7cc servers and directly connected TIMs,
the status of the TCO (communication module of the ST7cc software) is also
displayed. For more information, refer to the ST7cc Control Center manual
(see link \7\ in the appendix).
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 18
2 Engineering
• Position 3: Station
The picture-typical shows whether the station CPU can be reached
(subscriber), that the last general interrogation to the station was completed
without errors (GR) and that the time in the station is correct (clock).
A general request can also be triggered in the detail view. All data telegrams
possibly still stored there as well as a current process image are then
transferred from the CP in the station.
The other two command options (switching a continuous connection on and
© Siemens AG 2019 All rights reserved
off) are only relevant for a station that is connected via a dial-up network or a
leased line.
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 19
2 Engineering
The picture "RTU based on XXX" shows the process picture of a water tank. The
filling level of the water tank is regulated by the two valves.
Figure 2-1
2
3
© Siemens AG 2019 All rights reserved
4 5
• Position 1: Inflow valve for operating the pump (command and status display)
– Red: Pump is switched off
– Green: Pump is switched on
• Position 2: Outflow valve (command and status display)
– Red: Valve is closed
– Green: Valve is open
• Position 3: Graphic level display
• Position 4: Level display
• Position 5: Status display of the filling level, alarm is displayed when the tank is
full.
• Position 6: Function keys for switching to the corresponding overview screens
or for terminating the runtime
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 20
2 Engineering
If the fill level exceeds the 80% programmed in the CPU, an alarm is sent from
the RTU to the server and displayed in the "Fill level state" field.
© Siemens AG 2019 All rights reserved
NOTICE In this demo project, the control objects are not completely programmed, nor are
the states locked against each other. The corresponding program parts cannot
be used for a real plant.
This example shows only a few possibilities of TeleControl.
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 21
2 Engineering
2. Then stop the SINAUT ST7cc server using the "Shutdown" icon, as shown
below.
The LOG console and the command entry window are automatically closed.
© Siemens AG 2019 All rights reserved
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 22
3 Useful Information
3 Useful Information
This chapter describes the most important project engineering steps that led to the
delivered program.
6. Enter the desired IP addresses (see Table 2-1) and connect the modules to the
corresponding Ethernet (see Figure 1-2).
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 23
3 Useful Information
© Siemens AG 2019 All rights reserved
2. Select the RTU ET 200SP as "endpoint". Then open the "Add new connection
path" dialog.
3. Select a connection path for this connection from the displayed list and accept
it with "Add".
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 24
3 Useful Information
1. Create the PLC tags to be exchanged with the ST7cc server in a data block.
2. In the RTU go to "Local Modules > CP > Data Points" and insert the PLC tags
into the data point configuration via drag-and-drop.
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 25
3 Useful Information
© Siemens AG 2019 All rights reserved
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 26
3 Useful Information
Note The data points of the S7-1500 controller are configured in the TIM 1543 IRC.
For this the TIM must be assigned to the S7-1500 controller.
1. Open the WinCC Explorer and create a new WinCC project via "File > New".
2. Click on "Computer" to open the window with the properties ("Computer
properties").
3. Activate the "Tag Logging Runtime" option in the "Startup" tab.
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 27
3 Useful Information
© Siemens AG 2019 All rights reserved
4. Open the "Tag Management" and insert the ST7cc driver. To do this, right-click
on "Tag Management > Add new driver > ST7".
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 28
3 Useful Information
© Siemens AG 2019 All rights reserved
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 29
3 Useful Information
project.
5. Insert the stations via "Edit > New Station".
6. Enter the SINAUT participant number of the CPU.
The number must match the configured participant number for the CPU in the
STEP 7 project.
Configuring objects
1. Paste the desired objects by copying them from the library.
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 30
3 Useful Information
© Siemens AG 2019 All rights reserved
Note The subtype to be entered depends on the position of the station. For example,
subtype "3" must be entered if the station is configured below a central
TIM 1531-IRC.
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 31
3 Useful Information
Note The local ID can be found in STEP 7 under "Network View > Connections >
© Siemens AG 2019 All rights reserved
2. Generate the WinCC tags via "Edit > Complete WinCC Generation".
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 32
3 Useful Information
4. Copy the faceplates to the WinCC project via "Admin > Copy Faceplates to
WinCC Project".
© Siemens AG 2019 All rights reserved
5. Create the picture-typicals for your project via "Edit > Create the project
picture-typicals".
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 33
3 Useful Information
© Siemens AG 2019 All rights reserved
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 34
4 Appendix
4 Appendix
4.1 Service and support
Industry Online Support
Do you have any questions or need assistance?
Siemens Industry Online Support offers round the clock access to our entire
service and support know-how and portfolio.
The Industry Online Support is the central address for information about our
products, solutions and services.
Product information, manuals, downloads, FAQs, application examples and videos
– all information is accessible with just a few mouse clicks:
https://support.industry.siemens.com
Technical Support
The Technical Support of Siemens Industry provides you fast and competent
support regarding all technical queries with numerous tailor-made offers
– ranging from basic support to individual support contracts. Please send queries
to Technical Support via Web form:
www.siemens.com/industry/supportrequest
© Siemens AG 2019 All rights reserved
Service offer
Our range of services includes the following:
• Plant data services
• Spare parts services
• Repair services
• On-site and maintenance services
• Retrofitting and modernization services
• Service programs and contracts
You can find detailed information on our range of services in the service catalog
web page:
support.industry.siemens.com/cs/sc
SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 35
4 Appendix