Connection of

an S7-1200 RTU,
an S7-1500 and
an ET 200SP RTU
to a ST7cc central
station
Siemens
ST7cc / TIA Portal V15 / WinCC V7.4 / TeleControl Industry
Online
https://support.industry.siemens.com/cs/ww/en/view/109761107 Support
Legal information

Legal information
Use of application examples
Application examples illustrate the solution of automation tasks through an interaction of several
components in the form of text, graphics and/or software modules. The application examples are
a free service by Siemens AG and/or a subsidiary of Siemens AG (“Siemens”). They are non-
binding and make no claim to completeness or functionality regarding configuration and
equipment. The application examples merely offer help with typical tasks; they do not constitute
customer-specific solutions. You yourself are responsible for the proper and safe operation of the
products in accordance with applicable regulations and must also check the function of the
respective application example and customize it for your system.
Siemens grants you the non-exclusive, non-sublicensable and non-transferable right to have the
application examples used by technically trained personnel. Any change to the application
examples is your responsibility. Sharing the application examples with third parties or copying the
application examples or excerpts thereof is permitted only in combination with your own products.
The application examples are not required to undergo the customary tests and quality inspections
of a chargeable product; they may have functional and performance defects as well as errors. It is
your responsibility to use them in such a manner that any malfunctions that may occur do not
result in property damage or injury to persons.

Disclaimer of liability
Siemens shall not assume any liability, for any legal reason whatsoever, including, without
limitation, liability for the usability, availability, completeness and freedom from defects of the
application examples as well as for related information, configuration and performance data and
any damage caused thereby. This shall not apply in cases of mandatory liability, for example
under the German Product Liability Act, or in cases of intent, gross negligence, or culpable loss of
life, bodily injury or damage to health, non-compliance with a guarantee, fraudulent
non-disclosure of a defect, or culpable breach of material contractual obligations. Claims for
damages arising from a breach of material contractual obligations shall however be limited to the
© Siemens AG 2019 All rights reserved

foreseeable damage typical of the type of agreement, unless liability arises from intent or gross
negligence or is based on loss of life, bodily injury or damage to health. The foregoing provisions
do not imply any change in the burden of proof to your detriment. You shall indemnify Siemens
against existing or future claims of third parties in this connection except where Siemens is
mandatorily liable.
By using the application examples you acknowledge that Siemens cannot be held liable for any
damage beyond the liability provisions described.

Other information
Siemens reserves the right to make changes to the application examples at any time without
notice. In case of discrepancies between the suggestions in the application examples and other
Siemens publications such as catalogs, the content of the other documentation shall have
precedence.
The Siemens terms of use (https://support.industry.siemens.com) shall also apply.

Security information
Siemens provides products and solutions with industrial security functions that support the secure
operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept.
Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems, machines
and networks. Such systems, machines and components should only be connected to an
enterprise network or the Internet if and to the extent such a connection is necessary and only
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
at: https://www.siemens.com/industrialsecurity.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 2
Table of contents

Table of contents
Legal information ......................................................................................................... 2
1 Introduction ........................................................................................................ 4
1.1 Overview............................................................................................... 4
1.2 Principle of operation............................................................................ 7
1.3 Components used ................................................................................ 7
2 Engineering ........................................................................................................ 8
2.1 Installing and commissioning ............................................................... 8
2.1.1 Installation and loading......................................................................... 8
2.1.2 Configuring the PC station ................................................................... 9
2.2 Configuring ST7cc and WinCC servers ............................................. 12
2.2.1 Assigning a computer name in WinCC Explorer ................................ 12
2.2.2 Configuring ST7cc Config .................................................................. 13
2.2.3 Start ST7cc and WinCC Runtime ....................................................... 16
2.3 Operation ............................................................................................ 17
2.3.1 Operating WinCC startup screen ....................................................... 17
2.3.2 Operate "RTU based on XXX" screens .............................................. 20
2.3.3 Ending WinCC and ST7cc Runtime ................................................... 21
3 Useful Information ........................................................................................... 23
3.1 Configure modules in STEP 7 ............................................................ 23
3.2 Configuring WinCC and ST7cc Config ............................................... 27
© Siemens AG 2019 All rights reserved

3.2.1 Creating WinCC project...................................................................... 27


3.2.2 Configuring ST7cc .............................................................................. 29
4 Appendix .......................................................................................................... 35
4.1 Service and support ........................................................................... 35
4.2 Links and Literature ............................................................................ 36
4.3 Change documentation ...................................................................... 36

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 3
1 Introduction

1 Introduction
1.1 Overview
With the integration of the SINAUT project planning in the TIA Portal (from V14
SP1 Upd2), the complete communication configuration takes place in one tool.
The TeleControl portfolio has been expanded with the TIM 1531 IRC, which can be
connected to the central control station as a stand-alone device.
This means that one or more RTUs can be used as substations in existing
TeleControl systems or in new systems with the SINAUT ST7 protocol.
In this application example, an RTU based on SIMATIC S7-1500, a
SIMATIC S7-1200 using the CP 1243-8 IRC and a SIMATIC ET 200SP using the
CP 1542SP-1 IRC are each configured in a new system with TIA Portal.

The following graphic shows the configuration scenario that is implemented in this
example.
© Siemens AG 2019 All rights reserved

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 4
1 Introduction

Figure 1-1

Central control station

SINAUT ST7cc
WinCC

SCALANCE M816-1

Central TIM
TIM 1531 IRC
© Siemens AG 2019 All rights reserved

RTU based on S7-1200 RTU based on ET 200SP

SCALANCE SCALANCE
M816-1 M874-3
RTU based on PROFINET / IE
VPN tunnel
S7-1500

SCALANCE
M816-1

Station TIM
TIM 1531 IRC

Note The core of this scenario is the TeleControl configuration. To keep the
documentation clear, the RTU is directly connected to the central control station
via Ethernet (see Figure 1-2).

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 5
1 Introduction

Figure 1-2

Central control station

SINAUT ST7cc
WinCC

Central TIM
TIM 1531 IRC

RTU based on ET 200SP


RTU based on S7-1200
© Siemens AG 2019 All rights reserved

RTU based on PROFINET / IE

S7-1500

Station TIM
TIM 1531 IRC

Delimitation
• For the WinCC configuration, only the communication-relevant settings are
described.
• The configuration of the VPN tunnel and the SCALANCE M devices is not
described in this documentation. The possible remote network configurations
are described in the link \3\.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 6
1 Introduction

1.2 Principle of operation


Use case
The filling level of a water tank is to be controlled and monitored from a central
control station. The following requirements apply:
• The level of the water tank should be simulated in each RTU.
• The current level should be sent to the central station.
• The pump and valves should be controlled from the central station.
• The current status of the pump and valves should be sent to the central station.

1.3 Components used


The following hardware and software components were used to create this
application example:
Table 1-1
Components Quantity Article number Note
SIMATIC Field PG M4 1 - -
TIM 1531 IRC 2 6GK7543-1MX00-0XE0 V 1.1 or higher
© Siemens AG 2019 All rights reserved

S7-1214C DC/DC/DC 1 6ES7214-1AG40-0XB0 V 4.2 or higher


CP 1243-8 IRC 1 6GK7243-8RX30-0XE0 V 3.1
CPU 1510SP-1 PN for 1 6ES7510-1DJ01-0AB0 V 2.5
ET 200SP
CP 1542SP-1 IRC 1 6GK7542-6VX00-0XE0 V 2.0
S7-1511-1 PN 1 6ES7511-1AK01-0AB0 V 2.5
STEP 7 V15 Professional 1 6AV6381-2BM07-4AX0 -
WinCC V7.4 SP1, RC 2048 1 6AV6381-2BP07-4AX0 -
SINAUT ST7cc V3.1 SP3 S 1 6NH7997-7CA31-0AA1 -
SIMATIC NET PC Software 1 6GK1704-1LW15-0AA0 -
V15 IE Lean

This application example consists of the following components:


Table 1-2
Components File name Note
Project 109761107_ST7cc_TIM_S7-1500_S7- Contains the TIA
1200_ET_200SP_CODE_V10.zip portal and the
WinCC project.
Documentation 109761107_ST7cc_TIM_S7-1500_S7- -
1200_ET_200SP_DOC_en_V10.pdf

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 7
2 Engineering

2 Engineering
This application example supports you in the creation of the communication
configuration. It enables a quick functional test of the hardware and software
interfaces between the products described here.
The application example shows the basic interaction of the TeleControl modules.
However, it itself does not represent a real application in the sense of a
technological problem solution with definable properties.

2.1 Installing and commissioning


The following table provides an overview of all IP addresses used in this example.
The fixed assignment of IP addresses is assumed.
Table 2-1
Components IP address Description
ST7cc computer 192.168.1.100 Central control station
TIM 1531 IRC Port 1 192.168.1.1 Central TIM
Port 2 192.168.0.1
Port 3 192.168.2.1
S7-1214C DC/DC/DC with 192.168.0.11 CP of the S7-1200 RTU
CP 1243-8 IRC
ET 200SP with 192.168.0.21 CP of the ET 200SP RTU
© Siemens AG 2019 All rights reserved

CP 1512SP-1 PN
S7-1511-1 PN Port 1 192.168.1.31 TIM of the S7-1500 RTU
with Port 2 192.168.0.31
TIM 1531 IRC
Port 3 192.168.2.31

The subnet mask in all network components is 255.255.255.0.

2.1.1 Installation and loading

1. Install the hardware and software components (Table 1-1) according to the
description in the operating instructions of the respective components
(chapter 4.2).
2. Connect the hardware components as shown in Figure 1-2.

Note During the creation of this example, one computer was used simultaneously as a
programming computer and as a central control station.
If you use separate computers, the following software must be installed on the
central control station:
• SIMATIC WinCC Runtime
• SINAUT ST7cc
• SIMATIC NET PC software

Note Note that the S7-1200 CPs are mounted to the left of the CPU. The CPs for the
ET 200SP are mounted on the right side of the CPU.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 8
2 Engineering

3. Unzip the file "109761107_ST7cc_TIM_S7-1500_S7-


1200_ET_200SP_CODE_V10.zip".
4. Launch TIA Portal on the programming computer and retrieve the file
"109761107_ST7cc_TIM_S7-1500_S7-1200_ET_200SP_TIA.ap15".
5. Enter the following login information to open the project:
– User name: administrator
– Password: Administrator1
6. Connect the Ethernet interface of the programming computer with the Ethernet
interface of the CPU or TIM you want to load.
7. Load all stations and the TIMs.
© Siemens AG 2019 All rights reserved

2.1.2 Configuring the PC station

A "PC station" is a PC with communication modules and software components


within a SIMATIC automation solution.
The hardware configuration of a PC station can be compared with the configuration
of an S7 station In SIMATIC: Similarly, components of a PC station, such as
modules or software interfaces, are assigned and parameterized to a virtual slot.

Importing the PC station


1. Assign the IP address to the computer that is to be configured as the central
control station according to Table 2-1.
2. Open the program "Station Configurator".
3. Click on "Import Station ...". (1) to import the Control Center .xdb file from the
XDB folder of the TIA project folder. Confirm the import with "OK" (2).

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 9
2 Engineering
© Siemens AG 2019 All rights reserved

4. The components are restarted. The imported configuration looks as shown in


the following figure.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 10
2 Engineering

Note If the components are not started immediately without errors, restart the
computer.

Note Importing is possible only when the imported configuration matches the existing
local configuration. Make sure that the IP address of the PC/PG matches the
configuration in the TIA Portal.
Incorrect components are marked.

Specifying access points


After the configuration of the PC station, the access point of the ST7cc-PC in the
network is now defined.
1. Open the "Siemens Communication Settings" via the corresponding desktop
icon or via the Windows search.
2. Click on "Access Points" (1) on the left in the directory tree of the PC station.
The available access points are displayed in the right window.
3. Click on the arrow to the left of "CP_H1_1" (2) to set this access point.
4. Then select the setting "CP designation.TCPIP.1" from the drop-down list
"Associated interface parameter assignment" (3) and accept the setting by
© Siemens AG 2019 All rights reserved

clicking on the button "Apply" (4).

The initial commissioning of the PC station has been completed.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 11
2 Engineering

2.2 Configuring ST7cc and WinCC servers


2.2.1 Assigning a computer name in WinCC Explorer

The file "109761107_ST7cc_S7-1500_S7-1200_ET_200SP_CODE_V10.zip"


contains the WinCC and ST7cc projects.
1. Unzip the file "109761107_ST7cc_TIM_S7-1500_S7-
1200_ET_200SP_CODE_V10.zip".
2. Start WinCC Explorer.
3. Open the file "109761107_ST7cc_TIM_S7-1500_S7-
1200_ET_200SP_WinCC.mcp" via "File > Open…". The file is available in the
"109761107_ST7cc_TIM_S7-1500_S7-1200_ET200SP_WinCC" folder.
4. The computer name "DESKTOP" was parameterized in the WinCC project.
The setting of the computer name in WinCC and in Windows must match.
Customize the computer name by selecting "Computer" (1).
5. Then open the properties dialog "Computer Properties" by double-clicking on
the server "DESKTOP" (2).
© Siemens AG 2019 All rights reserved

6. Now enter the name of your computer under "Computer name" and accept the
entry with "OK".

7. When prompted, restart WinCC Explorer.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 12
2 Engineering

2.2.2 Configuring ST7cc Config

1. Start the program "ST7cc Config" via the corresponding desktop icon and then
open the project " ST7cc_TIM_S7-1500_S7-1200_ET_200SP_WinCC > ST7cc
> ST7_PROJEKT.XML" via "File > Open".
2. Open the "Project settings" window via "Edit" and adjust the paths for the
project. Confirm your settings with "OK".

Note You can look up the files to be selected in manual \7\ in chapter 3.3.2.
List of files to be selected:
1. "st7_project_english.txt"
2. "st7_typicals_english.txt"
3. "st7_project.mmf"
4. "st7_project_local.mmf"
5. "st7_project_remote.mmf".
© Siemens AG 2019 All rights reserved

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 13
2 Engineering

3. Confirm the subsequent dialog with "Save".

4. Then open the menu "Global settings" via "Edit".


5. In the Server 1 section, enter the computer name and IP address
"192.168.1.100" for the ST7cc server.
© Siemens AG 2019 All rights reserved

Click on "Add server information to system" to activate the settings you have
made.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 14
2 Engineering

6. Check whether all messages end with "... OK" and confirm the settings with
"OK".
© Siemens AG 2019 All rights reserved

7. Go to the "Project" tab and click "Activate current project for ST7cc Runtime"
(1).

8. Close the dialog with "OK" (2).


9. Save the settings.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 15
2 Engineering

2.2.3 Start ST7cc and WinCC Runtime

To start the ST7cc and WinCC Runtime, proceed as follows:


1. Start the ST7cc Runtime via the corresponding icon on the desktop.
2. The DOS output window and the log window of the SINAUT server are
opened.

Among other things, the log window of the SINAUT server shows the
connection setup with the SINAUT subscribers and that the general queries of
these subscribers, which were started automatically when the system was
started, were terminated without errors.
3. Wait until the ST7cc server is running. This is the case when the "ST7CC
Server" window appears.
© Siemens AG 2019 All rights reserved

4. After the ST7cc server has been started, start the WinCC Runtime in the
WinCC Explorer.

After the ST7cc and WinCC runtime have been started, the SINAUT demo
project is active and the start screen of the WinCC Runtime appears.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 16
2 Engineering

Your SINAUT demo system is now ready for operation.


© Siemens AG 2019 All rights reserved

2.3 Operation
In the following chapter we will introduce you to the operation of the demo project
as well as the test and diagnostic options provided by the components used. The
prerequisite for operation is that the installation and configuration has taken place
in accordance with chapter 2.1 and 2.2.

2.3.1 Operating WinCC startup screen

The WinCC start screen displays the faceplates with status information for all
TeleControl stations. These faceplates can be generated by SINAUT ST7cc Config
Tool and integrated into a project.
1. Click with the left mouse button on the respective faceplate to open the list with
the details.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 17
2 Engineering

The picture-typical of the corresponding SINAUT participant appears.


• Position 1: ST7cc server state
© Siemens AG 2019 All rights reserved

Besides the number of existing ST7cc servers and directly connected TIMs,
the status of the TCO (communication module of the ST7cc software) is also
displayed. For more information, refer to the ST7cc Control Center manual
(see link \7\ in the appendix).

• Position 2: Local TIM


The picture-typical shows whether the TIM is reachable (subscriber), the last
general interrogation to the TIM was completed without errors (GR) and the
time on the TIM is OK (clock).
In the detail view, you can manually trigger a general request to the TIM, which
then transmits its most current accounting information. The processing of the
general interrogation can be followed at the GR display as well as in the text
field "GR" in the faceplate.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 18
2 Engineering

• Position 3: Station
The picture-typical shows whether the station CPU can be reached
(subscriber), that the last general interrogation to the station was completed
without errors (GR) and that the time in the station is correct (clock).
A general request can also be triggered in the detail view. All data telegrams
possibly still stored there as well as a current process image are then
transferred from the CP in the station.
The other two command options (switching a continuous connection on and
© Siemens AG 2019 All rights reserved

off) are only relevant for a station that is connected via a dial-up network or a
leased line.

• Position 4: Function keys


Use the function keys to switch between the images. You can also end the
Runtime by clicking the "Stop Runtime" button.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 19
2 Engineering

2.3.2 Operate "RTU based on XXX" screens

The picture "RTU based on XXX" shows the process picture of a water tank. The
filling level of the water tank is regulated by the two valves.
Figure 2-1

2
3
© Siemens AG 2019 All rights reserved

4 5

• Position 1: Inflow valve for operating the pump (command and status display)
– Red: Pump is switched off
– Green: Pump is switched on
• Position 2: Outflow valve (command and status display)
– Red: Valve is closed
– Green: Valve is open
• Position 3: Graphic level display
• Position 4: Level display
• Position 5: Status display of the filling level, alarm is displayed when the tank is
full.
• Position 6: Function keys for switching to the corresponding overview screens
or for terminating the runtime

To use this example, proceed as follows:


1. Turn on the pump by left-clicking the inflow valve icon.
2. Then close the outflow valve.
The status of the valves is sent from the CPU to the ST7cc server and
displayed accordingly.
The fill level of the water tank is indicated by the bar graph display and in the
"Fill level Water Tank" field.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 20
2 Engineering

If the fill level exceeds the 80% programmed in the CPU, an alarm is sent from
the RTU to the server and displayed in the "Fill level state" field.
© Siemens AG 2019 All rights reserved

NOTICE In this demo project, the control objects are not completely programmed, nor are
the states locked against each other. The corresponding program parts cannot
be used for a real plant.
This example shows only a few possibilities of TeleControl.

2.3.3 Ending WinCC and ST7cc Runtime

To end the Runtime, proceed as follows:


1. Use the "Stop Runtime" symbol or stop the WinCC Runtime via the WinCC
Explorer, even if you have previously closed the interface.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 21
2 Engineering

2. Then stop the SINAUT ST7cc server using the "Shutdown" icon, as shown
below.
The LOG console and the command entry window are automatically closed.
© Siemens AG 2019 All rights reserved

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 22
3 Useful Information

3 Useful Information
This chapter describes the most important project engineering steps that led to the
delivered program.

3.1 Configure modules in STEP 7


1. Create a STEP 7 project.
2. Then insert the hardware to be used.
The CPs and the TIM can be found in the "Hardware catalog" under
"Communication modules > Industrial Remote Communication".
3. Activate the TeleControl communication for the CP / the TIM and select the
protocol "ST7".
4. Insert a SIMATIC PC station with a communication card (here with an "IE
General").
5. Activate the option "Generate XDB file" in the properties of the SIMATIC PC
station. This file stores the configuration of the PC station that you need for the
settings in the SIMATIC Station Configurator.
© Siemens AG 2019 All rights reserved

6. Enter the desired IP addresses (see Table 2-1) and connect the modules to the
corresponding Ethernet (see Figure 1-2).

Configure TeleControl connections


1. Open "Devices & Networks" and open the editor "Network data". Switch to the
"TeleControl" tab to configure the TeleControl connections. Create a new
connection between your device and the ST7cc server. In the following steps
the connection from the ST7cc server to the RTU "ET 200SP" is configured.
Select the ST7 server as "starting point".

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 23
3 Useful Information
© Siemens AG 2019 All rights reserved

2. Select the RTU ET 200SP as "endpoint". Then open the "Add new connection
path" dialog.

3. Select a connection path for this connection from the displayed list and accept
it with "Add".

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 24
3 Useful Information

The configuration of the TeleControl connection is completed.

Creating data points


© Siemens AG 2019 All rights reserved

1. Create the PLC tags to be exchanged with the ST7cc server in a data block.

2. In the RTU go to "Local Modules > CP > Data Points" and insert the PLC tags
into the data point configuration via drag-and-drop.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 25
3 Useful Information
© Siemens AG 2019 All rights reserved

3. Configure the data points in the ''Properties'' window.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 26
3 Useful Information

Note The data points of the S7-1500 controller are configured in the TIM 1543 IRC.
For this the TIM must be assigned to the S7-1500 controller.

3.2 Configuring WinCC and ST7cc Config


© Siemens AG 2019 All rights reserved

3.2.1 Creating WinCC project

1. Open the WinCC Explorer and create a new WinCC project via "File > New".
2. Click on "Computer" to open the window with the properties ("Computer
properties").
3. Activate the "Tag Logging Runtime" option in the "Startup" tab.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 27
3 Useful Information
© Siemens AG 2019 All rights reserved

4. Open the "Tag Management" and insert the ST7cc driver. To do this, right-click
on "Tag Management > Add new driver > ST7".

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 28
3 Useful Information
© Siemens AG 2019 All rights reserved

3.2.2 Configuring ST7cc

Creating a ST7cc project and adding participants


1. Start the "ST7cc Config" program and then create a new project via "File >
New".
2. Save the new ST7cc project in the storage folder of the WinCC project under
the structure "WinCC project name > ST7cc folder".
3. Insert the local TIM for the ST7cc server via "Edit > New local TIM".

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 29
3 Useful Information

4. Enter the SINAUT participant number of the TIM.


The number must match the configured participant number in the STEP 7
© Siemens AG 2019 All rights reserved

project.
5. Insert the stations via "Edit > New Station".
6. Enter the SINAUT participant number of the CPU.
The number must match the configured participant number for the CPU in the
STEP 7 project.

Configuring objects
1. Paste the desired objects by copying them from the library.

2. Configure the objects as required.


Make sure that the object number matches the configured object number in the
STEP 7 project.

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 30
3 Useful Information
© Siemens AG 2019 All rights reserved

Note The subtype to be entered depends on the position of the station. For example,
subtype "3" must be entered if the station is configured below a central
TIM 1531-IRC.

Making settings for WinCC and for the communication connection


1. Open the menu for the project settings via "Edit > Project Settings". Switch to
the "Communication" tab. Enter the participant number of the ST7cc server.
Then click "New". Enter the participant number of the local TIM and the local ID
for the connection between TIM and ST7cc server. Confirm your settings with
"OK".

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 31
3 Useful Information

Note The local ID can be found in STEP 7 under "Network View > Connections >
© Siemens AG 2019 All rights reserved

Local Connection Name".

2. Generate the WinCC tags via "Edit > Complete WinCC Generation".

3. Check the created tags in "WinCC Tag Management".

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 32
3 Useful Information

4. Copy the faceplates to the WinCC project via "Admin > Copy Faceplates to
WinCC Project".
© Siemens AG 2019 All rights reserved

5. Create the picture-typicals for your project via "Edit > Create the project
picture-typicals".

6. Save the ST7cc project

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 33
3 Useful Information
© Siemens AG 2019 All rights reserved

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 34
4 Appendix

4 Appendix
4.1 Service and support
Industry Online Support
Do you have any questions or need assistance?
Siemens Industry Online Support offers round the clock access to our entire
service and support know-how and portfolio.
The Industry Online Support is the central address for information about our
products, solutions and services.
Product information, manuals, downloads, FAQs, application examples and videos
– all information is accessible with just a few mouse clicks:
https://support.industry.siemens.com

Technical Support
The Technical Support of Siemens Industry provides you fast and competent
support regarding all technical queries with numerous tailor-made offers
– ranging from basic support to individual support contracts. Please send queries
to Technical Support via Web form:
www.siemens.com/industry/supportrequest
© Siemens AG 2019 All rights reserved

SITRAIN – Training for Industry


We support you with our globally available training courses for industry with
practical experience, innovative learning methods and a concept that’s tailored to
the customer’s specific needs.
For more information on our offered trainings and courses, as well as their
locations and dates, refer to our web page:
www.siemens.com/sitrain

Service offer
Our range of services includes the following:
• Plant data services
• Spare parts services
• Repair services
• On-site and maintenance services
• Retrofitting and modernization services
• Service programs and contracts
You can find detailed information on our range of services in the service catalog
web page:
support.industry.siemens.com/cs/sc

Industry Online Support app


You will receive optimum support wherever you are with the "Siemens Industry
Online Support" app. The app is available for Apple iOS, Android and Windows
Phone:
support.industry.siemens.com/cs/ww/en/sc/2067

SINAUT_ST7cc_TIM_S7-1500_S7-1200_ET_200SP
Entry-ID: 109761107, V1.0, 04/2019 35
4 Appendix

4.2 Links and Literature


Table 4-1
No. Topic
\1\ Siemens Industry Online Support
https://support.industry.siemens.com
\2\ Link to the entry page of the application example
https://support.industry.siemens.com/cs/ww/en/view/109761107
\3\ Overview document: Secure remote access with VPN
https://support.industry.siemens.com/cs/ww/en/view/26662448
\4\ SIMATIC NET: S7-1500 - TeleControl TIM 1531 IRC
https://support.industry.siemens.com/cs/ww/en/view/109748454
\5\ SIMATIC NET: S7-1200 - TeleControl CP 1243-8 IRC
https://support.industry.siemens.com/cs/ww/en/view/109757834
\6\ SIMATIC NET: ET 200SP - Industrial Ethernet CP 1542SP-1, CP 1542SP-1 IRC
and CP 1543SP-1
https://support.industry.siemens.com/cs/ww/en/view/109741690
\7\ SIMATIC NET: Industrial Remote Communication TeleControl ST7cc Control
Center
https://support.industry.siemens.com/cs/ww/en/view/63203610
© Siemens AG 2019 All rights reserved

4.3 Change documentation


Table 4-2
Version Date Change
V1.0 04/2019 First version