MIC-2 MKII DIN Technical Specs

This document provides technical specifications for the MIC-2 MKII DIN data monitoring instrument, including its voltage and current input ranges, data rates, environmental operating conditions, connections, accuracy ratings, auxiliary power supply details, EMC standards compliance, and physical dimensions. Key specifications include voltage measuring range of 0-1.2xUN, data rate up to 38.4kbps, operating temperature range of -25°C to 70°C, IP52 front and IP30 rear protection, and panel mounting in a 92x92mm cutout.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
101 views1 page

MIC-2 MKII DIN Technical Specs

This document provides technical specifications for the MIC-2 MKII DIN data monitoring instrument, including its voltage and current input ranges, data rates, environmental operating conditions, connections, accuracy ratings, auxiliary power supply details, EMC standards compliance, and physical dimensions. Key specifications include voltage measuring range of 0-1.2xUN, data rate up to 38.4kbps, operating temperature range of -25°C to 70°C, IP52 front and IP30 rear protection, and panel mounting in a 92x92mm cutout.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Data sheet

Technical specifications, MIC-2 MKII DIN


Voltage inputs Data rate 1200 (9600) to 38400
Nominal voltage UN L- L 480 V AC (cat III) bits/s
L-L 690 V AC (cat II)
Measuring range 0 to 1.2 x UN
Overload capacity 1500 V continuous Environmental conditions
3250 V for 1min Operation temperature -25 to 70°C
VT primary 220 V to 500 kV Storage temperature -40 to 85°C
VT secondary 100 V to 400 V Standard IEC 60068-2-2
IEC 60068-2-1
Fuse 1 A slow blow
Humidity, relative 5-97 % RH
Current inputs condensing
Nominal current IN 5 A AC Standard IEC 60068-2-6 Db
Measuring range 0 to 10 A
Overload capacity 20 A continuous Connections
100 A for 1 s Measuring inputs Current input fixed
CT primary 5 A to 50 kA block, wire max. 5 mm²
CT secondary 5A Screw torque 0.5 Nm/5.5 lb-inch
Load 0.5 VA Other Pluggable block
Wire max. 1.5 mm²
Frequency Screw torque 0.25 Nm/2.5 lb-inch
Nominal frequency fN 50/60 Hz
Measuring range 45 Hz to 65 Hz Mounting
Measuring point V1 phase voltage Panel mounted Max. 6 mm thick
Panel cutout 92 x 92 mm +0.8 mm
Accuracy Multi-instrument only (3.62” x 3.62”)
Voltage 0.2 % or 4” round
Current 0.2 %
Power 0.5 % Protection
Power factor 0.5 % Front IP52 (EN 60529)
Frequency 0.2 % Rear IP30 (EN 60529)
Energy 0.5 %
Harmonic 5.0 % Safety IEC/EN 61010-1,
UL 61010-1
Standard IEC 60051 300 V installation cat.
III, pollution degree 2
Auxiliary power supply 600 V installation cat.
Universal AC/DC power supply II, pollution degree 2
Supply voltage 100 to 240 L-N / +/-10 %
100 to 415 L-L V AC +/-10 % Weight
50/60 Hz MIC-2 MKII 320 g (0.8 lbs.)
100…300 V DC MIC-2 MKII DIN 280 g (0.7 lbs.)

Consumption ≤ 5 VA
Fuse 1 A slow blow EMC IEC/EN 61000-6-2
IEC/EN 61000-6-4
Communication
Vibration 3 to 13.2 Hz: 2 mmpp
RS-485 Modbus RTU 13.2 to 100 Hz: 0.7 g
Number of devices Max. 32 units To IEC 60068-2-6
Cable type Belden 3105 A or equiva- To IACS UR E10
lent (twisted pair and
shielded)
Maximum cable length up to 1000 m

DEIF A/S Page 3 of 8