Developing program for MicroLogix controller and interfacing it with
InTouch SCADA application
2. Create a PLC subroutine called BATCH and call it into the main program.
RClk on Program Files and create new subroutine; name it BATCH as shown in Fig. 5.
From Windows Start, select All Programs, then Wonderware, and then System
Management Console .
As shown in Fig. 7 under DAServer Manager, Default Group, Local computer, add
ArchestrA.DASABCIP server .
Add configuration , new CIP port and new MicroLogix communication object
(New_ML_EN_000).
Figure 7. Creating a Communication Link between PLC and SCADA
6. Configuration of communication link (OPC server).
Click on New_ML_EN_000. Name the controller (Host Name) that we need to
communicate with (e.g. 130.220.164.17) as shown in Fig. 8.
Select the next TAB, Device Groups. Name the Group (e.g.) ABPLC. Leave the update
default interval (1000 ms) as shown in Fig. 9.
Create Tag names related to logical
operation in the PLC program Link Tags with PLC addresses
Figure 10. Creating Tags and linking them to PLC data files.
To save changes Clk on Archestra.DASABCIP, Stop the server, Save Changes and
Restart DASABCIP server. Check the small simbols as shown in Fig. 11 to make sure
the server is stopped and them restarted again.
8. Creating the interface between your PLC and the your SCADA Application.
Select Special, then select Access Names, then click on Add New Access Name as in Fig.
15.
Figure 15. Adding Access Name for SCADA to access PLC data files
As shown in Fig. 16, enter the Access name (e.g.PLC); the Application Name must be
DASABCIP and the Topic Name must be ABPLC (as entered in Fig. 9). These names were
configured in SMC (System Management Console). Topic Name is a Group Name and
DASABCIP is the server name (Application Name). Node name can be left blank as you are
using a single computer in this application.
You can create your own HMI or follow the steps below to create an HMI.
To create Tag Display on the Main Screen, open Main Screen (InTouch –Window
Maker) and open object Wizard on the main panel. Select Tag name Value display as
shown in Fig. 17.
Now, from the Special menu select the Tag Name directory. Create new Tag (Clk. New), select
Type, in this case I/O Integer.
Copy name of the tag from SMC (System Management Console) and use it as Tag Name. Select
Access name PLC From Access Name Window as shown in Fig. 19. Save Tag and Close the
Window.
The Access Name is PLC Check Use Tag name as Item Name box.
In case this Tag exists but is not used we can delete unused tags.
Link the Display value on the Main Screen with the corresponding Tag.
Select Display , DClk on Tag Name, DClk on the Tag name and select tag from Tag Name
Dictionary (Real_Tank_Value) as shown in Fig. 20. Select Number format for display and
press OK
Figure 20. Linking Display value with its Tag name.
Make sure DASABCIP Server is running.
Running application should display value of the integer N11:1 (Real_Tank_Value) from PLC.
Use the same procedure for creating a Tag for N11:0 (Requested_tank_Level_Value). Allow
Input from the user. Limit input value from 0 to 1000 (maximum capacity of the tank in our
example).
Now, create Tags for all other PLC data files and any other additional ones that you want to use;
e.g. insert a Switch (Wizards, Buttons, Set/Reset Display). Create new tag (B10:2/7
Enable_Tank_Operation), select I/O Discrete and Access Name PLC.
DClk on the Button, Display Wizard window appears; DClk on Tagname and select Enable_Tank_Switch
from the Tagname dictionary and press OK.
Set Messages of Operation and press OK. Test and see values in the PLC program.
Repeat for all other Tags associated with the program (BATCH).
Clk. Tag name Directory and create new tags selecting Type of the tags Names Which can be
copied from SMC, defining access Name topic and save changes.
Create 3 momentary buttons using wizards (place and arrange using Arrange align options from
main menu). Select buttons for fill, empty and auto mode, assign Tag names and made related
Labels, change action to Direct.
Create visual control for button. Select 2 Ellipses from panel place it on the screen and arrange
(Use arrange align and make a symbol from main menu); color them together in the manner they
will fit the buttons.
Test in Runtime mode (If B10:2/4 bit is active in PLC program, object must blink). Now we can place the
ellipse over the button’s red area and make it look like one object.
Ellipse overlaps button red area
Copy Ellipse object and use it for Fill, Auto buttons. Assign control bits accordingly.
Create Tank. Choose Rounded rectangle from panel and enlarge radius.
Clk on the object select vertical fill and analog fill color, adjust Values.
Analog color adjustment example.
An example of a final SCADA HMI may look similar to the one shown in Fig. 21.
The HMI is in runtime mode and shows the current level of the fluid in the tank and also the set
value (using slider).
Keep in mind this is just an example and you are expected to create your own HMI, which can be
completely different.
Appendix A