HYD                                                            TG52784
RELAY SETTING CALCULATION                          REV. NO. 02
HYD
                     RELAY SETTING CALCULATION
                        Project: -2X34.5MW- GTGs
                    M/S GURUGOBIND SINGH REFINEERY
FORMAT   Prepared   scr   Approved                                   Date
D-201                                                                9/13/22010
REV-00                                                               Revised on04/10/11
         COPYRIGHT AND CONFIDENTIAL
         The information on this document is the property of BHEL. It must not be used directly or
                      indirectly in any way detrimental to the interest of the company.
                                                                                   TG52784
                          RELAY SETTING CALCULATIONS FOR RELAY 7UM62                REV 02
 HYDERABAD                  PROJECT:2X34.5 GTG FOR GURU GOBIND SINGH
                                            REFINERY
                                   Generator & System Data:
1.0 Rated active out put                                                             34.5 MW
2.0 Rated Apparent out put                                                          43.13 MVA
3.0 Rated Voltage                                                                      11 KV
4.0 Allowed deviaion on the voltage( + )                                               10 %
4.0 Allowed deviaion on the voltage(  ‐)                                               10 %
5.0 Rated Current                                                                    2264 A
6.0 Rated power factor                                                                 0.8
7.0 Rated Frequency                                                                    50 Hz
8.0 D‐Axis Synchronous Reactance ( Xd )                                             1.947 P.U
9.0 D‐Axis transient Reactance ( X’d )                                             0.2168 P.U
10 D‐Axis sub transient Reactance ( X”d )                                          0.1491 P.U
11 CT primary current                                                                3000 A
12 CT secondary current                                                                  1A
13 CT ratio                                                                          3000
14 PT primary voltage   ( 11000/√3)                                              6351.04 V
15 PT secondary voltage     ( 110/√3)                                               63.51 V
16 PT ratio                                                                           100
17 Continuous Neg. Seq. Capability  ( Percentage of rated curent)                      10 %
                           2
18   Thermal capability (I2 t)                                                         20 Sec
19 Short circuit time constnat of Generator 
   Short circuit time constnat of Generator                                          0 71 sec
                                                                                     0.71
20 Transformer impedance                                                               15 %
21 Fault Current                                                                       40 KA
22 Transformer Secondary voltage                                                       33 KV
23 Transformer MVA                                                                     50 MVA
24 HV CT ratio                                                                       1000
25 Neutral grounding transformer
     KVA                                                                               60 KVA
     Primary voltage                                                               11000 V
     Secondary voltage                                                                240 V
26 Loading resistor                                                                    0.5 Ohms
27 NGT Seondary CT ratio                                                              250 /1A
28 NGT secondary current                                                              250 A
                                         ELECTRICAL MACHINES ENGINEERING    Date : 9/13/10
     Prepared                                      Checked       Approved   Rev 02
     scr                                  scr                S K PANDEY
                      RELAY SETTING CALCULATIONS FOR                                TG52784
                               RELAY 7UM62                                           REV 02
 HYDERABAD             PROJECT:2X34.5 GTG - GURUGOBIND
                              SINGH REFINERY
List of Protections ( Part of 7UM62)
     1    Generator Differential Protection (87G)
     2    Stator Earth fault protection (95%) ‐ (64G1)
     3    Stator Earth fault protection (100%)‐(64G2)
     4    Rotor First Earth Fault protection (Stage‐l) ‐64F.1
     5    Rotor First Earth Fault protection (Stage‐2)‐ 64F.2
     6    Gen. Overvoltage Protection(stage‐l)‐ (59.1G)
     7    Gen. Overvoltage Protection(stage‐2)‐(59.2G)
     9    Generator Overfluxing protection (Stage‐1)‐24G1
     10   Generator Overfluxing protection (Stage‐2)‐24G2
     11   Over frequency protection (Stage‐1 ) ‐(81.3)
     12   Over frequency protection (Stage‐2)‐(81.4)
     13   Loss of Excitation with U/V protection‐(40G)
     14   Loss of Excitation without U/V protection‐(27/40G)
     15   Voltage Restrained Overcurrent Protection‐(51V)
     16    Local Breaker Backup Protection (50LBB)
     17   Generator Overcurrent protection (51.1G)
     18   Undervoltage Protection stage‐1(27.1G)
     19   Undervoltage Protection stage‐2(27.2G)
     20   Dead Machine Protection (50G)
     21   Generator Negative Sequence Protection (Stage‐l) ‐(46G1)
     22   Generator Negative Sequence Protection (Stage‐2)‐(46G2)
     23   Pole slipping protection(78G)
     24   Under frequency protection (Stage‐l) ‐(81.1G)
     25   Under frequency protection (Stage‐2)‐(81.2G)
     26   Generator backup impedance protection(21G)
     27   Generator & Gen. Transformer Overall Differential Protection (87OA)   ‐  7U612
28        Generator  Differential protection   ‐   7U612
     29   Gen.Transforrmer Restricted E/F protn. (64RT)  ‐ 7SJ61
     30   Reverse power protection   ‐  7SJ62
                                           Note : rev.02   prepared as per  site  settings (i,e 51v,46,21,64R)
                                           RELAY SETTING CALCULATIONS FOR
                                                    RELAY 7UM62                                         TG52784
                                                                                                         REV 02
 HYDERABAD                 PROJECT:2X34.5MW GTGs FOR GURUGOBIND SINGH REFINERY
1.0 Over voltage protection: Stage -I ( 59.1G)
    This protection is provided to change regulation of AVR from auto to Manual in case Auto
    channel of AVR fails.
   Type of relay                       : Part of 7UM62
   Rated voltage of generator          :                                                         KV +10%
   The percentage of higher voltage than rated cont.voltage for I Stage
   of over voltage protection for changeover from auto to manual                                          5%
   Hence, setting shall be (105 + x) % of rated Voltage                                                115 %
    PT Secondary rated voltage for setting                                                           126.5 V
   Time delay recommended =                                                                             0.5 Sec
    Action : Alarm and change regulation from Auto1 to Auto2.
2.0 Over voltage Protection : Stage II ( 59 .2G)
   This protection is provided to protect generator against over voltages
   Type of relay : Part of 7UM62
   This protection shall be chosen at 10 % higher than stage -I
   Over voltage setting =                                                                              125 %
   PT Secondary voltage                                                                                110 V
   This time delay shall not be too long to avoid strain on the machine
   Relay setting =                                                                                   137.5 V
   Recommended time delay =                                                                               2 sec
    Action : To trip 86C
3.0 Over current relay - with voltage restraint (51V )
   This protection is provided to protect generator against heavy over loads and
   short circuits
   Type of relay:Part of 7UM62
   Rated Generator voltage UN, Gen                                                                       11 KV
   Direct Axis Transientreactance Xd'                                                              0.2168 p.u
   Transient synchronous generated voltage Up'= 1.2UN, Gen                                            13.2 KV
   Rated apparent power of stepup Transformer                                                            50 MVA
   Rated apparent power of Generator                                                               43.125 MVA
   Short circuit current                                                                              9309 A
   Generator load current                                                                             2264 A
   Current transformer ratio                                                                          3000 A
   Peak current = 1.3 IN                                                                              2943 A
   Setting for Ip = Peak current/CTR                                                                 0.981
   The short circuit time constant of the generator is (As per test report)                           0.71 sec
   The generator must trip before that time                                                          0.690 sec
   As per IEC characterstic
   t = [ (0.14)/ { I/Is) ^ 0.02 – 1 ) }) * TMS
   where I = measured current , Is = Current threshold setting , TMS = Time multiplier setting
   TMS                                                                                                0.11
   Current setting adopted                                                                              1.0 A
   Time multiplier setting                                                                            0.11
   The pickup threshold depends on the voltagel evel for pickup is (70% of VT sec.)                      77 V
                                           RELAY SETTING CALCULATIONS FOR
                                                    RELAY 7UM62                                                 TG52784
                                                                                                                 REV 02
HYDERABAD                 PROJECT:2X34.5MW GTGs FOR GURUGOBIND SINGH REFINERY
  Settings
  O/C Ip                                                                                                        ON
  Ip                                                                                                            1.0 A
  T Ip                                                                                                        0.11 sec
  IEC curve                                                                                              Normal Inverse
  Volt. Influence                                                                                        Volt. Restraint
  U<                                                                                                             77 V
   Action : To trip 86C
4 Negative sequence proteciton (46G)
  Type of relay                         : Part of 7UM62
  The permissible permanent inverse current refering to the normal machine current
  given by manufacture IsT                                                                                       10 %
  IN Mach                                                                                                     2264 A
  IsT                                                                                                            10 %
  Current Transformer- primary                                                                                3000
  Setting value I2perm                                                                                        7.55 %
  Asymmetry factor K= I² t                                                                                       20 sec
  The factor K is derived from the unbalanced load characteristic by reading the time corresponding
  K at I/IN =1
  tperm                                                                                                          20 sec
  The constant Kprimary                                                                                          20 sec
  Kprimary is converted to the secondary side Ksec                                                           11.39 sec
  Cold -down time - Time required to cool down under admissible unbalanced current
  tCooldown                                                                                                   2000 sec
  Asymmetrical faults cause high negative phase sequence currents, a definite time stage is
  detecting the asymmetrical short circuit current
  A phase-to phase fault (I) results negative phase sequence current
  I2 = (1/ √3)*I                                                                                              0.58 I
  Settings :
  Stage I: For Alarm
 Recommended alarm threshold :                                                                                7.65 %
 Recommended time setting for alarm :                                                                            10 Sec
  Stage II:
  Unbalance load                                                                                                ON
 Trip threshold setting I2>> ( Little higher than stage I)                                                   10.00 %
 T I2 >>                :                                                                                        3 Sec
  T Warn                                                                                                         20 sec
  Factor K                                                                                                   11.39 sec
  T cool down                                                                                                 2000 sec
  Action: To Trip 86B
5 Differential protection (87G)
  Type of relay                          : Part of 7UM62
  Differential Current    Idiff = │I1   + I2│
  The stabilizing or restraint current = │I1│ + │I2│
  I - DIFF> the sensitive threshold of the differential protection varies proportionally with the
  restrained values but. the current proportional errors due to transformation, CT errors deviates the
  requirements due to saturation.
                                                     RELAY SETTING CALCULATIONS FOR
                                                              RELAY 7UM62                                            TG52784
                                                                                                                      REV 02
 HYDERABAD                        PROJECT:2X34.5MW GTGs FOR GURUGOBIND SINGH REFINERY
   For high currents a stabilisation has to be given with add on stabilization for correct tripping on faul
   Idiff                                                                                                             0.1 In
   An increase of pickup value on startup provides additional security against overfunctioning when
   a nonenergised protection object is switched on. The pickup value I-DIFFis now increased by a
   settable factor
   I-REST.START up is set at 1 as the prtection object is generator
   Action : To trip 86A
 6 LOSS OF FIELD PROTECTION (40 G) With U/Vblock
   Type of relay                                  : Part of 7UM62
   UN    - Machine                                                                                                    11 KV
   IN   - Machine                                                                                                  2264
   Xd machine                                                                                                     1.947
   CT Primary IN        CT prim                                                                                    3000
   VoltageTransformer UN VTprim                                                                                       11 KV
   1/Xdsec   = (1/Xd)(INMach/UNMach)(UN VTprim/INCTprim)                                                           0.39
   1/Xd with safety factor of 1.05                                                                                 0.41
   For α1, The angle of under excitation limiting the voltage regulator is selected or the inclination
   angle of the machine stability.
   The angle will be between 60 and 80 degree
   Angle (α1)                                                                                                         70 Deg.
   The minimum excitation value for low active power is selected to 0.9 times the of 1/Xd
   1/Xd for low active power                                                                                       0.37
   Angle (α2)                                                                                                         90 Deg.
   For machine dynamic stability the value must be between the synchronous reactance
   and the transient reactance i.e.,between 2.0254 and 0.2255                                                        1.1
   The angle of excitation limit                                                                                      90 Deg.
   If the static limitis exceeded the voltage regulator must increase the excitation with a signal with de
   Delay for signal                                                                                                   10 sec
   ( to give a time for response to raise)
   Characteristic 1 & 2 Excitation voltage failure time delay                                                        1.5 sec
   For characteristic 3 dynamic stability ,time delay                                                                0.5 sec
   Settings
   Underexcitation                                                                                                   ON
   1/Xd Characteristic 1                                                                                           0.41
   Angle 1                                                                                                            70 Deg.
   T Characteristic1                                                                                                  10 sec
   1/Xd Characteristic 2                                                                                           0.37
   Angle 2                                                                                                            90 Deg.
   T Characteristic 2                                                                                                 10 sec
   1/Xd Characteristic 3                                                                                             1.1
   Angle 3                                                                                                            90 Deg.
   T Characteristic 3                                                                                                0.5 sec
   T SHRT                                                                                                            1.5 sec
   Action : To trip 86A
7.0 REVERSE POWER PROTECTION -stage-1 (32G)
   Type of relay                                  : Part of 7SJ62
   The level of the active power input is determined by the friction loss to be overcome
                                               RELAY SETTING CALCULATIONS FOR
                                                        RELAY 7UM62                                      TG52784
                                                                                                          REV 02
HYDERABAD                   PROJECT:2X34.5MW GTGs FOR GURUGOBIND SINGH REFINERY
 Setting = Psec/Snsec =   (Pmach/SNMach)*(UNMach/Unprim)*(INMach/INPrim)                               0.30
 Delay time to Trip                                                                                        2 sec
 Settings :
 Reverse power                                                                                           ON
 P > Reverse                                                                                           -0.30 %
 T-SV-Closed                                                                                             2.0 sec
 Action : To trip 86C
8 Backup Impedance Protection                  (21G)
 The maximum Load current                                                                              2264
 The pick up valueof current(1.2 to 1.5 times)                                                         2716
 Pickup secondary Current                                                                             0.905
 As the excitation is arrived from the generator terminals UVSeal-in is switched on
 Under Voltage set at                                                                                     75 %
 Under voltage seal-in time                                                                              1.5 sec
 Transformer Impedance                                                                                 0.15 p.u
 Secondary reactance
 Zone 1 primary(70% of Tr.Z)                                                                           0.25 Ohms
 Zone1 Secondary                                                                                       7.62 Ohms
 Zone2secondary(100% ofTr Z)                                                                          10.89 Ohms
 Z1B Over reach (120%)                                                                             13.0680 Ohms
 Zone1Time                                                                                                 1 secs
 Zone2 time                                                                                              1.2 secs
 T - end                                                                                                1.5 secs
 POWER SWING- the rate of change      g of impedance
                                             p       is the measurement
 To arrive the value for setting, the minimum operating Z, the difference to the setting of the
 impedance
 Z1 and the gradient of impedance in a time                                                            6.67
 Z1                                                                                                    6.67
 ZL,min                                                                                                52.0
 dZ/dt = (Zlmin-Z1) /∆t
 The rateof time∆t is taken as 20ms
 dZ/dt is set at                                                                                       2265 Ohms/sec
 The estimation of time is taken from the proximity of rate o fchange in 180deg.
 dZ/dt(180deg.) assumed                                                                                   20 Ohms/sec
 Zcharacterstic = Z1 =                                                                                 6.67 Ohms
 T= 2* Zcharacteristic/ dZ/dt(180deg)                                                                  0.67 sec
 For delay times of more than 0.67 sec, no power swing blocking is required.
 Action :To trip 86C
9 Pole slipping protection
 Type of relay                              : Part of 7UM62
 Generator Maimum Rated output SN,G                                                                    34.5 MW
 Generator Terminal Voltage UN,G                                                                          11 KV
 Generator Rated Capacity                                                                             43.13 MVA
 Generator Rated Current IN.G                                                                          2264 A
 Power Factor cosΦ                                                                                       0.8
 Unit Transformer Capacity                                                                                50 MVA
                                      RELAY SETTING CALCULATIONS FOR
                                               RELAY 7UM62                                              TG52784
                                                                                                         REV 02
HYDERABAD               PROJECT:2X34.5MW GTGs FOR GURUGOBIND SINGH REFINERY
 Unit Transformer HV rating                                                                              33 KV
 Unit Transformer LV rating                                                                              11 KV
 HVRated current                                                                                       875
 LV Rated Current                                                                                     2264
 Measurement is enabled only on the current exceeding the threshold value
 I1> = 120% of nominal current                                                                     0.9054
 As out-of-step conditions are symmetrical occurances the pickup threshold of the negative seq
 component will be about 20%of the nominal current
 I2<                                                                                               0.1509
 The impedance values are to be perceived for the setting,the power swing reactance
 of the machine,which is the transient reactance of the machine
 Zb = Xd'; Zc - Forward towards the unit transf.
 The characterstic is divided into two portions 1. lower section of the characterstic
 2. the upper section the electrical center of the swing.
 Power swings are threephase symmetrical occurances.
  Xd' =UN,Gen/(Root3 *IN)*Xd'XCTR/PTR                                                                18.25 Ohms
 Xsc of the transformer                                                                              10.89 Ohms
 Assuming the characteristic should cover 85% of the                                                  9.26 Ohms
 transformer reactance , the setting of Zc
 Assuming that the remaining transformer reactance and the covered system reactance                   1.63
 should be ( 15% of transformer impedence
                                  p       for non salient p
                                                          pole machines))
 The polygon width Za is the maximum detectable power swingfrequency.
 Za ≈ 0.289 Ztot                                                                                        7.9 Ohms
 Max. Power swing frequency fp = (4/π)*(1/T)*(Za/Ztot)
 T= 20ms for 50Hz
 fp                                                                                                      18
 Zc = 80% Xsc                                                                                         8.71
 Assuming the additional line section impedance Zd                                                       10 Ohms
 Zd-Zc                                                                                                1.29
 Ztotal = Zb+Zc                                                                                      26.96 Ohms
 Za ≈ 0.289 Ztot                                                                                      7.79 Ohms
 Number of power swings                                                                                   4
 Holding time                                                                                            20 Sec
 Settings :
 Out-of-step                                                                                            ON
 I1> Release                                                                                       0.9054
 I2< Release                                                                                       0.1509
 Za                                                                                                   7.79 Ohms
 Zb                                                                                                  18.25 Ohms
 Zc                                                                                                  9.257 Ohms
 Zd-Zc                                                                                                27.0 Ohms
 PHI Polygon                                                                                             90 Deg
 REP. CHAR. 1                                                                                             1
 REP. CHAR. 2                                                                                             4
                                       RELAY SETTING CALCULATIONS FOR
                                                RELAY 7UM62                                            TG52784
                                                                                                        REV 02
HYDERABAD                     PROJECT:2X34.5MW GTGs FOR GURUGOBIND SINGH REFINERY
   T - Holdng                                                                                           20 sec
   T-signal                                                                                              0 Sec
   Action : To trip 86A
10 Undervoltage protection (27G)
   Type of Relay : Part of 7UM62
   First stage under voltage setting                                                                    94 V
   The time of actuation is selected according to stability requirements                                 3 sec
   Second stage under voltage setting                                                                   83 V
   Time of actuation must be small                                                                       5 sec
   Settings :
   Undervoltage                                                                                        ON
   U<                                                                                               93.50 V
   T U<                                                                                                  3 sec
   U<<                                                                                              82.50 V
   T <<                                                                                                  5
   Action : To trip 86A
11 Frequency Protection (81.1,81.2G)
   This protection is provided to protect the generator against operation at
   low frequencies .
   Type of Relay : Part of 7UM62
   Alarm settings are to be made at 0.5 Hz intervals to alert the operator for corrective
   action and load management. Hence, following settings are recommended.
   Stage
      g -1: Freqency
               q   y setting
                           g:                                                                        48.5 Hz
   Time delay                                                                                            2 Sec
   Action : Alarm
   Stage -2: Freqency setting :                                                                      47.5 Hz
   Time delay :                                                                                        1.5 Sec
   Action : To trip 86B
12 Frequency Protection (81.3G,81.4G)
   This protects the machine against over speeding.
   Type of Relay : Part of 7UM62
   Stage I : for Alarm.
   Frequency Setting :                                                                                  51 HZ
   Time delay             :                                                                              1 sec
   Stage II : for trip.
   Frequency Setting :                                                                               51.5 HZ
   Time delay             :                                                                            1.5 sec
   Action : To trip 86B
13 0-95% STATOR EARTH FAULT PROTECTION (64G1)
   Type of Relay : Part of 7UM62
   For a protected Zone of 95% the protection must operate at 5% of the displacement voltage             5V
   The earth fault current generated 5% of the full earth current                                    0.00 A
   The magnitude of the eath fault current is determined by loading resistor a small angle of
   deviation may result                                                                                 15 deg.
                                       RELAY SETTING CALCULATIONS FOR
                                                RELAY 7UM62                                                        TG52784
                                                                                                                    REV 02
HYDERABAD                  PROJECT:2X34.5MW GTGs FOR GURUGOBIND SINGH REFINERY
   The time delay for earth fault actuation                                                                        0.2 sec
   Action : Alarm & To trip 86A
   Note : 5V is typcal, - voltage shall be measured during normal operation. Voltage setting
   may be adopted 2.0 volts higher than max. measured value during rated full load of generat
14 64G2 - 95- 100% Stator E/F protection
   Third harmonics U/V threshold setting ( VN3H < ) must be set below the 3 rd hormonics voltage
   present during normal operation and Third harmonics O/V threshold setting ( VN3H > ) must be
   set above the 3rd harmonics voltage present during normal operation
   Third Harmonic U/V ( VN3H < ) =                                                                                 0.5 V
   Time Delay                                                                                                        1 Sec
   Third Harmonic O/V ( VN3H > ) (Typical)                                                                           2V
   Time Delay                                                                                                        1 Sec
            These settings are typical. Voltage shall be measured during normal operation. Voltage
   setting may be adopted accordingly.
   Note : Third harmonic U/V thresold setting must be below the 3rd harmonic voltage
   present during normal operation & 3rd harmonic voltage to be measured    when gen. is running at rated load
   The 3rd harmonic voltage is normally lowest when is not loaded. However the 3rd harmonic voltage shall
   be measured when gen. is fully loaded
   Recommended setting is : set 50% of minimum value of 3rd harmonic voltage measured
   Action : To trip 86A
14 Rotor Earth Fault Protection (64R)
   Type of Relay : Partpof 7UM62 y         q      y          g (           )                y
   means of 7XR61unit. Due to bias voltage, with proper earth isolation a current flows through
   earth capacitance
   Warning Stage -I ,                                                                                               10 mA
   Time delay                                                                                                        5 secs
   Trip stage -II                                                                                                23.00 mA
   Time delay                                                                                                        1 sec
   Action : Alarm & To trip 86A
15 Gen. Breaker failure Protection (50 LBB)
   Type of Relay : Part of 7UM62
   Setting :
   Phase current setting       :                                                                                   0.2 A
   Time Delay    :                                                                                                200 msec
   Action : To trip 33KV breaker trip coil-1 & 2
16 Generator Overcurrent protection(51.1G)
   Type of Relay : Part of 7UM62
   Setting :
   Phase current setting       ( 110% of rated current refered to secondary)                                      0.83 A
   Time delay                                                                                                       10 sec
   Action: Alarm
                                         RELAY SETTING CALCULATIONS FOR
                                                  RELAY 7UM62                                              TG52784
                                                                                                            REV 02
HYDERABAD                 PROJECT:2X34.5MW GTGs FOR GURUGOBIND SINGH REFINERY
17 Dead Machine protection (50G)
   Type of Relay : Part of 7UM62
   The protection is for limiting the damage caused by the accidental energisation of the
   stationary or not synchronized generator.
   The Current setting adopted must be more sensitive than the threshold value of the O/C setting
   Current setting                                                                                      0.905 A
   Higher than the overcurrent setting
   The Voltage setting must be adopted for nominal conditions
   The undervoltage setting is 60%                                                                          66 V
   The time of operation is selected more than that of the O/C time setting                                1.2 sec
   Drop out time delay                                                                                       1 sec
   Settings :
   Inadvertant energisaion                                                                                 ON
   I stage                                                                                              0.905
   Release U1 <                                                                                             66 V
   Pickup at U1<                                                                                           1.2 sec
   Drop out T U1<                                                                                            1 sec
   Action : To trip 86A
18 Generator overfluxing protection
   Type of relay : part of 7UM62
   stage-1
   V/F setting                                                                                           1.15
   Time delay                                                                                              10 sec
   stage-2
   V/F setting
         tti                                                                                               1.4
                                                                                                           1 4
   Time delay                                                                                                2 sec
                            RELAY SETTING CALCULATIONS FOR
                                                                                       TG52784
                PROJECT:2X34.5MW GTG FOR GURUGOBING SINGH                               REV 01
HYDERABAD                       REFINEERY
 1 Overall Differential Protection (87O)
   Type of relay          : Part of 7UT612
   GT Capacity                                                                                 50 MVA
   GT Primary Volts                                                                            11 KV
   GT Secondary Volts                                                                          33 KV
   CT ratio                                                                                 1000
   %Z                                                                                          15 %
   Considering the CT errors, OLTC regulation error currents(10%) & margin,the
   value of 0.30I of the protected trafo is selected.                                      5832.0 A
   Primary full load current                                                                2624 A
   Secondary foll load current                                                               875 A
   Calculation of differential current                                                     874.80
   87-2 I DIFF>                                                                              0.20 I/In
   FLC/Fault current                                                                         0.15
   Allowing Ctratio error 87-2 I DIFF>                                                        0.2
   87-2 I DIFF>>                                                                                 8 I/In
   Add on Stabilization Current                                                              0.08
   Instant Restraint Ratio(2nd Hormonic)                                                      0.2
   Stabilizing Ratio for 5th Hormonics                                                        0.3
   Action : To trip 86A
 2 Restriced Earth fault proteection _
   Type of Relay  : 7SJ61
   No zero sequence current will flow during the normal  operation .
   i.e. starpoint current is Isp =o 
   Recommended setting 
   The phase currents are 3Io Ia+Ib+Ic 0
   The phase currents are  3Io = Ia+Ib+Ic = 0                                    0.3In
                                                                                 0 3In
   Time Delay                                                                    0.2 ses
   Action : To trip 86A