Ax 1703

Firmware Description

UMPM98
IEC 870-5-101 Multi-Point Traffic MASTER
STATKRAFT

HW-Type: 2541 / FW-Type: 2545

© 2004 by VA TECH SAT GmbH & Co


All rights reserved.

Any kind of disclosure and reproduction


whatsoever of this document or of parts thereof is
permitted only upon prior written consent by
VA TECH SAT.

Technical specifications are used for purposes of


product description only and are no guaranteed
specifications in legal terms. Subject to
modifications - also in terms of technology.
UMPM98 Firmware Description Ax 1703

This document is applicable to the following product(s):

UMPM98 Rev. 01 and higher

Version Revision Date Change


A, 1 00 21.06.04 first issue

About this Document:


author / editor: J. Hahn / E. Josefik
server\service: \\VIE001\ENT_TDOK
directory: \Ax1703\FW\UMPM98\
file name(s): UMPM98.DOC
file format: Word 97

created last change released


on by on by on by
21.06.04 SW-AUT/HN SW-AUT/ 21.06.04 SW-AUT/HN

ii SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Table of Contents

1. General ................................................................................................ 1-1

2. Technical Data .................................................................................... 2-1


2.1. IEC 60870-5-101 Interoperability of ACP 1703 using SM2541 (SIP) with
Firmware UMPM98 (unbalanced master) ..............................................................2-2
2.1.1. System or Device Function.............................................................................2-3
2.1.2. Network Configuration ....................................................................................2-3
2.1.3. Physical Layer ................................................................................................2-4
2.1.4. Link Layer .......................................................................................................2-5
2.1.5. Application Layer ............................................................................................2-6
2.1.6. Basic Application Functions..........................................................................2-12
2.2. Limitations ............................................................................................................2-16
2.3. Configuration ........................................................................................................2-17
2.4. Used Interface Lines ............................................................................................2-18

3. Protocol Description .......................................................................... 3-1

4. Message Conversion.......................................................................... 4-1


4.1. Address Conversion ...............................................................................................4-2
4.2. Linearization ...........................................................................................................4-3
4.3. Message Conversion of Process Information in Control Direction
(SAT Ax 1703 o RTU-101) ...................................................................................4-4
4.3.1. Single / Double Commands............................................................................4-5
4.3.1.1. Parameterization.....................................................................................4-8
4.3.2. Regulating Step Commands ..........................................................................4-9
4.3.2.1. Parameterization...................................................................................4-12
4.3.3. Setpoint Commands .....................................................................................4-13
4.3.3.1. Parameterization...................................................................................4-16
4.4. Message Conversion of System Information in Control Direction
(SAT Ax 1703 o RTU-101) .................................................................................4-17
4.4.1. General Interrogation Command..................................................................4-19
4.4.2. Reset RTU Command ..................................................................................4-20
4.4.2.1. Parameterization...................................................................................4-21
4.5. Message Conversion of Process Information in Monitor Direction
(RTU-101 o SAT Ax 1703)..................................................................................4-22
4.5.1. Parameterization ..........................................................................................4-24
4.5.2. Conversion of Time Format ..........................................................................4-25
4.5.3. Intermediate state / faulty state suppression................................................4-26

5. Protocol-specific Functions .............................................................. 5-1


5.1. Redundancy Function ............................................................................................5-1
5.2. Data acquisition by Polling (station polling) ...........................................................5-2
5.3. Clock Synchronization of RTU´s ............................................................................5-3
5.3.1. Time Setting....................................................................................................5-3
5.4. Handling of faulty Stations .....................................................................................5-5
5.4.1. Retry Handling ................................................................................................5-5
5.4.2. Interface Fault.................................................................................................5-5
5.5. Transmission Device (Modem) ..............................................................................5-6

6. System Technical Parameters........................................................... 6-1


6.1. Overview ................................................................................................................6-1
6.1.1. Station Definition ............................................................................................6-1
6.1.2. Common Settings ...........................................................................................6-2

SA2-545-X.XX/93-00 iii
UMPM98 Firmware Description Ax 1703

6.1.2.1. Free definable Transmission Facility ...................................................... 6-3


6.1.3. Message Retries............................................................................................. 6-5
6.1.4. Redundancy ................................................................................................... 6-6
6.1.5. Station Call Prioritization ................................................................................ 6-6
6.1.6. Advanced Parameters.................................................................................... 6-7
6.1.6.1. Monitoring times ..................................................................................... 6-8
6.1.6.2. Call Procedure per Type Identification ................................................... 6-9
6.1.6.3. IEC Parameter ...................................................................................... 6-10
6.1.6.4. Real Time Remote Synchronization ..................................................... 6-11
6.1.6.5. Software Test Points............................................................................. 6-12
6.2. Details .................................................................................................................. 6-13

A. Appendix: Diagnostic ........................................................................ A-1


A.1. Class internal .........................................................................................................A-1
A.2. Class external ........................................................................................................A-3
A.3. Class communication .............................................................................................A-9
A.4. Class test..............................................................................................................A-14

B. Appendix: Literature Index................................................................ B-1

iv SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

1. General

Type: Protocol firmware


Firmware designation: UMPM98 (HW: 2541/FW: 2545)
Protocol element designation: - (Special protocol element)

x Basis firmware:
Additional module (SIP): SM2541-B
Prom-Type: FLASH-File

SA2-545-X.XX/93-00 1-1
UMPM98 Firmware Description Ax 1703

1-2 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

2. Technical Data

The protocol firmware is designed for the communication of Ax 1703 system components
rd
and 3 party RTU´s using IEC 60870-5-101 protocol (called RTU-101 in the following) at
Statkraft / PROSAM project.
UMPM98 protocol firmware implement specific functionality defined in NUC (Norwegian User
Conventions Revision 2.0) which is not available as Ax-1703 standard functionality or can
not be realized using CAEx.

x UMPM98 protocol firmware emulates IEC 60870-5-101 MASTER function


(UNBALANCED PRIMARY)

x supported basic functions of UMPM98 see "IEC 60870-5-101" and


"Norwegian IEC870-5-101 User Conventions Revision 2.0"
(IEC 60870-5-101 interoperability included in this document)

x IEC address conversion (CASDU, IOA) for selected type identifications in receive and
transmit direction
─ 1 message SAT internal can be converted to 1 message to the RTU with different
address (and different type identifications if supported)
─ 1 message received from the RTU can be converted to 1 messages to SAT
internal with different address (and different type identifications if supported)

x format conversion for short floating point, normalized and scaled values for selected
type identifications in receive and transmit direction

x special handling for setpoint commands to avoid different values for ACTCON
ACTTERM (if format conversion is used)

x special handling for "originator address" (commands and setpoints)


ACTCON / ACTTERM have to send back only to that controlling station
(SCADA system) which has sent the command/setpoint

x "1 out of n" handling for commands and setpoints

x assignment for command address to return information address for ACTTERM


simulation.

x Intermediate -/ faulty state suppression handling for double-point information in


monitor direction

This protocol element implements, as an adaptation to non-SAT systems, only a part of the
functionality and the data formats of the non-SAT interface. For a concrete case of
application, it is therefore to be checked, to what extent the real requirements correspond
with the functionality implemented here and to what extent additional expansions or
adaptations are required.
Note:
All screen shots in this document will show you examples for possible parameter settings. The parameters,
names for system-technical-plant and names for parameter range will be different from your parameters.

SA2-545-X.XX/93-00 2-1
UMPM98 Firmware Description Ax 1703

2.1. IEC 60870-5-101 Interoperability of ACP 1703 using SM2541 (SIP) with
Firmware UMPM98 (unbalanced master)

This companion standard presents sets of parameters and alternatives from which subsets
must be selected to implement particular telecontrol systems. Certain parameter values,
such as the number of octets in the COMMON ADDRESS of ASDU's represent mutually
exclusive alternatives. This means that only one value of the defined parameters is admitted
per system. Other parameters, such as the listed set of different process information in
command and in monitor direction, allow the specification of the complete set or subsets, as
appropriate for given applications. This clause summarizes the parameters of the previous
clauses to facilitate a suitable selection for a specific application. If a system is composed of
equipment stemming from different manufacturers it is necessary that all partners agree on
the selected parameters.

Note:
This IEC 60870-5-101 interoperability specify the functionality to the serial connected RTU-101´s.

The selected parameters should be marked in the white boxes as follows:

Function or ASDU is not used

X Function or ASDU is used as standardized (default)

R Function or ASDU is used in reverse mode

B Function or ASDU is used in standard and reverse mode

The possible selection (blank, X, R, or B) is specified for each specific clause or parameter.

Note:
In addition, the full specification of a system may require individual selection of certain parameters for certain parts
of the system, such as the individual selection of scaling factors for individually addressable measured values.

? Function or ASDU is planned, please contact the product management

Function or ASDU is used in a specific project

2-2 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

2.1.1. System or Device Function

(system-specific parameter, indicate the system’s or station’s function by marking one of the
following with ‘X’)

System definition
X Controlling Station (Master)
Controlled Station (Slave)

2.1.2. Network Configuration

(network-specific parameter, all configurations that are used are to be marked ‘X’)

X Point to point X Multipoint-partyline


X Multiple point to point Multipoint-star
X Redundant lines
(as defined in Norwegian IEC870-5-101 User Conventions Revision 2.0)

SA2-545-X.XX/93-00 2-3
UMPM98 Firmware Description Ax 1703

2.1.3. Physical Layer

(network-specific parameter, all interfaces and data rates that are used are to be marked ‘X’)

Transmission speed (control direction)

Unbalanced interchange Unbalanced interchange Balanced interchange Circuit


Circuit V.24/V.28 Circuit V.24/V.28 X.24/X.27
Standard Recommended if >1200 bit/s

X 100 bits/s X 2400 bits/s 2400 bits/s 56000 bits/s


X 200 bits/s X 4800 bits/s 4800 bits/s 64000 bits/s
X 300 bits/s X 9600 bits/s 9600 bits/s
X 600 bits/s X 19200 bits/s 19200 bits/s
X 1200 bits/s 38400 bits/s 38400 bits/s

Transmission speed (monitor direction)

Unbalanced interchange Unbalanced interchange Balanced interchange Circuit


Circuit V.24/V.28 Circuit V.24/V.28 X.24/X.27
Standard Recommended if >1200 bit/s

X 100 bits/s X 2400 bits/s 2400 bits/s 56000 bits/s


X 200 bits/s X 4800 bits/s 4800 bits/s 64000 bits/s
X 300 bits/s X 9600 bits/s 9600 bits/s
X 600 bits/s X 19200 bits/s 19200 bits/s
X 1200 bits/s 38400 bits/s 38400 bits/s

2-4 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

2.1.4. Link Layer

(network-specific parameter, all options that are used are to be marked ‘X’. Specify the
maximum frame length. If a non-standard assignment of class 2 messages is implemented
for unbalanced transmission, indicate the Type ID and COT of all messages assigned to
class 2.)

Frame format FT 1.2, single character 1 and the fixed time out interval are used exclusively
in this companion standard.

Link transmission procedure Address filed of the link

Balanced transmission not present (balanced transmission only)


X Unbalanced transmission X 1 Octet
X 2 Octets
X structured
X unstructured

Frame length
Maximum length L (number of octets, posiible 9-255)

When using an unbalanced link layer, the following ASDU types are returned in class 2
messages (low priority) with the indicated causes of transmission:

The standard assignment of ASDUs to class 2 messages is used as follows:

Type identification Cause of transmission

9, 11, 13, 21 <1>

X A special assignment of ASDUs to class 2 messages is used as follows:

Type identification Cause of transmission

all all

Note:
In response to a class 2 poll, a controlled station may respond with class 1 data when there is no class 2 data
available.

SA2-545-X.XX/93-00 2-5
UMPM98 Firmware Description Ax 1703

2.1.5. Application Layer

Transmission mode for application data

Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 60870-5-4, is used
exclusively in this companion standard.

Common address of ASDU


(system-specific parameter, all configurations that are used are to be marked „X“)

X 1 Octet X 2 Octets

Information object address


(system-specific parameter, all configurations that are used are to be marked „X“)

X 1 Octet X structured
X 2 Octets X unstructured
X 3 Octets

Cause of transmission
(system-specific parameter, all configurations that are used are to be marked „X“)

X 1 Octet 2 Octets (with originator address) (1)

(1) RTU-101 use only 1 byte for COT – so originator address is not used on communication link to RTU-101.

2-6 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Selection of standard ASDUs

Process information in monitor direction


(station-specific parameter, mark each Type ID „X“ if it is only used in the standard direction, „R“
if only used in the reverse direction, and „B“ if used in both directions)

X <1> := Single-point information M_SP_NA_1


X <2> := Single-point information with time tag M_SP_TA_1
X <3> := Double-point information M_DP_NA_1
X <4> := Double-point information with time tag M_DP_TA_1
X <5> := Step position information M_ST_NA_1
X <6> := Step position information with time tag M_ST_TA_1
<7> := Bitstring of 32 bit M_BO_NA_1
<8> := Bitstring of 32 bit with time tag M_BO_TA_1
X <9> := Measured value, normalized value M_ME_NA_1
X <10> := Measured value, normalized value with time tag M_ME_TA_1
<11> := Measured value, scaled value M_ME_NB_1
<12> := Measured value, scaled value with time tag M_ME_TB_1
X <13> := Measured value, short floating point value M_ME_NC_1
X <14> := Measured value, short floating point value with time tag M_ME_TC_1
<15> := Integrated totals M_IT_NA_1
X <16> := Integrated totals with time tag M_IT_TA_1
<17> := Event of protection equipment with time tag M_EP_TA_1
<18> := Packed start events of protection equipment with time tag M_EP_TB_1
<19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1
<20> := Packed single-point information with status change detection M_PS_NA_1
<21> := Measured value, normalized value without quality descriptor M_ME_ND_1

X <30> := Single-point information with time tag CP56Time2a M_SP_TB_1


X <31> := Double-point information with time tag CP56Time2a M_DP_TB_1
X <32> := Step position information with time tag CP56Time2a M_ST_TB_1
<33> := Bitstring of 32 bit with time tag CP56Time2a M_BO_TB_1
X <34> := Measured value, normalized value with time tag CP56Time2a M_ME_TD_1
<35> := Measured value, scaled value with time tag CP56Time2a M_ME_TE_1
X <36> := Measured value, short floating point value with time tag CP56Time2a M_ME_TF_1
X <37> := Integrated totals with time tag CP56Time2a M_IT_TB_1
<38> := Event of protection equipment with time tag CP56Time2a M_EP_TD_1
<39> := Packed start events of protection equipment with time tag CP56Time2a M_EP_TE_1
<40> := Packed output circuit information of protection equipment with time tag CP56Time2a M_EP_TF_1

Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, <19>
or of the set <30> - <40> are used.

SA2-545-X.XX/93-00 2-7
UMPM98 Firmware Description Ax 1703

Process information in control direction


(station-specific parameter, mark each Type ID „X“ if it is only used in the standard direction,
„R“ if only used in the reverse direction, and „B“ if used in both directions)

X <45> := Single command C_SC_NA_1


X <46> := Double command C_DC_NA_1
X <47> := Regulating step command C_RC_NA_1
X <48> := Set point command, normalized value C_SE_NA_1
<49> := Set point command, scaled value C_SE_NB_1
<50> := Set point command, short floating point C_SE_NC_1
<51> := Bitstring of 32 bit C_BO_NA_1

System information in monitor direction


(station-specific parameter, mark „X“ if used)

X <70> := End of initialization M_EI_NA_1

System information in control direction


(station-specific parameter, mark each Type ID „X“ if it is only used in the standard direction,
„R“ if only used in the reverse direction, and „B“ if used in both directions)

X <100> := Interrogation command C_IC_NA_1


<101> := Counter interrogation command C_CI_NA_1
<102> := Read command C_RD_NA_1
X <103> := Clock synchronization command C_CS_NA_1
X <104> := Test command C_TS_NA_1
X <105> := Reset process command C_RP_NA_1
<106> := Delay acquisition command C_CD_NA_1

Parameter in control direction


(station-specific parameter, mark each Type ID „X“ if it is only used in the standard direction,
„R“ if only used in the reverse direction, and „B“ if used in both directions)

<110> := Parameter of measured value, normalized value P_ME_NA_1


<111> := Parameter of measured value, scaled value P_ME_NB_1
<112> := Parameter of measured value, short floating point value P_ME_NC_1
<113> := Parameter activation P_AC_NA_1

2-8 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

File transfer
(station-specific parameter, mark each Type ID „X“ if it is only used in the standard direction,
„R“ if only used in the reverse direction, and „B“ if used in both directions)

<120> := File ready F_FR_NA_1


<121> := Section ready F_SR_NA_1
<122> := Call directory, select file, call file, call section F_SC_NA_1
<123> := Last section, last segment F_LS_NA_1
<124> := ACK file, ACK section F_AF_NA_1
<125> := Segment F_SG_NA_1
<126> := Directory {blank or X, only available in monitor (standard) direction} F_DR_TA_1

SA2-545-X.XX/93-00 2-9
UMPM98 Firmware Description Ax 1703

Type identifier and Cause of Transmission Assignments


(station-specific parameter)

Shaded boxes are not required.


Black boxes are not permitted in this companion standard
Blank = Function or ASDU is not used.
Mark Type Identification/Cause of transmission combinations:
‘X’ if only used in the standard direction
‘R’ if only used in the reverse direction
‘B’ if used in both directions

Type Identification Cause of transmission


1 2 3 4 5 6 7 8 9 10 11 12 13 20 37 44 45 46 47
to to
36 41

<1> M_SP_NA_1 X X
<2> M_SP_TA_1 X
<3> M_DP_NA_1 X X X X
<4> M_DP_TA_1 X X X
<5> M_ST_NA_1 X X X X
<6> M_ST_TA_1 X X X
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1 X X
<10> M_ME_TA_1 X
<11> M_ME_NB_1
<12> M_ME_TB_1
<13> M_ME_NC_1 X X
<14> M_ME_TC_1 X
<15> M_IT_NA_1
<16> M_IT_TA_1 X X
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1
<30> M_SP_TB_1 X
<31> M_DP_TB_1 X X X
<32> M_ST_TB_1 X X X
<33> M_BO_TB_1
<34> M_ME_TD_1 X
<35> M_ME_TE_1
<36> M_ME_TF_1 X
<37> M_IT_TB_1 X X
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X
<46> C_DC_NA_1 X X X X X
<47> C_RC_NA_1 X X
<48> C_SE_NA_1 X X X X
<49> C_SE_NB_1

2-10 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Type Identification Cause of transmission


1 2 3 4 5 6 7 8 9 10 11 12 13 20 37 44 45 46 47
to to
36 41
<50> C_SE_NC_1
<51> C_BO_NA_1
<70> M_EI_NA_1*) X
<100> C_IC_NA_1 X X X
<101> C_CI_NA_1
<102> C_RD_NA_1
<103> C_CS_NA_1 X X
<104> C_TS_NA_1 X X
<105> C_RP_NA_1 X X
<106> C_CD_NA_1
<110> P_ME_NA_1
<111> P_ME_NB_1
<112> P_ME_NC_1
<113> P_AC_NA_1
<120> F_FR_NA_1
<121> F_SR_NA_1
<122> F_SC_NA_1
<123> F_LS_NA_1
<124> F_AF_NA_1
<125> F_SG_NA_1
<126> F_DR_TA_1*)

*) blank or X only

Semantics of CAUSE OF TRANSMISSION


note: see IEC60870-5-101 standard for cause of transmission definition – COT numbers included in the
interoperability document is not standard but helpful in UMPM98 protocol document.

<0> := not used <20> := interrogated by station interrogation


<1> := periodic, cyclic <21> := interrogated by group 1 interrogation
<2> := background scan <22> := interrogated by group 2 interrogation
<3> := spontaneous <23> := interrogated by group 3 interrogation
<4> := initialized <24> := interrogated by group 4 interrogation
<5> := request or requested <25> := interrogated by group 5 interrogation
<6> := activation <26> := interrogated by group 6 interrogation
<7> := activation confirmation <27> := interrogated by group 7 interrogation
<8> := deactivation <28> := interrogated by group 8 interrogation
<9> := deactivation confirmation <29> := interrogated by group 9 interrogation
<10> := activation termination <30> := interrogated by group 10 interrogation
<11> := return information caused by a remote command <31> := interrogated by group 11 interrogation
<12> := return information caused by a local command <32> := interrogated by group 12 interrogation
<13> := file transfer <33> := interrogated by group 13 interrogation
<14..19> := reserved for further compatible definitions <34> := interrogated by group 14 interrogation
<35> := interrogated by group 15 interrogation
<36> := interrogated by group 16 interrogation

<37> := requested by general counter request <44> := unknown type identification


<38> := requested by group 1 counter request <45> := unknown cause of transmission
<39> := requested by group 2 counter request <46> := unknown common address of ASDU
<40> := requested by group 3 counter request <47> := unknown information object address
<41> := requested by group 4 counter request
<42..43> := reserved for further compatible definitions <48..63>:= for special use (private range)

SA2-545-X.XX/93-00 2-11
UMPM98 Firmware Description Ax 1703

2.1.6. Basic Application Functions

Station initialization
(station-specific parameter, mark „X“ if function is used)

X Remote initialization

Cyclic data transmission


(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)

Cyclic data transmission

Read procedure
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)

Read procedure

Spontaneous transmission
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)

B Spontaneous transmission

Note:
No spontaneous transmission (blank field) is not supported

Double transmission of information objects with cause of transmission spontaneous


(station-specific parameter, mark each information type ‘X’ where both a Type ID without
time and corresponding Type ID with time are issued in response to a single spontaneous
change of a monitored object)

The following type identifications may be transmitted in succession caused by a single status
change of an information object. The particular information object addresses for which
double transmission is enabled are defined in a project-specific list.

Single-point information M_SP_NA_1, M_SP_TA_1, M_SP_TB_1 and M_PS_NA_1


Double-point information M_DP_NA_1, M_DP_TA_1 and M_DP_TB_1
Step position information M_ST_NA_1, M_ST_TA_1 and M_ST_TB_1
Bitstring of 32 bit M_BO_NA_1, M_BO_TA_1 and M_BO_TB_1 (if defined for a specific project)
Measured value, normalized value M_ME_NA_1, M_ME_TA_1, M_ME_ND_1 and M_ME_TD_1
Measured value, scaled value M_ME_NB_1, M_ME_TB_1 and M_ME_TE_1
Measured value, short floating point value M_ME_NC_1, M_ME_TC_1 and M_ME_TF_1

2-12 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Station interrogation
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)

B global
group 1 group 7 group 13
group 2 group 8 group 14
group 3 group 9 group 15
group 4 group 10 group 16
group 5 group 11
group 6 group 12

Information Object Addresses assigned to each group must be shown in a separate table.

Clock synchronization
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)

X Clock synchronization

Command transmission
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)

B Direct command transmission (1)


B Direct set point command transmission (3)
B Select and execute command (2)
Select and execute set point command (4)
C_SE ACTTERM used

B No additional definition
B Short pulse duration (duration determined by a system parameter in the outstation)
B Long pulse duration (duration determined by a system parameter in the outstation)
Persistent output

(1) direct command transmission is used only for regulating step commands <TI=47> to RTU-101 !
(2) Select and execute command transmission is used only for single-/double commands <TI=45,46> to RTU-101 !
(3) Direct setpoint command transmission is used only for <TI=48> to RTU-101 !
(4) Select and execute setpoint command transmission is not used to RTU-101 !
note: set point command from control station (or CAEx) to UMPM98 is direct or select-before-operate.

SA2-545-X.XX/93-00 2-13
UMPM98 Firmware Description Ax 1703

Transmission of integrated totals


(station- or object-specific parameter, mark „X“ if function only used in standard direction, „R“
if only used in the reverse direction, and „B“ if used in both directions)

B Mode A: Local freeze with spontaneous transmission


B Mode B: Local freeze with counter interrogation
B Mode C: Freeze and transmit by counter interrogation commands
Mode D: Freeze by counter interrogation command, frozen values reported spontaneously

Counter read
B Counter freeze without reset
Counter freeze with reset
Counter reset

B General request counter


B Request counter group 1
B Request counter group 2
B Request counter group 3
B Request counter group 4

Parameter loading
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)

Threshold value
Smoothing factor
Low limit for transmission of measured value
High limit for transmission of measured value

2-14 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Parameter activation
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)

act/deact of persistent cyclic or periodic transmission of the addressed object

Test procedure
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)

X Test procedure

File transfer
(station-specific parameter, mark each used function „X“)

File transfer in monitor direction

Transparent file
Transmission of disturbance data of protection equipment
Transmission of sequences of events
Transmission of sequences of recorded analog values

File transfer in control direction

Transparent file

Background scan
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)

Background scan

Note: used for data which are transmitted caused by a self-initiated general interrogation

Acquisition of transmission delay


(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)

Acquisition of transmission delay

SA2-545-X.XX/93-00 2-15
UMPM98 Firmware Description Ax 1703

2.2. Limitations

x UMPM98 implement only "unbalanced primary" (= MASTER) of IEC 60870-5-101

x UMPM98 implements only a subset of IEC 60870-5-101


(see Norwegian User conventions 2.0)

x max. 100 RTU-101´s can be connected to UMPM98

x max. 3500 data points in transmit- / receive direction


note:
calculation of possible combinations of datapoints:
- Total free memory of SM2541/UMPM98 (Rev.001) protocol firmware ... 141000 bytes
- each datapoint requires 38 bytes of memory
- each datapoint with linearization parameter requires additional 10 bytes of memory

o e.g. 3500 datapoints ............................................................................. 3500 x 38 bytes = 133000 bytes


800 datapoints (of the 3500 above) are with linearization parameters ... 800 x 10 = 8000 bytes
total = 141000 bytes

x max. 20 different regulating step commands <TI=47> running at the same time

x max. 20 different setpoint commands <TI=48,49,50> running at the same time

x no retry suppression for command handling in UMPM98 protocol firmware !


Note:
Retry suppression handling is a standard functionality of IEC60870-5-101/-104.

x <TI=7> "bitstring of 32 bit" is not supported by UMPM98 !

x <TI=110> "parameter of measured value, normalized value" and


<TI=112> "parameter of measured value, short floating point value"
(Parameter loading "Threshold value", "Smoothing factor") are not supported by
UMPM98 !
Note:
Parameter in control direction will be supported by AK-1703 connected to controlling station using
IEC 60870-5-104

x <TI = 51> "bitstring of 32 bit" is not supported by UMPM98 !

x Blocking in control direction is not supported by UMPM98 !

x no inversion for double point information or double commands.


Note:
Inversion is "changing of the state".

x suppression for "faulty state position" or "intermediate state position" for max. 20
double-point information in monitoring direction at the same time.

x Non-linear linearization for conversion of measured values and setpoint commands is


not supported by UMPM98 protocol firmware !
Note:
CAEx can also not be used for non-linear linearization of setpoint commands!
(see special handling for setpoint commands to avoid different values for ACTCON, ACTTERM)

2-16 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

2.3. Configuration

Controlling station(s)

Control Control Control


System A System B System n

IEC60870-5-104 (NUC)

Ax-1703
1

IEC60870-5-101 (NUC)

RTU-101 RTU-101 RTU-101

Controlled station(s)

1 UMPM98 protocol firmware

SA2-545-X.XX/93-00 2-17
UMPM98 Firmware Description Ax 1703

2.4. Used Interface Lines

In V.24 Mode the following interface lines are used:

TXD <103> Transmit Data


RXD <104> Receive Data
DCD <109> Data Carrier Detect
RTS <105> Request To Send
GND <102> System Ground

Note:
For Statkraft / PROSAM project RTS and DCD will not be used !

2-18 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

3. Protocol Description

See IEC 60870-5-101.

SA2-545-X.XX/93-00 3-1
UMPM98 Firmware Description Ax 1703

3-2 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

4. Message Conversion

The conversion of the message formats from Ax 1703 (internal) l RTU-101 and the
changing of the address information is called "message conversion".
The conversion of the address information will be parameterized using the OPM (object-
oriented process data manager) SIP message address conversion for UMPM98 protocol
firmware.

ATTENTION:
Only messages included in the SIP message address conversion will be sent to the RTU-
101 or received from the RTU-101. All other messages not included in the SIP message
address conversion will be ignored without an warning or error indication!

The selected parameters are marked in the white boxes as follows:

conversion is not supported

X conversion is supported

SA2-545-X.XX/93-00 4-1
UMPM98 Firmware Description Ax 1703

4.1. Address Conversion

The conversion of the address information will be parameterized using the OPM (object-
oriented process data manager) SIP message address conversion for UMPM98 protocol
firmware.
IEC address conversion (CASDU, IOA) for selected type identifications in control and
monitor direction.

x 1 message SAT internal can be converted to 1 message to the RTU with different
address (and different type identifications if supported)
x 1 message received from the RTU can be converted to 1 messages to SAT internal
with different address (and different type identifications if supported)

SAT 1703 address (internal IEC address):

CASDU1
CASDU2 5-stage freely parameterizable SAT 1703 address
IOA1 possible: 0 - 255
IOA2
IOA3

note:
SAT internal IEC address is always full size (2 byte CASDU, 3 byte IOA) and must be unique in the SIP message
address conversion.

RTU-101 IEC address (external IEC address):

CASDU1
CASDU2 5-stage freely parameterizable SAT 1703 new address
IOA1 possible: 0 - 255
IOA2
IOA3

note:
Number of bytes used for CASDU and for IOA is to be parameterized in the IEC parameter block of the BSE
(SAT internal) for each communication interface individually.
The external IEC address must be unique in the SIP message address conversion.

Example for "SIP message address conversion" for UMPM98 in control direction

4-2 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

4.2. Linearization

The conversion of type identifications will be parameterized using the OPM (object-oriented
process data manager) SIP message address conversion for UMPM98 protocol firmware.
For supported conversions of TI´s see chapter "message conversion in control direction" and
"message conversion in monitor direction".
The linearization will be used only for conversion of measured values and setpoint
commands.

The linearization is defined by

X0 raw value 0 %
X100 raw value 100 % Y=k.x+d
Y0 engineering value 0 % where k = (Y100 – Y0)/(X0 – X100)

x For all kind of measurements the "OV-bit" is set if received value is smaller than X0 or
greater than X100. Calculated value is set to Y0 if received value is smaller than X0.
Calculated value is set to Y100 if received value is greater than X100.
x IV-bit will not be modified

The parameters for linearization can be defined for each entry in the OPM-Parameters for
UMPM98 (SIP message address conversion).
Non-linear linearization is not supported by UMPM98 protocol firmware!

+ Y100

X0

X100 row value

Y0

OV-bit

SA2-545-X.XX/93-00 4-3
UMPM98 Firmware Description Ax 1703

4.3. Message Conversion of Process Information in Control Direction


(SAT Ax 1703 o RTU-101)

One message of a specific type identification from SAT internal can be converted to one
message of a specific type identification to the RTU IEC 60870-5-101.

Type Identification Type identification to RTU-101


(SAT internal)
45 46 47 48 49 50 51

TI TI
(104) (101) (101)
<58> <45> C_SC_NA_1 X X
<59> <46> C_DC_NA_1 X
<60> <47> C_RC_NA_1 X
<61> <48> C_SE_NA_1 X
<62> <49> C_SE_NB_1
<63> <50> C_SE_NC_1 X
<64> <51> C_BO_NA_1

Note:
- "TI-101" is the type identification used SAT internal from BSE o SIP and to the RTU-101 on communication line.
- "TI-104" is the type identification used SAT-internal and from control center (IEC60870-5-104 NUC).

UMPM98 protocol firmware will accept only messages <TI=45..50> with <COT=6,8>
(=activation, deactivation) - all another messages will be ignored !
Note:
If a command will be received from control center with illegal COT this will be confirmed with "ACTCON neg"
by BSE !

4-4 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

4.3.1. Single / Double Commands

Following special handling is implemented in UMPM98 protocol firmware for


single commands <TI=45> (<TI=58> on 104) and
double commands <TI=46> (<TI=59> on 104):

x "1 out of n" for each link address


Only one command is possible at the same time for each link address (=RTU-101
station address) on a communication line.
rd
If more than one communication interface is used with RTU-101 or 3 party RTU´s
connected to one AK-1703, "1 out of n" will be handled for each communication link
individually.
(=no "1 out of n" for total AK-1703).
ACTCON neg. will be sent for commands from UMPM98 protocol firmware if another
command is in progress.

x address conversion for CASDU and IOA in transmit direction


(see chapter address conversion)

x ACTCON (ACTTERM) will be sent back only to the one control center which has sent
the single- / double command.
note:
The Originator address is not used on IEC60870-5-104(NUC) - the originator address
is assigned AK-1703 internally (AK-1703 topology parameter setting).
UMPM98 protocol firmware will send the ACTCON (ACTTERM) with the originator address assigned and
the control center´s address of the single- / double command (=the not converted address).
ACTCON pos. will be sent to the control center only if the ACTCON pos. received from the RTU-101 is valid
(correct CASDU, IOA, COT) – otherwise an ACTCON neg. will be sent to the control center.

x mapping of single-/double commands 104 o RTU-101:


- select-before-execute (104) o select-before-execute (101)

x optional mapping of single command to double command:


- <TI=45> "ON" o <TI=46> "ON" (can be parameterized in OPM)
- <TI=45> "ON" o <TI=46> "OFF" (can be parameterized in OPM)
- <TI=45> "OFF" o <TI=46> "OFF" (fixed implementation in UMPM98)

x As DEACTIVATION is not supported by RTU-101 and a selected command in the


RTU-101 can not be deselected – a DEACTIVATION command will always be
confirmed with ACTCON neg. by UMPM98 protocol firmware.
A selected command will stay selected in the RTU-101 until timeout in RTU-101
expires and the command will also stay selected in UMPM98 protocol firmware until
timeout in UMPM98 expires.

SA2-545-X.XX/93-00 4-5
UMPM98 Firmware Description Ax 1703

x As ACTTERM is not supported by RTU-101 – ACTERM will be simulated by UMPM98


protocol firmware.
If a return information is assigned to the command, ACTTERM pos. will be simulated if
the return information will be received with the correct state from the RTU-101 within
the timeout. The timeout will not be stopped in UMPM98 if the return information will
be received with intermediate -/ faulty- / or opposite state and therefore the command
will be still selected.

If no return information is assigned to the command – ACTTERM pos. will be


simulated immediately after valid ACTCON pos. was received from the RTU-101.

If a single command <TI=45>(<TI=58> on 104) is mapped to a double command


<TI=46> (101) the return information from RTU-101 must be an single point
information.
The return information for a double command must be a double point information.
note:
The return information address (= SAT internal IEC address = 104 address) will be assigned to the
commands address in the OPM-parameters (SIP message address conversion in control direction).

x ACTCON neg. will be sent by UMPM98 protocol firmware (or BSE) in following cases:
─ protocol element failed or RTU-101 link address failed (ACTCON neg. from BSE)
─ command not included in OPM message address conversion in transmit direction
or detail routing on BSE (ACTCON neg. from BSE)
─ always for a DESELECT single-/double command
─ this command or another command is already selected or running "1 out of n"
─ EXECUTE for not selected command or EXECUTE from an other control center as
SELECT command (selected command will stay selected)
─ CASDU, IOA, COT, DCS (double command state) or SCS (single command state)
and QU of the EXECUTE command is not equal to the SELECT command
─ not permitted double command state (DCS)
─ not supported QU (QU > 2 is not supported)
─ ACTCON from the RTU-101 is missing
─ ACTCON neg. received from RTU-101 for SELECT or EXECUTE
─ ACTCON pos. received from RTU-101 for SELECT or EXECUTE command with
not expected CASDU , IOA, COT, DCS and QU or SCS and QU.

o The command in the UMPM98 protocol firmware will be canceled


(command is not longer selected).
The command in the RTU-101 could be is still selected.

o If the same command will be selected again from the control center within the
SELECT-EXECUTE timeout in the RTU-101 – an ACTCON neg. will be sent
from the RTU-101.
note:
If UMPM98 protocol firmware will receive an ACTCON (pos. or neg.) from the RTU-101 without an
command in progress, this ACTCON will be ignored by UMPM98.

4-6 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Application function of Communication Communication


UMPM98 RTU-101
Controlling Station services services

SELECT command <TI=45, 46>, COT=6, SE=1


<TI=45, 46>, COT=6, SE=1

SELECT

ACTCON
SELECT confirmation <TI=45, 46>, COT=7, SE=1
<TI=45, 46>, COT=7, SE=1

DEACTIVATE command <TI=45, 46>, COT=8, SE=x

<TI=45, 46>, COT=9, SE=x


DEACTIVATE confirmation
„ACTCON negative“

EXECUTE command <TI=45, 46>, COT=6, SE=0


<TI=45, 46>, COT=6, SE=0
EXECUTE

ACTCON
EXECUTE confirmation <TI=45, 46>, COT=7, SE=0
<TI=45, 46>, COT=7, SE=0
1

EXECUTE termination
<TI=45, 46>, COT=10, SE=0 return indication

return indication

EXECUTE termination
<TI=45, 46>, COT=10, SE=0

1 If no return indication is assigned to the command - ACTTERM will be simulated directly after ACTCON

SA2-545-X.XX/93-00 4-7
UMPM98 Firmware Description Ax 1703

4.3.1.1. Parameterization

Example for "SIP message address conversion" for UMPM98 in control direction for single-double commands

note:
there is only one parameter category defined in the OPM for commands – in this chapter only the relevant settings
for single-/double commands will be described.

Supported SAT 1703 message formats:

x Single command <TI=45> (<TI=58> on 104)


x Double command <TI=46> (<TI=59> on 104)

Address conversion SAT 1703 o RTU-101:

x CASDU1,CASDU2, IOA1, IOA2, IOA3 ... 5-stage freely parameterizable


SAT 1703 internal IEC address (=source address) of single-/double command.
possible: 0 – 255

x TI ... type identification (SAT internal BSE o SIP)


possible: 45,46

x RS-CASDU1, RS-CASDU2, RS-IOA1, RS-IOA2, RS-IOA3 ... 5-stage freely


parameterizable internal IEC address (=104 address) of the return information.
note: if no return information is available - CASDU and IOA must be set to 255 !
possible: 0 – 255

x 101-CASDU1, 101-CASDU2, 101-IOA1, 101-IOA2, 101-IOA3 ... 5-stage freely


parameterizable RTU101 IEC address of the single-/double command
possible: 0 – 255

x 101-TI ... type identification for RTU-101


possible: 45,46

x link address ... link address of RTU-101 (station address)


possible: 0 – 254

x SC "ON" o DC (mapping of single commands)


possible: OFF, ON

4-8 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

4.3.2. Regulating Step Commands

Following special handling is implemented in UMPM98 protocol firmware for


regulating step commands <TI=47> (<TI=60> on 104).

x Up to 20 different regulating step commands can be used at the same time


on a communication line and also for the same link address (RTU-101 station
address)
o no "1 out of n" for regulating step commands!
note:
A regulating step command with the same RTU-101 address can only be active once.

x address conversion for CASDU and IOA in transmit direction


(see chapter address conversion)

x ACTCON will be sent back only to the control center which has sent the regulating
step command
note:
Originator address is not used on IEC60870-5-104(NUC) - the originator address is assigned according the
AK-1703 topology parameter setting.
UMPM98 protocol firmware will send the ACTCON with the originator address assigned and the control
center´s address of the regulating step command (=the not converted address).

x SELECT / DESELECT is not supported for regulating step commands.


SELECT command or DESELECT command will always be confirmed from UMPM98
protocol firmware with ACTCON neg.

x mapping of regulating step commands 104 o RTU-101:


- direct-operate (104) o direct-operate (101)

x As ACTTERM is not supported by RTU-101 – ACTERM will be simulated by UMPM98


protocol firmware.
ACTTERM will be simulated immediately after valid ACTCON pos. was received from
the RTU-101.

SA2-545-X.XX/93-00 4-9
UMPM98 Firmware Description Ax 1703

x ACTCON neg. will be sent by UMPM98 protocol firmware (or BSE) in following cases:
─ protocol element failed or RTU-101 link address failed (ACTCON neg. from BSE)
─ command not included in OPM message address conversion in transmit direction
or detail routing on BSE (ACTCON neg. from BSE)
─ always for a SELECT regulating step command or DESELECT regulating step
command
─ max. number of supported regulating step commands actually running
─ EXECUTE for regulating step command with the same CASDU and IOA is still
running
─ not permitted RCS (regulating step command state)
─ not supported QU (QU > 2 is not supported)
─ ACTCON from the RTU-101 for EXECUTE regulating step command is missing
─ ACTCON neg. received from RTU-101 for EXECUTE regulating step command
─ ACTCON pos. received from RTU-101 for EXECUTE regulating step command
with expected CASDU and IOA but not expected COT, RSC, QU.
o If ACTCON pos. will be received from RTU-101 for EXECUTE regulating step
command with different CASDU or IOA this ACTCON will be ignored by the
UMPM98 protocol firmware.
Other actually running regulating step commands will not be affected !
note:
If ACTCON will be received from the RTU-101 without an regulating step command in progress, this
ACTCON will be ignored from the UMPM98 protocol firmware.

4-10 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Application function of Communication Communication


UMPM98 RTU-101
Controlling Station services services

SELECT command <TI=47>, COT=6, SE=1

SELECT confirmation
<TI=47>, COT=7, SE=1
ACTCON neg.

DEACTIVATE command <TI=47>, COT=8, SE=x

DEACTIVATE confirmation
<TI=47>, COT=9, SE=x
ACTCON neg.

EXECUTE command <TI=47>, COT=6, SE=0


<TI=47>, COT=6, SE=0
EXECUTE

ACTCON
EXECUTE confirmation <TI=47>, COT=7, SE=0
<TI=47>, COT=7, SE=0

EXECUTE termination
<TI=47>, COT=10, SE=0

SA2-545-X.XX/93-00 4-11
UMPM98 Firmware Description Ax 1703

4.3.2.1. Parameterization

Example for "SIP message address conversion" for UMPM98 in control direction for regulating step commands

note:
there is only one parameter category defined in the OPM for commands – in this chapter only the relevant settings
for regulating step commands will be described.
(e.g. return information is not used for regulating step commands)

Supported SAT 1703 message formats:

─ Regulating step command <TI=47> (<TI=60> on 104)

Address conversion SAT 1703 o RTU-101:

x CASDU1,CASDU2, IOA1, IOA2, IOA3 ... 5-stage freely parameterizable


SAT 1703 internal IEC address (=source address) for regulating step command
possible: 0 – 255

x TI ... type identification (SAT internal BSE o SIP)


possible: 47

x 101-CASDU1, 101-CASDU2, 101-IOA1, 101-IOA2, 101-IOA3 ... 5-stage freely


parameterizable RTU101 IEC address of the regulating step command
possible: 0 – 255

x 101-TI ... type identification for RTU-101


possible: 47

x link address ... link address of RTU-101 (station address)


possible: 0 – 254

4-12 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

4.3.3. Setpoint Commands

Following special handling is implemented in UMPM98 protocol firmware for


setpoint commands <TI=48> (<TI=61,63> on 104).

x Up to 20 different setpoint commands can be used at the same time


on a communication line and also for the same link address (RTU-101 station
address)
o no "1 out of n" for regulating step commands !
note:
A setpoint command with the same RTU-101address can only be active once.

x address conversion for CASDU and IOA in transmit direction


(see chapter address conversion)

x ACTCON for the setpoint command will be sent back only to the control center which
has sent the setpoint command.
note:
As format conversion is used for setpoint commands it is not possible to use the setpoint value received in
ACTCON from the RTU-101 because there can be an difference caused by format conversion and
linearization. To eliminate this problem the UMPM98 protocol firmware will store all the received setpoint
command information from the control center for the supported number of setpoint commands.
If "ACTCON pos" will be received from the RTU-101 with expected values – "ACTCON pos" to the control
center will be sent using the previous received values for the setpoint command from the control center.
o If "ACTCON pos" will be received from the RTU-101 with different value for setpoint – "ACTCON neg"
will be sent to the control center with setpoint value received from the control center.

x ACTTERM is not supported for setpoint commands !

x As SELECT and DESELECT is not supported by RTU-101 o SELECT and


DESELECT will be simulated by UMPM98 protocol firmware only for setpoint
commands configured as select-before-execute in OPM (SIP message address
conversion).

x mapping of setpoint commands 104 o RTU-101:


- select-before-execute (104) o direct-execute (101)
- direct-execute(104 or from CAEx) o direct-execute (101)
Mapping of setpoint commands can be configured for each setpoint commands in the
OPM (SIP message address conversion for UMPM98).

SA2-545-X.XX/93-00 4-13
UMPM98 Firmware Description Ax 1703

x ACTCON neg. will be sent by UMPM98 protocol firmware (or BSE) in following cases:
─ protocol element failed or RTU-101 link address failed (ACTCON neg. from BSE)
─ setpoint command not included in OPM message address conversion in transmit
direction or detail routing on BSE (ACTCON neg. from BSE)
─ max. number of supported setpoint commands actually running
─ EXECUTE setpoint command received for not selected setpoint command
configured as select-before-execute
─ EXECUTE setpoint command received from an other control center as
SELECT setpoint command.
note: selected setpoint command on UMPM98 will stay selected
(only if command is configured as select-before-execute)

─ EXECUTE setpoint command received with CASDU, IOA, COT, setpoint value, QL
not equal to the SELECT setpoint command
(only if command is configured as select-before-execute)
─ ACTCON from the RTU-101 for EXECUTE is missing
─ ACTCON neg. received for EXECUTE setpoint command from RTU-101
─ ACTCON pos. received from RTU-101 for EXECUTE setpoint command with
expected CASDU and IOA but not expected COT, setpoint value, QL.
o If ACTCON pos. will be received from RTU-101 for EXECUTE setpoint
command with different CASDU or IOA this ACTCON will be ignored by the
UMPM98 protocol firmware.
Other actually running setpoint commands will not be affected !
note:
If UMPM98 protocol firmware will receive an ACTCON (pos. or neg.) from the RTU-101 without an
setpoint command in progress, this ACTCON will be ignored by UMPM98.

4-14 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Application function of Communication Communication


UMPM98 RTU-101
Controlling Station services services

SELECT setpoint
command <TI=48,50>, COT=6, SE=1

SELECT setpoint <TI=48,50>, COT=7, SE=1


confirmation
„ACTCON positive“ 1

DEACTIVATE setpoint
command <TI=48,50>, COT=8, SE=x

DEACTIVATE setpoint <TI=48,50>, COT=9, SE=x


confirmation
„ACTCON positive“ 1

EXECUTE setpoint
command <TI=48,50>, COT=6, SE=0
<TI=48>, COT=6, SE=0
EXECUTE

EXECUTE setpoint ACTCON


confirmation <TI=48>, COT=7, SE=0
<TI=48,50>, COT=7, SE=0

1 ACTCON pos. Will be sent only if this setpoint command is configured as select-before-execute

SA2-545-X.XX/93-00 4-15
UMPM98 Firmware Description Ax 1703

4.3.3.1. Parameterization

Example for "SIP message address conversion" for UMPM98 in control direction for setpoint commands

Supported SAT 1703 message formats:

x Set point command, normalized value <TI=48> (<TI=61> on 104)


x Set point command, short floating point <TI=50> (<TI=63> on 104

Address conversion SAT 1703 o RTU-101:

x CASDU1,CASDU2, IOA1, IOA2, IOA3 ... 5-stage freely parameterizable


SAT 1703 internal IEC address (=source address) of setpoint command
possible: 0 – 255

x TI ... type identification (SAT internal BSE o SIP)


possible: 48, 50

x linearization
X_0%, X_100%, Y_0%, Y_100%
possible: normalized: -1..+1
short floating point: ±1.175494E-38 to ±3.402823E+38

x 101-CASDU1, 101-CASDU2, 101-IOA1, 101-IOA2, 101-IOA3 ... 5-stage freely


parameterizable RTU101 IEC address for setpoint command
possible: 0 – 255

x 101-TI ... type identification for RTU-101


possible: 48

x link address ... link address of RTU-101 (station address)


possible: 0 – 254

x mapping
possible: select-before-operate -> direct,
direct -> direct

4-16 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

4.4. Message Conversion of System Information in Control Direction


(SAT Ax 1703 o RTU-101)

System messages in control direction <TI=100,103,104> must not be included in the OPM
parameters for SIP message address conversion in transmit direction.

Type Identification Type identification to RTU-101


(SAT internal)
100 101 102 103 104 105 106

TI TI
(104) (101) (101)
<58> <100> C_IC_NA_1 X
<103> C_CS_NA_1 X
<104> C_TS_NA_1 X
<58> <45> C_SC_NA_1 X

note:
- "TI-101" is the type identification used SAT internal from BSE o SIP and to the RTU-101 on communication line.
- "TI-104" is the type identification used SAT-internal and from control center (IEC60870-5-104 NUC).

SA2-545-X.XX/93-00 4-17
UMPM98 Firmware Description Ax 1703

Station interrogation command <TI=100> from control center via IEC60870-5-104 / NUC
interface will be handled directly from the AK 1703 data base of the BSE with the 104
interface.
Station interrogation command <TI=100> from control center will not be forwarded to
RTU-101.
Communication interface specific "general interrogation command " will be possible using
<TI=58> on IEC60870-5-104 / NUC.
o see also chapter Statkraft/PROSAM specific "general interrogation command" for a
specific communication interface.

Clock synchronization command <TI=103>


Clock synchronization of the AK-1703 will be done via AK´s IEC 60870-5-104 interface
(=NIP) according RFC1305 (NTP).
note: NTP use IP/UDP protocol.
After restart of AK-1703 the NIP request the time from the NTP-Server. After AK`s time is set
the NIP request the actual time every minute from the NTP-Server.

The time synchronization of the RTU-101 will be done by UMPM98 protocol firmware
using <TI=103> clock synchronization command. This will be sent spontaneous from AK-
internal time management to the UMPM98 protocol firmware after restart of AK-1703 (or
restart of the BSE) if time will be set or changed.

The periodic time setting of the RTU-101 will be done by the protocol firmware UMPM98.

Test command <TI=104>


The test command function can be parameterized in AK 1703 for each communication
interface on BSE / L06 "IEC 870-5-101/104" parameter block in the chapter "parameter for
test command".

Parameters:
– cycle time to transmit the test command
– monitoring time for confirmation of the test command

The test command will be generated by communication function on BSE (AK-1703 internal)
and sent using <TI=104> test command to each link address parameterized for the specific
communication interface.
The <TI=104> test command will be sent by UMPM98 protocol without modification to
RTU-101.

Reset process command <TI=105> from control center via IEC60870-5-104 / NUC
interface will be handled directly from the AK-1703.
Reset process command <TI=105> from control center will not be forwarded to RTU-101.
Reset process command for RTU-101 from control center via IEC60870-5-104 / NUC
interface will be possible using <TI=58> on IEC60870-5-104 NUC.
o see also chapter Statkraft/PROSAM specific "Reset RTU command" for a specific
RTU-101.

4-18 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

4.4.1. General Interrogation Command

A Statkraft/PROSAM specific "general interrogation command for a specific communication


interface in AK-1703" (GI-command) is sent from the control center as a DIRECT command
<TI=45> to CAEx (in AK 1703).
CAEx will send always ACTCON pos. and ACTTERM pos. immediately for this command to
the control center (without a closed loop to the protocol application).
ACTTERM pos. will be sent directly after ACTCON pos. from CAEx.

This GI-command from the control center will be converted by CAEx to a SAT internal
command <TI=45>. This SAT internal command is converted by the PST function (PST
control message) to a "communication line specific" interrogation command <TI=100>
(global to all stations).

This Message is sent out to the RTU-101 from the UMPM98 protocol firmware.
The RTU-101 will send back the data assigned to the GI in the following polling cycle.
If ACTCON and ACTTERM will be received from the RTU-101 this will be forwarded to
AK-1703 intern but as ACTCON / ACTTERM is not expected from the RTU-101 this will be
discarded within AK-1703.

Data sent by the RTU with <COT=20> (interrogated by station interrogation) will be
converted in AK-1703 to <COT=2> (background scan). It can be configured in AK-1703 if
this "background scan data" should be sent via IEC60870-5-104 interface to the controlling
station. ACTCON / ACTERM received from the RTU-101 will not be forwarded to the AK´s
IEC60870-5-104 interface.

note:
- No "1 out of n" handling for this specific "GI-command" on CAEx or UMPM98 protocol
firmware !
- A general interrogation <TI=100> sent from the controlling station to AK-1703 will be
answered directly from the database of the BSE of the IEC60870-5-104 interface.

SA2-545-X.XX/93-00 4-19
UMPM98 Firmware Description Ax 1703

4.4.2. Reset RTU Command

A Statkraft/PROSAM specific "reset RTU command for a specific RTU" is sent from the
control center as a DIRECT command <TI=45> to CAEx (in AK-1703).

CAEx will send always ACTCON pos. and ACTTERM pos. immediately for this command to
the control center (without a closed loop to the protocol application).
ACTTERM pos. will be sent directly after ACTCON pos. from CAEx.

This reset RTU command will be converted by CAEx to a SAT internal command <TI=45>
and sent to the UMPM98 protocol firmware.
Using <TI=105> for this command in the field "101-TI" in the OPM message address
conversion in transmit direction (for commands) will activate an specific function on UMPM98
protocol firmware.

─ no select-before-execute for this single command (only direct)


─ no "1 out of n" handling on UMPM98 protocol firmware
─ no handling for return information
─ no ACTCON / ACTERM by UMPM98 protocol firmware
─ <COT=6> cause of transmission must be "<6>:=activation"
─ <SCS=1> single command state must be "ON"
─ <S/E=0> "EXECUTE"

This Message is sent out to the RTU-101 as <TI=105> "Reset process command" from the
UMPM98 protocol firmware.
The RTU-101 will perform the reset RTU command (if supported).
If ACTCON and ACTTERM will be received from the RTU-101 this will be forwarded to
AK-1703 intern but as ACTCON / ACTTERM is not expected from the RTU-101 this will be
discarded within AK-1703.

Note:
The reset RTU command is sent to the RTU-101 as reset process command <TI=105> with the parameters for
CASDU assigned in the OPM parameters and IOA = 0 and <QRP=1> (=general reset of Process).

4-20 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

4.4.2.1. Parameterization

This specific reset RTU command using <TI=45> single command must be included in the
detail routing and in the OPM message address conversion for UMPM98 protocol firmware.

Example for "SIP message address conversion" for UMPM98 in control direction for reset RTU command

note:
there is only one parameter category defined in the OPM for commands – in this chapter only the relevant settings
for reset RTU command using <TI=45> single command will be described.

Supported SAT 1703 message formats:

x Single command <TI=45>

Address conversion SAT 1703 o RTU-101:

x CASDU1,CASDU2, IOA1, IOA2, IOA3 ... 5-stage freely parameterizable


SAT 1703 internal IEC address (=CAEx source address) of reset RTU command
possible: 0 – 255

x TI ... type identification (SAT internal BSE o SIP)


possible: 45

x 101-CASDU1, 101-CASDU2, 101-IOA1, 101-IOA2, 101-IOA3 ... 5-stage


parameterizable RTU-101 address for reset RTU command
possible: CASDU ... 0 – 255, IOA = 0

x 101-TI ... type identification for RTU-101


possible: 105

x link address ... link address of RTU-101 (station address)


possible: 0 – 254

SA2-545-X.XX/93-00 4-21
UMPM98 Firmware Description Ax 1703

4.5. Message Conversion of Process Information in Monitor Direction


(RTU-101 o SAT Ax 1703)

One message of a specific type identification from RTU-101 can be converted to 1 message
of the supported type identifications to SAT internal with different new address.

Type Identification Type identification from RTU-101


(SAT internal)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

TI TI
(104) (101) (101)
<1> <1> M_SP_NA_1
<2> <2> M_SP_TA_1
<3> <3> M_DP_NA_1
<4> <4> M_DP_TA_1
<5> <5> M_ST_NA_1
<6> <6> M_ST_TA_1
<7> <7> M_BO_NA_1
<8> <8> M_BO_TA_1
<9> <9> M_ME_NA_1
<10> <10> M_ME_TA_1
<11> <11> M_ME_NB_1
<12> <12> M_ME_TB_1
<13> <13> M_ME_NC_1
<14> <14> M_ME_TC_1
<15> <15> M_IT_NA_1
<16> <16> M_IT_TA_1
<17> <17> M_EP_TA_1
<18> <18> M_EP_TB_1
<19> <19> M_EP_TC_1
<20> <20> M_PS_NA_1
<21> <21> M_ME_ND_1
<30> <30> M_SP_TB_1 X X
<31> <31> M_DP_TB_1 X X
<32> <32> M_ST_TB_1 X X
<33> <33> M_BO_TB_1
<34> <34> M_ME_TD_1 X X X X
<35> <35> M_ME_TE_1
<36> <36> M_ME_TF_1 X X X X
<37> <37> M_IT_TB_1 X
<38> <38> M_EP_TD_1
<39> <39> M_EP_TE_1
<40> <40> M_EP_TF_1

4-22 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Type Identification Type identification from RTU-101


(SAT internal)
20 21 30 31 32 33 34 35 36 37 38 39 40

TI TI
(104) (101) (101)
<20> <20> M_PS_NA_1
<21> <21> M_ME_ND_1
<30> <30> M_SP_TB_1 X
<31> <31> M_DP_TB_1 X
<32> <32> M_ST_TB_1 X
<33> <33> M_BO_TB_1
<34> <34> M_ME_TD_1 X X
<35> <35> M_ME_TE_1
<36> <36> M_ME_TF_1 X X
<37> <37> M_IT_TB_1 X
<38> <38> M_EP_TD_1
<39> <39> M_EP_TE_1
<40> <40> M_EP_TF_1

note:

- "TI(101)" is the type identification used from the RTU-101 on communication line and SAT internal
from SIP o BSE.

- "TI(104)" is the type identification used to control center (IEC60870-5-104 NUC).

- SAT internal always "long time format" CP56Time2a is used !

- If type identification with time tag is used in monitor direction this TI must be parameterized in the
OPM parameters (SIP message address conversion). The corresponding type identification used for general
interrogation will be supported automatic (this TI must not be included in the OPM parameters).
o If type identification without time tag is used in monitor direction this type identification must be parameterized
in the OPM parameters (SIP message address conversion).
e.g.: (1) <TI=2> is used in monitor direction for spontaneous data
o <TI=2> must be parameterized in OPM
o <TI=1> will be supported automatic (not to be parameterized in OPM)

(2) <TI=1> is used in monitor direction for spontaneous data


o <TI=1> must be parameterized in OPM

Corresponding type identifications spontaneous - GI:

corresponding type identification (GI) spontaneous type identification


<TI=1> Single-point information <TI=2> Single-point information with time tag
<TI=3> Double-point information <TI=4> Double-point information with time tag
<TI=9> Measured value, normalized value <TI=10> Measured value, normalized value with time
tag
<TI=13> Measured value, short floating point value <TI=14> Measured value, short floating point value
with time tag
<TI=1> Single-point information <TI=30> Single-point information with time tag
CP56Time2a
<TI=3> Double-point information <TI=31> Double-point information with time tag
CP56Time2a
<TI=5> Step position information <TI=32> Step position information with time tag
CP56Time2a
<TI=9> Measured value, normalized value <TI=34> Measured value, normalized value with time
tag CP56Time2a

<TI=13> Measured value, short floating point value <TI=36> Measured value, short floating point value
with time tag CP56Time2a

SA2-545-X.XX/93-00 4-23
UMPM98 Firmware Description Ax 1703

4.5.1. Parameterization

Example for "SIP message address conversion" for UMPM98 in monitoring direction

Supported SAT 1703 message formats:

x Single-point information with time tag CP56Time2a <TI=30>


x Double-point information with time tag CP56Time2a <TI=31>
x Step position information with time tag CP56Time2a <TI=32>
x Measured value, normalized value with time tag CP56Time2a <TI=34>
x Measured value, short floating point value with time tag CP56Time2a <TI=36>
x Integrated totals with time tag CP56Time2a <TI=37>

Address conversion RTU-101 o SAT 1703:

x link address ... link address of RTU-101 (station address)


possible: 0 – 254

x CASDU1, CASDU2, IOA1, IOA2, IOA3 ... 5-stage freely parameterizable


SAT 1703 address
possible: 0 – 255

x TI ... type identification


possible: 30, 31, 32, 34, 36, 37

x linearization (only for <TI=9, 10, 13, 14, 34, 36> )


X_0%, X_100%, Y_0%, Y_100%
possible: normalized: -1..+1
short floating point: ±1.175494E-38 to ±3.402823E+38

x intermediate time (only for double-point information)


possible: short, long

x 101-CASDU1, 101-CASDU2, 101-IOA1, 101-IOA2, 101-IOA3 ... 5-stage freely


parameterizable RTU101 address of the data point
possible: 0 – 255

x 101-TI ... type identification of RTU-101


possible: 1, 2, 3, 4, 5, 6, 9, 10, 13, 14, 16, 30, 31, 32, 34, 36, 37

4-24 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

4.5.2. Conversion of Time Format

All type identifications received from RTU-101 (monitor direction) will be sent from
SIP o BSE with 7 octet binary time format "CP56Time2a" (= long time format).

x information from RTU-101 "without time tag":


Time stamp SIP o BSE: AK 1703 internal time (CP56Time2a) at receiving time

x information from RTU-101 with time tag "CP24Time2a":


Time stamp SIP o BSE: received time from RTU-101 converted from "CP24Time2a"
to CP56Time2a according "conversion of time format"

x information from RTU-101 with time tag CP56Time2a:


Time stamp SIP o BSE: CP56Time2a received from RTU-101

CP24Time2a : = CP24{milliseconds,minutes,res1,invalid}
(3 octet binary time =short time format)

CP56Time2a : = CP56{milliseconds, minutes, res1, invalid, hours, res2, summer time, day
of month, day of week, months, res3, years, res4}
(7 octet binary time = long time format)

CP24Time2a format does not include the hour and date - this date and time information will
be added by the UMPM98 protocol firmware.

x When the AK1703 internal time is not set (e.g. after RESET or POWER UP), the
invalid bit of the time tag will be set and the actual hour and date will be added without
modification for all received messages with time tag CP24Time2a until the AK1703´s
time is set correctly.

x When the AK1703 internal time is set correctly, the actual hour and date will be added
without modification for all received messages with time tag CP24Time2a except in
following cases:

─ the actual minute of AK1703 is in the range of "0..5" and the received minute is in
the range of "55..59" o 1 hour will be subtracted from the CP56Time2a

─ the actual minute of AK1703 is in the range of "55..59" and the received minute is
in the range of "0..5" o 1 hour will be added to the CP56Time2a

The RTU-101 will be clock synchronized from UMPM98 protocol firmware with
<TI=103> clock synchronization command in the following cases:

– periodically / default: once per minute


(this can be configured by system technical parameter / chapter advanced parameters)
st
– spontaneous / when time or date changes or after restart of AK-1703 after 1 time setting
of UMPM98 protocol firmware

Restriction:
If the communication link is broken and the RTU-101 does not clear the RTU internal
transmit data base, the hour and date can not be assigned correctly for old data stored in the
RTU-101 by UMPM98 protocol firmware.
Also the invalid bit for time stamp will not be set!

Note:
IEC60870-5-101 does not define an procedure to clear data stored in the transmit data base of the RTU-101.

SA2-545-X.XX/93-00 4-25
UMPM98 Firmware Description Ax 1703

4.5.3. Intermediate state / faulty state suppression

The protocol firmware UMPM98 implements a suppression of intermediate state ("00") and
faulty state ("11") for double-point information in monitoring direction.

The suppression will be supported for max. 20 different double-point information with
"intermediate state" or "faulty state" at the same time with a time resolution of 1 sec.

If the suppression handling is running for 20 double-point information - other double-point


information with "intermediate state" or "faulty state" will be sent to BSE without an
suppression handling.

System technical parameters for intermediate-/faulty state suppression:


– faulty position suppression time
– intermediate position suppression time - short
– intermediate position suppression time - long

In the OPM parameters (SIP message address conversion in monitoring direction) the
intermediate time suppression "short" or "long" can be selected for each double-point
information individually.

When the parameter "faulty position suppression time" is set to "0" - no faulty state
suppression will be done by UMPM98 protocol firmware.
When the parameter for the assigned "intermediate position suppression time - short or long"
is set to "0" - no intermediate state suppression will be done by UMPM98 protocol firmware.

Double-point information received from RTU-101 with "intermediate state" or "faulty state"
will be sent after suppression timeout with following time stamp to the BSE:

<TI=3> double point information (without time tag)


Time stamp: AK 1703 internal time (CP56Time2a) at receiving time.

<TI=4> double point information with time tag (CP24Time2a)


Time stamp: received time from RTU-101 converted from "CP24Time2a" to
CP56Time2a according "conversion of time format" at receiving
time.

<TI=31> double point information with time tag CP56Time2a


Time stamp: CP56Time2a received from RTU-101

If an intermediate state ("00") or faulty state ("11") for double-point information will be
received from RTU-101 with <COT = 20..36> (station interrogation) no suppression for
intermediate state or faulty state will be done by UMPM98 protocol firmware.

When the double-point information changes from state "OFF" o "intermediate or faulty" and
than back to "OFF" the intermediate or faulty state will be suppressed but the "OFF" state
will be forwarded again from SIP o BSE.
When the double-point information changes from state "ON" o "intermediate or faulty" and
than back to "ON" the intermediate or faulty state will be suppressed but the "ON" state will
be forwarded again from SIP o BSE.

When the double-point information changes permanently from "intermediate state" ↔ "faulty
state" the suppression time will always be retriggered – in this state the double-point
information will also not be forwarded if any bit in the status will change (e.g. NT, IV,...) .

4-26 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

5. Protocol-specific Functions

5.1. Redundancy Function

The protocol firmware UMPM98 can be switched to STANDBY- / or ACTIVE-mode using the
AK 1703 internal redundancy control messages.

The ACTIVE Master is polling all the connected RTU´s according station call prioritization
defined in the system technical parameters. Data messages will be sent spontaneous to the
RTU´s.
If data messages will be sent continually to the RTU – UMPM98 protocol firmware will send
alternate 1 data message and then 1 station poll message.

The function of the STANDBY-mode can be defined in the system technical parameters:

– interface "TRISTATE" ... no polling of RTU´s = "listening mode (1)"

– interface "ACTIVE" ...... no polling of RTU´s = "listening mode (1)"

– interface "ACTIVE" ....... polling of RTU´s


The detailed operation in this mode can be parameterized in the system technical
parameters "advanced parameters / Redundancy operation mode" of the UMPM98
protocol firmware.

(a) AX1703 redundancy mode


Standard polling of RTU´s – all received messages will be forwarded to BSE.
Received messages from STANDBY Master will be marked with P-Bit (P = passiv)
SAT internally.

(b) Norwegian User Conventions (NUC) redundancy mode


Polling mode only using "REQUEST STATUS of LINK".
Data messages will not be sent to / requested from RTU-101.
RTU´s not answering will be set as faulty.

Data messages will not be forwarded AK-1703 internal from BSE to interfaces in STANDBY
mode.

Notes:
(1) Listening mode: All received messages will be forwarded to the BSE.
In order to synchronize the firmware - which is in standby operation - to the same FCB
(Frame Count Bit) as the active one, the current FCB is either taken from the monitored
Reset of Remote Link or from a valid long message.

SA2-545-X.XX/93-00 5-1
UMPM98 Firmware Description Ax 1703

5.2. Data acquisition by Polling (station polling)

The transmission of the data from the RTU´s to the MASTER station is done only on station-
selective station interrogation (polling). Spontaneous transmission of the data from the RTU
is, therefore, not possible. Altered data remain stored in the RTU and, on a station
interrogation of this station, are transmitted to the MASTER station.

RTU´s which have a large amount of data to be transmitted can be interrogated by the
MASTER station several times immediately one after the other before a station change is
made.

Data from the MASTER station to the RTU are spontaneously transmitted after the end of
the running message transmission of the interrogation cycle. Following this, the interrupted
interrogation cycle is continued.

The interrogation cycle can be made either continuously or just on request. The interrogation
cycle counts as having ended if the configured number of station calls has been executed for
the last station.

The station interrogation does not automatically guarantee that the entire amount of data
which is initiated for transmission is transmitted in one interrogation cycle.

By configuration of the station interrogation in the MASTER station (Number of calls until
station change), "getting stuck" at a station with continuously changing data can be
prevented.

Stations which have not stored any data for the transmission are not removed from the
interrogation cycle. To optimize the interrogation cycle, for such stations (independent of the
"Number of station calls until station change" configuration) a station change is carried out
immediately after one call.

Faulty stations likewise continue to be interrogated in the interrogation cycle but for such
stations no message repeating (retries) is carried out during the station interrogation.

5-2 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

5.3. Clock Synchronization of RTU´s

5.3.1. Time Setting

Clock synchronization of the AK-1703 (Statkraft/PROSAM project) will be done via AK´s
IEC 60870-5-104 interface (=NIP) according RFC1305 (NTP).
note: NTP use IP/UDP protocol.
After restart of AK-1703 the NIP request the time from the NTP-Server. After AK`s time is set
the NIP request the actual time every minute from the NTP-Server.

The time synchronization of the RTU-101 will be done by UMPM98 protocol firmware
using <TI=103> clock synchronization command. This will be sent spontaneous from AK-
internal time management to the UMPM98 protocol firmware after restart of AK-1703 (or
restart of the BSE) if time will be set or changed.
UMPM98 protocol firmware will include the total actual time (format: CP56Time2a) corrected
by an parameter-settable correction value (only if "free definable" interface modem will be
selected).

Time value in <TI=103> = takt + tcorr + tmsg

takt ... actual time of AK-1703


tcorr .. correction time
see advanced parameters / real time remote synchronization
"correction time of message transfer time"
Note:
─ If the time value in <TI=103> should have the time when sending the 1st bit of the time synchronization
message - the correction time must include the tp + tv.
(tmsg = 0)
─ If the time value in <TI=103> should have the time when receiving the last bit of the time synchronization
message in the RTU - the correction time must include the tp + tv + tmsg

tmsg . transmission time for time sync message


(depends on used baudrate, number of bytes for Link address, CASDU, COT, IOA)
tmsg = (1/ baudrate) *11 * (7 + 9 + n)
n = no_link + no_CASDU + no_IOA + no_COT
no_link ................number of octets for address field of the link
no_CASDU.........number of octets for CASDU
no_IOA ...............number of octets for IOA
no_COT..............number of octets for Cause of transmission

The periodic time setting (=clock synchronization) of the RTU-101 will be done by the
protocol firmware UMPM98.

At start up, the time setting of the RTU´s is discarded by the UMPM98 firmware until the
protocol element internal time is set correctly so that the current ms can be correctly entered
into the time setting message.

The MASTER will sent the clock synchronization message always as BROADCAST
message so that this message will be received by the RTU´s within the same minute.
Binary information stored in the data base of the RTU will be sent with the "old time" if time
changes after clock synchronization.

Note:
If all parameterized RTU´s are faulty – no clock synchronization message will be sent by UMPM98 protocol
firmware. If at least one of the parameterized RTU´s are OK the clock synchronization message will be sent as
BROADCAST message by UMPM98 protocol firmware.

SA2-545-X.XX/93-00 5-3
UMPM98 Firmware Description Ax 1703

The time setting message is also used for time synchronization.

If lower precision of the real time data is sufficient, the synchronization of the RTU´s can also
take place via the serial communications line.

The RTU-101 will be clock synchronized from UMPM98 protocol firmware with
<TI=103> clock synchronization command in the following cases:

– periodically / default: once per minute


(this can be configured by system technical parameter / chapter advanced parameters)
st
– spontaneous / when time or date changes or after restart of AK-1703 after 1 time setting
of UMPM98 protocol firmware

5-4 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

5.4. Handling of faulty Stations

Faulty RTU´s will be detected by the MASTER in the normal polling cycle.
Faulty RTU´s will be polled once in the interrogation cycle (without retry handling) using
"request status of link".

5.4.1. Retry Handling

If the acknowledgement for a message which was sent out from the MASTER station will not
be received, this message is repeated n times (n = configurable number). If the MASTER will
not receive an answer from the RTU during these retries, the RTU (SAT internal station
address) is marked as faulty and the interface failure is also displayed on LED´s.

The acknowledgement timeout is calculated per automatically according the actual


parameter setting.
If the used communication system or an additional reaction delay of the RTU will cause
additional delays this can be adjusted in the parameter tSignal = Signal runtime of the
message (= Correction factor).

5.4.2. Interface Fault

When a RTU does not answer to a polling message of the MASTER after parameterized
retry count – this RTU (SAT internal station address) will be set as faulty (if parameterized).

If all parameterized RTU´s will be detected as faulty by the MASTER the communication
interface in AK-1703 will be indicated as faulty – in this state only "request status of link" will
be sent for the parameterized RTU´s (also no clock synchronization will be sent).

SA2-545-X.XX/93-00 5-5
UMPM98 Firmware Description Ax 1703

5.5. Transmission Device (Modem)

It is possible to use a transmission device with preset time; the use of a "user setting" is also
possible.

Default times:

Transmission Operating RTS tp tv tn tdis DCD t- t-stab t-duration t-delay


medium mode fixed bounce

4-wire RS-232 YES 0 0 3 bit 35 YES 5 5 10000 200

2-wire RS-232 NO 0 30 3 bit 35 YES 5 5 10000 200

DMS 1) RS-232 YES 0 0 5 bit 0 NO 0 0 0 0

DMS 2) RS-232 NO 0 50 5 bit 35 YES 5 5 10000 200

OPTICAL RS-232 NO 0 1 0 0 NO 0 0 0 0

RADIO - Digital RS-232 NO 30 100 11 bit 50 YES 10 5 0 200

RADIO - Analog RS-232 NO 50 300 50 100 YES 10 5 0 200

Direct conn. RS-485 NO 0 1 0 0 NO 0 0 0 0

DLC modem RS-232 NO 0 1 bit 1 bit 0 NO 0 0 0 0

4-wire RS-232 YES 0 0 3 bit 0 YES 5 5 10000 200


SAT CE701

2-wire RS-232 NO 22 30 3 bit 0 YES 5 5 10000 200


SAT CE701

free definable RS-232 NO 30 100 11 bit 0 NO -- -- -- --

All times are n*1 ms.

1) DMS in ring configuration.


2) DMS with WT in ring configuration.

5-6 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

6. System Technical Parameters

6.1. Overview

6.1.1. Station Definition

x Stat-No.
Parameter settings: 0-99 (SAT internal station address)
default: 255 (not used)
x Link-address (on the communication line)
Parameter settings: 0-254 (link address for RTU-101)
default: 0
x station enable
Parameter settings: 0 = disabled; default: 1 = enabled
x station failure
Parameter settings: 0 = do not notify station failure,
default: 1 = notify station failure
x Priority level
Parameter settings: default: 0 = high priority
1 = medium priority, 2 = low priority (A), 3 = low priority (B)
x No. of calls (max. number of calls for specific link address before change to next
station address)
Parameter settings: 0, default:1 , 2 , 3

SA2-545-X.XX/93-00 6-1
UMPM98 Firmware Description Ax 1703

6.1.2. Common Settings

x Baud rate in transmit direction


Parameter settings: 100, 200, 300, 600, default: 1200, 2400, 4800, 9600, 19200

x Baud rate in receive direction


Parameter settings: 100, 200, 300, 600, default: 1200, 2400, 4800, 9600, 19200

x interface modem
Parameter settings: - free definable
- default: SAT Modem "4-wire circuit transmission line"
(SAT-VFM,-WT,-WTK,-WTK-S,-CE0700)
- SAT Modem "2-wire circuit transmission line"
(SAT-VFM,-WT,-WTK,-WTK-S,-CE0700)
- SAT-DMS (ring configuration)
- SAT-DMS (ring configuration; AU remote via WT)
- optical
- radio digital
- radio analog
- Null modem interface (RS-485)
- SAT DLC-Modem
(CE0740,CE0741, CE0742, LA0740, LA0741)
- SAT Modem "4-wire circuit transmission line" (SAT-CE0701)
- SAT Modem "2-wire circuit transmission line" (SAT-CE0701)
- SAT Modem "2-wire circuit transmission line"
(SAT-CE0701 over modem)
- SAT Modem "2-wire circuit transmission line"
(SAT-CE0701 over Westermo TD-32)
- SAT Modem "2-wire circuit transmission line"
(SAT-CE0701 over Westermo GD-01)
- Null modem interface (RS-232)
only if one RTU-101 has to be connected
- SATTELINE 2ASxE time slot radio modem

6-2 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

6.1.2.1. Free definable Transmission Facility

x Electrical interface
Parameter settings: default: RS232 (V.24/V.28),
RS422 (V.11), RS485 (V.11)

x Asynchron_isochron
Parameter settings: default: asynchronous "V.24/V.28" (16x bit timing),
isochron "X.24/X.27" (single bit timing)

x Bit timing (only for Isochronous):


Parameter settings: extern (bit timing from RXC input),
internal (bit timing at the TXC-output)

x Pause time (tp)


Parameter settings: 0-32767[ms/Bit] default: 0

x Pause time Time Base (tp)


Parameter settings: default: ms, bit

x Set up time (tv)


Parameter settings: 0-32767[ms/Bit] default: 0

x Set up time Time Base (tv)


Parameter settings: default: ms, bit

x Run out time (tn)


Parameter settings: 0-32767[ms/Bit] default: 0

x Run out time Time Base (tn)


Parameter settings: ms, default: Bit

x Disable time (tdis)


Parameter settings: 0-32767[ms/Bit] default: 0

SA2-545-X.XX/93-00 6-3
UMPM98 Firmware Description Ax 1703

x Disable time Time Base (tv)


Parameter settings: ms, default: Bit

x DCD assessment
Parameter settings: not enabled; default: enabled

x Bounche suppression time (tbounce)


Parameter settings: 0-65535[ms] default: 0

x Stability monitoring time (tstab)


Parameter settings: 0-65535[ms] default: 0

x Transmission delay continuous level transmission line (tcldly)


Parameter settings: 0-65535[sec] default: 0

x Continuous level monitoring time (tcl)


Parameter settings: 0.1-6553.5[sec] default: 0

Note:
For Statkraft/PROSAM project RTS and DCD will not be used – so all the Parameters for "free definable
transmission facility" can be set to defaults !

o "free definable transmission facility" must be parameterized for Statkraft/PROSAM


projects to activate the correct time synchronization algorithm as defined for
Statkraft/PROSAM. (see also chapter "Time synchronization of RTU´s")

6-4 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

6.1.3. Message Retries

x Retries for init-messages (after reset)


Number of retransmissions for init-message of the master.
Parameter settings: 0 – 255; default: 2

x Retries for station selective data message


Number of retransmissions for station selective message Master o Slave.
Parameter settings: 0 – 255; default: 2

x Retries for data messages "unacknowledged to all"


Number of retransmissions for data messages "unacknowledged to all"
(Master o Slave)
Parameter settings: 0 – 255; default: 2

SA2-545-X.XX/93-00 6-5
UMPM98 Firmware Description Ax 1703

6.1.4. Redundancy

x Behavior if passive
Parameter settings: default: interface "TRISTATE"
interface "ACTIVE", listening mode (=STANDBY)
interface "ACTIVE", calling mode (=OPERATION)

x Delay time standby o active


Parameter settings: 0 – 2000 sec;
default: 1 sec

x Receive timeout standby


Parameter settings: 0 – 60000 sec; 0 ... no monitoring

6.1.5. Station Call Prioritization

x No. of station calls in high priority level


Parameter settings: 0, default: 1, 2..99

x No. of station calls in medium priority level


Parameter settings: 0, default: 1, 2..99

x No. of station calls in low priority level (A)


Parameter settings: 0, default: 1, 2..99

x No. of station calls in low priority level (B)


Parameter settings: 0, default: 1, 2..99

6-6 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

6.1.6. Advanced Parameters

x Continuous Cycle
Parameter settings: default: Enabled, not Enabled

x Minute raster of RT remote synchronization


Parameter settings: default: 0, 1 – 255
note: 0 = 1 minute raster (fixed)

x selective RT remote synchronization


Parameter settings: Enabled, default: not Enabled
Note:
For Statkraft/PROSAM project "selective RT remote synchronization" must be enabled !

SA2-545-X.XX/93-00 6-7
UMPM98 Firmware Description Ax 1703

6.1.6.1. Monitoring times

x idle monitoring time


Parameter settings: 0...32767

x idle monitoring time time base


Parameter settings: Bit, ms

x Character monitoring time


Parameter settings: 0...32767

x Character monitoring time time base


Parameter settings: Bit, ms

x expected acknowledgem_time_corr_factor
Parameter settings: 0...655,35

x Timeout Confirmation
Parameter settings: 1...255 sec

x Timeout Termination
Parameter settings: 1...255 sec

x Timeout Execution
Parameter settings: 1...255 sec

x faulty position suppression time


Parameter settings: 1...255 sec

x intermediate suppression time – short


Parameter settings: 1...255 sec

x intermediate suppression time – long


Parameter settings: 1...255 sec

6-8 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

6.1.6.2. Call Procedure per Type Identification

x Type identification xx (TI)


Parameter settings: 0...255

x Continuous call time xx


Parameter settings: 0...6000,0

SA2-545-X.XX/93-00 6-9
UMPM98 Firmware Description Ax 1703

6.1.6.3. IEC Parameter

x DFC timeout
Parameter settings: 0...60000

x set originator address in transmit direction always up 0


Parameter settings: NO, YES

x Redundancy operating mode


Parameter settings: - AX1703
- Norwegian User Conventions (NUC)

Summertime bit, day of week in the time tag (transmission)

x set summer time (SU) -/ set days of week (DOW) always up 0


Parameter settings: Yes, default: NO

6-10 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

6.1.6.4. Real Time Remote Synchronization

This parameters will be visible only if "selective RT remote synchronization" is enabled.

x Minute raster measuring message transmission time


Parameter settings: 0-255, default: 5

x Correction time of message transfer time


Parameter settings: 0-65535, default: 0

SA2-545-X.XX/93-00 6-11
UMPM98 Firmware Description Ax 1703

6.1.6.5. Software Test Points

Note: not relevant for user (only for developer) !

6-12 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

6.2. Details

Common settings

Parameter Description Values/Ranges

baud rate receiving baud rate receiving direction [50] 50 [Bd]


direction [75] 75 [Bd]
[100] 100 [Bd]
[110] 110 [Bd]
[134] 134,5 [Bd]
[150] 150 [Bd]
[200] 200 [Bd]
[300] 300 [Bd]
[600] 600 [Bd]
[1050] 1050 [Bd]
[1200] 1200 [Bd]
[1800] 1800 [Bd]
[2000] 2000 [Bd]
[2400] 2400 [Bd]
[4800] 4800 [Bd]
[9600] 9600 [Bd]
[19200] 19200 [Bd]

baud rate transmit baud rate transmit direction [50] 50 [Bd]


direction [75] 75 [Bd]
[100] 100 [Bd]
[110] 110 [Bd]
[134] 134,5 [Bd]
[150] 150 [Bd]
[200] 200 [Bd]
[300] 300 [Bd]
[600] 600 [Bd]
[1050] 1050 [Bd]
[1200] 1200 [Bd]
[1800] 1800 [Bd]
[2000] 2000 [Bd]
[2400] 2400 [Bd]
[4800] 4800 [Bd]
[9600] 9600 [Bd]
[19200] 19200 [Bd]

SA2-545-X.XX/93-00 6-13
UMPM98 Firmware Description Ax 1703

Parameter Description Values/Ranges

interface modem Selection of the interface modem. Most of the parameters [0] free defineable
for the predefined interface modems are standardized [1] SAT Modem "4-wire circuit
and not changeable. transmission line" (SAT-
VFM,-WT,-WTK,-WTK-S,-
CE0700)
[2] SAT Modem "2-wire circuit
transmission line" (SAT-
VFM,-WT,-WTK,-WTK-S,-
CE0700)
[3] SAT-DMS (ring
configuration)
[4] SAT-DMS (ring
configuration; AU remote via
WT)
[5] OPTICAL
[6] radio digital
[7] radio analogue
[8] NULL-Modem interface
(RS-485)
[9] SAT-DLC-Modem
(CE0740,-CE0741,-CE0742,-
LA0740,-LA0741)
[10] SAT Modem "4-wire
circuit transmission line"
(SAT-CE0701)
[11] SAT Modem "2-wire
circuit transmission line"
(SAT-CE0701)
[12] SAT Modem "2-wire
circuit transmission line"
(SAT-CE0701 over modem)
[13] SAT Modem "2-wire
circuit transmission line"
(SAT-CE0701 over Westermo
TD-32)
[14] SAT Modem "2-wire
circuit transmission line"
(SAT-CE0701 over Westermo
GD-01)
[15] NULL-Modem interface
(RS-232)
[100] SATTELLINE 2ASxE
time slot radio modem

Common settings | SAT-DLC-Modem

Parameter Description Values/Ranges

DIP switch S1/1 The internal Baudrate at the DLC-Modem must be [0] OFF
parametrized via DIP-Switches direct at the DLC-Modem [1] ON
and must accord to this parametrization.

DIP switch S1/2 The internal Baudrate at the DLC-Modem must be [0] OFF
parametrized via DIP-Switches direct at the DLC-Modem [1] ON
and must accord to this parametrization.

DIP switch S1/3 The internal Baudrate at the DLC-Modem must be [0] OFF
parametrized via DIP-Switches direct at the DLC-Modem [1] ON
and must accord to this parametrization.

DIP switch S1/4 The internal Baudrate at the DLC-Modem must be [0] OFF
parametrized via DIP-Switches direct at the DLC-Modem [1] ON
and must accord to this parametrization.

6-14 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Parameter Description Values/Ranges

frequency range [0] 10-30kHz


[1] 30-90kHz

Common settings | Time slot radio modem (SATTELLINE 2ASxE)

Parameter Description Values/Ranges

failure monitoring Integer [###]


0 to 255 [min]

length of time slot Integer [##]


1 to 59 [s]

start second of time slot Integer [##]


0 to 59 [s]

Common settings | free defineable transmission facility

Parameter Description Values/Ranges

Bit timing: (only for Bit timing: (only for "Isochronous") either external (from [0] extern (bit timing from
"Isochronous") RXC-inpu) or intern (at TXC-output) RXC input)
[1] internal (bit timing at the
TXC-output)

DCD assessment DCD assessment [0] Not enabled


[1] Enabled

Transm.delay contin.lvl A further message transmission is carried out for Float [####.#]
tr.line(tcldly) "continuous level", at the latest, after expiry of the 0.1 to 6553.5 [s]
"Transmission delay". 0 [s]

asynchron_isochron asynchronous (V.24/V.28, 16 x bit timing) or isochron [0] asynchronous "V.24/V.28"


(X.24/X.27 1 x bit timing) (16 x bit timing)
[1] Isochron "X.24/X.27" (
single bit timing)

bounce suppression time bounce suppression time (tbounce) Integer [#####]


(tbounce) 0 to 65535 [ms]

continuous level continuous level monitoring time (tcl) Float [####.#]


monitoring time (tcl) 0.1 to 6553.5 [s]
0 [s]

disable time (tdis) disable time after a received message Integer [#####]
0 to 32767 [ms / Bit]

disable time time base Parametrized times in bits depend on the the baudrate! [0] Bit [ms / Bit]
(tdis) [1] ms [ms / Bit]

electrical interface electrical interface [0] RS232 (V.24/V.28)


[1] RS422 (V.11)
[2] RS485 (V.11)

pause time (tp) Before a message transmission the set pause time is Integer [#####]
waited before switching on the transmit level (RTS). 0 to 32767 [ms/Bit]

pause time_time base Parametrized times in bits depend on the the baudrate! [0] Bit [ms / Bit]
(tp) [1] ms [ms / Bit]

SA2-545-X.XX/93-00 6-15
UMPM98 Firmware Description Ax 1703

Parameter Description Values/Ranges

run-out time (tn) After the end of the message transmission, the transmit Integer [#####]
level(RTS) is only switched off after expiry of the reset 0 to 32767 [ms / Bit]
time.

run-out time_time base Parametrized times in bits depend on the the baudrate! [0] Bit [ms /Bit]
(tn) [1] ms [ms /Bit]

set up time (tv) After switching on the transmit level (RTS) the message Integer [#####]
transmission is started after expiry of the set-up time. 0 to 32767 [ms / Bit]
Note: For "tv=0" there is no carrier switching (RTS=OFF)!

set up time_time base (tv) Parametrized times in bits depend on the the baudrate! [0] Bit [ms / Bit]
[1] ms [ms / Bit]

stability monitoring time stability monitoring time (tstab)\ The "new" DCD state is Integer [#####]
(tstab) only utilized\ after expiry of the stability monitoring time\ 0 to 65535 [ms]
for the message synchronisation.

Message retries

Parameter Description Values/Ranges

Retries for INIT- Number of max. message retrys Integer [###]


messages (after reset) 0 to 255

Retries for data msg. Number of max. message retrys Integer [###]
"unack. to all" 0 to 255

Retries for station Number of max. message retrys Integer [###]


selective data msg. 0 to 255

Redundancy

Parameter Description Values/Ranges

Delay time delay time in case of sitch over from STANDBY->ACTIVE Integer [####]
standby=>active 0 = switch without delay 0 to 2000 [s]

behavior if passive behavior if passive [0] interface "TRISTATE"


[1] "interface "ACTIVE",
listening mode (=STANDBY)
[3] "interface "ACTIVE",
calling mode (=OPERATION)

receive timeout standby receive timeout in standby mode 0 = no monitoring! Float [####.]
0 to 60000 [s]

Station call prioritization

Parameter Description Values/Ranges

No. of stat. calls in high Number of station calls until level change Integer [##]
priority lvl 0 to 99

No. of stat. calls in low Number of station calls until level change Integer [##]
prior. lvl(A) 0 to 99

No. of stat. calls in low Number of station calls until level change Integer [##]
prior. lvl(B) 0 to 99

6-16 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Parameter Description Values/Ranges

No. of stat. calls in mid. Number of station calls until level change Integer [##]
priority lvl 0 to 99

Advanced parameters

Parameter Description Values/Ranges

Minute raster of RT 0 = each minute Integer [###]


remote sychroniz. 0 [min]
1 to 255 [min]

continuous cycle continuous cycle [0] Not enabled


[1] Enabled

selective RT remote [0] Not enabled


sychronization [1] Enabled

Advanced parameters | IEC-parameter

Parameter Description Values/Ranges

DFC-timeout receive timeout in standby mode 0 = no monitoring! Float [####.]


0 to 60000 [s]

Redundancy operating [0] AX1703


mode [1] Norwegian User
Conventions (NUC)

set originator address in [0] NO


transmit direction always [1] YES
up 0

Advanced parameters | IEC-parameter | Summertime bit, Weekday in the real-time


stamp(transmission)

Parameter Description Values/Ranges

set days of week (DOW) [0] NO


always up 0 [1] YES

set summer time (SU) [0] NO


always up 0 [1] YES

Advanced parameters | Software test points

Parameter Description Values/Ranges

DLC-Correction factor [0] NO


[1] YES

Handshake RTS,GPB The change of this parameter required profoundness [0] NO


(ASCII-Mode) communication knowledge. A specialist should be [1] YES
contacted before.

Handshake RTS,GPB The change of this parameter required profoundness [0] NO


(HEX-Mode) communication knowledge. A specialist should be [1] YES
contacted before.

SA2-545-X.XX/93-00 6-17
UMPM98 Firmware Description Ax 1703

Parameter Description Values/Ranges

Init-end processing The change of this parameter required profoundness [0] NO


communication knowledge. A specialist should be [1] YES
contacted before.

User-Softwaretestpoint [0] NO
10 [1] YES

User-Softwaretestpoint [0] NO
11 [1] YES

User-Softwaretestpoint [0] NO
12 [1] YES

User-Softwaretestpoint [0] NO
13 [1] YES

User-Softwaretestpoint [0] NO
14 [1] YES

User-Softwaretestpoint [0] NO
15 [1] YES

User-Softwaretestpoint 2 [0] NO
[1] YES

User-Softwaretestpoint 3 [0] NO
[1] YES

User-Softwaretestpoint 4 [0] NO
[1] YES

User-Softwaretestpoint 5 [0] NO
[1] YES

User-Softwaretestpoint 6 [0] NO
[1] YES

User-Softwaretestpoint 7 [0] NO
[1] YES

User-Softwaretestpoint 8 [0] NO
[1] YES

User-Softwaretestpoint 9 [0] NO
[1] YES

ZDT-filter The change of this parameter required profoundness [0] NO


communication knowledge. A specialist should be [1] YES
contacted before.

correction time of the time The change of this parameter required profoundness [0] NO
synchr. communication knowledge. A specialist should be [1] YES
contacted before.

data and The change of this parameter required profoundness [0] NO


acknowledgement communication knowledge. A specialist should be [1] YES
between BSE contacted before.

level locking station The change of this parameter required profoundness [0] NO
locking communication knowledge. A specialist should be [1] YES
contacted before.

mask for blocking data The change of this parameter required profoundness [0] NO
pick-up communication knowledge. A specialist should be [1] YES
contacted before.

6-18 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Parameter Description Values/Ranges

master-standby The change of this parameter required profoundness [0] NO


switchover communication knowledge. A specialist should be [1] YES
contacted before.

stop_serialtest_after_com The change of this parameter required profoundness [0] NO


m_error communication knowledge. A specialist should be [1] YES
contacted before.

Advanced parameters | call procedure per type identification

Parameter Description Values/Ranges

continuous call time 0 When a message is transmitted to a selective station, this Float [####.#]
station can be interrogated permanent for a definable 0.0 to 6000.0 [s]
time. (0=no perman

continuous call time 1 When a message is transmitted to a selective station, this Float [####.#]
station can be interrogated permanent for a definable 0.0 to 6000.0 [s]
time. (0=no perman

continuous call time 10 When a message is transmitted to a selective station, this Float [####.#]
station can be interrogated permanent for a definable 0.0 to 6000.0 [s]
time. (0=no perman

continuous call time 11 When a message is transmitted to a selective station, this Float [####.#]
station can be interrogated permanent for a definable 0.0 to 6000.0 [s]
time. (0=no perman

continuous call time 12 When a message is transmitted to a selective station, this Float [####.#]
station can be interrogated permanent for a definable 0.0 to 6000.0 [s]
time. (0=no perman

continuous call time 13 When a message is transmitted to a selective station, this Float [####.#]
station can be interrogated permanent for a definable 0.0 to 6000.0 [s]
time. (0=no perman

continuous call time 14 When a message is transmitted to a selective station, this Float [####.#]
station can be interrogated permanent for a definable 0.0 to 6000.0 [s]
time. (0=no perman

continuous call time 2 When a message is transmitted to a selective station, this Float [####.#]
station can be interrogated permanent for a definable 0.0 to 6000.0 [s]
time. (0=no perman

continuous call time 3 When a message is transmitted to a selective station, this Float [####.#]
station can be interrogated permanent for a definable 0.0 to 6000.0 [s]
time. (0=no perman

continuous call time 4 When a message is transmitted to a selective station, this Float [####.#]
station can be interrogated permanent for a definable 0.0 to 6000.0 [s]
time. (0=no perman

continuous call time 5 When a message is transmitted to a selective station, this Float [####.#]
station can be interrogated permanent for a definable 0.0 to 6000.0 [s]
time. (0=no perman

continuous call time 6 When a message is transmitted to a selective station, this Float [####.#]
station can be interrogated permanent for a definable 0.0 to 6000.0 [s]
time. (0=no perman

continuous call time 7 When a message is transmitted to a selective station, this Float [####.#]
station can be interrogated permanent for a definable 0.0 to 6000.0 [s]
time. (0=no perman

SA2-545-X.XX/93-00 6-19
UMPM98 Firmware Description Ax 1703

Parameter Description Values/Ranges

continuous call time 8 When a message is transmitted to a selective station, this Float [####.#]
station can be interrogated permanent for a definable 0.0 to 6000.0 [s]
time. (0=no perman

continuous call time 9 When a message is transmitted to a selective station, this Float [####.#]
station can be interrogated permanent for a definable 0.0 to 6000.0 [s]
time. (0=no perman

type identification 0 (TI) After a message is transmitted to a selective station, it Integer [###]
can be continuously interrogated for a parameterizable 0 to 255
time (=continuous calling).

type identification 1 (TI) After a message is transmitted to a selective station, it Integer [###]
can be continuously interrogated for a parameterizable 0 to 255
time (=continuous calling).

type identification 10 (TI) After a message is transmitted to a selective station, it Integer [###]
can be continuously interrogated for a parameterizable 0 to 255
time (=continuous calling).

type identification 11 (TI) After a message is transmitted to a selective station, it Integer [###]
can be continuously interrogated for a parameterizable 0 to 255
time (=continuous calling).

type identification 12 (TI) After a message is transmitted to a selective station, it Integer [###]
can be continuously interrogated for a parameterizable 0 to 255
time (=continuous calling).

type identification 13 (TI) After a message is transmitted to a selective station, it Integer [###]
can be continuously interrogated for a parameterizable 0 to 255
time (=continuous calling).

type identification 14 (TI) After a message is transmitted to a selective station, it Integer [###]
can be continuously interrogated for a parameterizable 0 to 255
time (=continuous calling).

type identification 2 (TI) After a message is transmitted to a selective station, it Integer [###]
can be continuously interrogated for a parameterizable 0 to 255
time (=continuous calling).

type identification 3 (TI) After a message is transmitted to a selective station, it Integer [###]
can be continuously interrogated for a parameterizable 0 to 255
time (=continuous calling).

type identification 4 (TI) After a message is transmitted to a selective station, it Integer [###]
can be continuously interrogated for a parameterizable 0 to 255
time (=continuous calling).

type identification 5 (TI) After a message is transmitted to a selective station, it Integer [###]
can be continuously interrogated for a parameterizable 0 to 255
time (=continuous calling).

type identification 6 (TI) After a message is transmitted to a selective station, it Integer [###]
can be continuously interrogated for a parameterizable 0 to 255
time (=continuous calling).

type identification 7 (TI) After a message is transmitted to a selective station, it Integer [###]
can be continuously interrogated for a parameterizable 0 to 255
time (=continuous calling).

type identification 8 (TI) After a message is transmitted to a selective station, it Integer [###]
can be continuously interrogated for a parameterizable 0 to 255
time (=continuous calling).

6-20 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Parameter Description Values/Ranges

type identification 9 (TI) After a message is transmitted to a selective station, it Integer [###]
can be continuously interrogated for a parameterizable 0 to 255
time (=continuous calling).

Advanced parameters | monitoring times

Parameter Description Values/Ranges

Character monitoring time Maximum pause between sequential bytes of a message. Integer [#####]
After a message interruption was detected, the idle 0 to 32767 [ms / Bit]
monitoring time is started.

Character monitoring Parametrized times in bits depend on the the baudrate! [0] Bit [ms / Bit]
time_time base [1] ms [ms / Bit]

Timeout Confirmation Integer [###]


1 to 255 [s]

Timeout Execute Integer [###]


1 to 255 [s]

Timeout Termination Integer [###]


1 to 255 [s]

expected_acknowledgem The expected acknowledgement time is determined Float [###.##]


_time_corr_factor automatically. Signal transfer times and other delays must 0 to 655.35 [s]
be considered in the "expected acknowledgement time
correction factor."

faulty position Integer [###]


suppression time 0 to 255 [sec]

idle monitoring time After transmission faults or message interruption, the line Integer [#####]
is monitored for quiescent state. After expiry of this 0 to 32767 [ms / Bit]
monitoring time, the resynchronisation of the receiver
takes place. By using the DCD input, faster
resynchronisation can be achieved.

idle monitoring time_time Parametrized times in bits depend on the the baudrate! [0] Bit [ms / Bit]
base [1] ms [ms / Bit]

intermediate position Integer [###]


suppression time - long 1 to 255 [sec]

intermediate position Integer [###]


suppression time - short 1 to 255 [sec]

Advanced parameters | real time remote sychronization

Parameter Description Values/Ranges

correction time of Integer [#####]


message transfer time 0 to 65535 [ms]

minute raster measuring 0= 1 minute cycle Integer [###]


msg.transf. time 0 to 255 [min]

SA2-545-X.XX/93-00 6-21
UMPM98 Firmware Description Ax 1703

6-22 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

A. Appendix: Diagnostic

A.1. Class internal

Class internal - Record 0 : Internal error in the operating system

Bit Description

00 RAM error

01 STACK error
The defined stack range has been exceeded;
Replace system element or notify SAT.

02 Firmware shut down


Diagnosis:
- Read out system diagnostics ring (command ID R)
in ST emulation (possibly store to file)

03 Too less free space


There is not enough free RAM memory available
for the dynamic memory management;
Diagnosis:
- Change parameterization of size definitions
(e.g. realtime rings, pool size)
- Notify SAT.

08 CPU 80186 error


Occurs on an internal software error.

SA2-545-X.XX/93-00 A-1
UMPM98 Firmware Description Ax 1703

Class internal - Record 2 : Parameter error ZSE

Bit Description

00 Parameter error detected by SIP

01 Parameter error of the LOCAL parameter block no. 06


Diagnosis:
- TI 38-40 and 136-143 requires parameter setting with
time
- TI 160 requires parameter setting without time
- transmission of the objects on GI with/without time;
value > 3
- number of octets for cause of transmission (COT) <> 2
- number of octets for common address of ASDU
(CASDU) <> 2
- number of octets for information object address (IOA) <>
3
- number of octets for time stamp <> 7

02 Parameter error ZSE general

03 Parameterized station number is invalid.


Diagnosis: Selected station number is greater than 100
and
also not a BROADCAST station number.

04 Parameterized station number is invalid.


Diagnosis: Same station number is used more then once.

05 Invalid Parameters for IEC870 link-layer

06 Invalid Parameters for IEC870 application layer

07 Invalid Parameters for Redundancy

15 Parameter setting for time zone is not valid

Class internal - Record 3 : ZSE format conversion error

Bit Description

00 Format conversion error in the transmit direction

02 Format conversion error in the receive direction

15 Conversion error in PST-control-messages


Diagnosis:
- Read out system diagnostics ring (command ID R) in
ST emulation (if possible store to file)

Class internal - Record 4 : Invalid Parameters for protocol specific application layer

Bit Description

00 Error when preparing the routing information

01 General parameter error of multi-point-protocol

A-2 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Class internal - Record 10 : Parameter error dedected by ZSE

Bit Description

10 Parameter error in detail routing in receive direction

11 Parameter error in detail routing in transmit direction

A.2. Class external

Class external - Record 0 : DFC-Bit Timeout for the Stations Nr. 0 - 15

Bit Description

00 DFC-Bit Timeout for the Stations Nr. 0

01 DFC-Bit Timeout for the Stations Nr. 1

02 DFC-Bit Timeout for the Stations Nr. 2

03 DFC-Bit Timeout for the Stations Nr. 3

04 DFC-Bit Timeout for the Stations Nr. 4

05 DFC-Bit Timeout for the Stations Nr. 5

06 DFC-Bit Timeout for the Stations Nr. 6

07 DFC-Bit Timeout for the Stations Nr. 7

08 DFC-Bit Timeout for the Stations Nr. 8

09 DFC-Bit Timeout for the Stations Nr. 9

10 DFC-Bit Timeout for the Stations Nr. 10

11 DFC-Bit Timeout for the Stations Nr. 11

12 DFC-Bit Timeout for the Stations Nr. 12

13 DFC-Bit Timeout for the Stations Nr. 13

14 DFC-Bit Timeout for the Stations Nr. 14

15 DFC-Bit Timeout for the Stations Nr. 15

SA2-545-X.XX/93-00 A-3
UMPM98 Firmware Description Ax 1703

Class external - Record 1 : DFC-Bit Timeout for the Stations Nr. 16 - 31

Bit Description

00 DFC-Bit Timeout for the Stations Nr. 16

01 DFC-Bit Timeout for the Stations Nr. 17

02 DFC-Bit Timeout for the Stations Nr. 18

03 DFC-Bit Timeout for the Stations Nr. 19

04 DFC-Bit Timeout for the Stations Nr. 20

05 DFC-Bit Timeout for the Stations Nr. 21

06 DFC-Bit Timeout for the Stations Nr. 22

07 DFC-Bit Timeout for the Stations Nr. 23

08 DFC-Bit Timeout for the Stations Nr. 24

09 DFC-Bit Timeout for the Stations Nr. 25

10 DFC-Bit Timeout for the Stations Nr. 26

11 DFC-Bit Timeout for the Stations Nr. 27

12 DFC-Bit Timeout for the Stations Nr. 28

13 DFC-Bit Timeout for the Stations Nr. 29

14 DFC-Bit Timeout for the Stations Nr. 30

15 DFC-Bit Timeout for the Stations Nr. 31

A-4 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Class external - Record 2 : DFC-Bit Timeout for the Stations Nr. 32 - 47

Bit Description

00 DFC-Bit Timeout for the Stations Nr. 32

01 DFC-Bit Timeout for the Stations Nr. 33

02 DFC-Bit Timeout for the Stations Nr. 34

03 DFC-Bit Timeout for the Stations Nr. 35

04 DFC-Bit Timeout for the Stations Nr. 36

05 DFC-Bit Timeout for the Stations Nr. 37

06 DFC-Bit Timeout for the Stations Nr. 38

07 DFC-Bit Timeout for the Stations Nr. 39

08 DFC-Bit Timeout for the Stations Nr. 40

09 DFC-Bit Timeout for the Stations Nr. 41

10 DFC-Bit Timeout for the Stations Nr. 42

11 DFC-Bit Timeout for the Stations Nr. 43

12 DFC-Bit Timeout for the Stations Nr. 44

13 DFC-Bit Timeout for the Stations Nr. 45

14 DFC-Bit Timeout for the Stations Nr. 46

15 DFC-Bit Timeout for the Stations Nr. 47

SA2-545-X.XX/93-00 A-5
UMPM98 Firmware Description Ax 1703

Class external - Record 3 : DFC-Bit Timeout for the Stations Nr. 48 - 63

Bit Description

00 DFC-Bit Timeout for the Stations Nr. 48

01 DFC-Bit Timeout for the Stations Nr. 49

02 DFC-Bit Timeout for the Stations Nr. 50

03 DFC-Bit Timeout for the Stations Nr. 51

04 DFC-Bit Timeout for the Stations Nr. 52

05 DFC-Bit Timeout for the Stations Nr. 53

06 DFC-Bit Timeout for the Stations Nr. 54

07 DFC-Bit Timeout for the Stations Nr. 55

08 DFC-Bit Timeout for the Stations Nr. 56

09 DFC-Bit Timeout for the Stations Nr. 57

10 DFC-Bit Timeout for the Stations Nr. 58

11 DFC-Bit Timeout for the Stations Nr. 59

12 DFC-Bit Timeout for the Stations Nr. 60

13 DFC-Bit Timeout for the Stations Nr. 61

14 DFC-Bit Timeout for the Stations Nr. 62

15 DFC-Bit Timeout for the Stations Nr.

A-6 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Class external - Record 4 : DFC-Bit Timeout for the Stations Nr. 64 -79

Bit Description

00 DFC-Bit Timeout for the Stations Nr. 64

01 DFC-Bit Timeout for the Stations Nr. 65

02 DFC-Bit Timeout for the Stations Nr. 66

03 DFC-Bit Timeout for the Stations Nr. 67

04 DFC-Bit Timeout for the Stations Nr. 68

05 DFC-Bit Timeout for the Stations Nr. 69

06 DFC-Bit Timeout for the Stations Nr. 70

07 DFC-Bit Timeout for the Stations Nr. 71

08 DFC-Bit Timeout for the Stations Nr. 72

09 DFC-Bit Timeout for the Stations Nr. 73

10 DFC-Bit Timeout for the Stations Nr. 74

11 DFC-Bit Timeout for the Stations Nr. 75

12 DFC-Bit Timeout for the Stations Nr. 76

13 DFC-Bit Timeout for the Stations Nr. 77

14 DFC-Bit Timeout for the Stations Nr. 78

15 DFC-Bit Timeout for the Stations Nr. 79

SA2-545-X.XX/93-00 A-7
UMPM98 Firmware Description Ax 1703

Class external - Record 5 : DFC-Bit Timeout for the Stations Nr. 80 -95

Bit Description

00 DFC-Bit Timeout for the Stations Nr. 80

01 DFC-Bit Timeout for the Stations Nr. 81

02 DFC-Bit Timeout for the Stations Nr. 82

03 DFC-Bit Timeout for the Stations Nr. 83

04 DFC-Bit Timeout for the Stations Nr. 84

05 DFC-Bit Timeout for the Stations Nr. 85

06 DFC-Bit Timeout for the Stations Nr. 86

07 DFC-Bit Timeout for the Stations Nr. 87

08 DFC-Bit Timeout for the Stations Nr. 88

09 DFC-Bit Timeout for the Stations Nr. 89

10 DFC-Bit Timeout for the Stations Nr. 90

11 DFC-Bit Timeout for the Stations Nr. 91

12 DFC-Bit Timeout for the Stations Nr. 92

13 DFC-Bit Timeout for the Stations Nr. 93

14 DFC-Bit Timeout for the Stations Nr. 94

15 DFC-Bit Timeout for the Stations Nr. 95

Class external - Record 6 : DFC-Bit Timeout for the Stations Nr. 96 -99

Bit Description

00 DFC-Bit Timeout for the Stations Nr. 96

01 DFC-Bit Timeout for the Stations Nr. 97

02 DFC-Bit Timeout for the Stations Nr. 98

03 DFC-Bit Timeout for the Stations Nr. 99

A-8 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

A.3. Class communication

Class communication - Record 2 : Communication error to Station no. 0 - 15

Bit Description

00 Communication error to Station no. 0

01 Communication error to Station no. 1

02 Communication error to Station no. 2

03 Communication error to Station no. 3

04 Communication error to Station no. 4

05 Communication error to Station no. 5

06 Communication error to Station no. 6

07 Communication error to Station no. 7

08 Communication error to Station no. 8

09 Communication error to Station no. 9

10 Communication error to Station no. 10

11 Communication error to Station no. 11

12 Communication error to Station no. 12

13 Communication error to Station no. 13

14 Communication error to Station no. 14

15 Communication error to Station no. 15

SA2-545-X.XX/93-00 A-9
UMPM98 Firmware Description Ax 1703

Class communication - Record 3 : Communication error to Station no. 16 - 31

Bit Description

00 Communication error to Station no. 16

01 Communication error to Station no. 17

02 Communication error to Station no. 18

03 Communication error to Station no. 19

04 Communication error to Station no. 20

05 Communication error to Station no. 21

06 Communication error to Station no. 22

07 Communication error to Station no. 23

08 Communication error to Station no. 24

09 Communication error to Station no. 25

10 Communication error to Station no. 26

11 Communication error to Station no. 27

12 Communication error to Station no. 28

13 Communication error to Station no. 29

14 Communication error to Station no. 30

15 Communication error to Station no. 31

A-10 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Class communication - Record 4 : Communication error to Station no. 32 - 47

Bit Description

00 Communication error to Station no. 32

01 Communication error to Station no. 33

02 Communication error to Station no. 34

03 Communication error to Station no. 35

04 Communication error to Station no. 36

05 Communication error to Station no. 37

06 Communication error to Station no. 38

07 Communication error to Station no. 39

08 Communication error to Station no. 40

09 Communication error to Station no. 41

10 Communication error to Station no. 42

11 Communication error to Station no. 43

12 Communication error to Station no. 44

13 Communication error to Station no. 45

14 Communication error to Station no. 46

15 Communication error to Station no. 47

SA2-545-X.XX/93-00 A-11
UMPM98 Firmware Description Ax 1703

Class communication - Record 5 : Communication error to Station no. 48 - 63

Bit Description

00 Communication error to Station no. 48

01 Communication error to Station no. 49

02 Communication error to Station no. 50

03 Communication error to Station no. 51

04 Communication error to Station no. 52

05 Communication error to Station no. 53

06 Communication error to Station no. 54

07 Communication error to Station no. 55

08 Communication error to Station no. 56

09 Communication error to Station no. 57

10 Communication error to Station no. 58

11 Communication error to Station no. 59

12 Communication error to Station no. 60

13 Communication error to Station no. 61

14 Communication error to Station no. 62

15 Communication error to Station no. 63

A-12 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

Class communication - Record 6 : Communication error to Station no. 64 - 79

Bit Description

00 Communication error to Station no. 64

01 Communication error to Station no. 65

02 Communication error to Station no. 66

03 Communication error to Station no. 67

04 Communication error to Station no. 68

05 Communication error to Station no. 69

06 Communication error to Station no. 70

07 Communication error to Station no. 71

08 Communication error to Station no. 72

09 Communication error to Station no. 73

10 Communication error to Station no. 74

11 Communication error to Station no. 75

12 Communication error to Station no. 76

13 Communication error to Station no. 77

14 Communication error to Station no. 78

15 Communication error to Station no. 79

SA2-545-X.XX/93-00 A-13
UMPM98 Firmware Description Ax 1703

Class communication - Record 7 : Communication error to Station no. 80 - 95

Bit Description

00 Communication error to Station no. 80

01 Communication error to Station no. 81

02 Communication error to Station no. 82

03 Communication error to Station no. 83

04 Communication error to Station no. 84

05 Communication error to Station no. 85

06 Communication error to Station no. 86

07 Communication error to Station no. 87

08 Communication error to Station no. 88

09 Communication error to Station no. 89

10 Communication error to Station no. 90

11 Communication error to Station no. 91

12 Communication error to Station no. 92

13 Communication error to Station no. 93

14 Communication error to Station no. 94

15 Communication error to Station no. 95

Class communication - Record 8 : Communication error to Station no. 96 - 99

Bit Description

00 Communication error to Station no. 96

01 Communication error to Station no. 97

02 Communication error to Station no. 98

03 Communication error to Station no. 99

A.4. Class test

Class test - Record 0 : Test mode of the operating and base systems

Bit Description

00 Memory test disabled

A-14 SA2-545-X.XX/93-00
Ax 1703 Firmware Description UMPM98

B. Appendix: Literature Index

The following documents are recommended to supplement the " UMPM98"


description:

IEC 870-5-1, "Transmission Frame Formats"


st
(1 issue, February 1990)

IEC 870-5-2, "Link Transmission procedures"


st
(1 edition, June 1992)

DIN EN 60870-5-5 "Fernwirkeinrichtungen und Fernwirksysteme" [Telecommunications


equipment and telecommunications systems]
Part 5: Transmission protocol
Main section 5: Fundamental application functions
(IEC 870-5-5: 1995) German version EN 870-5-5: 1995

DIN EN 60870-5-101 "Fernwirkeinrichtungen und Fernwirksysteme" [Telecommunications


equipment and telecommunications systems]
Part 5: Transmission protocol
Main section 101: Application-related standards for basic telecommunications tasks
(IEC 870-5-101: 1995) German version EN 870-5-101: 1995

Norwegian IEC870-5-101 User Conventions, Preliminary Version Revision no.: 1.4

Norwegian IEC870-5-101 User Conventions, Preliminary Version Revision no.: 2.0

SAT Description: "Ax 1703 Data Formats"


Item number: MA0-000-x.xx

SA2-545-X.XX/93-00 B-1
UMPM98 Firmware Description Ax 1703

B-2 SA2-545-X.XX/93-00