(Elec) Generator Excitation System
(Elec) Generator Excitation System
presented by Toshiba
CONTENTS
1. OUTLINE OF GENERATOR CONTROL SYSTEM
2. HARDWARE DESCRIPTION OF AVR CUBICLE
3. HARDWARE DESCRIPTION OF FCB CUBICLE AND
THYRISTOR RECTIFIER CUBICLE
4. HARDWARE DESCRIPTION OF GACP
5. EXCITATION SYSTEM MAINTENANCE
1. Outline of
Generator Control System
OEL
+ OUTPUT V/F
90R OUTPUT
- High 15 DEGREE
value -
- (1+TA1*S) (1+TA3*S)
GENERATOR gate KA1 THYRISTOR GATE
TERMINAL VOLTAGE + CONTROL SIGNAL
(1+TA2*S) (1+TA4*S)
+
135 DEGREE
PSS
OUTPUT
UEL
OUTPUT
15 DEGREE
+ (1+TM1*S)
70R KMA THYRISTOR GATE
(1+TM2*S) CONTROL SIGNAL
-
135 DEGREE
GENERATOR
FIELD CURRENT
OEDT
IF T>=
IF-OED
Field
current OEPT OEP
T>=
OPERATE
IF-OEP
IF OEPT
t= OEDT
IF -OEP t=
IF - OED
OED=1.05
V/FDT
V/F T>=
V/F-V/FD
V/F
t = V/FDT / (V/F-1.05)
V/FD=1.05
Iq
Iq
–a1・Vg+b1・Ip
Ip
–a2・Vg+b2・Ip
y2 b2=y2/x2
–a2
x2
y1 b1=y1/x1
–a1 x1
57R SETTING
GENERATOR
REACTIVE POWER
Iq
y
x
a b=y/x
Ip
0.1 PU
Power TP・S (1+TP1*S) (1+TP3*S) (1+TP5*S) -
KP PSS
(1+TP*S) (1+TP2*S) (1+TP4*S) (1+TP6*S) OUTPUT
+ -0.1 PU
OPTION
2. Hardware Description of
AVR CUBICLE
PWU(A) *A
*B
PWU(B)
DC
AC
EX-TR
THYRISTOR RECTIFIER
FCB CUBICLE 2CT CUBICLE
N-1 PULSE
AMPLIFIER
31E
FCB
GEN Field
flashing
P Discharge
S register
SH
64F
Station battery
Description
“ The information contained herein is confidential and proprietary. Under copyright laws , this manual cannot be reproduced in any form
without the prior written permission of TOSHIBA.”
Copyright 2011, Toshiba Corporation.
P-20
“ The information contained herein is confidential and proprietary. Under copyright laws , this manual cannot be reproduced in any form
without the prior written permission of TOSHIBA.”
Copyright 2011, Toshiba Corporation.
P-21
CH 2
CONNECTOR
CH 3
CONNECTOR
“ The information contained herein is confidential and proprietary. Under copyright laws , this manual cannot be reproduced in any form
without the prior written permission of TOSHIBA.”
Copyright 2011, Toshiba Corporation.
P-22
SW
These LEDs
indicate
each channel
DI status
CONNECTOR
CONNECTOR
SW
These LEDs
indicate
each channel
DO status
CONNECTOR
CONNECTOR
3. Hardware Description of
FCB Cubicle and Thyristor
Rectifier Cubicle
PWU(A) *A
*B
PWU(B
)
DC
AC
EX-TR
Station battery
FIELD CIRCUIT
BREAKER
(41E)
GROUND RELAY
(64F)
41E
FROM BATTERY
64F
31E
Copyright 2011, Toshiba Corporation.
P-28
4. Hardware Description of
GACP
PWU(A) *A
*B
PWU(B
)
DC
AC
EX-TR
THYRISTOR RECTIFIER
2CT
FCB Cubicle CUBICLE
N-1 PULSE
AMPLIFIER
31E
FCB
GEN Field
flashing
P Discharge
S register
SH
64F
Station battery
SC SYSTEM CONTROLLER
PERFORMS THE AUXILIARY CONTROL.
OPS
CH0
Connector
for Device-Net
CH 2
CONNECTOR
CH 3
CONNECTOR
CHA
CONNECTOR
CHB
CONNECTOR
SW
CONNECTOR
SW
These LEDs
indicate
each channel
DO status
CONNECTOR
CONNECTOR
SW
These LEDs
indicate
each channel
DO status
CONNECTOR
CONNECTOR
Description of LEDs
RUN : Lights while microprocessor is operating
ERR : Lights when errors occur
ONLINE 0 : Lights during data transmission/reception on CH 0
ONLINE 1 : Lights during data transmission/reception on CH 1
LINK : Lights when RS-232C is connectedRS-232C is connected
SD : Lights when data transmission of RS-232C
RD : Lights when data reception of RS-232C
5 EXCITATION SYSTEM
MAINTENANCE
5-3TROUBLE SHOOTING(1/2)
Failure item Contents of failure Result Necessary steps
LOSS OF EXC-□ The output of the Excitation The excitation controller in question ・Check the input/output voltage of the failed
POWER controller power unit has is removed from service and is power unit and investigate the cause of failure.
SOURCE dropped. automatically switched over to the ・When the power unit is faulty, replace it.
stand by system.
EXC -□ CPU The CPU card of Excitation The excitation controller in question ・Check the CPU card in question.
FAULT controller has detected is removed from service and is ・ If the CPU card is faulty, replace it.
anomaly. automatically switched over to the
stand by system.
EXC -□ PIO Anomaly is found in PIO The excitation controller in question ・Check the input/output characteristic of the
BNORMAL card. is removed from service and is PIO card in question and investigate the cause of
switched over to the stand by failure.
system. ・When the PIO card is faulty, replace it.
□–VT FUSE VT input voltage fall is The excitation controller in ・Retrieve the transient records of the master
BLOWN detected. question is removed from ・controllers investigate the cause of trouble.
service and is switched over to
the stand by system.
□–OVER Generator over excitation is The excitation controller in question ・Retrieve the transient records of the master
EXCITATION detected. is removed from service and is controllers of both systems and investigate the
switched over to the standby cause of trouble.
system. .
□–PLA FAULT Output pulse from the pulse The excitation controller in question ・Check the input/output characteristic of the
generator is open. is removed from service and is phase control card and the pulse amplifier unit,
switched over to the standby and investigate the cause of trouble.
system. ・If the phase control card or the pulse amplifier is
faulty, replace it.
□:A or B
□:A or B
END