Flusarc Compact CBCC Technical Data Sheet
Flusarc Compact CBCC Technical Data Sheet
1 Flusarc36
Its compact size permits easy and fast installation, and fits easily in prefabricated substations, kiosk
substations or wind towers.
Operating Conditions
According to IEC 60694 / EN 60694
Temperature of Ambient Air
Average Value over 24 Hours 35 °C
Maximum Value 40 °C
Minimum Value "Indoor" - 25 °C
Installation Altitude above Sea Level up to 2000m (T1 & M 1000m)
(Higher Values on Request)
Regulations, Guidelines and Standards
Switchgear IEC 62271-200 / EN 62271-200
Switchgear IEC 60694 / EN 60694
Behaviour in the event of internal faults IEC 60298 / EN 60298
Earthing Switch IEC 62271-102 / EN 62271-102
Disconnector IEC 62271-102 / EN 62271-102
Three-Position Disconnector and Disconnector IEC 62271-102 / EN 62271-102
Multi-Purpose Switch Dissconnector IEC 60265-1 / EN 60265-1
Load Disconnector Fuse Combination IEC 62271-105 / EN 62271-105
Circuit Breaker IEC 62271-100 / EN 62271-100
Current Transformer IEC 61869-2
Voltage Transformer IEC 61869-3
Voltage Detection Systems IEC 61243-5
Protection against accidental contact, foreign objects and IEC 60529 / EN 60529
water
Installation HD 637 S1
Operation of Electrical Equipment EN 50110-1
Electrical Dimensions
Rated Voltage 36 kV
Rated Operating Voltage 33 kV
Rated Power Frequency Withstand Voltage 70 kV
Rated Lightning Impulse Withstand Voltage 170 kV
Rated Short-Time Withstand Current 20 kA
Rated Short-Circuit Duration 1s
Rated Peak Current 50 kA
Rated Short Circuit Breaking Current 20 kA
Rated Current Busbar 630 A
Auxiliary Voltage
Control 220 V AC
Motor 220 V AC
Protection/Control 220 V AC
Remote Control 220 V AC
Degree of Protection
Main Circuits IP 67
Drives IP 3X
Cable Compartment IP 2XC
LV Cabinet IP 2XC
Installation
Arrangement of Switchgear (Rear) Free-Standing
Minimum Clearance to Building Rear Wall 100 mm
Minimum Clearance Front 700 mm
Minimum Clearance to Side Left 100 mm
Minimum Clearance to Side Right 100 mm
Design
Design Indoor Version
Extensibility Not Extensible
IAC Classification AFL
IAC Capacity 20kA/1s
Ambient Temperature(Max.) 40 °C
Ambient Temperature(Min.) -25 °C
OperatingInstruction English
Paint
Paint RAL 9003 - Class C2
1.3.1.1 CB-C-C
Quantity 1
Dimensions
Cubicle Width 1480 mm
Cubicle Height 1720 mm
Cubicle Depth 1087 mm
Properties
Type of Subsection CB-CB-C
Type of Product Compact
Design of Basement With Support Structure
Pressure Gauge Standard
Voltage Indication System VPIS V2
Packaging Wooden Case+Barrier Bag
1.3.1.1.1 CB
Quantity 1
Type of Cubicle Circuit Breaker Panel
Electrical Dimensions
Rated Frequency [Hz] 50
Rated Current Outgoing 630 A
Properties
Protection Relay VIP 400
Mitop With
Current Transformer Type CUA(<200A)
1.3.1.1.2 C
Quantity 2
Type of Cubicle Cable Feeder with Switch
Disconnector
Electrical Dimensions
Rated Frequency [Hz] 50
Rated Current Outgoing 630 A
1.3.1.2 Accessories
1 Handle Switch
1 Spring Charger CB