Secador TZE 650 - 500
Secador TZE 650 - 500
EMS OPTION
LDP OPTION
3V OPTION
FOREWORD
Reading this user manual will fully familiarize you with the Ingersoll-Rand adsorption
dryer. You will be better able to run this equipment in accordance with its intended use.
This manual contains important information for safe, proper and economic dryer
installation, start-up, operation and maintenance. Always keep it within reach where the
adsorption dryer is being used.
It is necessary to follow all instructions as written. Careful reading will avert danger,
avoid unnecessary downtime, and minimize work for yourself and wear on the
equipment.
In addition to carefully reading this technical manual in its entirety, you must understand
your National, State and local rules and regulations regarding safety in the workplace,
their necessary precautions and procedures.
Each person responsible for the set-up, start-up, operation, maintenance or repair of
this adsorption dryer must have first read and understood this user manual – including
all the safety tips.
i
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
ii
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
TABLE OF CONTENTS
1. INTRODUCTION ..................................................................................................................................................1
1.1 GENERAL.............................................................................................................................................................1
1.2 PRODUCT INFORMATION......................................................................................................................................1
1.2.1 Pressure Vessel Regulations........................................................................................................................2
1.2.2 Leak Test......................................................................................................................................................2
1.3 SAFETY INSTRUCTIONS ........................................................................................................................................2
1.3.1 Identification of Signs and Symbols in this Manual.....................................................................................2
1.3.2 General Safety Tips for Assembly, Inspection and Maintenance.................................................................3
1.4 TECHNICAL DATA SHEET ....................................................................................................................................4
1.4.1 Models TZE400 to TZE820..........................................................................................................................4
1.4.2 Models TZE1000 to TZE1800......................................................................................................................5
1.4.3 Models TZE2100 to TZE3500......................................................................................................................6
1.4.4 Dryer Flow Capacities ................................................................................................................................7
1.5 OVERLOADING ....................................................................................................................................................8
1.6 TRANSPORT .........................................................................................................................................................8
1.7 STORAGE .............................................................................................................................................................8
1.8 USE OF A PREFILTER AND AFTERFILTER ..............................................................................................................8
2. INSTALLATION....................................................................................................................................................9
2.1 GENERAL.............................................................................................................................................................9
2.2 MECHANICAL ASSEMBLY ....................................................................................................................................9
2.3 FILTER INSTALLATION .......................................................................................................................................10
2.3.1 Prefilter Installation (Shipped Loose) .......................................................................................................10
2.3.2 Afterfilter Installation (Shipped Loose) .....................................................................................................11
2.3.3 Filter Skid with 3 Valve Bypass (If Dryer Includes 3V Option).................................................................11
2.4 ELECTRICAL CONNECTION ................................................................................................................................11
2.5 EMS CONTROL CONNECTION ...........................................................................................................................12
3. EQUIPMENT OPERATION ..............................................................................................................................13
3.1 GENERAL OPERATING PRINCIPLES ....................................................................................................................13
3.1.1 Dryer Program Steps.................................................................................................................................14
3.2 OPERATOR CONTROLS / LOW-VOLTAGE CONTROL PANEL ...............................................................................16
3.2.1 Dryer Status...............................................................................................................................................18
3.2.2 Alarm Information .....................................................................................................................................19
3.2.3 Dryer Operation Modes.............................................................................................................................20
3.2.4 Heater Sheath Information ........................................................................................................................20
3.2.5 Heater Outlet Information .........................................................................................................................21
3.2.6 Regeneration Outlet Information...............................................................................................................21
3.2.7 Dryer Off, Dryer On, EMS On – 3-Position Switch..................................................................................21
3.2.8 Status Lamps..............................................................................................................................................22
3.2.9 Pressure Gages..........................................................................................................................................22
3.3 INITIAL START-UP .............................................................................................................................................22
3.3.1 Pressurizing Dryer.....................................................................................................................................22
3.3.2 Energizing Dryer Controls ........................................................................................................................23
3.3.3 Pressure Switch Adjustment.......................................................................................................................24
3.3.4 EMS Start Up.............................................................................................................................................24
3.4 SHORT-TERM SHUTDOWN .................................................................................................................................26
3.5 SHUTDOWN IN CASE OF A FAULT OR FOR MAINTENANCE .................................................................................26
3.6 RESTARTING ......................................................................................................................................................26
4. MAINTENANCE..................................................................................................................................................27
4.1 CHECKLIST ........................................................................................................................................................27
iii
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
4.1.1 Daily Check ...............................................................................................................................................27
4.1.2 Weekly Check..............................................................................................................................................27
4.1.3 Quarterly Check (Every Three Months) ....................................................................................................27
4.1.4 Annual Check.............................................................................................................................................28
4.2 CHANGING THE FILTER ELEMENT......................................................................................................................28
4.3 REPLACEMENT OF THE DESICCANT ...................................................................................................................29
5. PARTS LISTINGS ...............................................................................................................................................31
5.1 PARTS LIST FOR TZE400 TO TZE650................................................................................................................31
5.2 PARTS LIST FOR TZE820 TO TZE1225..............................................................................................................32
5.3 PARTS LIST FOR TZE1500 TO TZE2100............................................................................................................33
5.4 PARTS LIST FOR TZE2500 TO TZE3500.............................................................................................................34
6. FAULTS AND TROUBLESHOOTING.............................................................................................................38
6.1 DEWPOINT HAS DETERIORATED .............................................................................................................38
6.2 HIGH HUMIDITY ALARM OR SENSOR FAILURE ...................................................................................39
6.3 PRESSURE DROP TOO HIGH.......................................................................................................................39
6.4 SWITCHING FAILURE ALARM...................................................................................................................39
7. DRAWINGS..........................................................................................................................................................42
iv
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
1. INTRODUCTION
1.1 GENERAL
This adsorption dryer includes the latest technology and safety features. Its use,
however, can endanger life and limb and can lead to considerable damage to the
equipment and other material assets if:
• it is improperly used,
1
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
The pressure vessels are designed and built to meet the American Society of
Mechanical Engineers (ASME) standards. They fulfill the test of the certifying procedure
and carry the ASME symbols U or UM.
RANGE OF APPLICATION
Design Pressure Max: 150 psig
Each Ingersoll-Rand adsorption dryer is subjected to, and passes, a leak test prior to
shipment.
The safety tips contained in this manual, whose disregard could endanger people and
equipment, are indicated by a general danger sign and the additional markings Danger!
or Attention! or Warning!
Danger! / Attention!
Safety sign in accordance with DIN 4844 - W9
Safety tips printed directly on the adsorption dryer must be heeded at all times and must
be kept completely legible.
2
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
The purchaser is to ensure that all assembly, maintenance and inspection work is
carried out by personnel qualified to do it.
The personnel involved in assembly, operation, maintenance and inspection must have
the corresponding qualifications to do this work. Areas of responsibility and supervision
of the personnel must be clearly established by the purchaser. Should the personnel
not possess the necessary knowledge, then they must be instructed. If need be, this
training may be carried out by the manufacturer/supplier at the request of the purchaser.
Further, the purchaser is to ensure that all personnel completely understand and follow
the content of this manual.
Attention!
Danger!
• Review the Material Safety Data Sheet (MSDS) provided with the
desiccant
3
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
4
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
5
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
6
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
The specific size/model of your dryer was selected to meet performance requirements
based on an analysis of air supply and demand capacities. The model selection chart
provided following should confirm that this dryer remains suitable for its intended use.
The table following is based on -40oF PDP, 8-hour cycle, activated alumina and average
inlet air flow for non-LDP-equipped dryers with EMS. Consult our factory for rated air
flows on LDP-equipped dryers.
Rated inlet air flow (scfm) at given pressures (psig)
Design Inlet o
(Based upon 100 F inlet air temperature)
MODEL Air Pressure
(psig) 60 70 80 90 100 110 120 130 140
TZE400 150 220 265 310 355 400 440 480 520 550
TZE500 150 305 355 400 460 500 550 590 645 680
TZE650 150 360 435 505 580 650 705 790 850 905
TZE820 150 460 550 640 735 820 905 990 1070 1150
TZE1000 150 615 715 805 920 1000 1140 1255 1325 1420
TZE1225 150 690 825 955 1100 1225 1360 1490 1610 1735
TZE1500 150 785 960 1150 1275 1500 1600 1730 1875 2010
TZE1800 150 1010 1210 1405 1610 1800 1995 2190 2375 2535
TZE2100 150 1095 1345 1600 1835 2100 2275 2500 2700 2890
TZE2500 150 1480 1735 1985 2270 2500 2820 3100 3355 3585
TZE3000 150 1685 2015 2340 2680 3000 3330 3645 3960 4235
TZE3500 150 1900 2300 2700 3095 3500 3845 4195 4570 4890
Example: To size for an inlet flow of 950 SCFM @ 105 F and 110 psig.
1. Select model that produce at least 950 SCFM at 110 psig. This case would be the TZE1000 which
can dry 1140 SCFM.
2. Multiply pressure corrected flow by the temperature correction factor to obtain the flow of the dryer
corrected for pressure and temperature:
1140 X (0.85) = 969 SCFM
3. Confirm model selection. Model TZE1000 can flow 969 SCFM at the inlet conditions specified;
requirements of 950 SCFM are less: TZE1000 is correct.
7
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
NOTE: Settings for EMS: Standard Dryers: EMS Control -40°F (-40°C)
High Humidity -35°F (-35°C)
LDP Dryers: EMS Control -100°F (-74°C)
High Humidity -95°F (-69°C).
1.5 OVERLOADING
Attention! Protect the adsorption dryer from overloads!
The adsorption dryer can become overloaded if:
• The flow volume of the medium to be dried increases
• The temperature of the air at entry and, correspondingly, its
humidity increases
• The minimum operating pressure decreases
• The prefiltration and separation of impurities are not sufficient or the
filter drain fails
• Introduction of oil into the air stream.
1.6 TRANSPORT
Immediately upon delivery of the adsorption dryer, it must be checked for any damage
that may have occurred during transport. If necessary, the damage must be recorded
on the shipping waybill/receipt. Liability for such damage usually rests with the shipper.
Contact Ingersoll-Rand to arrange for any required service or replacement parts.
Attention!
For transport within your company site, only the skids of the adsorption
dryer may be used. Lifting at any other points on the equipment will void
the warranty and damage the equipment.
1.7 STORAGE
If the adsorption dryer is to be stored for a long period of time, its place of storage must
be dry and free of dust. The ambient temperature cannot go below 33°F (+1°C).
8
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
Both filters are equipped with a differential pressure indicator to ensure a direct display
of the degree of contamination of the filter elements.
2. INSTALLATION
2.1 GENERAL
Ensure that the installation site is free of dust, dirt and litter. The site floor must be level
and strong enough to support the equipment. The site itself must be an heated
environment (minimum 50°F) to ensure proper operation and warranty protection.
Ensure that the Ingersoll-Rand adsorption dryer is carried only by its skid base frame.
The adsorption dryer must be positioned so that the side from which it is to be operated
is easily accessible. The piping is to be connected at a slightly downward slope. Install
isolation valves on the inlet and outlet sides of the adsorption dryer. Also, a bypass
pipe with an additional isolation valve should be mounted onto the adsorption dryer to
allow for an uninterrupted supply of compressed air in case the adsorption dryer
requires maintenance or repair. The bypass assembly is optionally provided (see
paragraph 1.2) or can be customer furnished. If vibrations occur at the installation site,
the adsorption dryer skid frame is to be placed onto vibration dampers.
• Using the mounting holes provided on the skid, anchor the dryer to a solid, level
foundation designed to support the equipment.
• Do not hydrostatically test the pressure vessels. All TZE dryer pressure vessels
and welded piping are hydrostatically tested at one and one-half times the design
pressure after fabrication and before assembly.
• Desiccant for models TZE820 and up is shipped loose and must be installed on
site. Refer now to paragraph 4.3 for instructions on installing the desiccant.
• Due to vibration during shipping some tube fittings may have loosened.
Therefore, inspect all connections and tighten if required.
9
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
• Ensure that the inlet and outlet connections to and from the dryer are made using
the correctly rated fittings and piping to meet the design conditions.
NOTE: System isolation and by-pass valves should be installed. If not supplied
by Ingersoll-Rand as part of the equipment package (i.e., 3V option – see
paragraph 1.2), they should be supplied and installed by others. Ensure
that this bypass facility is installed so that future servicing of the dryer
system off-line may take place.
• Full flow relief valves to protect the system from over-pressure must be
customer-provided in accordance with local regulations.
• The purge exhaust on the TZE650 and smaller dryers is equipped with an
exhaust muffler. If required, the muffler can be removed and purge exhaust can
be connected to a vent header. Follow recommendations for pipe sizing listed
below.
• The purge exhaust connection on the TZE820 and larger dryers must be
connected to a vent header. To ensure satisfactory regeneration of the desiccant
chambers, the purge exhaust piping should be sized as follows to prevent back-
pressure build up.
EXTENDED LENGTH PIPE SIZE REQUIRED
TO 10 FEET SAME SIZE AS DRYER EXHAUST
TO 25 FEET 1 SIZE LARGER THAN DRYER EXHAUST
TO 50 FEET 2 SIZES LARGER THAN DRYER EXHAUST
TO 100 FEET 3 SIZES LARGER THAN DRYER EXHAUST
Caution!
The noise at the outlet of the exhaust header may exceed 100 dBa, and
the flow velocity will be high. Exhaust must be piped to an area where
these flow velocities and noise levels can be safely tolerated.
• Mount prefilter in such a way as to allow clearance for the element installation
and removal.
• The filter must be piped so that the correct flow direction indicated on the filter is
followed.
10
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
• Ensure that all piping and valves are equivalent or larger in size to the dryer inlet
connection.
• Mount afterfilter in such a way as to allow clearance for the element installation
and removal.
• The filter must be piped so that the correct flow direction indicated on the filter is
followed.
• Ensure that all piping and valves are equivalent or larger in size to the dryer inlet
connection.
2.3.3 FILTER SKID WITH 3 VALVE BYPASS (IF DRYER INCLUDES 3V OPTION)
• Filters skid should be located as close to dryer as possible. Use the skid bolt
holes to secure the assembly.
• Ensure that the skid is located such that the 3-valve bypass will bypass the dryer
and filters when in use.
• Check the flow direction of each filter to ensure the prefilter is connected to the
inlet pipe of the dryer and afterfilter is connected to the outlet pipe of the dryer.
• Connect the filter skid piping and dryer skid piping using materials and fabrication
procedures that are suitable for compressed air pressure piping. All flanges are
ANSI B16.5 Class 150 raised face flanges.
• Connect the dryer to a correctly sized power supply. Refer to the dryer
nameplate or the electrical drawing (see section 7) for the supply voltage and
amperage requirement to properly size the electrical service. Only one electrical
connection is required. All internal wiring was done at the factory.
11
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
NOTE: A disconnect switch is not provided with the dryer and must be supplied
by the customer in accordance with the local electrical code.
• Ground the frame of the dryer in accordance with the local electrical code.
• It is recommended that the common alarm relay, located in the dryer control
panel, be connected to the control room or operator station so that an immediate
response to the dryer alarm may be given when required.
• Before energizing the electrical circuit, the electrical heater assembly should be
inspected to determine that no moisture has accumulated in the heater enclosure
or terminations. A 1000V meg-ohmmeter should be used to determine the
phase-to-ground insulation resistance for each phase. A minimum value of 500
kOhms should exist.
• A 10-ft length of 1/8-in stainless steel tubing and necessary compression fittings
are provided.
• Run the tubing back to the hygrometer housing. Cut to necessary length and
connect to the upper connection fitting. Tubing is semi-flexible so care must be
taken when bending to ensure the tubing does not kink.
• If the sample port is installed at a distance longer than the tubing supplied,
contact your Ingersoll-Rand distributor for assistance.
12
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3. EQUIPMENT OPERATION
3.1 GENERAL OPERATING PRINCIPLES
This dryer model has two parallel adsorption chambers filled with desiccant. While the
medium is being dried flowing top-down in one chamber, regeneration takes place from
the bottom up in the other chamber. The changeover from one chamber to the other is
controlled by the Energy Management System that monitors desiccant performance by
measuring the outlet air dew point. It can operate continuously and is fully automatic.
The standard dryer with EMS has a cycle time of eight hours. Half the cycle time is
dedicated to air drying work and the other half to desiccant regeneration, with one
chamber working to dry the air while the other regenerates. The dryer is configured at
the factory.
Wet air enters the working desiccant chamber (it can be either the left or right) at the
inlet switching valves (top) and is dried as it flows downward through the desiccant bed.
Dry air exits the dryer through the outlet check valve.
The regeneration of the off-line tower begins with a heating cycle. After having
depressurized the off-line tower, the purge orifice allows a portion of the dry outlet air to
flow across the regeneration heater. The heated regeneration air then passes upward
through the desiccant bed where it picks up previously adsorbed moisture from the
desiccant and is then evacuated to atmosphere through the purge exhaust valve.
At the completion of the regeneration heating cycle, the cooling cycle begins. The
regeneration heater is de-energized. The purge orifice allows a portion of the dry outlet
air to flow through the off-line tower. It is then evacuated to atmosphere through the
purge exhaust valve. When the cooling cycle is completed, the purge exhaust valve is
closed and the off-line tower is repressurized. Once at line pressure, the dryer is ready
to switch drying from one tower to the other. Dryer models TZE3000 and 3500 have
purge control valves which close once at line pressure and prior to switching from one
tower to the other.
The purge air is controlled by a purge adjusting valve and purge orifice located in the
purge line. Purge pressure is indicated on the purge pressure gauge.
Ingersoll-Rand high-efficiency prefilters and reverse-flow afterfilters are designed to
remove solids, oil and water condensate from compressed air and other neutral,
compressed gases. These filters provide high flows and low differential pressures.
13
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
The prefilter is designed to flow from the inside to the outside. The afterfilter is designed
to flow from the outside to the inside. Solids are filtered out by impact or by the effect of
inertia, whereas oil particles and drops of moisture are filtered out by the effect of
coalescence. The contaminants collect at the bottom of the filter vessel and are drained
automatically or manually.
This automatic dryer is equipped with a PLC which retains last-position data in the event
of a power failure or fast shutdown. The dryer will restart at the last position or can be
manually cycled on the operator interface to reset at step 1.
14
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
DEPRESSURIZE DEPRESSURIZE
STEP 3 RIGHT CHAMBER STEP 10 LEFT CHAMBER
EV-2L & EV-3L (IF L/C <10 psig)
EV-2R & EV-3R (IF R/C <10 psig) ENERGIZE EV-1R & EV-11L
ENERGIZE EV-1L & EV-11R
REPRESSURIZE REPRESSURIZE
STEP 6 RIGHT CHAMBER STEP 13 LEFT CHAMBER
ENERGIZE EV-1L & EV-11R ENERIZE EV-1R & EV-11L
120 SEC PASS & BOTH 120 SEC PASS & BOTH
CHAMBERS ARE ABOVE 60 psig CHAMBERS ARE ABOVE 60 psig
GO TO STEP 8 GO TO STEP 1
15
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
16
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
TEXT
DISPLAY
F1 – DRYER STATUS
F2 – MANUAL STEP AHEAD (MANUAL MODE ONLY)
F3 – DRYER ALARM STATUS
F4 – ALARM RESET
SHIFT – In order to choose one of the next four options, the SHIFT button
must be pressed first. An “s” in the lower right corner indicates the
upper row is now active.
17
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
The F1 key is pressed to display the present status of the dryer. This allows you to see
which step of the program cycle is currently engaged. A message can appear below
the dryer status at any time when in manual mode. A blinking arrow on the right side of
the display will indicate this. To access the messages, press the green arrow on the
right side of the interface.
18
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
The F3 button is pressed to display the status of the dryer alarms. If there is no alarm,
a NO ALARM message will appear. If more than one alarm is active, a flashing arrow
will appear on the right side of the display. To access the messages, press the green
arrow on the right side of the panel. In order to reset non-active alarms, press the F4
key. When all the alarm conditions have been cleared, the NO ALARM message will
appear.
19
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
The F5 button is pressed to display the dryer mode of operation. The actual mode will
be displayed whether it is in automatic or manual mode. To change the actual mode of
the dryer, press F2 when in the dryer mode screen. The actual mode will change from
one to the other each time the F2 button is pressed. If the dryer mode screen is left
unattended for thirty seconds, it will automatically switch to the dryer status screen. In
manual mode, the READY TO STEP AHEAD PRESS F2 TO CONTINUE message
will be shown when the dryer is ready to perform the next step. In order to go to the
next step in manual mode you must not be in the dryer operation mode screen. Failure
to do so will simply change the operating mode of the dryer.
The F6 button accesses heater sheath information. On this screen the actual sheath
temperature in degrees Fahrenheit is displayed and so is the temperature setpoint for
the sheath over-temperature alarm. The setpoint cannot be changed from the panel.
20
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
The F7 button accesses the heater outlet information. On this screen the actual
temperature in degrees Fahrenheit is displayed and so is the temperature setpoint for
the heater outlet over-temperature and heating failure alarm. The setpoint cannot be
changed at the panel.
The F8 button accesses regeneration outlet information. On this screen the actual
temperature in degrees Fahrenheit is displayed and so are the control setpoints for end
of heating and end of cooling. The setpoints cannot be changed at the panel.
This 3-position switch provides for manual selection of dryer basic functions. Ensure
that the switch is set at DRYER OFF before beginning the initial startup procedure.
21
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
A green light announces that there is POWER at the control panel when lit. A red light
announces that there is an ALARM condition when lit. Refer to the operator monitor to
determine the cause.
Three gages are mounted in a row above the low-voltage control panel. The two
outside read the pressure within each chamber (left side for left chamber, right for right)
and the middle gage shows the purge pressure.
• Prefilter, afterfilter and pilot air filter vent valves are closed
22
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
bubble tested for leaks. Any leaks should be repaired and retested prior to placing the
equipment in service. If some gas other than the process air will be used for leak
testing, consult Ingersoll-Rand for its compatibility with system components before
proceeding.
Fully open the inlet isolation valve.
When the system is filled with process air and leak tight, slowly open the system outlet
valve to pressurize the downstream piping. During this procedure, ensure that the dryer
system pressure does not fall beyond 95% of its reading prior to opening the system
outlet valve. This will protect the equipment internal components (i.e., filter elements,
desiccant) from gas velocities above design conditions.
When pressurizing is complete, then fully open the system outlet valve to place the
equipment in service.
Verify that the system inlet pressure and temperature are at the design operating levels
(see paragraph 1.4)
Ensure that the pilot pressure regulator is set between 80 and 100 psig.
23
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
On the TZE dryer there are four pressure switches: PSH-1, PSL-1, PSH-2 and PSL-2.
The PSH pressure switches are set at 30 psig below the operating pressure of the
dryer, and use the normally open contact. When the adjustment is done, the contact
between C and NC should close when increasing to the desired pressure.
The PSL switches are set at 10 psig regardless of the operating pressure and use the
normally closed contact. When the adjustment is done, the contact between C and NC
should close when decreasing to the desired pressure.
To increase the pressure, screw the knob toward the pressure switch diaphragm (see
figure 3). To decrease the pressure, turn away from the pressure switch diaphragm.
ADJUSTMENT
KNOB
FIGURE 3 – PRESSURE SWITCH ADJUSTMENT
3.3.4 EMS START UP
24
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
• Check that the sample line is connected from the dryer outlet to the inlet valve on
the humidity probe sample cell.
• Check that the humidity probe is installed into the sample cell.
• Partially open the discharge valve of the sample cell to vent off a small amount of
sample air. Do not fully open discharge valve.
• Perform a soap bubble test to check for leaks on all parts of the sample line
connections and the humidity sample cell.
• The digital display will now read the dewpoint of the dryer system. It will take a
short period of time for a humidity probe to be purged of humidity.
25
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
• First close all the shutoff valves up- and downstream of dryer
Danger!
Dryer will remain pressurized.
• First switch off the dryer. Make certain dryer is not in heating or cooling mode.
The dryer electrical panel will still have power. The dryer disconnect must be
turned off before opening electrical panel.
• Close all the isolation valves upstream and downstream of the adsorption dryer.
• Depressurize the dryer by using the hand valve mounted at the bottom of the
desiccant chamber.
• Depressurize the filters by opening vent valves at the bottom of each filter vessel.
Danger!
Before any kind of maintenance or repair work is done, the dryer
must be depressurized and disconnected from the power source.
3.6 RESTARTING
• Close the hand valve mounted at the bottom of the afterfilter and at the bottom of
each desiccant chamber
• Slowly open the inlet isolation valve and pressurize the dryer up to the regular
operating pressure by keeping the shutoff valve mounted behind the afterfilter
closed.
26
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
4. MAINTENANCE
4.1 CHECKLIST
These checks are to be carried out by the operator during the routine operations cycle.
• Check dryer operating cycle for proper operation of valve operators, solenoid
valves, dump valves, heaters, pressure switches and temperature controller.
• Inspect pilot air filter element. If element seems clogged, dirty or damaged,
replace it.
27
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
• Disassemble, clean and inspect the inlet switching, purge exhaust and
depressurization valves/actuators. Replace all worn or damaged parts.
• Disassemble, clean and inspect the outlet and purge check valves. Replace all
worn or damaged parts.
• Inspect the desiccant through the chamber fill port. Replace desiccant if
degraded or if oil is present (see paragraph 4.3).
• Replace prefilter, afterfilter and pilot air filter elements at least once a year.
Danger!
Change filter elements only when the housing is fully depressurized
• Separate the lower part of the housing from the upper part
• Install the new filter and the O-ring/gasket, making sure that the filter seats
perfectly
Attention!
Filters may contain pollutants as appropriate to their function.
Dispose of used filters in accordance with your local, state and federal
28
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
regulations.
• Care in installation
• Time in service.
The following clues will suggest that you examine the desiccant and consider its
replacement:
• Remove the drain plug and empty the old desiccant into a container
29
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
Danger!
• Screw the plug back in and fill with new desiccant from above (refer to paragraph
1.4 regarding quantities for each chamber)
• Start up the adsorption dryer in accordance with paragraph 3.3 for initial start-up.
30
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
5. PARTS LISTINGS
5.1 PARTS LIST FOR TZE400 TO TZE650
Description TZE400 TZE500 TZE650
Part # Qty Part # Qty Part # Qty
Consumables
Prefilter ( Element Only ) Refer to filter
nameplate or
Afterfilter ( Element Only ) consult factory
Muffler 38328167 2 38328167 2 38328167 2
Moisture Indicator 38016713 1 38016713 1 38016713 1
Activated Alumina – Pounds 38335253 544 38335253 700 38335253 866
Probe -100 to +20C 38035510 1 38033510 1 38033510 1
LDP Option
Activated Alumina – Pounds 38335253 364 38335253 470 38335253 580
Molecular Sieve 4A – Pounds 38340030 180 38340030 230 38340030 286
Inlet Valve
Inlet Valve Kit/ 38331666 2 38331666 2 38331666 2
Inlet Valve 38331658 2 38331658 2 38331658 2
Solenoid Block 38331120 1 38331120 1 38331120 1
Gasket Consult factory
Outlet Valve
Valve Kit Consult factory
Check Valve 38015855 2 38015855 2 38015855 2
Gasket 38049490 4 38049490 4 38049490 4
Purge
Purge Valve Kit 38331708 2 38331708 2 38331708 2
Purge Valve 38007076 1 38007076 1 38007076 1
Purge Exhaust Valve 38331716 2 38331716 2 38331716 2
3V Bypass Option
Ball Valve 38049540 3 38049540 3 38049540 3
EMS
Digital Panel Meter 38431730 1 38431730 1 38431730 1
Replacement Parts
Pressure Gauge 38006714 3 38006714 3 38006714 3
PLC 38028759 1 38028759 1 38028759 1
Power Supply 38328357 1 38328357 1 38328357 1
Text Display 38018065 1 38018065 1 38018065 1
Thermocouple 38031001 1 38031001 1 38031001 1
Relief Valve 38007084 2 38007084 2 38007084 2
Temperature Indicator 38006698 2 38006698 2 38006698 2
Heater 38028668 1 38028668 1 38028676 1
Gasket Consult factory
Pressure Regulator 38015145 1 38015145 1 38015145 1
Pressure Switch 38006565 5 38006565 5 38006565 5
Light Bulb 38335212 2 38335212 2 38335212 2
31
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
32
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
33
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
34
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
Valve Kit 38437299 1 38437307 1 38437307
Check Valve 38015764 2 38015822 2 38015822 2
Gasket 38329637 4 38329645 4 38329645 4
35
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
36
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
37
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
38
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
Inlet flow exceeding design flow rate Reduce inlet flow as necessary
Depressurize filters and inspect elements.
Pre or after filter element dirty or clogged
Replace if dirty or clogged.
39
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
40
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
41
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
7. DRAWINGS
42
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
43
INGERSOLL-RAND COMPANY, 800-A BEATY STREET, DAVIDSON, NORTH CAROLINA, 28036 – USA
TEL: (704) 896-4000 / FAX: (704) 896-4648
WWW.AIR.IRCO.COM