V-LFP48100 48V100Ah
Vision Technology delivers safe lithium iron phosphate
battery solutions for Telecom application.
Overview Features
The V-LFP 48V100Ah back-up lithium iron phosphate RS485/RS232 communication output for monitoring
battery system is developed for backup of Telecom Built-in BMS with Charging current limitation
equipment. Under normal condition, grid AC power Built-in automatic protection for over-charge,
supply to rectifier module and the Telecom loads and over-discharge and over-temperature conditions
charge battery pack; When the AC power fail, rectifier State of charge and state of health indication
module stop power supply, the battery serves for Built-in battery control for efficient operation
Telecom equipment, to ensure the Telecom equipment Internal cell balancing
runs normally; when the AC power is switched on Compatible with standard Telecom rectifiers
again, power rectifier module for Telecom equipment Maintenance free
recover to while charge the battery pack.
Specifications V-LFP48100
Voltage 48 V
Nominal Capacity (40°C , 0.5C) 100 Ah
Weight (Approximate) 43.0±0.3Kg
Normal energy (40°C , 0.5C) 5120 Wh
Energy Volumetric energy density 153Wh/L
Gravimetric energy density 119Wh/kg
Dimensions (W*D*H) Width*Depth* Height 442mm*425mm*178mm
Impedance (Max, at 1000Hz.) <30mΩ
Standard Discharge Max. constant current 100A
25°C Cut-off voltage 43.2V
Charge Voltage 56V
Standard charge Max. constant current 100A
25℃ Recommended charging
30A(0.3C) for 3.5 hours
current and time
Round trip efficiency(%) >98%
Calendar life 25℃ >10 years
Cycle life (0.2C, 25℃) 80% DOD 4000 cycles
Charging: 0℃~60℃
Recommend operating temperature
Discharging: -20℃~60℃
Recommend storage temperature Recommended range: 0℃~55℃
www.vision-batt.com
BMS Parameters.
Setting value
NO. Type Function Remarks
V-LFP48100 48V100Ah
1 Cell Voltage Protection 3.90V Protection Recover at 3.6V
Charge
2 Total Voltage Protection 60.0V Protection Recover at 54.0V
Voltage
3 Cell Voltage Protection 2.5V Protection Recover at 3.1V
Discharge
4 Total Voltage Protection 43.2V Protection Recover at 48.0V
5 charge Normal ≤100A
6 Normal ≤100A
Delay 30s ,recovery in
7 Current Over Current Protection 1 >100A and <150A
every 60s
Discharge
Delay 3s ,recovery in
Over Current Protection 2 >150A and <200A
every 60s
8 Short Circuit Protection ≥200A Delay 1mS
Charging < 0℃
9 Cell Temp 1 Low temp protection Delay 1~2S
Discharging <- 20℃
Charging >70℃
10 Temp Cell Temp 2 High temp protection Delay 1~2S
Discharging >75℃
11 PCB Range ≥95℃ Recovery at 75℃
Make all cells be balance All cell voltages≤3.65V
Cell VMax.≥3.40V and VMax. - VMin≥40mV,
12 Balance during charging process. and VMax. - VMin≤40mV,
Balance Start balance
Current: 150mA Stop balance
Battery Status.
1. Stop/Transport Mode. In working mode, turn off air switch, battery will go to STOP mode with low self-discharge. In
STOP mode, charging MOS and discharging MOS are turn off, battery cannot charge, discharge or communicate.
2. Working Mode. In STOP mode, connect the battery to SMPS, turn on air switch, battery will go to working mode. In
working mode, BMS will monitor battery voltage, current, and temp and communication is available, charging MOS
and discharging MOS are closed, Battery will operate as the settings.
3. Sleep Mode. After turn on the battery, if the battery voltage below low voltage protection, BMS will go to sleep mode
in 1 minute. In sleep mode, charging MOS and discharging MOS are closed; BMS will check the current in every 1
Min, if there is charging current connecting; battery will turn to working mode.
4. Error Mode. In working mode, if there is: ①.Battery cells, ΔU>2.5V, or ②.Any cell voltage>4.1V or <0.5V, or ③.
Battery temp is <-30℃ or +100℃. BMS will go to error mode, ALM will bright and other LED will shut down, and go
to STOP mode, charging MOS and discharging MOS are turn off. Need to make troubleshoot.
www.vision-batt.com
Performance Curve.
Discharge Performance at 25 ℃ and 45°C Temperature effects on capacity at 0.2C
58 110
54 100
50 90
Capacity (%)
Voltage (V)
46 80
42
70
1C 0.1C
0.5C 0.2C
38 60
0 20 40 60 80 100 120 -30 -20 -10 0 10 20 30 40 50 60 70
Capacity (%) 0.1C 0.2C 0.5C 1.0C Temperature (℃)
Charge and Discharge at 40℃,0.5C Self-discharge at different temperature
110
54 Charge 100
Capacity (%)
50 90
Voltage (V)
80
46 70
60 45℃ 35℃ 25℃
42 55℃
50
Discharge
38 40
30
0 20 40 60 80 100 120 0 2 4 6 8 10 12 14 16 18 20 22 24
Capacity (%) Storage time (months)
Cycles life total capcity with DOD at 25 ℃ 0.8C
110
100
90
Capacity (%)
80 30%
100% 80% 50%
70
60
0 40 80 120 160 200 240 280 320 360 400
Clycle life total KAh
Performance may vary depending on, but not limited to cell usage and application. If cell is used outside specifications, performance will diminish.
All specifications are subject to change without notice. All information provided herein is believed, but not guaranteed, to be current and accurate.
www.vision-batt.com