SPECIFICATIONS: DEDICATED OUTDOOR
AIR SYSTEMS
PEFY-AF
Model Name PEFY-AF1200CFM PEFY-AF1200CFMR
Power Source 208 / 230V, 1 Phase, 60Hz
Cooling Capacity Btu/h *1 112,000 112,000
Heating Capacity Btu/h *1 61,400 61,400
Reheat Capacity Btu/h - 24, 200
Cooling W 660 / 780
Power Consumption
Heating W 660 / 780
Cooling A 3.19 / 3.45
Current
Heating A 3.19 / 3.45
External Finish Galvanized
Height In. 18-9/16
Dimensions Width In. 49-1/4
Depth In. 55-1/8
Net Weight Unit Pounds 287 309
Heat Exchanger Cross Fin (Aluminum Plate Fin and Copper Tube)
Type x quantity Sirocco Fan x 2
Airflow Rate *2 CFM 1,200
Fan External Static 0.40-0.60-0.88 (208V) 0.28-0.48-0.80 (208V)
In. WG
Pressure 0.64-0.80-1.04 (230V) 0.52-0.72-0.96 (230V)
Motor Type Single-phase Induction Motor
Air Filter Field Supply
Liquid (High
Pressure) In. 3/8
Main Coil
(Flare)
Refrigerant Pipe
Dimensions Gas (Low Pressure)
In. 7/8
(Flare)
Liquid (High
Pressure) In. - 7/8
Reheat Coil
(Flare)
Refrigerant Pipe
Dimensions Gas (Low Pressure)
In. - 3/8
(Flare)
Drain Pipe Dimension (O.D.) In. 1-1/4 x 2
Sound Pressure 36-38-41 (208V)
Low-Mid-High dB(A)
Level *3 39-41-43 (230V)
50° F WB to 95° F WB (109° F DB)
Cooling
Operating (10° C WB to 35° C WB [43° C DB])
Temperature Range -4° F WB to +60° F WB
Heating
(-20° C WB to +15.5° C WB)
PUHY-P120TKMU (-BS), PUHY-P120YKMU (-BS) PURY-P120TKMU (-BS), PURY-P120YKMU (-BS)
Connectable Outdoor Unit
PUHY-P120TJMU (-BS), PUHY-P120YJMU (-BS) PURY-P120TJMU (-BS), PURY-P120YJMU (-BS)
Notes: Ventilation Air: Providing sufficient ventilation air is an important part of very building design
*1 Cooling/Heating Capacity indicates the maximum value at operation under the ASHRAE Standard 62 provides the minimum air requirements. Also check local codes.
following conditions:
Cooling | Entering Indoor Unit: 87° F (31° C) D.B. / 80° F (27° C) W.B. Specifications are subject to change without notice.
Cooling | Outdoor Unit: 87° F (31° C) D.B.
Heating | Entering Indoor Unit: 32° F (0° C) D.B. LIMITED WARRANTY | Seven-year compressor and one year parts. Extended
Heating | Outdoor Unit: 32° F (0° C) D.B. / 28° F (-2° C) W.B. warranty of up to 10 years is available. See our website for details on specific
additional application installation coverage
112