TCVN 6161:1996
VIETNAM STANDARDS                                                   TCVN 6161:1996
Fire protection – Market and Supermarket - Design requirements
1   Scope of application
This Standard specifies basic requirements for fire fighting and protection when
designing for new construction, renovation or enlargement of solidly-built markets, semi-
solidly-built markets and trading centers.
2. Extracted standards
TCVN 2622:1978        Fire fighting and protection for houses and buildings – Design
                      requirements
TCVN 6160:1996        Fire fighting and protection – High-rise buildings – Design
                      requirements.
TCVN 5738:1993        Fire alarm system – Technical requirements
TCVN 5760:1993        Fire-fighting system – General requirements for design, installation
                      and utilization
TCVN 5717: 1993       Lightning protection valve
TCVN 4756: 1989       Norms of electric equipment grounding and airing.
3 Terminology and definitions
3.1 Total shop area means the areas of business shops, stores.
3.2 Business area means total shop area and the areas of the rooms engaged in business.
3.3 Market is a place where concentrates several shops, stores, commodities and people
    buying, selling and bartering.
3.4 Trading center means an area where trading, commercial activities and business
    transactions take place, with multiform services.
4   Market classification
4.1 Classification based on building architecture
     a) solidly-built market means fixed market designed and constructed with fire-rates
        of I and II
1
TCVN 6161:1996
       b) semi solidly-built means fixed market where houses,shops and other works
          therein are designed and constructed with fire-rate of III.
       c) temporary market means unstable market where tents, kiosks located therein are
          built with fire-rates of IV, V.
       Note: Fire-rate of houses and construction works are specified in Table 1
                                               Table 1
                                             Fire-resistant limit, min.
    Building     Supporting
                                                                           Floor plate    Floor plate
      fire-     wall column,    Landing,                       Non
                                                  Non                       and other      and other
                lift chamber    stairs and                  supporting
    resistant     wall, fire    other lift
                                               supporting
                                                            inner wall
                                                                              floor          roof
      rate                                     outer wall                  supporting     supporting
                 protection    components                   (partition)
                                                                          components     components
                     wall
        I          150             60             30            30            60             30
       II          120             60             15            15            45             15
       III         120             60             15            15            45            N/A
       IV           30             15             15            15            15            N/A
       V                                           Not stipulated
4.2 Classification based on sizes and number of business owners
       a) Class-1 market is a market where there are more than 500 business-registered
          owners or where having total area of stalls over 2000m2.
       b) Class-2 market is a market having from 300 to 500 business registered owners or
          having a total area of stalls from 1200m2 to 2000m2.
       c) Class-3 market is a market having less than 300 business-registered owners or
          having a total area of stalls less than 1200m2.
5.    General requirements
5.1     When designing fire fighting and protection system for markets and trading centers,
        this Standard and other relevant norms shall be applied.
5.2     When locating markets and trading centers in high-rise building or houses with
        other using purposes, this Standard and TCVN 6160:1996 shall be complied.
5.3     When designing fire-fighting and protection system for newly-built, renovated or
        enlarged markets and trading centers, it shall be based on the master plan of the
        whole area or zone and closely combined to the fire-fighting and protection design
        solution of the next building (access arrangement, fire-fighting water supply
        system, fire alarm communication, etc.)
2
TCVN 6161:1996
5.4     Market and trading center design shall obtain approval for fire-fighting and
        protection design and equipment from the authority.
6     Plan arrangement
6.1 Market and trading center may be in the form of a separate house or several houses
    or located from ground floor to third floor of a multi-floor building with different
    using purposes such as residence, hotel, administration buildings, etc.
      Note:
      1) It is not allowed to locate market and trading center in a two-floor building.
      2) It is not required to change the structure of market and trading center which occupy the
         whole area of one floor of a building with other using purposes having more than 5
         floors.
      3) It is not allowed to locate market and trading center doing the business of flammable,
          explosive and noxious commodities in residential houses/buildings.
6.2 Market and trading center shall be divided onto following sections;
6.2.1    Business section, which includes stall, sitting-floor, stand, commodity delivering
         and receiving place, refreshment place, eating place, discotheque, goods display
         compartment and customer-serving rooms.
6.2.2    Auxiliary section including ordered commodity packaging storehouse, equipment
         repair room, advertisement.(?)
6.2.3    Administration section and entertainment section including directorial board
         office, management board office, correspondence bureau, accounting office,
         canteen, staff office, tradition room, fire protection room, health care room, etc.
6.2.4    Technical section including ventilation chamber, lift chamber, control panels,
         telephone switchboard, water pump station for daily activities, fire-fighting.
6.3 When arranging section, room of market, trading center in a high-rise building,
    following requirements shall be complied:
      a) commodity, flammable materials storehouses shall be located in upper floors, not
         close to other similar storehouse in lower floors.
      b) it is not allowed to design exit, entrance to administration section, auxiliary
         rooms, technical section through business section.
      c) separate passage shall be designed for storehouse and commodity area.
6.4 For market and trading center, it is required to design separate passage and stairs for
    customers and staff/workers.
3
TCVN 6161:1996
        Ways in and out and stairs for staff/workers shall be so designed that when necessary
        they can be used as emergency exits for customers in business section.
6.5 The main staircase from floor 1 to floor 2 of a market and trading center having fire-
    rates of I and II is allowed to be designed open, while other staircases shall be
    designed in stair chamber (?).
        For market and trading center having total area over 3600m2, it is allowed to install
        conveyor-belt stairs (escalator?)
6.6 The market and trading centers where not installing escalator shall only be allowed to
    arrange stalls/stands from floor 2 downwards. If an escalator is designed to be
    installed, it is permitted to situate stalls/stands from floor 3 upwards for one year
    when waiting for the escalator to be installed from the time the market and trading
    center are put into operation.
6.7 Width of passage in business section is stipulated in Table 2
                                               Table 2
                                                                Minimum width of passage
                    Type of passage
                                                           Market/trading     Market/trading
                                                           center in cities   center in towns
1. Main passage in business section:
    -                                                            2.8                2.0
           Market, trading center with total stall area
           up to 90m2
    -                                                            3.6                2.8
           Market, trading center with total stall area
           over 90m2
    -                                                            2.8                2.0
           There is no buffer room from stalls/stands to
           door.
    -                                                            4.2                3.4
           There is buffer room from stalls/stands to
           door.
2. Other passages
    -
           Between two rows of stalls/stands selling             1.8                1.8
           materials, ready-made clothes
    -
           Between two rows of stalls/stands selling             1.2                1.2
           shoes/sandals
    -
           Between two rows of other parallel                    1.2                1.2
           stands/stalls
Note: The distance between 2 main passages in business section shall be 20m.
7   Fire protection requirements
4
TCVN 6161:1996
7.1 Design for market and trading center shall conform to the requirements for fire
    protection safety distance, materials and fire resistant limits of each components
    stated in TCVN 2622:1978
7.2 The number of building floor, maximum area between two fireproof walls of a
    market and trading center shall be subject to fire-rate, as stipulated in Table 3.
                                            Table 3
    Fire-rate of marker        Number of floor allowed, floor            Max. area between 2
    and trading center                                                    fireproof walls, m2
            I,II            Not limited, but building height shall not
                             exceed that stated in TCVN 6160:1996               2200
            III                                 2                               1800
            IV                                  1                               1400
            V                                   1                                500
Note: The maximum area between two fireproof walls is allowed to increase 100% once such
buildings are equipped with automatic fire-fighting system.
7.3 The fireproof walls shall be built from foundation or foundation beam, via other
    structures up to end of market and trading center height if the building roof is made
    of non-flammable materials, and 0.6m higher than the roof if the roof is made of
    inflammable materials. In case the fireproof is located along the building, it is
    required to be 0.6m higher than the roof, whatever materials the roof is made of.
    Fireproof walls shall be made of non-flammable materials with minimum fire
    resistant limit of 150 minutes.
7.4 In market and trading center with fire-rates of III, IV and V, the fire protection
    distance shall have minimum width of 6m and divide the roof wall into separate
    areas.
      The gable wall of fire-protection distance shall arise from the roof at least 0.6m. In
      fire-protection distance, walls shall be of tight types, columns shall have minimum
      fire-resistant limit of 150 minutes. The enclosing structures of fire-protection
      distance shall be made of non-flammable materials with minimum fire resistant limit
      of 60 minutes. Doors shall have minimum fire resistant limit of 45 minutes.
7.5 Warehouse shall be designed separately with dividing walls made of non-flammable
    materials, with minimum fire resistant limit of 45 minutes to maintain flammable
    commodities and materials.
7.6 Door of warehouse, door of commodity storeroom shall be designed in two-leaf type
    with width not less than 1.3m and height not less than 2.3m, made of non-flammable
    materials having minimum fire-resistant limit of 45 minutes.
5
TCVN 6161:1996
7.7 Service pipes (water supply, drainage, sanitary, etc.) of market and trading center
    shall have fire-rates of I, II and be made of non-flammable materials.
7.8 Floor structure of market and trading center shall not be empty. It is not allowed to
    build with asphalt concrete. Floor of toilet and bathroom shall be at least 2cm lower
    than that of next room.
7.9 Design for other fireproof components for market and trading center shall conform to
    the regulations stated in TCVN 2622:1978.
8   Fire escape
8.1 Design for market and trading center shall ensure emergency exit once on fire and
    make favorable conditions for the performance of the fire brigade.
    Number of emergency exits shall not be less than 2 and shall be located in different
    places.
8.2 The distance from the furthest door of any room/compartment (except for bathroom,
    toilet and warehouse) to the closest exit is stated in Table 4.
                                         Table 4
                                        Allowed furthest distance, m
     Fire rate       From room/compartment located       From room/compartment with
                            between two exits               exits to a closed corridor
     I and II                       40                                  25
        III                         30                                  15
        IV                          25                                  12
        V                           20                                  10
8.3 The number of people in business section, according to standard, shall be 1.35m 2 of
    floor are/01 person. Total width of passage, fire escape shall include those of main
    stairs, lift chamber internal stairs and external stairs.
    Total width of exit door, flight of stairs or door, passage on exit way shall be
    calculated based on the number of people in the most crowded floor (excluding floor
    1) and as stipulated as follows:
    a) Floor 2: 1meter/125 people
    b) Floor 3 and above: 1meter/100 people
    Note: Width of exit when calculated can be small but shall not be less than that stated
    in Table 5.
8.4 The emergency staircase from business section to outside shall not go through to the
    basement.
6
TCVN 6161:1996
8.5 The width of specialized flight of stairs shall not be less than 1.15m. Stair gradient
    shall be 1:2.
8.6 Width of passage, corridor, door and stair flight on emergency exit shall be as stated
    in Table 5
                                          Table 5
                                                            Width, m
       Type of passage
                                         Minimum                             Maximum
           Passage                            1                             As calculated
           Corridor                          1.4                            As calculated
             Door                            0.8                                 2.4
        Flight of stairs                     1.05                                2.4
Note:
1) For market and trading center having a total area of store equal of larger than 90m 2, the
   customer’s way in and out shall have a minimum width of 0.9m.
2) The number of stairs of each stair flight shall neither be less than 3 nor more than 18.
8.7 It is not permitted to use corkscrew staircase and fan-shaped staircase as exits.
8.8 It is not allowed to design sliding door, turning door on exit way. Doors on the
    emergency exit shall be made open outside or along the exit with automatic-closing
    device.
    Note: Doors to get out of rooms where permanently accommodate not over 15 people and
    doors out of warehouse having an area less than 200m 2 and toilet doors are allowed to be
    designed to open inside.
8.9 The height of door or passage on emergency exit shall not be less than 2m. For
    basement and wall-foot floor, it shall not be less than 1.9m. For roof cellar, it shall
    not be less than 1.5m.
8.10    Floor height of market and trading center shall not be lower than 3.3m; if the
    business section has a total area of stands/stalls equal to or larger than 300m 2, then
    the height shall not less than 4.2m.
    The height of market and trading center cellar and mezzanine shall not be less than
    2.7m. The minimum height from floor to the lower level of a protruding component
    shall not be less than 2.4m.
8.11    It is allowed to use exterior fire staircase instead of second emergency exit. The
    exterior staircase for escape shall have a minimum width of 0.7m, maximum
    gradient of 60o against horizontal surface with handrails of 0.8m high.
7
TCVN 6161:1996
9       Electrical and lighting equipment
9.1 The electrical equipment to be installed in a market and trading center shall ensure
    that:
    -
           the power system supplied for fire-fighting pump, break-down lighting system
           once on fire shall be separate from other electrical system.
    -
           if allowed, the power supply source should be taken from two separate electrical
           networks (excluding generator source)
9.2 The power source supplied for daily activities, security and emergency case lighting
    system, automatic fire alarm and fire fighting shall be separated for the main control
    panel of the market and trading center. It shall be ensured that once the power supply
    source for daily activities/lighting system is shut down, one of the above-said power
    sources shall not be affected.
9.3 Break-down lighting system once on fire shall be designed and installed in business
    section, on the passage and way in/out of the market and trading center having total
    area of stalls/stands from 90m2 or more.
        Break-down lighting system once on fire shall be installed along the corridor and
        staircase of administration section and other living activity section of the market and
        trading center.
        For market and trading center having total area of stands/stalls over 180m 2, it is
        required to install ‘LỐI RA – EXIT” indicator light on way in and out and
        emergency exit of such system, connected to the break-down lighting network.
9.4 In business section, it should be designed nigh-time security lighting system on the
    passages and emergency exits. Once on fire, these shall be used as breakdown
    lighting system.
9.5 Local lighting system of stalls/shop windows shall be made of florescent lights and
    designed as separate group from the main control panel for living activity power
    network.
9.6 The power supply source for computer, money-counting machine, drier, electrical
    equipment testing power shall be designed as separate group from the main control
    panel for living activity power network.
9.7 The main control panel of the market and trading center, the living activity control
    panel and group control panel shall be installed out of business section. In case it is
    impossible to install in business section, it is permitted to install at the end of
    business section or in the final compartment of business section. The control panel
    shall be installed in a box made of non-flammable materials with symbol placed on
    box door.
8
TCVN 6161:1996
9.8 Lighting control of stands/stalls in business section shall be based on centrally-
    controlled method and through group control panel to the receiver then to the
    stands/stalls.
      Switch, breaker of power system for warehouse, room or other chamber shall be
      located outside, mounted on non-flammable walls or in column-hung boxes.
9.9 No power sockets is allowed to be installed in warehouse or commodity storage.
9.10      When designing lighting system with bulbs, such bulbs shall be designed with
      lampshade. The lampshade shall be made of non-flammable materials. It shall be
      ensured that the distance from the light to the flammable materials shall not be less
      than 0.5m. For florescent lamps, there shall be lamp chute and cover.
9.11      The continuously-consumed power current of insulated conductor and electrical
      cable shall not go beyond the standardized current of conductor.
9.12      The connection or branch of electrical conductor/cable shall ensure the same
      electric-conduct standard as a continuous conductor/electric cable and shall not be
      affected by any external forces.
9.13     It is not allowed to place in the same pipe, box or chute the living activity power
      network, breakdown network and/or automatic fire-fighting alarm system.
9.14       When putting conductor or electric cable through foundation, wall, ceiling and
      floor, they shall be placed in steel pipe or pipes with similar hardness. The internal
      diameter shall be of 1.5 times larger than outer diameter of conductor or electric
      cable.
9.15      The electric conduit shall conform to using purpose and architectural feature of
      market and trading center as well as other fire-fighting and protection technical
      requirements as stipulated in Table 6.
                                          Table 6
    Form and method of placing electric conduit on surfaces
                        and details
                                                                 Conductor, electric cable
                                    made of non-flammable
    made of flammable materials
                                           materials
                                  A. Open-placed conduits
                                                       Conductor with or without
                                                       shield, electric cable with
On clamps, supports          Direct
                                                       shield made of non-flammable
                                                       materials.
                                                       Conductor with shield made of
Direct
                                                       non-flammable materials
                                                       Conductor with or without
In pipe and box made of non- In pipe and box made of shield, electric cable with
flammable materials          non-flammable materials   shield made of non-flammable
                                                       materials.
                            B. Closed placing conduits
9
TCVN 6161:1996
With lining made of non-
                                                                         Conductor with or without
flammable materials, plastered
                                                                         shield, electric cable with
with mortar or tightly protected        Direct
                                                                         shield made of flammable
all sides with non-flammable
                                                                         materials
materials (1)
                                                                         Same as above but with non-
Direct                                  Direct
                                                                         flammable materials
                                        In pipe and box made of
In pipe and box made of non-                                             Conductor without shield,
                                        flammable materials cast
flammable materials, with non-                                           electric cable with shield made
                                        integral, in grooves.., in
flammable materials used as                                              of flammable and non-
                                        tightly-covered       non-
lining, plastered with mortar (2)                                        flammable materials.
                                        flammable materials
Note:
1) The lining made of non-flammable materials with minimum thickness of 10 mm
2) The pipe shall be plastered tightly with mortar or covered with fiber cement, with minimum
   thickness of 10 mm
3) The pipe (box0 cover made of non-flammable materials can be either fiber cement mortar or
   concrete with minimum thickness of 10mm.
9.16     Insulated conductor without shield, placed open and directly on the surfaces of
     pulley, support china, clamp, hung below tensed wire, on frame, in chute, etc. shall
     be made as follows:
     a) when the voltage is higher than 42 V in little dangerous rooms and when the
        voltage is equal to or less than 42V in any room, it shall be placed at a minimum
        height of 2m against floor surface.
     b) when the voltage is higher than 42V in dangerous and very dangerous rooms, it
        shall be placed at a minimum height of 2.5 m against floor surface.
     Note:- When the conductor is going down to light contact, electric plug or other electric
     consuming devices mounted on wall, the above requirements will not necessarily be
     satisfied.
9.17    When electric cable is placed open along the ceiling, wall or other structures of
     construction works, it shall be tightly installed with clamps in distances stated in
     Table 7.
                                                 Table 7
                                                         Allowable max. distance, m
     Conductor-placing                                  Conductor cross section, mm2
         method                                                                                 95 or
                             Up to 2.5            4         6     10     16 to 25   35 to 70
                                                                                                more
1. On pulley, clamp             0.80             0.80     0.80    0.80      1.0        1.2       1.2
2. On insulator mounted on
                                    1             2         2      2        2.5         3          6
   wall and ceiling.
10
TCVN 6161:1996
3. On insulator mounted on
   wall     belonging   to         2        2       2      2        2         2        2
   exterior conductor
4. On insulator placed at
   beam, column or wall
     -
          with copper core         6        12
     -
          with aluminum core                6       6      12
9.18 When placing conductor, electric cable passing pipes in pre-cast building structures
     or integral concrete structures, pipe connection shall be made of thread or welding.
9.19 It is not allowed to place conductor, electric cable without protection shield directly
     in or under wall, ceiling-plastering mortar where it is possible to nail or punch.
9.20 It is not allowed to embed a conductor in a supporting wall (horizontal) when the
     depth of burying ditch is higher than 1/3 of wall thickness. It is not permitted to
     place directly inside or under the mortar types of conductor, since the insulator as
     well as protection shield may get damaged by this mortar layer.
9.21 Conductor, electric cable which go through ceiling made of flammable materials to
     the roof-adjacent wall shall be put through non-flammable insulation pipes.
9.22 Electric wire terminals passing through wall shall be put through non-flammable
     insulation pipes and be structured to prevent water stagnancy or from flowing into
     the building, or it may go through the roof but shall be put in steel pipes and be
     ensured that the distance from the wire-supporting insulator of the inlet to the roof
     shall not be less than 2.75m. For stalls, kiosks of which there is no frequenter on the
     roof, the distance from the turning point to the roof shall not be less than 0.5m.
9.23 The distance between conductors themselves shall not be less than 100mm when
     the wire-fixing distance is up to 6m, and shall not be less than 150mm when the
     wire-fixing is more than 6m.
         The distance between conductor-fixing points shall be as stated in Table 7
         The distance from conductor to wall and such structures shall not be less than
         50mm.
9.24 Market and trading center shall be designed with lightning protection system. The
     lightning protection system shall be designed conforming to current regulations and
     TCVN 5717:1993 and TCVN 4576:1989.
10 Ventilation, smoke exhaustion
10.1 All markets and trading centers shall be designed with ventilation and smoke
     exhaustion systems. The ventilation system shall be made of non-flammable
     materials, hardly flammable or inflammable subject to fire, explosion rates of the
11
TCVN 6161:1996
     area where the system is installed and where the gas discharges from the system.
     The smoke exhaustion system shall be made of non-flammable materials.
10.2 The ventilation system shall be made of non-flammable materials where using or
     storing flammable or explosive gases, liquids or powders.
     For other cases, the ventilation system may be made of hardly flammable materials.
10.3 It is not permitted to connect to the common ventilation system those ventilation
     systems conducting gas which is easy to condense, conducting powder and other
     substances which may create poisonous, flammable or explosive mixtures due to
     mechanical, physical or chemical causes.
10.4 It is required to design ventilation system for the area and compartments selling
     chemicals, textiles or odor substances. When designing, ventilation rate shall be
     ensured to be more than 20m3/hour/person.
10.5 A ventilation system shall be designed separately from that of the building for the
     market and trading center located from floor 1 to floor 3 of an apartment building or
     buildings with other using purposes.
10.6 It is required to install a separate smoke exhaustion system going outside for the
     insulated rooms of market and trading center where containing flammable
     materials.
     The smoke exhaustion system shall be so designed that the pressure-balancing
     surface in the market and trading center shall not be less than 1.5m.
10.7 When designing and installing technical equipment, the requirements stipulated in
     current standards for each equipment category shall be complied with.
11 Fire alarm and fighting
11.1 The market and trading center classified as solid and semi-solid type shall be
     installed with automatic fire alarm system.
     Requirements for automatic fire alarm system shall conform to TCVN 5738:193.
     For the market and trading center out of the above regulation, there shall be fire
     alarm notice or other fire alarm regulations.
11.2 Market and trading center shall be designed with fire-fighting water supply system
     inside and outside of the building. Design of internal and external fire-fighting
     water supply system shall conform to TCVN 2622:1995, and local fire-fighting
     facilities shall also be equipped.
11.3 Around the market and trading center with height of 10m or more, measured from
     the pavement to the lower edge of the water-flowing roof, it is required to locate an
     exterior fixed iron fire-fighting ladder at every 150m interval.
12
TCVN 6161:1996
11.4 For market and trading center with business area over 2000m 2 and more than 500
     business owners or more than 3 floors (not subject to business area), it is required to
     install sprinkler system or drencher system.
      Note: For market and trading center with business area under 300m 2 and 75 business
      owners, it is not required to design interior water fire-fighting system.
11.5 When designing and constructing automatic water fire-fighting system for a market
     and trading center, it is required to conform to the regulations stated in TCVN
     5760:1993 and other technical documents issued by the authorities.
11.6 The exterior fire-fighting water output taken from the fire-fighting hydrant and
     calculated for a fire occurred in a market and trading center building is stipulated in
     Table 8.
                                           Table 8
                                    Water output calculated for a fire, l/s
 Fire resistant           Total area of stalls/stands, m2 (number of business owners)
      rate
                                                                                 More than
                    540 (136)     900 (225)        1800 (450)     2000 (500)
                                                                                 4000 (1000)
     I and II           5              5              10              10             15
       III              5             10              15              20             25
     IV and V          10             15              20              30             35
9.7 The number of fires occurred at the same time, calculated for water supply system of
    a market and trading center building with total area of stands/stalls equal to or less
    than 8000m2 or under 2000 business owners shall be 1 (fire). If total area of
    stalls/stands is more than 8000m2 or there are over 2000 business owners, it shall be
    2 (fires).
                                    _______________