CMP CMP PRODUCTS CABLE GLAND CATALOGUE
CMP INDUSTRIAL CABLE GLAND PRODUCTS
E1X TECHNICAL DATA
Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444
E1X Double Seal Industrial Cable Gland Mechanical Classifications* Impact = Level 8, Retention = Class D
For Braid & Steel Tape Armoured Cables Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
Electrical Classifications* Category B (Category A when used with braid, tape or pliable wire armour cables)
• Metal-to-metal armour clamping
GOST R Certificate No. POCC GB. 05.H00187
• Direct & remote installation
• Permanently crimped, low impedance earth termination GOST K Certificate No. KZ 7500361.01.01.25266
• Secure against self-loosening
RoK Permit For Use Number 19-02-UL-1957
• Displacement type inner seal
• Controlled outer ‘load retention’ seal Marine Approvals LRS: 01/00171 (E1), ABS: 01-LD234401/2-PDA
• Unique OSTG prevents overtightening
Ingress Protection Rating IP66 as standard (IP67, IP68 available upon request)**
• Designed to prevent Coldflow
• Deluge protection option Cable Gland Material Brass, Electroless Nickel Plated Brass, Aluminium
• -60˚C to +130˚C
Seal Material CMP Thermoset Rubber
• EMC tested
Wire Braid Armour, Screened Flexible (EMC) Wire Braid (e.g. CY / SY), Pliable Wire
Cable Type
Armour (PWA), Steel Tape Armour (STA), Aluminium Strip Armour (e.g. ASA)
Armour Clamping Detachable Armour Cone & AnyWay Universal Clamping Ring
Sealing Technique CMP Inner Displacement Seal & Unique CMP ‘LRS’ TM Outer Load Retention Seal
† Grooved Cone (X) is predominantly used for Wire Braid (e.g. GSWB, TCWB), Steel Tape Armour
(STA, DSTA) and Aluminium Strip Armour (ASA) but is also suitable for Single Wire Armour (SWA),
Aluminium Wire Armour (AWA) and Pliable Wire Armour (PWA) if the range is outside that of the Sealing Area(s) Cable Inner Bedding & Outer Cable Sheath
Stepped Cone (W).
Note: Grooved Cone (X) dimensions shown in the Cable Gland Selection Table below are for a Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444
double wire strand of braid armour cables. Tapes can also be doubled over. For cables that have only a
single layer of armour such as SWA the clamping range should be used as shown in the table below. Note : ** Refer to page 7 or [Link] for further information on Ingress Protection Ratings
If Tape Armour is to be used please contact CMP for advice.
Cable Gland Selection Table
Refer to illustration at the top of the page
Available Entry Threads “C” (Alternate Metric Armour Range † Across Across Combined Ordering
Thread Lengths Available) Cable Bedding Overall Cable
Grooved Cone Flats Corners Reference
Diameter “A” Diameter “B” Cable
Standard Option (X) “D” “D” (*Brass Metric)
Cable Gland Protrusion Gland
Thread Shroud
Size Thread Length “F” Weight
Length Ordering (Kgs)
Metric NPT Length NPT Min Max Min Max Min Max Max Max Size Type
(Metric) Suffix
(NPT) “E”
“E”
20s16 M20 10.0 1/2” 19.9 3/4” 3.1 8.6 6.1 13.1 0.3 1.0 24.0 26.4 72.5 20S16 E1X 1RA PVC04 0.163
20S M20 10.0 1/2” 19.9 3/4” 6.1 11.6 9.5 15.9 0.3 1.0 24.0 26.4 70.0 20S E1X 1RA PVC04 0.150
20 M20 10.0 1/2” 19.9 3/4” 6.5 13.9 12.5 20.9 0.4 1.0 30.5 33.6 73.0 20 E1X 1RA PVC06 0.210
25S M25 10.0 3/4” 20.2 1” 11.1 19.9 14.0 22.0 0.4 1.2 37.5 41.3 89.0 25S E1X 1RA PVC09 0.330
25 M25 10.0 3/4” 20.2 1” 11.1 19.9 18.2 26.2 0.4 1.2 37.5 41.3 89.0 25 E1X 1RA PVC09 0.330
32 M32 10.0 1” 25.0 1 1/4” 17.0 26.2 23.7 33.9 0.4 1.2 46.0 50.6 86.0 32 E1X 1RA PVC11 0.430
40 M40 15.0 1 1/4” 25.6 1 1/2” 22.0 32.1 27.9 40.4 0.4 1.6 55.0 60.5 90.0 40 E1X 1RA PVC15 0.620
50S M50 15.0 1 1/2” 26.1 2” 29.5 38.1 35.2 46.7 0.4 1.6 60.0 66.0 91.0 50S E1X 1RA PVC18 0.750
50 M50 15.0 2” 26.9 2 1/2” 35.6 44.0 40.4 53.0 0.6 1.6 70.1 77.1 95.0 50 E1X 1RA PVC21 0.950
63S M63 15.0 2” 26.9 2 1/2” 40.1 49.9 45.6 59.4 0.6 1.6 75.0 82.5 102.0 63S E1X 1RA PVC23 1.340
63 M63 15.0 2 1/2” 39.9 3” 47.2 55.9 54.6 65.8 0.6 1.6 80.0 88.0 104.0 63 E1X 1RA PVC25 1.340
75S M75 15.0 2 1/2” 39.9 3” 52.8 61.9 59.0 72.0 0.6 1.6 90.0 99.0 115.0 75S E1X 1RA PVC28 2.110
75 M75 15.0 3” 41.5 3 1/2” 59.1 67.9 66.7 78.4 0.6 1.6 100.0 110.0 117.0 75 E1X 1RA PVC30 2.420
90 M90 24.0 3 1/2” 42.8 4” 66.6 78.6 76.2 90.3 0.8 1.6 114.3 125.4 147.0 90 E1X 1RA PVC32 4.210
100 M100 24.0 4” 44.0 5” 76.0 90.9 86.1 101.4 0.8 1.6 123.0 135.3 140.0 100 E1X 1RA LSF33 4.450
115 M115 24.0 4” 44.0 5” 86.0 97.9 101.5 110.2 0.8 1.6 133.4 146.7 162.0 115 E1X 1RA LSF34 6.190
130 M130 24.0 5” 46.8 6” 97.0 114.9 110.2 123.2 0.8 1.6 152.4 160.6 174.0 130 E1X 1RA LSF35 8.340
*Note : For material options please add the following suffix to change the Ordering Reference ; Brass (no suffix required), Nickel Plated Brass “5”, Copper Free Aluminium “1”
For NPT options add the following digits to the material suffix; 1/2” = 31; 3/4” = 32; 1” = 33; 1 1/4” = 34; 1 1/2” = 35; 2” = 36; 2 1/2” = 37; 3” = 38; 3 1/2” = 39; 4” = 310 (Brass requires prefix ‘0’)
Examples: 32E1X1RA534 = Nickel Plated Brass 1-1/4” NPT, 50SE1X1RA035 = Brass 1-1/2” NPT, 20E1X1RA5 = Nickel Plated Brass M20
Dimensions are displayed in millimetres unless otherwise stated
TDS533 ISSUE6 08/15 [Link]