Machine Lab Manuals Final Modified On 12-2-2019
Machine Lab Manuals Final Modified On 12-2-2019
S.No. Experiment
To conduct the open circuit & short circuit tests of Transformer & to calculate efficiency
4
without loading the Transformer
Apparatus:
Discussion:
Voltage ratio test of a transformer is performed to find the turn ratio of the transformer. Turns ratio of a
transformer tells us that whether the transformer is step-up or step-down.
Polarity test of a transformer is performed to determine the polarity of the two windings of transformer so that
we can connect the two windings in series or in parallel and also two transformers in series or in parallel. The
correct polarity must be determined first in order to connect the transformers/windings in proper arrangement
either in series or in parallel.
Procedure:
Connections are made as shown in the diagram. The primary side is connected to single phase variable AC
voltage supply and voltmeter (Vp) in parallel. The secondary side is also connected to voltmeter (Vs) in
parallel. Note down the readings in table 2.1 as indicated by the voltmeters Vp and Vs.
Circuit Diagram:
Supply is switched on with the minimum 0 position. Vary the supply voltage and note down the readings in the
table.
Sr. E1 E2 N2/N1
No (V) (V)
1
2
3
4
5
Table 2.1 Results of turn’s ratio test of Transformer
Procedure:
Connect the H.V winding to an AC source. The rated voltage is applied to the primary and primary terminals
are marked as A1 and A2. The secondary winding terminals are marked as B1 and B2. A wire is connected
across A2 and B2 and a voltmeter connected across A1 and B1.
Circuit Diagram:
(a) (b)
If it measures the difference of V1 and V2 it mean A1 and B1 have same polarity as in figure 2.2 (a). The dots are
on same side. If voltmeter measure the addition of V1 and V2 it means A1 and B1 are of opposite polarity as in
figure 2.2 (b) the dots are on opposite side. Place 3 voltmeters; one at primary side and other at secondary side
and the third as connected in figure 2.2
Take the first reading and write down the value indicated by the voltmeters in table 2.2(a).
Sr. No EP ES E3
1
2
Table 2.2 Results of Polarity test of Transformer
_____________________________________________________________________________________
_____________________________________________________________________________________
Repeat the process by connecting the circuit as shown in figure 2.2 (b) and record your results in table 2.2
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
A T/F having primary voltage of 50V and primary current of 2A, if the secondary current is 4A what will be its
secondary voltage?
_______________________________________________________________________________________
_______________________________________________________________________________________
_______________________________________________________________________________________
_______________________________________________________________________________________
_______________________________________________________________________________________
Experiment No 3
Objective:
To determine the voltage regulation and efficiency of a single phase transformer on
a) Resistive Load
b) Inductive Load
c) Capacitive Load
Apparatus:
Discussion:
The voltage regulation of the transformer is the percentage change in the output voltage from no-load to full-
load. And since power factor is a determining factor in the secondary voltage, power factor influences voltage
regulation, is defined by equation.
Procedure:
• set up the transformer loading circuit shown in Figure 3.1. Make sure that all switches on the
Resistive, Capacitive, and Inductive Load modules are open, and connect meter inputs E1, E2,
I1, and I2 as shown in the figure. Different load values will be used to examine how the
secondary (load) voltage changes as transformer loading changes.
Figure 3.1 voltage regulation of Transformer circuit with resistive load
• Turn on the power supply and vary the voltage upto the rated value of transformer.
• Adjust the switches on the Resistive Load module to successively obtain the resistance values given in
Table 3.1. For each resistance value, record the measured values. When all values have been recorded,
turn the voltage control knob fully counterclockwise, and turn off the Power Supply.
• Repeat the process after connecting Inductive load at secondary of the transformer.
What is the transformer regulation if the no-load and full-load voltages are 100v and 95v respectively?
The secondary voltage can rise above its rated value when the load is _____________
The voltage measured across the secondary winding of a transformer with no load connected is 150 V. This
voltage drops to 147 V when the secondary current is equal to the nominal full-load current. What is the
transformer regulation?
_______________________________________________________________________________________
_______________________________________________________________________________________
_______________________________________________________________________________________
_______________________________________________________________________________________
_______________________________________________________________________________________
_______________________________________________________________________________________
_______________________________________________________________________________________
_______________________________________________________________________________________
_______________________________________________________________________________________
Experiment No 4
• To study the open circuit test and short circuit test of Transformer
• To calculate efficiency of Transformer without loading.
Apparatus:
Discussion:
In any electrical machine, 'loss' can be defined as the difference between input power and output power. An electrical
transformer is an static device, hence mechanical losses (like windage or friction losses) are absent in it. A
transformer only consists of electrical losses (iron losses and copper losses). Transformer losses are similar to losses
in a DC machine, except that transformers do not have mechanical losses.
These two transformer tests are performed to find the parameters of equivalent circuit of transformer and losses of t h e
transformer. Open circuit test and short circuit test on transformer are very economical and convenient because they
are performed without actually loading of the transformer. Open circuit test or no load test on a transformer is
performed to determine 'no load loss (core loss)' and 'no load current I0'. The circuit diagram for open circuit test is
shown in the figure below.
Usually high voltage (HV) winding is kept open and the low voltage (LV) winding is connected to its normal supply.
A wattmeter (W), ammeter (A) and voltmeter (V) are connected to the LV winding as shown in the figure. Now,
applied voltage is slowly increased from zero to normal rated value of the LV side with the help of a variac. When
the applied voltage reaches to the rated value of the LV winding, readings from all the three instruments are taken.
The ammeter reading gives the no load current I o. As Io itself is very small, the voltage drops due to this current can
be neglected. The input power is indicated by the wattmeter (W). But, as the other side of transformer is open
circuited, there is no output power. Hence, this input power only consists of core losses and copper losses. But as
described above, short circuit current is so small that these copper losses can be neglected. Hence, now the input
power is almost equal to the core losses. Thus, the wattmeter reading gives the core losses of the transformer.
The two components of no load current can be given as,
The connection diagram for short circuit test or impedance test on transformer is as shown in the figure below. The
LV side of transformer is short circuited and wattmeter (W), voltmere (V) and ammeter (A) are connected on the HV
side of the transformer. Voltage is applied to the HV side and increased from the zero until the ammeter reading
equals the rated current. All the readings are taken at this rated current.
The ammeter reading gives primary equivalent of full load current. (I SC). The voltage applied for full load current is
very small as compared to rated voltage. Hence, core loss due to small applied voltage can be neglected. Thus, the
wattmeter reading can be taken as copper loss in the transformer.
Therefore,
W = Isc2Req
(Where Req is the equivalent resistance of transformer)
Therefore, equivalent reactance of transformer can be calculated from the formula
Zeq2 = Req2 + Xeq2.
Hence, it is seen that the short circuit test gives copper losses of transformer and approximate equivalent resistance
and reactance of the transformer.
1. Core Losses:
Core losses occur in the core of transformer it depends upon the type of material which is used for core. There
are two types of core loss in transformer
a) Eddy Current Losses:
In transformer, AC current is supplied to the primary winding which sets up alternating magnetizing flux. When
this flux links with secondary winding, it produces induced emf in it. But some part of this flux also gets linked
with other conducting parts like steel core or iron body or the transformer,
which will result in induced emf in those parts, causing small circulating current in them. This current is called
as eddy current. Due to these eddy currents, some energy will be dissipated in the form of heat.
b) Hysteresis Losses:
Hysteresis loss is due to reversal of magnetization in the transformer core. This loss d epends upon the
volume and grade of the iron, frequency of magnetic reversals and value of flux density.
2. Copper Losses:
Copper loss is due to Ohmic resistance of the transformer windings. Copper loss for the primary winding is
I12R1 and for secondary winding is I22R2. Where, I1 and I2 are current in primary and secondary winding
respectively, R1 and R2 are the resistances of primary and secondary winding respectively. It is clear that Cu
loss is proportional to square of the current, and current depends on the load. Hence copper loss in transformer
varies with the load.
Procedure:
• Make connections for open circuit test as shown in figure 4.1.
• Make connections for short circuit test as shown in figure 4.2.
• For open circuit test load the transformer gradually from 0V to maximum supply voltage.
• For short circuit test load the transformer gradually and carefully until the ammeter reading indicates the
rated value of current of transformer.
ATTENTION!!!!!!!
NOTE: Do not load the transformer above its rated current, the windings will be burnt
Circuit Diagram:
Figure 4.1 Open Circuit Test
Sr. No E0 I0 P
(V) (A) (W)
1
Table 4.2 Short circuit test results
Sr. Load Core Copper losses = Total losses = Output Input Power = Efficiency
No losses (fraction of load) 2 Copper+ Core Power Output+ total ()
(W) * Copper losses losses (W) losses (%)
(W) (W) (W)
1 ¼ F.L
2 ½ F.L
3 ¾ F.L
4 F.L
5 5/4 F.L
Which side of the Transformer is short circuited in case of short circuit test of Transformer? _______________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
How can we reduce Hysteresis losses and eddy current losses in a transformer?
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
Experiment No 5
Objective:
• To observe the phase shifts between three phases
• To observe the phase shift between the voltages of transformer connected in
a) Y to Y connection
b) Delta to Delta connection
c) Y to delta connection
d) Delta to Y connection
Apparatus:
Introduction:
Many three-phase transformer configurations are possible when connecting the primary and secondary
windings of a three-phase transformer bank. Each configuration presents different characteristics. When
connecting a three-phase transformer bank in a circuit, it is therefore important to determine which
characteristics are advantageous to the circuit, and to choose the appropriate three-phase transformer
configuration accordingly. The four most common three-phase transformer configurations are wye-wye,
delta-delta, wye-delta, and delta-wye configurations.
Voltage, current, and phase relationships of the four common three-phase transformer
configurations
The most determining characteristics of each three-phase transformer configuration mentioned in the
previous section (i.e., the wye-wye, delta-delta, wye-delta, and delta-wye configurations) are their
respective voltage, current, and phase relationships between the primary windings and the secondary
windings. The following three sections discuss these relationships for each threephase transformer
configuration. Note that, as wye-wye and delta-delta configurations have similar voltage, current, and
phase relationships, both configurations are covered in the same section. Also note that, in the following
sections, the turns ratio of each transformer in the three-phase transformer bank is assumed to be equal
to 1:1. This allows observation of the effects each configuration has on the voltage, current, and phase
relationships of the three phase transformer bank, independently of the turns ratio.
and currents at the primary (neglecting transformer losses). Also, the line voltage sine waves at the
secondary are in phase with the line voltage sine waves at the primary. The same is true for the line
current sine waves at the secondary with respect to the line current sine waves at the primary.
Wye-delta configuration
When a three-phase transformer bank is connected in a wye-delta configuration, the values and phases
of the line voltages and currents at the secondary are different from those at the primary. Thus, in a wye -
delta configuration, the value of the line voltages at the secondary is equal to that of the line voltages at
the primary divided by√3. Conversely, the value of the line currents at the secondary is equal to that of
the line currents at the primary multiplied by √3. Furthermore, the line voltage sine waves at the
secondary lag behind those at the primary by 30°. The same is true for the line current sine waves at the
secondary with respect to the line current sine waves at the primary.
Delta-wye configuration
When a three-phase transformer bank is connected in a delta-wye configuration, the values and phases
of the line voltages and currents at the secondary are different from those at the primary. Thus, in a
delta-wye configuration, the value of the line voltages at the secondary is equal to that of the line
voltages at the primary multiplied by √3. Conversely, the value of the line currents at the secondary is
equal to that of the line currents at the primary divided by √3. Furthermore, the line voltage sine waves
at the secondary lead those at the primary by 30°. The same is true for the line current sine waves at the
secondary with respect to the line current sine waves at the primary.
1. Three-phase transformer banks allow the voltages in the three-phase ac power circuit to be s
tepped-up (i.e., to be increased) or stepped down (i.e., to be decreased).
2. Three-phase transformer banks provide electrical isolation between the primary windings and the
secondary windings.
Circuit Diagram:
Figure 5.1 Four different connections of 3-phase Transformers
Procedure:
• Connect the transformer’s primary and secondary windings according to the circuit diagram.
• Connect the voltmeters and connect the ac supply and set it to 50 volts.
• Open the phase analyzer in the Lab volt software and record the results.
Y to Y Connections
Y to Delta Connections
Delta to Y Connections
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
Q: Why there is phase shift from primary to secondary in star-delta and delta star
configurations?
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
Experiment No. 6
Objective:
Apparatus:
• DC Motor/Generator Module
• Prime Mover/Dynamometer Module
• DC Variable Supply
• Lab Volt Data Acquisition Interfacing module
• Connecting Leads
Discussion:
A motor is an electrical machine which converts electrical energy into mechanical energy. The principle of
working of a DC motor is that "whenever a current carrying conductor is placed in a magnetic field, it
experiences a mechanical force"
The shunt wound dc motor falls under the category of self excited dc motors, where the field windings are
shunted to, or are connected in parallel to the armature winding of the motor, as its name is suggestive of. And
for this reason both the armature winding and the field winding are exposed to the same supply voltage, though
there are separate branches for the flow of armature current and the field current.
Therefore the curve drawn between torque Vs armature current is a straight line transitory through the origin.
The shaft torque(Tsh) is a smaller amount than armature torque. From this curve it is proved that to start a heavy
load very large current is requisite. Hence the shunt DC motor should not be started at full load.
At normal condition the back E.M.F Eb and Flux Φ both are constant in a DC Shunt motor. Hence the armature
current differs and the speed of a DC Shunt motor will continue.Whenever the shunt motor load is increased
Eb=V-Ia Ra and flux reduces as a result drop in the armature resistance and armature reaction. On the other hand,
back e.m.f reduces marginally more than that the speed of the shunt motor decreases to some extent with load.
Speed Vs Armature Torque:
This curve is drawn between the speed of the motor and armature current with various amps. From the curve it
is understood that the speed reduces when the load torque increases.
With the above three characteristic it is clearly understood that when the shunt motor runs from no load to full
load there is slight change in speed. Thus, it is essentially a constant speed motor. Since the armature torque is
directly proportional to the armature current, the starting torque is not high.
Procedure:
Circuit Diagram:
• First of all set the prime mover/Dynamometer module mode on Dynamometer.
• Set the torque at 0 Nm. For this we have set the torque knob at 0 position (anticlockwise) on
Dynamometer.
• Set DC 220V at supply and adjust the field resistance rheostat at the position where motor’s rpm are
1500.
Now apply the torque at the steps of 0.1 increment and record the armature current, speed and value of torque in
table 5.1.
Observation:
Sr. T IA N
No
N.m (A) rpm
1 0
2 0.1
3 0.2
4 0.3
5 0.4
6 0.5
7 0.6
8 0.7
9 0.8
10 0.9
11 1
12 1.1
Table 5.1
Graphs:
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
Experiment No. 7
Objective:
Apparatus:
• DC Motor/Generator Module
• Dynamometer
• DC Variable Supply
• Labvolt Data Acquisition interface software
• Connecting Leads
Introduction:
The series motor is a motor in which the field electromagnet is a series winding connected in series with the
armature as shown in Figure 7-1. The strength of the field electromagnet, therefore, varies as the armature
current varies. Figure 7-1 shows the speed versus torque characteristic of a series motor when the armature
voltage is fixed. This characteristic shows that the speed decreases none linearly as the torque increases, i.e., as
the armature current increases.
We know that torque is directly proportional to the product of armature current and field flux, Ta ∝ ɸ.Ia. In DC
series motors, field winding is connected in series with the armature, i.e. Ia = If. Therefore, before magnetic
saturation of the field, flux ɸ is directly proportional to Ia. Hence, before magnetic saturation Ta α Ia2.
Therefore, the Ta-Ia curve is parabola for smaller values of Ia. After magnetic saturation of the field poles, flux
ɸ is independent of armature current Ia. Therefore, the torque varies proportionally to Ia only, T ∝ Ia.
Therefore, after magnetic saturation, Ta-Ia curve becomes a straight line.
The shaft torque (Tsh) is less than armature torque (Ta) due to stray losses. Hence, the curve Tsh vs Ia lies
slightly lower.
In DC series motors, (prior to magnetic saturation) torque increases as the square of armature current, these
motors are used where high starting torque is required.
For small load current (and hence for small armature current) change in back emf Eb is small and it may be
neglected. Hence, for small currents speed is inversely proportional to ɸ. As we know, flux is direc tly
proportional to Ia, speed is inversely proportional to Ia. Therefore, when armature current is very small the
speed becomes dangerously high. That is why a series motor should never be started without some mechanical
load. But, at heavy loads, armature current Ia is large. And hence, speed is low which results in decreased back
emf Eb. Due to decreased Eb, more armature current is allowed.
The series motor provides a strong starting torque and a wide range of operating speeds when it is
supplied by a fixed-voltage dc source. However, the speed, torque, and armature current depend on th e
mechanical load applied to the motor. Also, the series motor has non -linear operating characteristics as
suggested by the speed versus torque relationship in Figure 7 -1. As a result, it is difficult to operate a
series motor at a constant speed when the mechanical load fluctuates. Furthermore, the armature current
must be limited to prevent damage to the motor when it is starting (when power is applied to the motor).
Finally, a series motor must never run without mechanical load because the speed increase s to a very-
high value which can damage the motor (motor runaway).
Today, series motors can operate with fixed-voltage power sources, for example, automobile starting
motors; or with variable-voltage power sources, for example, traction systems
Circuit Diagram
Procedure:
Observation:
Sr. T IA N
No
N.m (A) rpm
1 0.3
2 0.4
3 0.5
4 0.6
5 0.7
6 0.8
7 0.9
8 1
9 1.1
Graphs:
Apparatus:
Introduction:
A dc generator is an electrical machine which converts mechanical energy into direct current electricity. This
energy conversion is based on the principle of production of dynamically induced emf. According to Faraday’s
laws of electromagnetic induction, whenever a conductor is placed in a varying magnetic field (OR a conductor
is moved in a magnetic field), an emf (electromotive force) gets induced in the conductor. The magnitude of
induced emf can be calculated from the emf equation of dc generator. If the conductor is provided with the
closed path, the induced current will circulate within the path. In a DC generator, field coils produce
an electromagnetic field and the armature conductors are rotated into the field. Thus, an electromagnetically
induced emf is generated in the armature conductors.
Although dc generators are rarely used today, it is important to know their operation because this helps
understanding how a separately-excited dc motor can be used as an electric brake in modern dc motor drives.
You saw earlier in this unit that a dc motor can be considered as a linear voltage-to-speed converter. This linear
conversion process is reversible, meaning that when a fixed speed is imposed on the motor by an external
driving force, the motor produces an output voltage E0, and thus, operates as a linear speed-to-voltage
converter, i.e., a dc generator. Figure 8-1 shows a DC Generator.
A shunt generator is a type of direct current electric generator in which field winding and armature winding
are connected in parallel, and in which the armature supplies both the load current and the field current.
Open Circuit Characteristics of Shunt Generator:
This curve is drawn between shunt field current(Ish) and the no load voltage (E0). For a given excitation current
or field current, the e.m.f generated at no load E0 varies in proportionally with the rotational speed of the
armature. Here in the Graph 1 the magnetic characteristic curve for various speeds are drawn. Due to residual
magnetism the curves start from a point slightly up from the origin. The external load resistance of the machine
needs to be maintained greater than its critical value otherwise the machine will not excite or will stop running
if it is already in motion.
Graph 2 showing the external characteristics of shunt DC generator. It is showing the variation of terminal
voltage with the load current. Ohmic drop due to armature resistance gives lesser terminal voltage the generated
voltage. That is why the curve lies below the internal characteristic curve.
The terminal voltage can always be maintained constant by adjusting the of the load terminal. Now, when IL
increased, then terminal voltage decreased. After certain limit, due to heavy load current and increased Ohmic
drop, the terminal voltage is reduced drastically. This drastic reduction of terminal voltage across the load,
results the increase in the load current although at that time load is high or load resistance is low.
That is why the load resistance of the machine must be maintained properly. The point in which the machine
gives maximum current output is called breakdown point.
In a Dc shunt generator the shunt field current indicated by If should be increased in order to get the desired
output terminal voltages at the terminal of Generator at rated speed (1500 rpm). The field rehoestat shoul d be
turned to anticlockwise position first and then it should be turned in clockwise position in order to increase the
terminal voltage and decreasing the field resistance. After obtaining the rated output voltage which is 220V,
then in 2nd part we will apply a resistive load on Generator to check its load current Vs Terminal voltage
characteristics.
E0 = EMF – I0Ra
The separately-excited dc generator provides flexible use because its characteristics can be changed by
changing the field current. However, a separate dc power source is needed to excite the field electromagnet.
This was a disadvantage when the first dc generators were used because dc sources were not commonly
available at the time. Therefore, dc generators that operate without a dc power source were designed. These are
referred to as self-excited dc generators.
Procedure:
• Set up the separately-excited dc generator circuit shown in Figure 8-4. Notice that no electrical load is
connected to the generator output.
• Set the Four-Quadrant Dynamometer/Power Supply or the Prime Mover/Dynamometer to operate as a
clockwise prime mover
• Set the prime mover speed to 1500 rpm
• Now increase the field current with the help of field rheostat and record your results at different intervals
Figure 8-4 DC shunt Generator circuit diagram on no load
• Now after completing this part connect a resistive load to DC shunt Generator output.
• Vary the load current in steps of 0.05A from 0.05A to 0.35A.
Results:
• Without Loading:
E1 If N
• With Loading:
E1 If N IL
Apparatus:
• DC Generator/Motor module
• Prime mover/Dynamometer module
• Rheostat
• DC Variable Supply
• Lab Volt Data Acquisition interfacing module
• Connecting Leads
Discussion:
In a compound generator, both series and shunt winding occurs .The shunt winding can be connected either
across the armature only (short-shunt connection S) or across armature plus series field (long-shunt connection
G). The compound generator can be cumulatively compounded or differentially compounded generator.
The series excitation aids the shunt excitation. The degree of compounding depends upon the increase in series
excitation with the increase in load current.
.
Figure Commulative compound Generator
Procedure:
Circuit Diagram:
• First of all Set the Prime mover Mode.
• Supply the power to prime mover and increase its voltage from 0 to 220V such that the rpm of generator
are 1500 and adjust the rheostat in such a way that the output voltages of generator are 220V
approximately.
• Now Apply the Resistive load at the steps of 0.05A increment but keep rpm constant by increasing the
speed of prime mover.
• After that record the load current and output voltages across Load.
Observations:
Eg IL N
Apparatus:
Discussion:
For better understanding the principle of three phase induction motor, the basic constructional feature of this
motor must be known to us. This Motor consists of two major parts:
Stator: Stator of three phase induction motor is made up of numbers of slots to construct a 3 phase winding
circuit which is connected to 3 phase AC source. The three phase winding are arranged in such a manner in the
slots that they produce a rotating magnetic field after 3Phase. AC supply is given to them.
Rotor: Rotor of three phase induction motor consists of cylindrical laminated core with parallel slots that can
carry conductors. Conductors are heavy copper or aluminum bars which fits in each slots & they are short
circuited by the end rings. The slots are not exactly made parallel to the axis of the shaft but are slotted a little
skewed because this arrangement reduces magnetic humming noise & can avoid stalling of motor.
The stator of the motor consists of overlapping winding offset by an electrical angle of 120°. When the primary
winding or the stator is connected to a 3 phase AC source, it establishes a rotating magnetic field which rotates
at the synchronous speed.
Secrets behind the rotation:
According to Faraday’s law an emf induced in any circuit is due to the rate of change of magnetic flux linkage
through the circuit. As the rotor winding in an induction motor are either closed through an external resistance
or directly shorted by end ring, and cut the stator rotating magnetic field, an emf is induced in the rotor copper
bar and due to this emf a current flows through the rotor conductor.
Here the relative speed between the rotating flux and static rotor conductor is the cause of current generation;
hence as per Lenz's law the rotor will rotate in the same direction to reduce the cause i.e. the relative v elocity.
Thus from the working principle of three phase induction motor it may observed that the rotor speed should
not reach the synchronous speed produced by the stator. If the speeds equals, there would be no such relative
speed, so no emf induced in the rotor, & no current would be flowing, and therefore no torque would be
generated. Consequently the rotor cannot reach the synchronous speed. The difference between the stator
(synchronous speed) and rotor speeds is called the slip. The rotation of the magnetic field in an induction motor
has the advantage that no electrical connections need to be made to the rotor.
The difference between the synchronous speed of the magnetic field, and the shaft rotating speed is slip -
measured in RPM or frequency.
It is common to express the slip as the ratio between the shaft rotation speed and the synchronous magnetic field
speed.
S = (ns - nm) / ns X100%
where
S = slip
ns = synchronous speed of magnetic field (rev/min, rpm)
na = shaft rotating speed (rev/min, rpm)
When the rotor is not turning the slip is 100 %.And Slip at no load is approximately 0.
Slip and Voltage:
When a motor starts to rotate the slip is 100 % and the motor current is at maximum. Slip and motor current are reduced
when the rotor begin turning.
Slip Frequency:
Frequency decreases when slip decrease.
Slip and Inductive Reactance:
Inductive reactance depends on the frequency and the slip. When the rotor is not turning the slip frequency is at maximum
and so is the inductive reactance.
A motor has a resistance and inductance and when the rotor is turning the inductive reactance is low and the power
factor approaches to one.
Slip and Rotor Impedance:
The inductive reactance will change with the slip since the rotor impedance is the phase sum of the constant resistance and
the variable inductive reactance.
When the motor starts rotating the inductive reactance is high and impedance is mostly inductive. The rotor has a low
lagging power factor. When the speed increases the inductive reactance goes down equaling the resistance.
Procedure:
Circuit Diagram:
E1 E2 E3 I1 I2 I3 P Q S T N P.f Slip
Graphs:
I1 Vs P
I1 Vs Q
I1 Vs S
I1 Vs P.f
Slip Vs Torque
Discussion:
• Synchronous Motor:
When a 3 phase electric conductors are placed in a certain geometrical positions (In certain angle from one
another) there is an electrical field generate. Now the rotating magnetic field rotates at a certain speed, that
speed is called synchronous speed. Now if an electromagnet is present in this rotating magneti c field, the
electromagnet is magnetically locked with this rotating magnetic field and rotates with same speed of rotating
field. Synchronous motor is called so because the speed of the rotor of this motor is same as the rotating
magnetic field. It is basically a fixed speed motor because it has only one speed, which is synchronous speed,
and therefore no intermediate speed is there or in other words it’s in synchronism with the supply frequency.
Synchronous speed is given by
120 𝑓
𝑁𝑟𝑝𝑚 =
𝑃
Normally its construction is almost similar to that of a 3 phase induction motor, except the fact that the
rotor is given dc supply, the reason of which is explained later. Now, let us first go through the basic
construction of this type of motor from the above picture, it is clear that how this type of motors are designed.
The stator is given is given three phase supply and the rotor is given dc supply.
Main Features of Synchronous Motors
1. Synchronous motors are inherently not self starting. They require some external means to bring their
speed close to synchronous speed to before they are synchronized.
2. The speed of operation of is in synchronism with the supply frequency and hence for constant supply
frequency they behave as constant speed motor irrespective of load condition
3. This motor has the unique characteristics of operating under any electrical power factor. This makes it
being used in electrical power factor improvement .
Principle of Operation Synchronous Motor
Synchronous motor is a doubly excited machine i.e. two electrical inputs are provided to it. Its stator winding
which consists of a 3 phase winding is provided with 3 phase supply and rotor is provided with DC supply. The
3 phase stator winding carrying 3 phase currents produces 3 phase rotating magnetic flux. The rotor carrying
DC supply also produces a constant flux. Considering the frequency to be 50 Hz, from the above relation we
can see that the 3 phase rotating flux rotates about 3000 revolution in 1 min or 50 revolutions in 1 sec. At a
particular instant rotor and stator poles might be of same polarity (N-N or S-S) causing repulsive force on rotor
and the very next second it will be N-S causing attractive force. But due to inertia of the rotor, it is unable to
rotate in any direction due to attractive or repulsive force and remain in standstill condition. Hence it is not self
starting. To overcome this inertia, rotor is initially fed some mechanical input which rotates it in same direction
as magnetic field to a speed very close to synchronous speed. After some time magnetic locking occurs and the
synchronous motor rotates in synchronism with the frequency.
Circuit Diagram:
Observation:
Results:
If Vs Is:
Experiment No. 12
Objective:
Discussion:
• SynchronousGenerator:
The generator in which permanent magnet/electromagnet is used instead of coil to provide excitation
field is termed as synchronous generator.
In general, synchronous generator consists of two parts rotor and stator. The rotor part consists of field
poles and stator part consists of armature conductors. The rotation of field poles in the presence of
armature conductors induces an alternating voltage which results in electrical power generation.
Where, ‘f’ indicates alternating current frequency and ‘P’ indicates number of poles.
A’
A
’
BB CC
Stator coils separated by 120o causes delay between phase EMFs by 120 degrees.
Phase difference depends upon the number of slots and number of coils per phase,
and position and orientation of coils.
Procedure:
Circuit Diagram:
Observation:
It is observed that as the Inductive load increase the terminal voltages decrease and as the capacitive load
increases the terminal voltages increases due to leading power factor of load. But there is no change in the speed
of generator.By increasing the field current the terminal voltages also increases.
Results:
IL vs Eg:
IL vs Regulation
Apparatus:
Discussion:
To synchronize the alternator with national grid, before synchronizing there are 4 conditions which are must be
fulfiled
The synchroscope would be rotating rapidly counter clockwise. If the generator breaker were to be
accidentally closed, the generator would be out of step with the external electrical system. It would
behave like motor and the grid would try to bring it up to speed.In doing so, the rotor and stator would
be slipping poles and damage (possibly destroy) the generator as described previously. The same
problem would occur if the generator were faster than the grid.
Procedure:
Setting:
• The flikring sequence should be same it means all bulbs on or off at the time.
• Flikring rate showld be zero it means they are all should be turn on or turn off (not
flashing).
• The intensty of glow should be minimum as much as possible.
Methods:
• Flickring sequence shows the phase angle sequence, to set the flickring sequence just
swap the any two phases of National Grid or Synchronous generator.
• Flickring rate shows the frequency difference, to set the frquency difference zero just
change the speed of Synchronous generator (increase or decrease is depend upon the
difference).
• The intensity of glow shows the Amplitude difference of both sinusoidal voltages, if the
glow intensity is high it means there is large difference between National grid voltages
and Synchronous generator voltages and vise versa.
• If All these condition fulfiled then turn on the synchronizing switch so that our
Synchronous generator will attached to the bus of national grid. Now its rpm depends that
either it is consuming or delivering the power to National Grid.
• After Synchronizing take reading of National grid and Synchronous generator voltages
and Synchronous generator current (of any one phase) and speed and torque of
Synchronous generator and active power of Synchronous generator.
• Increase the active power deliverd to National grid by Synchronous generator in
increments of 10 watts and record the measurments.
Circuit Diagram:
Observation:
Results: