The values below are given for normal operating condition as defined in IEC 60298, IEC
60694, IEC 62271-100 / 200
Switchgear Model 12A20 12A25
Rated voltage kV 12 12
Rated frequency Hz 50 50
Rated insulation level
-Power frequency withstand voltage/min kV 28/32 28/32
-Lightning impulse withstand voltage (peak) kV, 1.2/50 μs 75/85 75/85
Rated normal current of Busbar A 800/1250/2000
Rated short time withstand current kA/3s 20 25
Rated peak withstand current kA 50 63
Standard degree of protection (1)
Enclosure 4X
Compartment 3X
Dimension
Width mm 600, 800, (2000A)
Depth mm 2200,2250 (with PT)
Height mm 2300
Other values are available on request.
12A20 / 25
12kV METALCLAD SWITCHGEAR
Circuit Breaker Model VFT-12
Rated voltage kV 12
Rated current A 630/1250/2000
Rated frequency Hz 50
Rated insulation level
-Power frequency withstand voltage kV/ 1 min 28/32
-Lightning impulse withstand voltage kV, 1.2/50 μs 75/85
Rated short circuit breaking current kA, rms 50/63
Rated short circuit withstand current kA/3s 20/25
Rated short circuit making current (peak) kA 50/63
Mechanical endurance 10,000
Rated operating sequence/duty 0-0.3s-CO-3min-CO
Rated closing time ms <60
Rated opening time ms <50
Rated breaking time ms <60
Standard trip/close supply (1) Vdc 30/110
Other values are available on request.
Standard motor charging supply (2) Vdc (Vac) 30/110(240 Vac)
GENERAL DESCRIPTION
Indoor air insulated metalclad switchgear. Mechanical intelocks are provided to
safeguards against maloperation.
Vacuum circuit breaker is mounted on truck for
horizontal withdrawal and isolation. Design type tested to IEC 62271-100/200,
IEC 60298, IEC 60056, IEC 60694
Integral fault making earthing switch, class A on the
circuit side. Busbar earthing truck is optional.