CS400-R Fire Control System
Fire Detection and Discharge with CPU redundance
● The CS400-R fire control system is a completely
configurable and programmable system for fire & gas
detection and discharge activation. Thanks to its
configuration modularity and to the programming ease, the
use of this control system is suitable for various alarm
control and discharge functions.
● The CS400-R system is the evolution of CS400 system.
The modular cards of the system are the same as CS400
one: the distinguishing particular is due to the CPU
redundancy feature (MASTER-SLAVE functioning).
● Two serial ports (RS232 and opto-isolated RS485) allow
you to use remote warning devices (such as displays,
printers, etc.) or modbus devices (such as Plc etc.).
● The CS400-R fire control system can be connetted to
Ethernet network with TCP/IP protocol or Profibus,
DeviceNet, InterBus, CanOpen network, Wireless and GSM
connections.
● Software procedure concerning check of data and hardware
integrity allows to determine any fault in the state of the
plant and to intervene rapidly in order to keep the right
control of detection and release system.
● Also to guarantee a continous functioning, the electronics of
CS400-R plant has been planned in order to allow the
change of any hardware components with working system
and to allow input/output and power supply redundacy.
CS400-R Fire Control System
M402-R module
● The M402-R module is the central unit of the CS400-R fire
control system.
● The board is equipped with a CPU and with volatile memory
and Flash memory (retentive memory). The processor is
the master of the control system modules (slaves): with
proprietary protocol it queries the slave modules, reading
their status and settings, sends general and addressed
commands, implements the configurations and the system
parameters, processes the programming logics, saves the
system parameterization, stores the events and performs
the control self-check.
● The card works in redundancy. Two M402-R cards work in
parallel: they process the same data, they give the same
●
Microprocessor technology. programming logic, the same controls on cards. The
●
Volatile and Flash memory devices on the module. difference is due to the priority on communication bus with
●
Module hardware self-check. which the two CPU communicate with the plant cards. The
●
Operator panel management. CPU master communicates physically on bus, while the
●
Internal bus communication management with proprietary protocol. CPU slave communicates virtually. If the CPU slave
●
RS232 serial port and opto-isolated RS485 port management. monitors any CPU master functioning fault, it takes the
●
Modbus RTU protocol. control of the system (it becomes itself master) by putting
●
Profibus, DeviceNet, InterBus, CanOpen . network. the other CPU in a slave state. In this way the plant
●
Wireless and GSM connections. functioning is assured in any critical condition without any
●
Ethernet link with TCP/IP protocol. state change. Software procedure concerning check of data
●
Runtime operation software update. and hardware integrity together with CPU redundacy allows
●
Event and status log management. to operate rapidly in order to keep the right control of
●
Visual warning signals about the status of the module. detection and quenching system. There is also the
●
Mounting in 19’’ racks with locking screws. possibility of disconnecting the redundant system: in this
case the plant works with a single CPU.
CS400-R Fire Control System
M401 module
● The M401 module is the feeder of the CS400-R fire control
system. The feeder has been designed to assure the
highest security and reliability in the power supply of the
internal control system and of the external devices. In case
of main supply failure or overload, an electronic switch turns
on the batteries avoiding undesired stabilized voltage drop.
The control system hardware architecture allows the
creation of redundant systems: once one feeder fails, it is
disabled and its load is maintained by the other existent
feeders, without having necessarily to switch to the
batteries. The failed feeder can be removed from the rack
and replaced without altering the normal system operation.
● The M401 module checks the presence of batteries and
performs a periodic battery level test. The charge circuit
●
Microprocessor technology. allows to recharge hermetic lead batteries and supplies a
●
Module coding through dip-switch on board. steady maintenance voltage to preserve their status at best.
●
24V stabilized voltage adjustable for the internal power supply.
●
27.6V adjustable stabilized voltage for the battery charger.
●
27V rectified filtered voltage for connected devices power supply.
●
Power and battery level check (signaling for undervoltage and overvoltage).
●
Short circuit and battery inversion protections.
●
Periodic battery level test.
●
Redundant systems options.
●
Visual warning signals about the status of the module.
●
Mounting in 19’’ racks with locking screws.
CS400-R Fire Control System
M404 module
● The M404 module is designed for automatic putting off.
Through programming, it can be combined with detection
modules (M406 and M407). You can have a double-consent
combination with M406 (higher intervention security), or
programming can be combined to a wired control within the
control system. When the activation command is remotely
generated, the M404 module can also be used separately.
● Through a selector you can set automatic or manual
discharge intervention. In automatic mode, discharge is
activated when the module detects the corresponding
command, in manual mode it is activated only when the
operator executes a command via remote buttons or local
buttons on the control system.
●
Microprocessor technology. ● Moreover, the M404 module is set to inhibit discharge, that
●
Module coding through dip-switch on board. is, to stop timing before the solenoid valve is activated.
●
Line check for opening and short circuit.
●
Automatic/manual mode selector. ● All discharge activation or control lines are monitored.
●
Discharge inhibition input.
●
Double-consent discharge activation options. ● Redundance can be achieved through analog module.
●
Visual warning signals about the status of the board.
●
Mounting in 19’’ racks with locking screws.
CS400-R Fire Control System
M405 module
● The M405 module is set to manage 6 controlled lines of
commands. Its uses vary from automatic putting off to other
functions that need line status monitoring. You can
separately configure the lines from the operator panel of the
CS400-R control system. For each line, you can set the
control mode (inversion or current), or disable control: in
this case it is possible to select the quiescent state for the
line (normally active or inactive). Line activation is
performed through logical equations programming.
● Redundance can be achieved through analog module.
●
Microprocessor technology.
●
Module coding through dip-switch on board.
●
Line continuity and short circuit check.
●
Operator panel-configurable lines
●
Inversion or current control, intermittence, disabling, activation signaling.
●
Unchecked line quiescent state setting option.
●
Event and status logics programmable for every line.
●
Visual warning signals about the status of the module.
●
Mounting in 19’’ racks with locking screws.
●
Redundance can be achieved through analog module.
CS400-R Fire Control System
M406 module
● The M406 module is designed for fire detection: it manages
2 non-addressed analog lines, checking their current level,
signaling faults (in case of short circuit or opening) and
signaling the detector intervention (alarm condition).
● From the operator panel of the CS 400-R control system
you can separately configure the 2 lines, setting alarm level,
single or crossed line operation, output activation or
inhibition during test. By setting the crossed lines option,
the intervention of one line generates a prealarm condition,
while the intervention of both lines generates the alarm
condition.
● By setting the inhibition during test, you can perform the line
test procedure without activating the tested line outputs and
●
Microprocessor technology. the discharge commands, keeping the visual warning
●
Module coding through dip-switch on board. signals active. The test is automatically completed and the
●
Line check for opening/short circuit/detector intervention. outputs are reactivated if, during its execution, the M406
●
Lines can be separately configured from the operator panel. module reports the effective intervention of a fire alarm
●
Single or crossed line control mode. detector.
●
Settable alarm level.
●
Line disabling from front switch option. ● By using the front switch, you can separately disable the
●
Line test execution from front button with output inhibition option. lines.
●
Out of service/fault, alarm, discharge outputs.
●
Visual warning signals about the status of the module. ● Redundance can be achieved through analog module.
●
Mounting in 19’’ racks with locking screws.
●
Redundance can be achieved through analog module.
CS400-R Fire Control System
M407 module
● The M407 module is designed for fire detection: it manages
6 non-addressed analog lines, checking their current level,
signaling faults (in case of short circuit or opening) and
signaling the detector intervention (alarm condition).
● From the operator panel of the CS400-R control system you
can separately configure the lines, setting prealarm/alarm
level, line disabling, single or crossed line operation, single
or double intervention. By setting the crossed lines option,
the intervention of one line generates a prealarm condition,
while the intervention of both lines generates the alarm
condition. The double intervention implies that the M407
module verifies the line intervention condition (for higher
detection security): when an intervention condition is
detected, the line is temporarily reset. When a set amount
●
Microprocessor technology. of time has elapsed, should the intervention persist, the
●
Module coding through dip-switch on board. alarm state is signaled.
●
Line check for opening/short circuit/detector intervention.
●
Lines can be separately configured from the operator panel. ● You can also configure lines to manage the corresponding
●
Single or double intervention, single or crossed line control mode. intervention as a simple warning or fault event.
●
Settable prealarm and alarm level.
●
Line disabling option. ● Redundance can be achieved through analog module.
●
Alarm event can be configured as simple warning or fault.
●
Visual warning signals about the status of the module.
●
Mounting in 19’’ racks with locking screws.
●
Redundance can be achieved through analog module.
CS400-R Fire Control System
M408 module
● The M408 is designed to control non-addressed gas
detectors with standard output 4-20mA and is set to use 3
or 4-wire detectors.
● On the front panel there is a 3-digit display where you can
read line reading value in real time and a 20-LED bar
showing the measurement percentage.
● Detection line and measurement can be easily configured
from the operator panel of the CS 400-R control system.
Specifically, the operator can select: measurement range
(ppm, % LEL, oxigen, mA view), prealarm, alarm and fault
level, ascending or descending alarms, disabling and
maximum sampled value view. From the operator panel you
can also activate an automatic procedure for the module
●
Microprocessor technology. zero calibration, in order to avoid intervention with
●
Module coding through dip-switch on board. mechanical adjustments on the module.
●
Gas line monitoring for opening/short circuit/threshold overflow.
●
Line and measurement settings configurable from the operator panel. ● Besides, the M402-R is set to acquire and keep values
●
Reading range settings from operator panel. sampled by M408 modules, providing users with a virtual
●
Settable prealarm and alarm level and trigger. oscilloscope for each gas detection line.
●
Threshold overflow managed as alarm events or simple warnings.
●
Measurement maximum view. ●
The M408 is equipped with a current repetition line (4-
●
Range or mA view. 20mA) for remote devices with fault, prealarm and alarm
●
Self-zero calibration from operator panel. outputs.
●
Line disabling from operator panel option.
●
Current repetition in 4-20mA range and fault, prealarm and alarm outputs. ● Redundance can be achieved through analog module.
●
Visual warning signals about the status of the module and of line measurements.
●
Mounting in 19’’ racks with locking screws.
●
Redundance can be achieved through analog module.
CS400-R Fire Control System
M409 module
● The M409 module is designed to activate 6 programmable
relay outputs through CBE logics.
● You can set NO or NC contacts and separately configure
relay outputs to be normally active (to put in place “Fail
safe” logics) or inactive.
● On the module front panel there are LEDs indicating the
activation status and the module programming.
● Redundance can be achieved through analog module.
●
Microprocessor technology.
●
Relay outputs with NO or NC setting option through jumper on the module.
●
Operator panel-configurable outputs (normally active or inactive, intermittent).
●
Outputs can be programmed with CBE logic association.
●
Visual warning signals about the status of the module.
●
Mounting in 19’’ racks with locking screws.
●
Redundance can be achieved through analog module.
CS400-R Fire Control System
Esp module
● The ESP module controls addressable type devices, ESP
series by Hochiki, which includes a wide range of smoke
and heat detectors, analogue smoke detectors, manual
alarm call points, bells and input-output modules.
● The ESP module provides power and communication to the
addressable loop to monitor and control all addressable
analogue and digital devices series ESP.
● The card is equipped with front panel LEDs to indicate Fire
Alarm and Faults status.
● Detailed informations on addressable inputs are sent to
CPU for processing and displaying on LCD operating panel.
●
Microprocessor technology.
●
Module coding through dip-switch on board.
●
Up to 127 addresses Hochiki ESP protocol.
●
Protection for short circuit loop condition.
●
Open loop condition checked.
●
Devices disabling option.
●
Alarm event can be configured and managed as simple warning or fault.
●
Visual warning signals about the status of the module.
●
Mounting in 19’’ racks with locking screws.
CS400-R Fire Control System
Certifications and marks
●
The signaling and system management principles
and the information provided meet the European EN
54-2 provisions. The power system meets the EN
54-4 provisions.
●
CS400-R Fire control system is CE marked
(European provisions for Electromagnetic
compatibily and Electrical safety).
●
EN 61000-6-3:2001
●
EN 50130-4: 1995 + A1:1998
●
EN 60950-1:2001
CS400-R Fire Control System
Win400 Configuration And Supervision System
● Win400 is a software program to
configure and supervise fire-fighting
systems and it features a plugin structure.
● You can use this software structure to
check a high number of systems, in fact,
you can load a different plugin for every
kind of action.
● This software is very user-friendly and
can be highly customized.