12KV VCB Specs for Engineers
12KV VCB Specs for Engineers
September 2017
Engineering Department
Unless otherwise stated, equipment shall be designed, constructed and tested in accordance with
latest revisions of following Indian Standards:
a) Circuit Breaker IS:13118-1991
b) Potential Transformer IS:3156-1992
c) Current Transformers IS:2705-1992
d) Painting IS:5, Shade 631
e) Other applicable relevant Indian Standards
a) Multi-panel Vacuum Circuit Breaker shall consist of 12 kV, 25 kA Multi panels (Incoming,
Bus Coupler and Outgoing) Shunt Trip, Indoor type Vacuum Circuit Breaker with SAS
/SCADA Compatible facilities.
b) The equipment shall be complete with all necessary accessories and materials in accordance
with the Specification.
c) The base channel frames for the switchgear for grouting in the floor shall be complete with
anchor bolt, nuts and leveling attachment.
d) Special tools and tackles.
e) All relevant drawings, data and instruction manuals.
The equipment will be located indoors in a clean but humid and tropical atmosphere.
For the purpose of designing, the following conditions shall be considered unless otherwise
specified :
STANDARDTECHNICAL PARAMETERS
DESCRIPTION VALUES/
SL INFORMATIONS
1. Type of Switch Gear as per Arc Interrupter VCB
3. Frequency 50 c/s
A) Rated Voltage
The equipment shall be suitable generally for system of nominal voltage of 11000 Volts, 3 phase,
50 C/S, system may be effectively or non effectively earthed. Nominal voltage of the system
where the equipment will be used may be taken as 11 kV (Phase to Phase), which shall be
subjected to a variation upto 13 kV (Phase to Phase) on the higher side for prolonged period of
use. The rated voltage of equipment shall be considered as 12 kV.
The multi-panel Vacuum Circuit Breaker buses shall be rated for continuous current of 1250 Amps
for 12KV and maximum temperature rise of the bus and bus connection shall be limited as per
provision in the IS. The Circuit Breaker unit shall be rated for continuous current of 1250 Amps
for Bus-coupler switchgear, 800 Amps for incoming & outgoing switchgear.
a) General
The equipment shall be indoor, metal enclosed, floor mounted suitably isolated, Floor Level
horizontal draw-out Vacuum Circuit Breaker (Having SAS / SCADA Compatible facilities).
Design and construction shall be such as to allow for extension at either end in future.
b) Construction
Each board shall consist of stationary type, self-supporting sheet-steel cubicle and draw-out type
circuit breaker. The design and workmanship shall permit complete interchangeability of the
circuit breaker unit among multi-panel board including incoming & outgoing feeder breaker and
bus coupler breaker and vice-versa.
The circuit breaker cubicle shall have structural steel frame work enclosed on all sides and top by
sheet steel of minimum 2 mm thickness.
Overall height will be maximum 2700 mm. Overall width & depth will be maximum
710 mm. & 1950 mm respectively.
The cubicle shall be provided with a front access door with a removable back cover.
The circuit breaker, bus-bar, instrument transformer and cable end box shall be installed in
separate compartments within the cubicles.
The compartment shall be so constructed that failure of one equipment does not affect the
adjacent units. Suitable vent shall be provided for satisfactory performance. Each compartment
shall be separated from adjacent one by sheet steel barrier. Offered equipment shall be type
tested against internal arc as per provision in IEC Publication No. 298: 1981.
Relays, meters, switches and lamps shall be flush mounted on the hinged front door of either the
cubicle itself or the control cabinet built on the front of the cubicle.
All fixing bolts, screws etc. appearing on the panel shall be so arranged as to present a neat
appearance. Door hinges shall be concealed type.
Right angle side entry cable end box shall have to be provided as per requirement including
accessories for connection with bus of multi-panel board rated for 1250 Amps. Arrangement of
Potential transformers shall be provided with sealing arrangement by extension pieces, welded at
appropriate places of the potential transformer with stationary portion of equipment so that P.T.
cannot be displaced from its position when it is racked in position. The P.T. and secondary fuse
units when fitted over the top of P.T. / Cubicle, shall be provided with sealing arrangement by a
common steel sheet of sufficient rigidity and with suitably hinged at one side, so that after the
said fuse units are sealed, no part of the fuse grips and connections become accessible from
outside for displacement of the same.
The multi-way terminal block inside the cubicle where all the secondary leads from the CTs & PTs
will terminate shall be covered with insulated transparent cover having suitable sealing
arrangement for preventing access to those terminals for manipulation of connections or
loosening the same.
Test terminal block of metering circuit shall be covered having suitable sealing arrangement.
The main bus of each section of Multi-Panel Board shall be of high conductivity electrolytic
copper liberally sized for 1250A.
The bus-end connections shall be so supported as to be capable to safely withstand stresses due
to maximum short circuit current and also to take care of any thermal expansion.
Three phase bus shall be adequately insulated for working voltage. For air insulated circuit
breaker, bus-bar shall be provided with insulating sleeves and joints shall be provided with
insulated removable shrouds.
All bus connections, joints and taps shall be tinned or silver plated, Connections shall be as short
& straight as possible.
Necessary provision shall be made for testing current transformer primary by removing insulated
portion of the joints without any difficulty.
d) Name Plate
Name Plates of approved design shall be furnished at front and back of each cubicle for the
purpose of feeder designation.
Material for Nameplate shall be transparent plastic sheet of 3 mm thick and 25 mm x 150 mm
and shall be held by self tapping screws and shall be fixed at a conspicuous position.
Each unit shall be provided with a rating plate marked with the following :
f) Power Supply
For multi-panel board the provision for external DC and AC supplyhas to be arranged in
Incoming and Bus Coupler Panels.
Contractor shall run bus wires for providing this power supply to different cubicles of multi-panel
board. Isolating fuse units shall be provided for incoming supplies to each Switchgear Unit.
Min. permissible
Circuit
size of wire
Metering and relaying circuits connected to current Transformers 4sq.mm
Potential circuits for metering and relaying control, visual and 2.5 sq.mm
audible alarm & signaling circuits
All wiring shall be done in such a way that it will have sufficient clearance from High Voltage
System. Other than L.T.P.T. fuse, no fuse shall be provided in the circuit carrying power from PT
secondary for metering purpose.
Sufficient bus wires shall be provided for inter connecting with adjacent units both ways and also
for future connection to additional units.
The circuit breaker shall be provided with motor operated spring charged closing mechanism,
anti-pumping relay and also with manually charged spring closing mechanism trip free nature.
Requisite hand operating device shall be supplied with multi-panel board equipment.
i) Terminal Block
Multi-way terminal blocks complete with necessary binding screws & washers for wire
connections and marking strips for terminal identification shall be furnished for terminating
cubicle wiring and outgoing cables.
The terminals shall be bolted type robust, rust-free and suitable for connection of at least 2 nos.
2.5 mm² copper wires per terminal.
j) Cable Termination
HT Power Cable from LV side of power transformer shall enter in the rear bottom portion of
incoming breaker through 2 (Two) nos. rear entry cable end boxes, so double cable termination
arrangement to be provided with 2 (Two) sets of nut & bolts.
HT Power Cable for distribution feeder shall enter in the rear bottom portion of outgoing breaker
through rear entry cable end box.
HT Power Cable for connection to shunt capacitor bank or connection to another multi-panel
switchgear shall enter in the multi-panel board equipment from side of the panel through right
angle side entry cable end box.
HT Power Cables shall be of standard 3 core XLPE type, 11 kV grade cable of Aluminum
conductor.
Normally no rear entry cable end box shall be supplied with the equipment unless otherwise
required from design consideration. But provision shall be made for housing, fixing and covering
cable & cable end boxes in each incoming and outgoing switchgear panel.
However, rear entry cable end boxes shall have to be provided by the manufacturer for design
consideration if cables remain exposed at the back side of the panel.
Multi-core cable terminal box shall be provided in suitable locations at the back side of the panels
for connecting multi-core Control Cables.External DC and AC supply arrangement to be provided
in Incomer and Bus Coupler panelonly in a switch board.
k) Ground Bus
A grounding bus rated to carry maximum fault current shall be furnished along the full length of
the panel board. Each stationary unit shall be grounded directly to the ground bus.
Connectors shall be provided at two ends for connection to user’s ground conductor.
The frame of each circuit breaker shall be grounded through heavy multiple finger contacts at all
times except when breaker primary disconnecting devices separated by a safe distance.
l) Tropical Finish
All electrical equipment, accessories & wiring shall have fungus protection involving special
treatment of insulation and metal against fungus, insect & corrosion. Screens shall be furnished
on all ventilating covers to prevent entrance of foreign elements.
m) Painting
Modern method of painting like stove enameling or similar process as per provision in the Indian
Standard shall be followed for painting all surfaces of panel, after the frame work is made free of
scale, rust, foreign adhering mater or grease.
After cleaning the surfaces shall be given a phosphate coating followed by a coat of high quality
red oxide or yellow primer.
The equipment shall be finished in light gray with two coats of synthetic enamel paint or powder
coating as per relevant ISS.
Circuit Breakers shall be vacuum interrupting type. All breaker units shall be physically and
electrically interchangeable. The equipment shall be floor mounted and shall consist of stationary
Each Circuit breaker (i.e Incomer, feeder & B/c) shall be provided with Mechanical ‘ON’ & ‘OFF’
facility by operating suitable closing and opening devices. Each breaker shall be provided with
Mechanical ‘ON’ & ‘OFF’ indicators. Trip circuit healthy indication & spring charging indication are
to be provided. All the breaker shall be provided with motor operated spring charged closing
mechanism, antipumping relay and also with manual operated spring charged mechanism & trip.
Spring charge limit switch shall have at least 4NO & 2NC contact.
Each breaker shall have (3) positions – service, isolated and withdrawal positions marked. Each
breaker shall have mechanical indicators for spring “charged” and spring “discharged” conditions.
Mechanical safety interlocks shall be provided so that it is not possible for a circuit breaker :
Automatic safety shutters shall be provided to completely cover the female primary contacts,
which will be disconnected when the breaker is withdrawn. Bus-bar and feeder spout shutter
screen be pad locked independently.
Automatic tripping of the circuit breaker shall be effected by DC operated trip coil of voltage
rating as specified.
Each breaker shall be provided with electrical trip and close facility by using control switch.
Spring controlled switch with trip – neutral-close facility to be used. Electrical close and trip
operation should be dependent on Local/Remote Switch. However protection trip and emergency
trip circuit should be independent of Local/Remote Switch.
Vacuum interrupter for Vacuum Circuit Breaker shall be short time rated for minimum 25 kA for
100 nos. operations.
This will be a Vacuum Circuit Breaker for coupling two sections of buses. The Bus Couplershall be
rated for continuous current of 1250 Amps. It should be interchangeable with incomer and
feeders.
Bus coupler shall be floor mounted, vacuum interrupting and horizontal draw out type complete
with transfer trucks.
The Bus coupler shall be provided with motor operated spring charged closing mechanism, anti-
pumping relay and also with manual operated spring closing mechanism & trip free nature.
The Current Transformers shall be mounted on the rear side stationary portion of the unit and
shall be easily accessible for maintenance and testing purpose. The method of securing Current
Transformer in position shall be such that no undue strain comes on the winding/ terminals.
The Current Transformers shall be capable of safely withstanding the stresses due to maximum
short circuit current.
Current Transformer shall be free from absorption of moisture present in the air.
Universal type fixing arrangement shall be adopted for fixing all the Current Transformers
irrespective of their use as incoming or outgoing, and shall be such that replacement of Current
Transformer by any other ratio can be done without any difficulty.
No resin casting/ compounding shall be allowed at the junction where CT primary terminals will
be connected at High Voltage Bus to facilitate easy replacement/ removal and testing of CT by
way of primary injection at site without dismantling CT from the unit.
Secondary terminals of the CT shall be easily accessible to facilitate easy replacement/ removal
and testing of CT at site without dismantling CT from the unit.
Primary and secondary terminals of the CT shall be marked properly as per provision in the
relevant standard. P1 side of CT should be in bus side in incoming and feeder breakers.
Secondary terminals should be in the P2 side of the CT.
CT shall be easily replaceable by only removing the back cover of the unit.
Each CT shall be provided with wiring diagram plate as per relevant provision of IS showing
primary and secondary terminals for connection at different ratio for metering & protection cores.
Each CT shall be provided with a rating plate legible and indelibly marked with following :
CT & PT Secondary Wiring should be connected in Terminal Board with round type socket only
and properly crimped.
NOTE :Core III & IV CT secondary should be wired upto Multi core cable end box for providing
Differential/REF ( restricted earth fault) protection.
Panel should to be supplied with CT Ratio set at higher Ratio. CT Ratio changing arrangement
should be available by changing link arrangement.
PT should be 3 Phase , 5 Limb with star connection. Star point should be earthed in HV &LV side.
PT shall be resin cast/ dry type and shall be suitable in our system conditions
Each PT shall be provided with Vector diagram plate as per relevant provision of IS showing
primary and secondary terminals.
Each PT shall be provided with a rating plate legibly and indelibly marked.
The secondary circuit from all the PTs of the incoming panels shall be wired upto all the outgoing
panels so that supply to the potential coils of the meters can be maintained from any of the PTs.
Plug & socket type contacts shall be provided in the PT secondary. PT secondary terminals shall
be inaccessible from outside.
The Potential Transformer shall be mounted on rails on top of the unit and shall be connected on
the bus side. It can be plugged into and withdraw from service by pulling or pushing the PT by
the handle provided on the PT. This action shall traverse the PT along the rails and shall
automatically operate the spout shutters. The shutter drive also forms a latch, which holds the PT
in the service position and this latch shall be required to be released before PT can be isolated.
The body earthing of PT shall be of permanent type and shall be so designed that it will remain
earthed by bolted connection both under rack-in and rack-out conditions. Use of flexible wire
netting will be perhaps most suitable for this purpose.
1. Suitable for flush mounting on front panel of the switch cubicle to be installed in a indoor
substation.
2. The relay should be suitable to function in non AC environment having wide temperature
variation of 0 to 55˚C and relative humidity variation of 50 % to 100% throughout the year
also in presence of electrostatic, electromagnetic and transients prevailing in high voltage
system.
3. Relays should be suitable for both 1A & 5A CT input which can be easily selectable at
site and auxiliary DC supply of 30/110/220V.
5. Control of circuit breaker, supervision of status of spring of C.B. status of C.B are also
required
7. Communication feature :
● As a minimum, one independent RS 232, one RS 485 communication ports and one
Ethernet communication port that allow for simultaneous operation shall be provided, to be used
as follows.
a) For relay setting, modifications, extraction and analysis of faults / events / disturbance
records from a laptop through RS 232 at the front. Laptop is not required.
b) To interface with remote communication equipment (GSM GPRS/or othersuitable
communication system) for SCADA.
● The remote communication protocol of the numerical relays shall be IEC 61850.
● The relays should generate GOOSE messages as per ICE 61850 standards for interlocking and
also ensure interoperability with third party relays.
● Necessary user friendly configuration tool shall be provided to configure the relays. It should be
compatible SCL / SCD files generated by a third party system.
● GOOSE signal should be freely configurable for any kind of signals using graphic
tools / user friendly open software without use of any external converter
8. The bidder is to provide the following configuration and monitoring tool free of cost :
Offered Numerical Relay should have KEMA certification for validation of IEC 61850 protocol. At any
stage of evaluation/ ordering, interoperability functions (with third party system) of relays in IEC
61850 platform may be demonstrated free of cost, if asked by WBSETCL.Competent personnel from
the manufacturer should be deputed free of cost during commission of the system at six nos of
locations situated at any part of the state
c) One no. Anti Pumpingrelay is to be provided with all type of switchgear. The relay should not be
Plug-in-type & should have sufficient number of contact.
e)Annunciation Scheme
An annunciator to be provided in each panel except Bus Couplerpanel.The annunciator should be
Micro processor based with inbuilt Accept/Reset/Test/Mute push buttons for trip & non-trip
functions.DC operated common Hooters shall be provided in Bus Coupler breaker panel. The
Microprocessor based annunciator shall have provision of built in Watch Dog and Fast fault indication
with Trip and Non Trip Alarm functions. 6 (Six) window annunciator to be used in each panel.DC fail
annunciation is to be provided. Annunciator shall be ofMinilec or Alan make.
All relays shall be of flush type and the same shall be mounted on man height for easy
accessibility to reset mechanism by hand, standing on the floor of Control Room
Building.
a) Ammeter
One number Digital Ammeter (72×144 mm², nominal current : 1A) flush type for each phase,
shall be provided on each incoming and outgoing breaker panel. All Ammeters shall be suitable
for direct reading and calibrated according to CT ratio ofthe unit.
Ammeters shall be connected from metering circuit of CT Secondaries.
b) Voltmeter
One number of Digital Voltmeter :(72×144 mm², nominal voltage 11 KV) flush type shall be
provided on each incoming breaker panel. The Voltmeter shall be suitable for direct reading of 0
to 15 kV and calibrated according to PT ratio of the unit.
a)Indicating Lamps
ClasterLED type Indicating Lamps with built in series resistor holder and coloured lens shall be
provided in incoming/ outgoing/ bus coupler breaker panel mentioned below :
All the Indicating lamps as mentioned in above table, shall be provided in all incoming and
outgoing breaker panels. The bus coupler panel shall be provided with all the indications
except the last one.
For remote monitoring the wire for the indication should be terminated to the rear end of the
switchgear.
b)Push Buttons
Standard Push Buttons having Red coloured knob and required number of N/O & N/C self
returning contacts without locking arrangements for Emergency Trip functions shall be provided
in all the panels.
Trip Coil & closing coil shall be provided for tripping & closing the breaker through actuating
device rated for sub-station DC voltage. It shall be suitable for operation at minimum operating
voltage of 70% for Tripping and 85% for Closing operation. Trip coil and closing coil burden shall
be less than 200 watt.
Auxiliary switches properly rated and robust in nature shall be provided in incoming/ outgoing
and in bus coupler breaker. Auxiliary switches shall have sufficient number of normally open and
normally closed contacts for following functions :
All breakers shall have number of auxiliary switches and shall be wired upto SIC (Secondary
Isolated Contact) with identical SIC and ferrule numbers.
Insulated Spacer made of insulated fibre glass materials shall be provided in High Voltage System
to protect from absorption of moisture present in the air.
Each cubicle shall be provided with a Space Heater – 60 W 230 V AC, operated with controlling
tumbles and thermostat.
XII) a) DC Circuit
There shall be only one DC Incomer for the entire multi-panel board through a suitable 32 Amps
double pole MCB. A continuous DC bus shall be provided in the entire multi-panel switchboard for
control, protection, indication and for common annunciation scheme. DC supply should be fed to
in each panel for above purpose through a set of fuses on positive & negative side for control,
protection, trip circuit healthy indication and also a set of fuse & link for common annunciation
scheme.
b) AC Circuit
230 V single phase AC supply to the entire multi-panel board shall be fed from AC Distribution
Board through suitable 16 Amps Double pole MCB. A continuous AC bus shall be drawn in the
entire multi-panel switchboard for indication and supply to heater circuit. AC supply shall be fed
to in each panel for above purpose through a set of fuse and link.
c) PT Selection scheme
Each incoming and outgoing breaker panel shall be provided with suitable manually operated
selector switch having break before make type contacts including necessary wiring for selection
of voltage from different PT secondaries available for connection with energy meters. Voltmeter
(1) The Schematic diagram of control and indication circuit on a durable sticker shall be fixed in
a suitable place in incomer and feeder panels , and annunciation scheme in the Bus Coupler
panel.
(2) The wiring arrangement, position of Fuses, Terminal Block etc. in the panel should be such
that each and every connection can be accessed easily, Fuse tops can be opened / inserted
easily.
(3) Only Ring type sockets should be used wire termination in TB/ Relays/ Meters/ TTB etc. Fork
type socket can be used in Annunciator only
XIV) Accessories
7.0 TEST
A. Routine Test
Each Breaker panel including all accessories shall be completed, assembled, wired up, adjusted
and Routine tested as per relevant Indian Standard Specification.
B. Type Test
The Bidder shall submit complete Type Test Reports as mentioned under and as stipulated in the
relevant IS/IEC, carried out in a CPRI/NABL accredited/Govt. recognised Test House or
Laboratory on 12 KV, 800/1250A, 25 KA Floor Mounted Indoor Type Totally Enclosed Shunt Trip
Metering Switchgear with Vacuum Circuit Breaker Unit of identical design.
C. Acceptance Test
A. The following drawings and details shall be furnished along with each copy of bid as reference for
consideration of technical aspect of bid. The bidder shall submit a complete set of Type test
report as mentioned in the relevant IS & IEC.
General Arrangement Drawing showing constructional features and space required in the front for
withdrawal of breaker truck and in back, other accessories, power and control cable entry points
etc. with plan, elevation and views.
The manuals shall clearly indicate the installation method check-ups & tests to be carried
out before and after commissioning the equipment.
The contractor shall submit six (6) sets of approved drawings for each type of switchgear per
sub-station to the Chief Engineer, Engg. Deptt.for distribution purpose. Six copies of instruction
manuals in binding form for each type of switchgear per substation and data sheets for each
rating of equipment shall be submitted. The manuals shall clearly indicate the installation
methods, checkups and tests to be carried out for testing the equipment and maintenance
procedure.
c) In addition, every set of the panel shall also contain in water proof folder one set of
drawing, manual and leaflet for operation, maintenance and commissioning at site.
The Tenderer shall submit a recommended list of spare parts for five years of operation along
with item-wise price for each item of spares.
Rate of numerical O/C & E/F Relays, C.T., PT,Ammeter,Voltmeter,Annunciator,Control
Switch,Local-Remote Switch etc.to be quoted separately.We may procure these Items as
Spares from the successful Bidders.
10.0 DEVIATION
Normally the offer should be as per Technical Specification without any deviation. But any
deviation felt necessary to improve performance, efficiency and utility of equipment must be
mentioned in the 'Deviation Schedule' with reasons duly supported by documentary evidences
and advantages of such deviation. Such deviations suggested may or may not be accepted. But
deviations not mentioned in Deviation Schedule will not be considered.
Equipment Device Schedule of Incoming, Outgoing and Bus coupler Breaker of Multi-Panel Switch Board.
Quantity
Quantity
Description of Device Incoming Outgoing
Bus Coupler
Switchgear Switchgear
Relays
a) Numerical Non-Directional Over Current and Earth Fault
Protection Relays:4-element normal inverse with definite
minimum time non-directional microprocessor based over 1 no. 1 no. -
current and earth fault relay.3 nos. over current elements
& 1 no. earth fault element.
b) Trip Relay 1 no. 1 no. -
c) Trip Circuit Supervision Relay 1 no. 1 no. -
d) Annunciator 1 no. 1 no. -
e) DC Voltage operated electronic buzzer - - 2 nos.
Meters & Metering Accessories
a) Ammeter 3 nos. 3 nos. -
b) Voltmeter 1 no. - -
c) Voltage selector switch having provision of wing type knob
1 no. - -
and positions marked RY-YB-BR-OFF
d) Energy Meter (TVM) Only space Only space -
e)Test terminal block with cover having sealing arrangement 1 no. 1 no. -
Indicating Lamp
a) LED type indicating lamp with built in series resistor,
holder and coloured lens : 30/110 V DC for breaker ‘ON’ & 2 nos. 2 nos. 2 nos.
‘OFF’ indication.
b) LED type indicating lamp with built in series resistor,
holder & coloured lens : 30/110 V DC for trip circuit
3nos. 3 nos. 2 nos.
healthy and spring charged indication & Auto Trip
indication.
MCB : 2 pole, 16 Amps for incoming AC supply
1 no. - 1 no.
Fuses and Links As required As required As required
Manual PT selector switch with 3 (Three) position
1 no. 1 no. -
(PT1/PT2/PT3)
Heater – 60 W, 230 V AC with switch and thermostat 1 no. 1 no. 1 no.
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS & OTHER INFORMATION FOR INDOOR TYPE
SHUNT TRIP SWITCH GEAR WITH VCB (SCADA COMPATIBLE FACILITIES)
A. General :
2. Applicable Standard.
4. Rated Voltage.
5. Phase.
6. Frequency.
B. Buses :
1. Material.
2. Size.
5. Minimum Clearance
9. Short-Circuit Force-Kg/m.
C. Circuit Breaker :
1. Make
2. Type & Service
7. Current Rating.
a) Rated Current Amps.(r.m.s.)
b) Derated current due to site conditions& 50
Degree C Ambient Amps (rms).
c) 1 Sec. Thermal rating KA (r.m.s.)
d) Momentary KA (peak)
8. Temperature rise over 50Deg.C.Ambient Deg. C.
9. Interrupting Capacity based on duty cycle
I) Duty Cycle :
a) Symmetrical KA (rms)
b) Symmetrical MVA at rated voltage
c) Asymmetrical (KA if any)
II) Rated Breaking Capacity :
a) Single Phase Capacitor Breaking Capacity
(Amps.)
D. Current Transformers :
1. Make
2. Type
3. Reference Standard
4. Voltage
5. Frequency
E. Potential Transformers :
1. Make
2. Type
3. Reference Standard
4. Frequency
5. a) Rated Primary Voltage
b) Rated Secondary Voltage
c) Winding Connection.
6. a) Rated VA Burden per Phase.
b) VA Burden Thermal Limit.
7. Accuracy Class :
8. a) Class of Insulation.
b) Temperature Rise above 10 Deg.C
9. Over Voltage Factor.
10. Overall Dimension.
11. Weight.
12. Fuses L:
a) H.V.
b) L.V.
Relay Particulars –