02 - Wet Riser System

This document provides a wet riser calculation for Block F of a government building in Kuala Lumpur. It includes standards and design criteria, pump flow rate and head calculations. The pump head calculations consider static head, friction head, and required pressure. Based on a total required pump head of 107.06 meters, the selection is for a centrifugal pump as the duty pump, another centrifugal pump as standby, and a multi-stage impeller pump as the jockey pump.

Uploaded by

Jeghi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
50% found this document useful (2 votes)
822 views2 pages

02 - Wet Riser System

This document provides a wet riser calculation for Block F of a government building in Kuala Lumpur. It includes standards and design criteria, pump flow rate and head calculations. The pump head calculations consider static head, friction head, and required pressure. Based on a total required pump head of 107.06 meters, the selection is for a centrifugal pump as the duty pump, another centrifugal pump as standby, and a multi-stage impeller pump as the jockey pump.

Uploaded by

Jeghi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

MENGEMUKAKAN PELAN PINDAAN AS BUILT BAGI BLOK F, KOMPLEKS

JABATAN KERJA RAYA MALAYSIA ( JKR ), DI ATAS LOT NO 75, SEKSYEN 60


JALAN SULTAN SALAHUDDIN, BANDAR KUALA LUMPUR, 50480 WILAYAH
PERSEKUTUAN KUALA LUMPUR UNTUK :
TETUAN JABATAN KERJA RAYA MALAYSIA

WET RISER CALCULATION

1 STANDARDS : MS 1489 Part 2: 2012 , MS 1210 Part 1

2 DESIGN CRITERIA : Minimum pressure at landing valve – 4 bars

3 PUMP FLOW RATE : 1,500 Liter/min (total flow rate to serve lines of hose
from two separate landing valves simultaneously)

4 PUMP HEAD

4.1 Static head from pump to highest landing valve = 60.7 m

4.2 Friction Head

Pipe run from pump to furthest landing valve i.e Roof Top

i- Flow rate = 1500 L/min

ii- Length of Horizontal and Vertical Piping

150 mm dia. = 87m

iii- Equivalent pipe length due to pipe fittings, valves, etc. :

150 mm dia. gate valve : 1 no. x 5 m =5m


200 mm dia. gate valve : 1 no. x 5 m =5m
150 mm dia. check valve : 1 no. x 6.5 m = 6.5 m
200 mm dia. strainer : 1 no. x 10 m = 10 m
150 mm dia. elbows : 7 nos. x 3 m = 21 m

iv- Total equivalent length = item (ii) + item (iii)

150 mm dia. = 119.5 m


200 mm dia. = 15 m

v- Friction losses

= 119.5 x 4.50 + 15 x 1.20


100 100

= 5.38 m + 0.18 m
= 5.56 m

4.3 Pressure at Wet Riser Nozzle = 4 bar


= 40.8 m

WET RISER S/WR/1


4.4 Total Pump Head

Pump Head, H = static head + pressure drop due to friction in the piping
+ pressure required at outlet
= 60.7 m + 5.56 m + 40.8 m
= 107.06 m
≈ 355 ft

5 SELECTION OF PUMPS

Duty Standby Jockey

1 Prime mover Electric Electric Electric

2 Type Centrifugal Centrifugal Multi stage


Impeller

3 Rated Flow Rate 330 igpm 330 igpm 30 igpm

4 Rated Pressure 355 ft 355 ft 410 ft


Head

WET RISER S/WR/2