MENGEMUKAKAN PELAN PINDAAN AS BUILT BAGI BLOK F, KOMPLEKS
JABATAN KERJA RAYA MALAYSIA ( JKR ), DI ATAS LOT NO 75, SEKSYEN 60
JALAN SULTAN SALAHUDDIN, BANDAR KUALA LUMPUR, 50480 WILAYAH
PERSEKUTUAN KUALA LUMPUR UNTUK :
TETUAN JABATAN KERJA RAYA MALAYSIA
WET RISER CALCULATION
1 STANDARDS : MS 1489 Part 2: 2012 , MS 1210 Part 1
2 DESIGN CRITERIA : Minimum pressure at landing valve – 4 bars
3 PUMP FLOW RATE : 1,500 Liter/min (total flow rate to serve lines of hose
from two separate landing valves simultaneously)
4 PUMP HEAD
4.1 Static head from pump to highest landing valve = 60.7 m
4.2 Friction Head
Pipe run from pump to furthest landing valve i.e Roof Top
i- Flow rate = 1500 L/min
ii- Length of Horizontal and Vertical Piping
150 mm dia. = 87m
iii- Equivalent pipe length due to pipe fittings, valves, etc. :
150 mm dia. gate valve : 1 no. x 5 m =5m
200 mm dia. gate valve : 1 no. x 5 m =5m
150 mm dia. check valve : 1 no. x 6.5 m = 6.5 m
200 mm dia. strainer : 1 no. x 10 m = 10 m
150 mm dia. elbows : 7 nos. x 3 m = 21 m
iv- Total equivalent length = item (ii) + item (iii)
150 mm dia. = 119.5 m
200 mm dia. = 15 m
v- Friction losses
= 119.5 x 4.50 + 15 x 1.20
100 100
= 5.38 m + 0.18 m
= 5.56 m
4.3 Pressure at Wet Riser Nozzle = 4 bar
= 40.8 m
WET RISER S/WR/1
4.4 Total Pump Head
Pump Head, H = static head + pressure drop due to friction in the piping
+ pressure required at outlet
= 60.7 m + 5.56 m + 40.8 m
= 107.06 m
≈ 355 ft
5 SELECTION OF PUMPS
Duty Standby Jockey
1 Prime mover Electric Electric Electric
2 Type Centrifugal Centrifugal Multi stage
Impeller
3 Rated Flow Rate 330 igpm 330 igpm 30 igpm
4 Rated Pressure 355 ft 355 ft 410 ft
Head
WET RISER S/WR/2