Pt100-Temperature-Relay TR1200: 12 Sensors, Interface RS485

The TR1200 is a 12-channel temperature relay that can measure the temperature of up to 12 Pt100 sensors between -199°C and +850°C. It provides the sensor temperature data via an RS485 interface to be externally evaluated. It can be powered with an AC or DC voltage between 24-240V. The TR1200 supports the ZIEHL standard and Modbus RTU protocols to communicate temperature data and can replace two ZIEHL TR600 units. Its applications include monitoring temperatures in motors, generators, transformers, machines and plants.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
165 views2 pages

Pt100-Temperature-Relay TR1200: 12 Sensors, Interface RS485

The TR1200 is a 12-channel temperature relay that can measure the temperature of up to 12 Pt100 sensors between -199°C and +850°C. It provides the sensor temperature data via an RS485 interface to be externally evaluated. It can be powered with an AC or DC voltage between 24-240V. The TR1200 supports the ZIEHL standard and Modbus RTU protocols to communicate temperature data and can replace two ZIEHL TR600 units. Its applications include monitoring temperatures in motors, generators, transformers, machines and plants.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Pt100-Temperature Relays Type TR

Pt100-Temperature-Relay TR1200
12 Sensors, Interface RS485

TR1200 12-channel Temperature-Relay With protocol ZIEHL-standard it can replace two ZIEHL
for Sensors Pt100 (RTD) TR600.
Temperature-relays TR1200
measure the temperature of up The TR1200 is used where temperatures of many sen- 1
to 12 sensors within 199…+850 sors Pt100 shall be evaluated by a device with input
°C and provide the data at an RS485. TR1200 itself does not monitor temperatures
interface RS485 for external for limits. For direct monitoring of temperatures our de-
evaluation. With its universal vices with alarms and output relays are recommended.
power-supply AC/DC 24-240 V it
can be connected to all common Applications are e.g. monitoring of
supply-voltages. • motors and generators (windings, bearings, coolant,
The TR1200 provides the data ambient temperature)
as Modbus-RTU-protocol or ac- • transformers (windings, core, ambient tempera-
Part number: cording to the ZIEHL-standard. ture)
T224095 AC/DC 24-240 V • machines, plants and equipment

Features Sensors and Displays: • selectableProtocols see operating-manual on www.


• 12 inputs for sensors Pt100 ziehl.de
(RTD) • Relay for Error (1 co-contact) for sensor-error and
• Connection 2- or 3-wire operational failure
unneeded inputs can be swit-
ched off More Features:
• Monitoring of sensors for • easy operation and selection of temperatures at
short-circuit and interrupt the device
• 3-digit-display for tempera- • Sensor-simulation
ture • Code-protection against manipulation of settings
• LEDs for assigning the measu- • Universal supply-voltage AC/DC 24…240 V
red value, error, state of relay • Housing for switchgear-mount, 140 mm wide,
and interface mounting-height 55 mm
• Mounting on DIN-rail 35mm or with screws M4
Interface: (option)
• Interface RS485 (protocols
ZIEHL-standard and Modbus- Software for operation (download from www.ziehl.de)
RTU) • Software (Modbus) for programming the inputs
• Baud rate (4800/9600/19200) • Logging-function (with connected PC only)
and Parity-Bit • Hardware for every TR1200: PC with USB or RS232
interface + RS485-RS232 converter (depending on
the interface)
• Software: Win7/Win10 and Excel 2010-2016

ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, [email protected], www.ziehl.de 2019-10-14 49
Pt 100-Temperature Relays Type TR

Technical Data TR1200 Rated Supply Voltage Us AC/DC 24-240 V, 0/45...65 Hz, < 5 VA
DC: 20,4...297 V, AC: 20,4...264 V

Relay output 1 change-over contact (CO)


type 2, see "general technical informations"

Measuring inputs 12 x Pt100 (RTD) acc. to EN 60 751 / IEC 60 751


Measuring time sensor 0,25...3s (depending on number of sensors)
Measuring range -199°...850°C
Resolution 1°C
Tolerance ± 0,5% of value ± 1 K
Sensor-current ≤ 0,8 mA

RS485 interface
Adress of device 0...96
Baud rate 4800, 9600, 19200 baud
Parity N, O, E (non, odd, even)
cable-length max. 1000 m at 19200 baud

Testing conditions see "general technical informations"


Rated ambient temperature -20°C...+65°C
range

Housing Design V8
Dimensions (W x H x D) 140 x 90 x 58 mm, mounting height 55 mm
Protection housing/terminals IP 30 / IP 20
Attachment DIN-rail 35 mm acc. to EN 60715 or screws M4
(option)
Weight app. 350 g

50 ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, [email protected], www.ziehl.de