13 Item 205 LB3 Loop Board

The Loop Board is a connection board for 3 analogue addressable detector loops in the Salwico CS4000 fire alarm system. Each loop can have up to 254 devices. It has jumpers for run and programming modes, LED indicators for each loop, and connectors for power and the 3 detector loops. The 8-position DIP switch is used to set the unique address for the board from 1 to 255.

Uploaded by

AlexDor
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
349 views

13 Item 205 LB3 Loop Board

The Loop Board is a connection board for 3 analogue addressable detector loops in the Salwico CS4000 fire alarm system. Each loop can have up to 254 devices. It has jumpers for run and programming modes, LED indicators for each loop, and connectors for power and the 3 detector loops. The 8-position DIP switch is used to set the unique address for the board from 1 to 255.

Uploaded by

AlexDor
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

CS4000 System boards

LB3, Loop Board


Part no. 21210-001200

System: Salwico CS4000 fire alarm


5
Item 205, part of item 201
Description Data
The printed circuit board LB3, Loop Board is a system Nominal voltage 27 VDC
module in the Salwico CS4000 fire alarm system. Working voltage 19-30 VDC
Working current 340 mA
The Loop Board is a connection board for 3 analogue Cable terminals 2.5 mm2
addressable detector loops. Each analogue addressable Temperature range +5°C to +55°C
loop can have up to 254 loop units. Weight ~300 g
For more information about how to connect the different Dimensions (bxhxd) 247x127x25
CS4000 system boards together, please refer to the
CS4000 Service & Maintenance manual.

Example address switch setting:


Address switch
O
N
The 8-pole DIP switch is used to set the address for LB3
Loop Board. Each board in a system has its own unique 1 2 3 4 5 6 7 8
address. The address no. can be set from 1 to 255.
1 2 4 8 16 32 64 128

Board adress no.

1+4+64=69

Block diagram

Page 1 of 2
CS4000 System boards
LB3, Loop Board
Component layout

Jumpers LEDs
JP1 D1 Indication for processor, Green.
Run mode. Fitted during normal operation. D2 System fault. Yellow.
Move to JP2 during programming. D16 Fire indication, loop 1. Red.
JP2 D17 Fault indication, loop 1. Yellow.
Programming mode. Fitted during programming. D18 Communication, loop 1. Green.
Move to JP1 after programming is completed. D27 Fire indication, loop 2. Red.
JP3 D28 Fault indication, loop 2. Yellow.
Not used D29 Communication, loop 2. Green.
D38 Fire indication, loop 3. Red.
Connectors D39 Fault indication, loop 3. Yellow.
D40 Communication, loop 3. Green.
P1 Internal system channel A, incl. power supply from
RB, rectifier board.
P2 Contact for download of software to LB3
P3 Connection of detector loop 1
P4 Connection of detector loop 2
P5 Connection of detector loop 3
P6 Internal system channel B. Only used if redundancy
of the internal system channel is required.

Terminals
DESCRIPTION CONNECTOR TERMINAL NO. FUNCTION DATA
Fire loop 1 A side P3 11 + 28VDC,
P3 12 - max 300mA/loop
Fire loop 1 B side P3 13 +
P3 14 -
Fire loop 2 A side P4 21 +
P4 22 -
Fire loop 2 B side P4 23 +
P4 24 -
Fire loop 3 A side P5 31 +
P5 32 -
Fire loop 3 B side P5 33 +
P5 34 -

Specifications may be subject to change for improvement without prior notice Data sheet no: 21210-001200 05 1 E
Page 2 of 2