Fire Alarm Design Cheatsheet Example

The document provides an overview and notes for a fire alarm system for an example project. It includes information on the system type, codes and standards followed, locations of initiation and notification devices, monitoring requirements, and interactions with other building systems. The system will be an addressable, voice evacuation fire alarm system designed to NFPA 72-2013 standards and monitored by a central station. It will include smoke detectors, manual pull stations, and strobes throughout the building.

Uploaded by

John Buntales
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
450 views

Fire Alarm Design Cheatsheet Example

The document provides an overview and notes for a fire alarm system for an example project. It includes information on the system type, codes and standards followed, locations of initiation and notification devices, monitoring requirements, and interactions with other building systems. The system will be an addressable, voice evacuation fire alarm system designed to NFPA 72-2013 standards and monitored by a central station. It will include smoke detectors, manual pull stations, and strobes throughout the building.

Uploaded by

John Buntales
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

FIRE ALARM SUMMARY

EXAMPLE PROJECT

OVERALL NOTES
X
DESIGN SCOPE SCOPE DRAWINGS FULL-DESIGN INSTALL DRAWINGS USE SPECS 28 31 76
X X
SYSTEM TYPE TEMPORAL-3 VOICE MASS NOTIFICATION OTHER PER BASE STANDARDS
X
TYPE ADDRESSABLE CONVENTIONAL PER BASE STANDARDS
STANDARD NFPA 72 - 2013 NFPA 72 - 2016 NFPA 72 - 2019 OTHER
x
CODES IBC - 2012 IBC - 2015 IBC - 2018 OTHER
? ?
NFPA 101 - 2012 NFPA 101 - 2015 NFPA 101 - 2018 OTHER
X X
UFC 3-600-01 UFC 4-021-01

HIGH RISE NOTES


x
FIRE COMMAND CENTER NOT REQUIRED REQUIRED
x
STAIR DOOR OPERATION NOT REQUIRED REQUIRED
x
RADIO AMPLIFICATION NOT REQUIRED REQUIRED
x
SMOKE REMOVAL NOT REQUIRED REQUIRED
x
STAIR COMMUNICATION NOT REQUIRED REQUIRED
x
STANDBY POWER NOT REQUIRED REQUIRED

CARBON MONOXIDE NOTES


X
CARBON MONOXIDE NOT REQUIRED REQUIRED PER UFC 3-600-01 RFP P 311/658

CONTROL EQUIPMENT NOTES


X
CIRCUIT CLASS CLASS A CLASS B CLASS N CLASS X PER RFP P 311/658
x
CONDUIT NONE EMT IMC RIGID PER RFP P 311/658
X
OTHER FMC FOR CONNECTION TO DEVICES
X X
CONDUIT COLOR N/A RED MATCH NEARBY OTHER RED SLC BLUE FOR NAC, PER BASE STDS
X
MAIN PANEL LOCATION FRONT ENTRY MAIN ELECTRICAL OTHER PLANS SHOW MECHANICAL ROOM LOCATION.
X
MANUFACTURER NOT PROVIDED BOSCH FARADAY FIKE
FIRE-LITE GAMEWELL GE UTC KELTRON
MIRCOM NOTIFIER HONEYWELL SIEMENS
SILENT KNIGHT SIMPLEX GRINNELL OTHER
X
MODEL NOT PROVIDED OTHER
X
MONITORING CENTRAL STATION CONSTANT-SUPERV. REMOTE STATION OTHER MONACO W/ RADIO TRANSCIEVER
X X
REMOTE ANNUNCIATOR NOT PROVIDED FRONT ENTRY MAIN ELECTRICAL OTHER PER RFP P 311/658, LOC AT LOC. TBD
SURVIVABILITY LEVEL 0 LEVEL 1 LEVEL 2 LEVEL 3
X
BATTERY STANDBY 24 HRS 48 HRS 72 HRS OTHER 60 HRS, PER RFP P 311/658
X
BATTERY ALARM 5 MIN 15 MIN OTHER 30 MIN. , PER RFP P 311/658

CONTROL PROGRAMMING NOTES


X
POSITIVE ALARM NOT PROVIDED POSITIVE ALARM
X
SELECTIVE EVACUATION NOT PROVIDED SELECTIVE EVAC.
X
STAIR PRESSURIZATION NOT PROVIDED STAIR PRESSURIZ.

INITIATION: HEAT NOTES


? ?
HEAT DETECTORS ATTIC ELEVATORS ELEV. MACHINE RM. OTHER

INITIATION: SPOT-TYPE SMOKE NOTES


X X X
SMOKE DETECTORS AT CONTROL EQUIP. DWELLING UNIT ELECTRICAL ROOMS ELEVATORS SYSTEM W/ SOUNDER BASES. 1 IS SUPERVISORY, 2+ CUES BLDG.

SMOKE DAMPERS THROUGHOUT BLDG. OTHER

INITIATION: DUCT-TYPE SMOKE NOTES


X
LOCATION(S) NOT REQUIRED RETURN-SIDE SUPPLY-SIDE SMOKE DAMPERS PER NFPA 90A, PER RFP 538 / 658
?
REMOTE TEST NOT PROVIDED PROVIDED
X
SIGNAL ALARM SUPERVISORY RFP 314 / 658

INITIATION: MANUAL PULL STATIONS NOTES


X
LOCATIONS MAIN PANEL EVERY EXIT OTHER EVERY EXIT, RFP 312 / 658

INITIATION: SYSTEMS INTERACTION NOTES


x
ANSUL N/A MONITORED
x
AUDIO SHUTDOWN N/A SHUTDOWN
x
AUTOFRY N/A MONITORED
x
CLEAN AGENT N/A MONITORED
?
DOOR RELEASE N/A DOOR RELEASE
x
ELEVATORS N/A RECALL SHUNT
x
KNOX BOX NOT PROVIDED NOT MONITORED MONITORED MONITORED BY MONACO TRANSCIEVER
X
PUBLIC ADDRESS NOT PROVIDED PA OVERRIDE
X
SMOKE CONTROL NOT PROVIDED SMOKE CONTROL
X X
SPRINKLER SYSTEM FLOW PRESSURE TAMPER OTHER
X
VESDA N/A MONITORED

NOTIFICATION NOTES
X
ACOUSTIC. DIST. SPACES NO ADS SPACES DESIGNATED MUST MEET 0.7 CIS IN ALL OCCUP. SPACES, RFP P 312 / 658
X
ADA ROOMS NO ADA ROOMS STROBE(S) PROVIDED
X
APPLIANCE COLOR WHITE RED
X
LENS COLOR CLEAR AMBER BLUE
X
TEXT FIRE ALERT RED TEXT
x x
MOUNT STYLE CEILING WALL WALL-MOUNT EXTERIOR DEVICE
x
SCROLLING TEXT BOARDS NO TEXT BOARDS AT EACH EXIT OTHER PER RFP 312 / 658