Datenblatt
PROeco Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
PRO ECO 120W 12V 10A D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
You are looking for a reliable power supply with basic
functions.
With PROeco we can offer you low-cost switch-mode
power supply units with
high efficiency and system capability. Let’s connect.
In the series production of machines, in particular, switch-
mode power supply units with
above-average performance values can deliver genuine
competitive advantages.
The low-cost PROeco series offers all the basic functions
and delivers impressively
high performance and flexibility.
Our PROeco switch-mode power supply units feature a
compact design, high
efficiency and are extremely easy to maintain. Thanks to General ordering data
temperature protection,
short-circuit and overload resistance they can be
Type PRO ECO 120W 12V 10A
universally used in all Order No. 1469580000
applications. Version Power supply, switch-mode power supply unit, 12
Wide-ranging safety functions and compatibility with our V
GTIN (EAN) 4050118275803
diode and capacitance modules, together with UPS
Qty. 1 Stück
components for setting up a
redundant power supply, characterise solutions with
PROeco.
Erstellungs-Datum February 21, 2019 5:10:39 PM CET
Katalogstand 15.02.2019 / Technische Änderungen vorbehalten 1
Datenblatt
PROeco Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
PRO ECO 120W 12V 10A D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
Technische Daten www.weidmueller.com
Dimensions and weights
Width 40 mm Width (inches) 1.575 inch
Height 125 mm Height (inches) 4.921 inch
Depth 100 mm Depth (inches) 3.937 inch
Net weight 684 g
Temperatures
Operating temperature, max. 70 °C Operating temperature, min. -25 °C
Storage temperature, max. 85 °C Storage temperature, min. -40 °C
Operating temperature -25 °C...70 °C Storage temperature -40 °C...85 °C
Environmental Product Compliance
REACH SVHC Lead 7439-92-1
Input
AC current consumption 1.25 A @ 230 V AC / 2.25 AC input voltage range 85…264 V AC (Derating @
A @ 110 V AC 100 V AC)
Connection system DC current consumption 0.4 A @ 370 V DC / 1.2 A
Screw connection @ 120 V DC
DC input voltage range 80…370 V DC (Derating @ Frequency range AC
120 V DC) 47...63 Hz
Input frequency 47...63 Hz Input fuse (internal) Yes
Inrush current Rated input voltage 100...240 V AC (wide-
max. 40 A range input)
Recommended back-up fuse 4 A / DI, safety fuse Surge protection
6 A, Char. B, circuit breaker
3...5 A, Char. C, circuit
breaker Varistor
output
Capacitive load unrestricted Connection system Screw connection
Continous output current @ UNominal 10 A @ 55 °C, 7.5 A @ 70 Nominal output current for Unom
°C 10 A @ 55 °C
Output power 120 W Output voltage 12 V
Output voltage 10...16 V (adjustable via Overload protection
potentiometer) Yes
Parallel connection option yes, max. 5 Protection against inverse voltage Yes
Ramp-up time ≤ 100 ms Rated output voltage 12 V DC ± 1 %
Residual ripple, breaking spikes < 50 mV ss @ 12 V DC, I
Nenn
Erstellungs-Datum February 21, 2019 5:10:39 PM CET
Katalogstand 15.02.2019 / Technische Änderungen vorbehalten 2
Datenblatt
PROeco Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
PRO ECO 120W 12V 10A D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
Technische Daten www.weidmueller.com
General data
AC failure bridging time @ Inom > 80 ms @ 230 V AC / > Degree of efficiency
20 ms @ 115 V AC 87 %
Earth leakage current, max. 3.5 mA Housing version Metal, corrosion resistant
Indication LED green (Uoutput > MTBF
21.6 V DC), LED yellow
(Ioutput > 90% IRated
typ. ), LED red (overload,
overtemperature, short- > 500,000 h in
circuit, Uoutput < 20.4 V accordance with IEC
DC) 61709 (SN29500)
Max. perm. air humidity (operational) 5 %…95 % RH Mounting position, installation notice on terminal rail TS 35
Operating temperature Power factor (approx.) > 0.5 @ 230 V AC / > 0.53
-25 °C...70 °C @ 115 V AC
Power loss, idling 4W Power loss, nominal load 20 W
Protection against over-heating Protection against reverse voltages from
Yes the load > 18 V DC
Protection degree IP20 Short-circuit protection Yes
EMC / shock / vibration
Limiting of mains voltage harmonic in accordance with EN Noise emission in accordance with
currents 61000-3-2 EN55032 Class B
Vibration resistance IEC 60068-2-6 Interference immunity test acc. to EN 61000-4-2 (ESD),
EN 61000-4-3 (RS), EN
61000-4-4 (burst), EN
61000-4-5 (surge), EN
61000-4-6 (conducted),
EN61000-4-8 (Fields),
1 g according to EN50178 EN61000-4-11 (Dips)
Shock resistance IEC 60068-2-27 15 g In all directions
Insulation coordination
Insulation voltage output / earth 0.5 kV Insulation voltage output / earth 2 kV
Insulation voltage, input/output 3 kV Pollution severity 2
Protection degree I, with PE connection
Electrical safety (applied standards)
Electrical machine equipment For use with electronic equipment Acc. to EN50178 /
Acc. to EN60204 VDE0160
Protection against dangerous shock Protective separation / protection VDE0100-410 / acc. to
currents Acc. to VDE0106-101 against electrical shock DIN57100-410
Safety extra-low voltage SELV acc. to EN60950, Safety transformers for switch-mode
PELV acc. to EN60204 power supplies nach EN61558-2-16
Connection data (input)
Conductor cross-section, AWG/kcmil , Conductor cross-section, AWG/kcmil ,
max. 12 min. 26
Conductor cross-section, flexible , min. 0.5 mm² Conductor cross-section, rigid , max. 6 mm²
Conductor cross-section, rigid , min. 0.5 mm² Connection system Screw connection
Number of terminals 3 for L/N/PE Tightening torque, max. 0.6 Nm
Tightening torque, min. Wire connection cross section, flexible
0.5 Nm (input), max. 2.5 mm²
Erstellungs-Datum February 21, 2019 5:10:39 PM CET
Katalogstand 15.02.2019 / Technische Änderungen vorbehalten 3
Datenblatt
PROeco Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
PRO ECO 120W 12V 10A D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
Technische Daten www.weidmueller.com
Connection data (output)
Conductor cross-section, AWG/kcmil , Conductor cross-section, AWG/kcmil ,
max. 12 min. 26
Conductor cross-section, flexible , max. 2.5 mm² Conductor cross-section, flexible , min. 0.5 mm²
Conductor cross-section, rigid , max. 6 mm² Conductor cross-section, rigid , min. 0.5 mm²
Connection system Screw connection Number of terminals 6 (++,--,13,14)
Tightening torque, max. 0.6 Nm Tightening torque, min. 0.5 Nm
Signalling
Contact load (NO contact) max. 30 V DC / 1 A Floating contact Yes
Relay on/off Output voltage >21.6 V
DC/ <20.4 V DC, Overload
Approvals
Institute (cULus) Certificate no. (cULus)
E258476
Classifications
ETIM 5.0 EC002541 ETIM 6.0 EC002540
eClass 6.2 27-04-90-04 eClass 7.1 27-04-90-04
eClass 8.1 27-04-90-04 eClass 9.0 27-04-07-01
eClass 9.1 27-04-07-01
Product information
Descriptive text ordering data The internal varistor found in a switch-mode power supply does not replace the need for surge protection within
a system.
Approvals
Approvals
ROHS
Conform
Downloads
Approval/Certificate/Document of
Conformity DE_PA5200_160202_001.pdf
Brochure/Catalogue CAT 4.3 ELECTR 15/16 EN
Engineering Data EPLAN, WSCAD
Engineering Data STEP
User Documentation Operating instructions
Operating instructions
Erstellungs-Datum February 21, 2019 5:10:39 PM CET
Katalogstand 15.02.2019 / Technische Änderungen vorbehalten 4
Datenblatt
PROeco Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
PRO ECO 120W 12V 10A D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
Zeichnungen www.weidmueller.com
Electric symbol Derating curve
Erstellungs-Datum February 21, 2019 5:10:39 PM CET
Katalogstand 15.02.2019 / Technische Änderungen vorbehalten 5