(RA-GEMS) SM - V2S - User Manual
(RA-GEMS) SM - V2S - User Manual
User Manual
(Module Number: KGEOB10001)
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Identifies information that is critical for successful application and understanding of the
product.
AADvance, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
This document provides users of the Process Safety Toolkit with the
Introduction required information for the use of the Safety Two State Valve
(SM_V2S) in an AADvance based Safety Instrumented System.
A prerequisite for using the Process Safety Toolkit is that users have
the required AADvance and FTView proficiency and have taken the
Process Safety Toolkit training.
References
The following references should be consulted in conjunction with this
manual. The latest version of these documents are available from the
Rockwell Automation Literature Library.
Send/Receive
Method: Description:
Updated Information............................................................................................................................... i
Introduction ........................................................................................................................................... ii
OVERVIEW ..................................................................................................................... 1
Functional Overview.............................................................................................................................. 2
Alarms .................................................................................................................................................... 8
Instantiate ............................................................................................................................................ 15
Configure ............................................................................................................................................. 17
Examples ............................................................................................................................................. 19
Scenario 1 ............................................................................................................................................ 19
Scenario 2 ............................................................................................................................................ 21
Operator Device Commands (OCmd_), Maintenance Device Commands (MCmd_), and Readies
(Rdy_) ................................................................................................................................................... 35
Device Commands.................................................................................................................................. 35
Device Command Readies ........................................................................................................................ 36
HMI REFERENCE......................................................................................................... 42
Graphic Object..................................................................................................................................... 42
Graphical Representation ......................................................................................................................... 43
Mode Indicators ..................................................................................................................................... 44
Status Qualifier Indicators ......................................................................................................................... 45
Alarm Indicator....................................................................................................................................... 45
Faceplate.............................................................................................................................................. 47
FactoryTalk View ® Diagnostics ................................................................................................................. 48
Operator Tab ......................................................................................................................................... 49
Alarm Tab............................................................................................................................................. 52
Help Tab .............................................................................................................................................. 55
Maintenance Tab.................................................................................................................................... 57
Configuration - Device Tab ........................................................................................................................ 60
Overview
The SM_V2S (Two State Valve) object controls a Two State Valve in a
variety of modes and monitors for fault conditions. The Two State
Valve Function Block controls a single AADvance digital output, and
includes the capability to generate related digital output alarms, such
as Failed To Open, Failed To Close, and/or Illegal Feedback.
The Two State Valve Function Block includes the following
functionality
• Allows manual control of the valve output (when not in a
tripped state) by authorized personnel to handle testing or a
faulted input.
• Allows Maintenance Bypass by authorized personnel to carry
out maintenance work on the field device.
• Allows configuration of the Mean Time To Repair (MTTR), to
enable the object to alarm or alarm and shutdown a faulty
output after the configured time.
Use when:
• As part of the Safety Instrumented Function (SIF)
implementation you want to interface to a Two State Valve
which requires a single Digital Output (i.e. a single solenoid).
• You need to monitor and confirm the state of a Two State
Valve and produce alarms based on failed confirmation.
• You need to apply mode, permissives and interlocks to the
Digital Output.
Functional Overview
The following diagram provides an overview of the functionality of the module – it does NOT contain all
logical aspects. Of particular note are the absence of latches for statuses, the absence of ‘Configuration’
variables, and the effect of Disable on Safety Module functionality. For full functionality details, refer to
later sections of this document.
State
DO T9K.STA Validity
Check
State
Close Limit T9K.STA Validity Status1.7
Check OR (IO Fault)
State
Open Limit T9K.STA Validity
Check
Status1.4
(Discrepancy)
DO T9K.DIS
Status1.1
MCmd_MaintBypEnbl
Activate Maintenance Bypass
T (MaintByp Enabled)
Status1.15
TON
(MaintByp Expired)
Val_MaintBypTime
Val_MaintBypRT
Status2.1
(Any Close Command)
(Closed)
(A command to close the valve issued by either Operator
or Maintenance users or by Program control.)
Status2.3
Close Limit T9K.DI
(Closing)
Position
Status
Logic
Status2.4
Open Limit T9K.DI
(Opening)
Status1.14
(Loss of Opened)
Status1.10
AND
(Illegal Feedback)
Status1.11
AND TON
(Close Full Stall)
(Any Close Command)
(A command to close the Val_FullStallT
valve issued by either
Operator or Maintenance Status1.13 Status1.8
users or by Program
(Loss of Closed)
OR (Failed To Close)
control.)
AND TON
NOT
Val_TransitStallT
Status1.12
AND TON
(Open Full Stall)
(Any Open Command)
(A command to open the Val_FullStallT
valve issued by either
Operator or Maintenance Status1.14 Status1.9
users or by Program
(Loss of Opened)
OR (Failed To Open)
control.)
AND TON
NOT
Val_TransitStallT
Status1.6
MCmd_OOSEnbl
Disable Device
T (Disabled)
Status2.13
(Operator Mode)
Status2.15
(ProgOperLock)
Status1.5
NOT
(Config Error) Status2.12
AND
(Available)
Status1.6
NOT
(Disabled)
Status1.7
(IO Fault) Status1.2
TON
(MTTR PreExp)
Status2.9
Inp_Intl
(Bypassable Interlock Input) (Interlock Sts)
Status2.10
Inp_NBPerm
(Non-Bypassable Permissive Input) (NB Permissive Sts)
Status2.11
Inp_Perm
(Bypassable Permissive Input) (Permissive Sts)
LEGEND
Miscellaneous Main
Analog Discrete
Input/Output Input/Output
Input 1
Input 1 OR / AND Gate
Input Selector OR Output Logical OR / AND of ‘n’ Boolean inputs
Input 2 T Output Input 2 (only two shown in example OR gate)
Timer
Input TON Output
Timer function with optional ‘Remaining Time’ output.
Generates output based on timer type, Input status, and configured time ‘t’.
t Type may be TON (Timer ON delay), TOF (Timer OFf delay), or TP (Time Pulse).
Remaining Time
(optional)
Primary Operations The primary operations of the SM_V2S (Two State Valve) are to:
• Energize a solenoid to open the valve, or in the case of a
reverse acting (“fail open”) valve close the valve.
• Monitor optional open feedback and/or optional closed
feedback and display actual Valve status.
• Detect and alarm Failure to Open (feedback signal
confirming opened status not achieved with in defined
period), and Loss of Opened alarm (open limit made then
lost)
• Detect and alarm Failure to Close (feedback signal
confirming closed status not achieved with in defined period),
and Loss of Closed alarm ( closed limit made then lost)
• Monitor permissive conditions to prevent Valve operation.
• Monitor interlock conditions to drive Valve to ‘tripped’ state.
• Operate in maintenance, program and operator modes.
• Allow Maintenance Bypass of the device, available based on
security log in.
• Provide an “available” status, to indicate the Valve is
available for operation.
Modes of Operation The SM_V2S (Two State Valve) uses the following standard modes
implemented using embedded logic.
Mode Description
AADvance The SM_V2S will use the following space (code and data) in the
AADvance controller:
Code and Data Size
Component Overhead Per Instance
* The code and config space for these functions is included in the
instantiated data for this Function Block.
Alarms The SM_V2S (Two State Valve) has the following FactoryTalk View
alarms.
Alarm Description
* Close Full Stall While Closing, failed to lose the Opened confirmation
feedback within the configured time period
* Open Full Stall While Opening, failed to lose the Closed confirmation
feedback within the configured time period
Illegal Feedback Opened and Closed confirmation (limits) are both active
at the same time.
Quick Start
The Quick Start section is intended to provide a brief overview of the
steps required to implement a SM_V2S instance within your Controller
and HMI applications. Additional, detailed, information may be found in
the remainder of this document.
The files specified in the following sections are available from the
Package Downloader (search for ‘Process Safety Toolkit’). To install the
Package Downloader and be provided with access to the relevant
software, contact your regional GEMS Champion.
Perform the following steps to import the ActiveX component into your
FTView application. The provided data entry ActiveX file HMI-ActiveX-
Setup.exe needs to be registered on FTView SE server computers
and each client computer.
On HMI serve computer:
1. Copy HMI-ActiveX-Setup.exe to the following location:
C:\Users\Public\Documents\RSView Enterprise \ActiveX
Control Setup
2. Run the HMI-ActiveX-Setup.exe by double click the file.
On HMI client computer:
1. Copy HMI-ActiveX-Setup.exe to any location.
2. Run the HMI-ActiveX-Setup.exe by double-clicking the file.
Perform the following steps to import the SM_V2S Function Block into
your AADvance Controller application:
1. Store the provided SM_V2S.PXF file in a known location.
2. Open your AADvance Workbench project.
3. From the menu bar, click File > Import > Exchange File.
4. Select ‘Import from file’. Click Next.
5. Click ‘Browse’, and select the SM_V2S.pxf from the location in
which you stored it (as per step 1). Click Next.
6. Ensure the Function Block is selected in the Import Exchange
File window. Click Next.
7. Ensure the name is SM_V2S. Click Next.
8. Wait for the import to complete.
9. Click Close.
Determine whether the new module instance you want to create needs
Instantiate a Global or Local scoped tag.
1. A Global scoped tag is used when interface to the module is
required across multiple Programs.
2. A Local scoped tag is only available for use inside the
Program in which it resides.
In order to control the physical device, you must “map” the Input and
Map I/O Output interface points from the SM_V2S instance to the I/O cards
which contain the hardwired I/O for the physical device.
First determine the physical I/O associated to the device for which you
are creating the SM_V2S module instance. For the SM_V2S module,
the following I/O is used:
NOTE: If a Field I/O point is not mandatory and is not being used in
the configuration, it is necessary to create a ‘dummy’ variable of the
same type.
The following are the typical Interface Points to be used within your
logic:
• Commands (PCmd_) – Used to issue commands
• Statuses (Sts_) – Used to monitor status
• Values (Val_) – Used to monitor analog values
• Permissives (Perm, NBPm) – Used to enable/disable device
control
• Interlocks (IL, NBIL) – Used to drive the device to demand state
Examples Scenario 1
• Emergency Blowdown Valve (BDV1001) is a normally-
energized, normally closed valve with no limit switches.
• BDV1001 has one defined interlock, PAHH1001, which must
never be bypassed.
• All Alarms are not latched, and once the cause of the failure
has cleared the blowdown valve should return to the closed
position.
• In addition, the module shall annunciate the I/O Fault alarm if
the I/O module detects a fault.
• BDV1001 is controlled only by the application logic within the
controller; no manual command or Maintenance Bypass is
permitted.
Name: Value:
BDV1001.Cfg_Tag BDV1001
Tank 2
BDV1001.Cfg_Desc
Temperature
BDV1001.Cfg_MaintBypTime T#12hr
BDV1001.Cfg_MaintBypPreExpLim T#1hr
BDV1001.Cfg_MTTR T#12hr
BDV1001.Cfg_MTTRBypPreExpLim T#1hr
BDV1001.Cfg_FullStallTime T#5s
BDV1001.Cfg_TransitionStallTime T#10s
BDV1001.Config1 128
Config1.0 (Maint Byp) 0
Config1.1 (Spare) 0
Config1.2 (MTTR) 0
Config1.3 (Spare) 0
Config1.4 (Spare) 0
Config1.5 (Spare) 0
Config1.6 (Enable/Disable) 0
Config1.7 (IOFault) 1
Config1.8 (Failed To Close) 0
Config1.14 (Spare) 0
Config1.15 (Spare) 0
BDV1001.Config2 9
Config2.0 (Output auto-reset) 1
Scenario 2
• Shutdown Valve (ESV8005) is a normally-energized, normally
open solenoid valve with open (ESZO8005) and closed
(ESZC8005) limit switches.
• ESV8005 has connections to various programs within the
controller. These connections are combined externally into two
interlocks; one defined interlock (ESV8005_NBIL) must never
be bypassed, and another (ESV8005_IL) may be bypassed.
• All Alarms are configured (I/O Fault, Fail To Open, Failed To
Close, Illegal Feedback) and must be latched. Once the cause
of the failure has cleared the shutdown valve should not return
to the opened position until commanded to do so by the
operator.
• A non-bypassable permissive (ESV8005_NBPerm) is also
connected to allow the operator to open the valve only when
permitted.
• Maintenance Bypass is allowed. A 12-hour limit is applied to
all Maintenance Bypasses, with a 45-minute warning before
expiration.
• The valve SIF has a defined MTTR of 48hrs, but the valve
shall take no action on expiration. The end-user requests a
warning 1-hour before the MTTR expires so that they may
prepare to take action manually.
• The valve should close within 5-seconds of demand, and
should appear to have started closing within 2 seconds.
• The valve is part of a multi-train process, and may be disabled
by the operator if the process train is not in use.
• The operator wishes to see the valve voltage and current on
the faceplate.
Name: Value:
ESV8005.Cfg_Tag ESV8005
Tank 2
ESV8005.Cfg_Desc
Temperature
ESV8005.Cfg_MaintBypTime T#12hr
ESV8005.Cfg_MaintBypPreExpLim T#45min
ESV8005.Cfg_MTTR T#48hr
ESV8005.Cfg_MTTRBypPreExpLim T#1hr
ESV8005.Cfg_FullStallTime T#2s
ESV8005.Cfg_TransitionStallTime T#5s
ESV8005.Config1 16325
Config1.0 (Maint Byp) 1
Config1.1 (Spare) 0
Config1.2 (MTTR) 1
Config1.3 (Spare) 0
Config1.4 (Spare) 0
Config1.5 (Spare) 0
Config1.6 (Enable/Disable) 1
Config1.7 (IOFault) 1
Config1.8 (Failed To Close) 1
Config1.9 (Failed To Open) 1
Config1.10 (Illegal Feedback) 1
Config1.11 (Closed Limit Switch) 1
Config1.12 (Opened Limit Switch) 1
Config1.13 (V & I displayed) 1
Config1.14 (Spare) 0
Config1.15 (Spare) 0
ESV8005.Config2 776
Config2.0 (Output auto-reset) 0
Config2.1 (Safe State on MTTR) 0
Config2.2 (NDE output) 0
Config2.3 (NC valve) 1
Config2.4 (Spare) 0
Config2.5 (Spare) 0
Config2.6 (Spare) 0
Config2.7 (Spare) 0
Config2.8 (Latch alarms) 1
Config2.9 (Latch IOFault) 1
Config2.10 (Spare) 0
Config2.11 (Spare) 0
Config2.12 (Prog Mode > Oper) 0
Config2.13 (Prog Mode default) 0
Config2.14 (Spare) 0
Config2.15 (Spare) 0
Notes:
Configuration Enter the appropriate values from the following table into the SM_V2S
Function Block instance’s configuration parameters to configure it for
Parameters your application.
Use FactoryTalk View to set the string parameters, and AADvance
Workbench to set the applicable Configuration Parameters.
The parameters are organized into tables of functional subgroups
below which are also associated with a supporting HMI faceplate.
Note: Replace the string “<alarm>” in the generic element name with
any of the following specific alarm names to get the specific element:
• FailedToClose (inc. Loss of Closed and Open Full Stall)
• FailedToOpen (inc. Loss of Opened and Close Full Stall)
• IllegalFeedback
• IOFault
• MaintBypPreExp
• MaintBypExp
• MTTRPreExp
• MTTRExp
Configuration – HMI Interface: These parameters determine the text displayed on the Faceplate, command confirmation and
other HMI attributes.
Configuration – Alarms: These parameters determine the behavior of Valve alarms, including whether or not the alarm is
actively evaluated.
• Set (=1)
Each Valve alarm Latches. The user (HMI
or Logic) must issue a reset command after
the alarm condition returns to normal.
• Clear (=0)
The module automatically clears each Valve
alarm when the alarm condition returns to
normal
• Set (=1)
The IOFault alarm Latches. The user (HMI
or Logic) must issue a reset command after
the alarm condition returns to normal.
• Clear (=0)
The module automatically clears the IOFault
alarm when the alarm condition returns to
normal
Cfg_<alarm>Severity 1 Configuration value for <alarm> Severity: Val_Notify
1..250=Low,
251..500=Medium
501..750=High
751..1000=Urgent
Configuration – Alarm Thresholds, Deadband, & Duration: These parameters determine the levels at which each specific
Valve alarm is triggered and cleared.
Once the Config1.x (‘Has <alarm>’) configuration item is cleared (= Once the Config
0), the module will no longer generate the associated alarm, and the 0
Alarm Panel for the associated alarm will disappear from the HMI Alarm Panel for
Faceplate. Faceplate.
Each alarm is configured with a Priority value (as per value in the
table above). In the case where multiple alarms within the SM_V2S
Function Block are active simultaneously, Val_Notify will contain the
numeric value associated with the highest Priority alarm.
Configuration – Miscellaneous: These parameters determine the functionality used by the Valve and EU Minimum and
Maximum values for scaling the HMI.
Configuration – Program Interface: These parameters define the interaction between the Valve and the application program.
Notes:
Configuration (Cfg_) Configuration Data Elements are used to set configurable capabilities,
features and functions of the SM_V2S Safety Module.
The following Configuration data may be modified using the AADvance
Workbench:
Associated
Data Usage Configuration
Name: Type: : Default: Style: Description: Parameters:
Config1.8 UINT Input 1 BOOL 1=Failed To Close Condition exists and will
be checked
Config1.9 UINT Input 1 BOOL 1= Failed To Open Condition exists and will
be checked
Associated
Data Usage Configuration
Name: Type: : Default: Style: Description: Parameters:
Cfg_MTTRPreExpLim TIME Input T#4hr Time Mean Time to Repair Pre-Expiration Alarm
Time Threshold
Cfg_FullStallTime TIME Input T#5s Time Full Stall Time. Defines the period of time
(seconds) the module waits after receiving
command before setting the Full Stall
Status.
Cfg_TransitStallTime TIME Input T#15s Time Transit Stall (‘Movement’) Time. Defines
the period of time (seconds) the module
waits after receiving command before
setting the Failed To Close / Failed To
Open Status.
Alarms Subcategory The following Cfg_ tag elements are generic for all alarms defined for SM_V2S.
Replace the string “<alarm>” in the generic element name with any of the following specific alarm
names to get the specific element:
• FailedToClose
• FailedToOpen
• IllegalFeedback
• IOFault
• MaintBypPreExp
• MaintBypExp
• MTTRPreExp
• MTTRExp
Mode Commands (PCmd_, Mode Command Data Elements are used by application logic to
request SM_V2S mode-related actions, such as changing or
OCmd_, MCmd_) and Mode locking Modes.
Readies The following diagram shows how the various modes are
acquired and released and their priority. Note that each layer is
always active; that is, Program and Operator mode commands
affect the state of the Program / Operator mode even when
Maintenance Mode, is active.
The modes have the following priority:-
• Maintenance (Highest)
Control of the device is owned by maintenance. Operator
Commands and Settings from the HMI are accepted.
Bypassable interlocks and permissives are bypassed.
Non-bypassable interlocks and permissives override any
Maintenance commands.
• Program
Control of the device is owned by Program logic.
Program Commands (PCmd_) are accepted. All
interlocks and permissives are processed and override
any Program commands.
• Operator (Lowest)
Control of the device is owned by the operator. Operator
Commands (OCmd_) from the HMI are accepted. All
interlocks and permissives are processed and override
any Operator commands.
Maintenance Mode
Maint
MCmd_MaintBypRmv MCmd_MaintBypEnbl
PCmd_Unlock
PCmd_Acq OR PCmd_Rel OR
OCmd_UnlockRel OCmd_AcqLock
OCmd_UnlockRel
Mode Commands
Associated
Configuration
Name: Data Type: Usage: Default: Style: Description: Parameters:
Associated
Configuration
Name: Data Type: Usage: Default: Style: Description: Parameters:
Program Device Program Command Data Elements are used by application logic to
request SM_V2S actions, such as opening or closing the valve.
Commands (PCmd_)
Application logic sets the Program Command to 1 to request the
action. (See the Edge and Level section in the Preface for more
information). The SM_V2S Safety Module then performs the requested
action if it is in Program Mode and the action can be performed.
Device Commands
Associated
Configuration
Name: Data Type: Usage: Default: Style: Description: Parameters:
Operator Device Operator Commands and Maintenance Commands are used by the
Operator at the HMI to request actions, such as enabling or disabling,
Commands (OCmd_), suppressing or un-suppressing alarms; or other instance-specific
Maintenance Device actions.
Operator Commands are set (latched) by the HMI and are read and
Commands (MCmd_), then cleared (unlatched) by this Function Block, allowing a many-to-one
and Readies (Rdy_) relationship between HMI requestors and each Command.
Device Commands
Associated
Configuration
Name: Data Type: Usage: Default: Style: Description: Parameters:
Associated
Configuration
Name: Data Type: Usage: Default: Style: Description: Parameters:
Values (Val_) Value Data Elements contain process or device variables, the
notification level for alarm animation, and the current accepted values of
any limits or other settings (from Program Settings) for the SM_V2S
Function Block. The HMI displays these Values, and they are available
for use by other application logic.
Data Access for all Value Data Elements is set to Read Only, unless
noted in the “Usage” column (N = None, W = Read/Write)
Associated
Configuration
Name: Data Type: Usage: Default: Style: Description: Parameters:
0 = None
1 = Not in alarm, unacknowledged or reset
Val_Notify
required
2 = Low
4 = Medium
6 = High
8 = Urgent
From #2, # + 1 = Unacknowledged
Val_Current INT Output Decimal Digital Output Current
Val_Voltage UINT Output Decimal Digital Output Voltage
Status (Sts_) Status Data Elements contain process or device states, Mode status
and Alarm status. The HMI displays these Status points, and they are
available for use by other application logic.
Device Status
Associated
Configuration
Name: Data Type: Usage: Default: Style: Description: Parameters:
Associated
Configuration
Name: Data Type: Usage: Default: Style: Description: Parameters:
Status2.7
UINT Output BOOL 1=Any Limit Switch Fault (Input ≠2 and ≠4) or both limit •
switches on (Illegal Feedback)
UINT Output BOOL 0=Non-Bypassable Interlocks okay, •
Status2.8
1=Non-Bypassable Interlock input demand
UINT Output BOOL 0=Bypassable Interlocks okay, •
Status2.9
1=Bypassable Interlock input demand
UINT Output BOOL 0=Non-Bypassable Permissive okay, •
Status2.10
1=Non-Bypassable Permissive input demand
UINT Output BOOL 0=Bypassable Permissive okay, •
Status2.11
1=Bypassable Permissive input demand
Mode Status
Associated
Configuration
Name: Data Type: Usage: Default: Style: Description: Parameters:
Associated
Configuration
Name: Data Type: Usage: Default: Style: Description: Parameters:
Alarms Subcategory The following Cfg_ tag elements are generic for all alarms defined for SM_V2S.
Replace the string “<alarm>” in the generic element name with any of the following specific alarm
names to get the specific element:
• FailedToClose
• FailedToOpen
• IllegalFeedback
• IOFault
• MaintBypPreExp
• MaintBypExp
• MTTRPreExp
• MTTRExp
Notes:
HMI Reference
This chapter describes the HMI Graphic Object(s) and Faceplate(s)
provided for the GEMS SM_V2S (Two State Valve) and their detailed
features and functions.
Graphic Object Graphic Object(s) are used on the HMI Operator screens, and provide
end-users with:
• Information on the Valve’s current state.
• A touch field to open the Valve’s faceplate.
• A label (Valve’s device tag).
Graphical Representation
Grey Closed
White Opened
Magenta Unknown
Mode Indicators
SM_V2S Graphic Object(s) contain mode indicators for the Valve. The
following table lists the mode indicators.
SM_V2S Graphic Object(s) contain status qualifiers for the Valve. The
following table lists the status qualifier indicators.
Status1.7,
PVBad, Device Out of Range,
Status1.4,
Input Discrepancy, Under-
Status1.12,
Range, or Over-Range
Status1.13
Disabled Status1.6
Alarm Indicator
<alarm>.Disabled
Alarm Disabled or Shelved
<alarm>.Shelved
or Suppressed
<alarm>.Suppressed
Faceplate The SM_V2S Faceplate consists of tabbed pages. The Operator page
is the default display, when the Faceplate opens. Click the appropriate
tab at the top of the Faceplate to access a specific page.
Maintenance Exit
Any action initiated from the SM_V2S Faceplate (at run time) will be
logged in the FactoryTalk View ® Diagnostic log, this includes:
• Commands
• Setpoints
Operator Tab
Valve Description
Navigation
Mode Command
Mode Indication Buttons
Command Pane
Output current
and voltage
Communication
Status Indicator
Associated
Indicator Status Parameter
Security
Button / Field Action Required
Alarm Tab
The Alarm page provides a listing of all Alarms for the Valve. Each
Alarm is individually annunciated on this page, and each Alarm may
be disabled, enabled, acknowledged, and reset from this page.
Alarm Indicator /
Navigation Icon
Alarm Panel
Alarm Acknowledge
Command
Alarm Reset
Buttons
Associated
Indicator Status Parameter
Medium
4 Yellow
priority
Security
Button / Field Action Required
Help Tab
The Help page provides Help information for various commands and
status’s available on the Valve Faceplate.
Help
Navigation
Icons
Security
Button / Field Action Required
Maintenance Tab
Maintenance
Navigation Icon
Configuration
Faceplate Navigation
Disabled Indicator
Mode Indicator
Associated
Indicator Status Parameter
Security
Button / Field Action Required
Configuration
Device Tab
Navigation Icon
Description
Tag Name
Device Configuration
Check Boxes / Fields
Configuration Error
Alarm Error
Notes: