FOK-EIS-120 Fire Dampers CE Certification
FOK-EIS-120 Fire Dampers CE Certification
EN 15650:2010
• The fire dampers FOK-EIS-120 work as a separator • The casing is made of galvanised steel, and joined by
between two sectors of fire and ensure the same fire clinching system (cold forming the material).
resistance that the structural elements of
compartmentalisation, which limits the risk of spreading • It incorporates a solid perimeter frame to facilitate the
of fire by interior of the building. sealing between the fire damper and support
construction.
• FOK-EIS-120 fire dampers are according with the
following standards: • The housing is made from galvanized steel. It has a
symmetrical design that allows wall mounting
European Test Standard, EN 1366-2
regardless of air flow.
(Fire resistance tests for service installations –
Part 2: Fire dampers)
• The blade is made of ceramic material resistant to
European Classification Standard, EN 13501-3
high temperatures and abrasion.
(Fire classification of construction products and building
elements – •These dampers meet the conditions required for the
Part 3: Classification using data from fire resistance tests on symbol (S) to cold smoke seal.
products and elements used in building service installations:
fire resisting ducts and fire dampers) • The airtightness to the passage of cold smoke is
achieved through a joint between the perimeter of the
European Standard for CE Marking, EN 15650 housing and the blade.
(Ventilation for buildings. Fire dampers)
• For high temperatures, the damper is equipped with
European Test Standard, EN 60529:1991 an expanding intumescent seal, forming a paste that
(Degrees of protection provided by enclosures (IP Code))
prevents the passage of hot air and smoke from one
side of the damper to another.
European Test Standard EN 1751
(Ventilation for buildings – Air terminal devices –
• The operating devices of the dampers is automatic
Aerodynamic testing of dampers and valves)
shooting by means of a thermal fuse calibrated at 72°C
International Test Standard ISO 10294-4
to activate the closure when reaches that temperature.
(Fire resistance tests – Fire dampers for air distribution systems
Reset is manual except for motorized dampers.
Part 4: Test of thermal release mechanism)
02/18 1
DECLARATION OF PERFORMANCES
APPLUS - 0370
Performed tasks:
- Determination of the product type on the basis of type testing
(including
sampling), type calculation, tabulated values or descriptive
documentation of the
product;
- Initial inspection of the manufacturing plant and of factory
production control;
5. Certification body:
- Continuous surveillance, assessment and evaluation of factory
production control.
System 1
Certification number: 0370 – CPR – 1380
Test report:
11/3034-2632, 12/5477-1359, 14/8629-797, 17/12815-16,
18/12815-1800, 14/8629-947, 18/12815-700, 18/12815-701,
18/12815-703, 18-17552-1206
6. Performances (EN 15650 :2010):
Type of Mechanism
Dimensions Type Wall Class
installation orientation
7. The performances of the product identified in point 1, are in line with the declared performance in point 6.
This declaration of performance is issued under the responsibility of the
manufacturer listed in point 2.
Signed for and on behalf of the manufacturer:
02/18 2
CLASSIFICATION
…-MA Manual resetting damper. Is not necessary to open the box device.
…-MF… Damper operated by an actuator with switch off device at 24 or 230V.
PARTS
FOK-EIS-120-MA FOK-EIS-120-MF…
10
10 3
3
2 9
2 9
8
8
4
4 7
7
5
5 6
6 1
1
1. Casing 6. 6.Brida
90ºdeangled
conexión a 90º
flange 1. Casing 6. 90º angled flange
2. Blade 7. 7.Mecanismo
Operating/MA/
device /MA/ 2. Blade 7. Actuator /MF…/
3. Airtightness seal 8. 8.Indicador deindicator
Position posición 3. Airtightness seal 8. Position indicator
4. Intumescent seal 9. 9.Pulsador de accionamiento
Test button 4. Intumescent seal 9. Test switch
5. Perimetral frame 10. 10.
Fusible térmico
Thermal fusea 72ºC
72ºC 5. Perimetral frame 10. Thermoelectrical fuse 72ºC
DIMENSIONS
FOK-EIS-120-MA L L H H1
(mm) (mm) (mm) (mm)
200 700 200 -
250 800 250 -
300 900 300 -
350 1000 350 -
400 1100 400 -
450 1200 450 25
500 1300 500 50
550 1400 550 75
600 1500 600 100
700 150
FOK-EIS-120 /CR … 800 200
FOK-EIS-120-MF…
A B C
Ref. S/ dim.
(mm) (mm) (mm)
MFS… 115 121 32
MFS… 115 121 32
MFS… 191 121 40
MFB… 150 121 25
MFB… 160 121 32
02/18 3
OPERATING DEVICES
Optional 2 3
…- /PIF/ Closed switches device fig. MA
L
200… 1000 1050… 1500
200… 550 - /MA/ - /MA/
H
600… 800 - /MA/ -
Close (unlocking) A B
• Manual: Pressing the unlocking button (A)
• Automatic: The fusible link reaches 72ºC (B)
• Remote: - 72ºC
Open (resetting) C
• Manual: Turning counterclockwise 90º the manual resetting axe using a
tool with a smaller diameter than 8mm (C)
• Automatic: - 90º
0º
Electrical connection
*Switches normally closed contacts
NO NF COM NO NF COM
FC DC
Closed damper Open damper
signal signal
NO NF NO NF NO NF NO NF
CONTACT "FC" CONTACT "DC" CONTACT "FC" CONTACT "DC”
02/18 4
OPERATING DEVICES
Standard: 3
- Internal and external thermoelectrical fuse 72ºC 1
- Automatic resetting 9
- Automatic closing by fuse 72ºC
- Remote closing by interruption of power supply
- Manual test switch
- LED status fusible indicator
- Position damper indicator 4
- Closed switches
- IP54 Protection
5
Reference Time
a/size
Torque Voltage Consumption
Open/ Close
6 7
MFS24V 4 Nm CA 24V, CC 24/48V 3,5W (running)/ 2W (stationary) 90s/ 15s
MFS230V 4 Nm CA 230V 4,5W (running)/ 3,5W (stationary) 90s/ 15s fig. MFS…V
MFS24V 7 Nm CA 24V, CC 24/48V 3,5W (running)/ 2W (stationary) 90s/ 15s
MFS230V 7 Nm CA 230V 4,5W (running)/ 3,5W (stationary) 90s/ 15s 1. Actuator
MFS24V 18 Nm CA 24V, CC 24/48V 5W(running)/ 4W (stationary) 90s/ 15s 2. Position damper indicator
MFS230V 18 Nm CA 230V 6W (running)/ 4W (stationary) 90s/ 15s 3. Manual resetting
4. Manual lock
L 5. Plug closed switches cable
200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500
6. Thermoelectrical fuse cable
200
250 7. Power supply cable
300 8. Thermoelectrical fuse 72ºC
350
400
9. Manual test switch
450 10. LED status fusible indicator
H 500
550
600
650
700
750
800
Close (unlocking) A B C
• Manual: Pressing the manual test switch (A)
• Remote: By interrupting the power supply (B)
• Automatic: The fusible link reaches 72ºC (C) 72ºC
Open (resetting) D E
• Manual: Turning counterclockwise the manual resetting with allen key (D)
To keep the blade open, lock by manual lock
• Automatic: By supplying the power supply (E)
Electrical connection
AUXILIARY SWITCHES CABLE ACTUATOR 230VCA
MEANING Nº COLOR MEANING Nº COLOR
Switch "A" input S1 grey/ red Line 230VCA 3 Brown
Switch "A" normally-closed contact S2 grey/ blue Neutral 4 Blue
Switch "A" normally-open contact S3 grey/ pink
A. CLOSED DAMPER B. OPEN DAMPER
Switch "B" input S4 black/ red
S1 S4 S1 S4
Switch "B" normally-closed contact S5 black/ blue
Switch "B" normally-open contact S6 black/ pink
ACTUATOR 24VCA/24…48VCC S2 S3 S5 S6 S2 S3 S5 S6
CONTACT “A” CONTACT “B” CONTACT “A” CONTACT “B”
MEANING Nº COLOR
System potential 24VCA/ 24…48VCC 1 red • Fixed switching points at 5º and 80º
System neutral 2 black •• Fixed switching point at 5º to contact “A”
•• Fixed switching point at 80º to contact “B”
02/18 5
OPERATING DEVICES
Standard:
- Internal and external thermoelectrical fuse 72ºC 1 4
- Automatic resetting
- Automatic closing by fuse 72ºC 3
- Remote closing by interruption of power supply
- Manual test switch
- LED status fusible indicator
1. Actuator
- Position damper indicator 2. Position damper indicator
- Closed switches 3. Manual resetting
- IP54 Protection 4. Manual lock
5. Plug closed switches cable 7 5
6. Thermoelectrical fuse cable
7. Power supply cable
8. Thermoelectrical fuse 72ºC
9. Manual test button 6
10. LED status fusible indicator
fig. MFB…V
Reference Time Open/
Torque Voltage Consumption
a/size Close
MFB24V 9 Nm CA 24V/ CC 24/48V 4W (running)/ 1,4W (stationary) 60s/ 20s
Close (unlocking) A B C
• Manual: Pressing the manual test switch (A)
• Remote: By interrupting the power supply (B)
• Automatic: The fusible link reaches 72ºC (C) 72ºC
Open (resetting) D E
• Manual: Turning counterclockwise the manual resetting with allen key (D)
To keep the blade open, lock by manual lock
• Automatic: By supplying the power supply (E)
Electrical connection
MEANING Nº BFL/ BFN BF ACTUATOR 230VCA
Switch "A" input S1 Violet White MEANING Nº COLOR
Switch "A" normally-closed contact S2 Red White Neutral 1 Blue
Switch "A" normally-open contact S3 White White Line 230VCA 2 Brown
Switch "B" input S4 Orange White
A. CLOSED DAMPER B. OPEN DAMPER
Switch "B" normally-closed contact S5 Pink White
S1 S4 S1 S4
Switch "B" normally-open contact S6 Grey White
ACTUATOR 24VCA/24…48VCC
MEANING Nº COLOR
S2 S3 S5 S6 S2 S3 S5 S6
Neutral 1 Black CONTACT “A” CONTACT “B” CONTACT “A” CONTACT “B”
02/18 6
GENERAL POINTS
• The MADEL fire dampers are classified for the supporting constructions described in this manual or similar
supporting constructions with a same or superior fire resistance (more thickness/ density or number of
boards (according to EN 1366-2).
• Any variation in supporting construction as described in the previous point, different sealing or type of
installation regarding this document, the fire damper will not comply the classification.
• Install the fire damper with the blade closed and avoid excessive pressures in its casing.
• Avoid to project materials to the interior of the tunnel.
• Avoid vibrations in the installation.
• Check the opening and closing after the installation.
• The inner dimension of the air ducts can not be smaller than inside dimension of the damper.
02/18 7
INSTALLATION
- RIGID WALL
nom
0º 180º ina
l +1
50
±20
±20
Hnominal + 150
144
Starting plane of supporting construction/ sealing
4. Sealing
DETAIL A
A
Sealing: Mortar
02/18 8
INSTALLATION
- FLEXIBLE WALL
Dimensions Supporting construction Sealing Classification
3
Flexible 15 x2 (Plasterboard type F, s/ EN 520) + 48 (LM, 50Kg/m ) + Plasterboard +
200 x 200 to 1000 x 600 EI120 (ve i↔o) S (500Pa)
wall 15 x2 (Plasterboard type F, s/ EN 520), modulation 400mm ≥ 108mm instumescent mastic
* LM Mineral wool
0º 180º
3. Mounting frame
DETAIL A
DETALLE A
HóL H1 L1
(mm) (mm) (mm)
200 275 275
3 250 325 325
150
8
300 375 375
350 425 425
400 475 475
A
2
450 525 525
SECTION
SECCIÓN A-A’
A-A'
8 500 575 575
A' 4
7 550 625 625
DETALLE A
600 675 675
15 15
H1
B B'
L1 650 725 725
8 3
700 775 775
750 825 825
30
DESCRIPTION
Modulation spaced 400mm. Support structure consists in,
1. H Vertical profiles ( 48mm)
- Two vertical profiles, forming an “H” each one, spaced L1 and isolated with 2. H Horizontal profiles (48mm)
mineral wool (section A-A’). 3. Vertical profiles (48mm)
4. plasterboard type F (15mm)
- Two horizontal profiles, forming an “H” each one, spaced H1 and isolated with 5. Mineral wool
double plasterboard (section B-B’). 6. Vertical profile (48mm)
7. Steel metal screws (3.5 x 45 mm)
- “H” Horizontal profiles fixed to “H” vertical (Detail A) 8. Steel metal screws (3.5 x 9.5 mm)
02/18 9
INSTALLATION
- FLEXIBLE WALL
1 2
H1
L1
DESCRIPTION
1. Plasterboard 15mm
2. Steel metal screws (3,5 x 25mm)
Fix the first side of plasterboards on one side of the structure and trim the perimeter describer by the damper support
structure.
5. Isolation installation
DESCRIPTION
1. MINERAL WOOL(40mm, 50Kg/m3)
Fill the gap between the metal structure with mineral wool.
02/18 10
INSTALLATION
- FLEXIBLE WALL
1 2
DESCRIPTION
1. Plasterboard 15mm
2. Steel metal screws (3,5 x 25mm)
Fix the second side of plasterboards on the remaining side of the structure and trim the perimeter describer by the damper
support structure. The second plasterboard side must alternate the joints with the first side.
Then, it is carried out the joints processing between the plasterboards.
7. Sealing
DETAIL A DETAIL B
4
5 3
7
2
100
30
B
A
1
6
0º
9
45º
-5º
ST
OP
DESCRIPTION
1. FOK-EIS-120
2. Steel metal screws 4.2 x 70mm
3. Plasterboard (type F) 15mm
4. Mineral wool (48mm, 50Kg/m3
5. Horizontal profiles “H”
6. Intumescent mastic
7. Gap filled of Intumescent mastic
Place the damper such that the axis of the blade matches with the middle of the wall section. Seat correctly the damper into
the wall and fill the gap between them with plasterboard strips (30 mm width).
Fix the covering tapes (plasterboard strips, 100 mm width) to the support structure all around the perimeter of the damper
and on both sides.
Finally, we fill the gap between covering tapes and between covering tapes and the fire damper with intumescent mastic.
02/18 11
INSTALLATION
- RIGID FLOOR
0
±2
50 Hn
l +1 om
ina ina
no
m l +1
L 50 ±2
0
150 ≤ e 200 ≤ e
(dim. ≤ 1000 x 600) (dim. > 1000 x 600)
144
100
100
144
4. Sealing
DETAIL A
Sealing: Mortar
02/18 12
SPECIFICATION TEXT
(Manual)
Manufacturer MADEL.
(Motorized)
Manufacturer MADEL.
CODIFICATION
02/18 13
TECHNICAL DATA
FOK-EIS-120
FREE AREA FOR THE AIR PASS (m2) / CORRECTION VALUES FOR DPt, Lwa
L 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
H
Afree 0,007 0,019 0,03 0,042 0,053 0,065 0,077 0,088 0,1 0,111 0,12 0,13 0,14 0,155 0,166
200 Kr 1,070 1,075 0,930 0,920 0,895 0,875 0,865 0,855 0,845 0,830 0,815 0,8 0,785 0,77 0,76
Kf -24 -21,75 -17,5 -15,5 -14 -11,75 -10,25 -9,5 -8,75 -8 -7,5 -7,25 -7 -6,75 -6,5
Afree 0,013 0,035 0,056 0,078 0,099 0,121 0,143 0,164 0,186 0,207 0,22 0,25 0,26 0,28 0,31
300 Kr 0,805 0,790 0,740 0,685 0,645 0,625 0,615 0,6 0,59 0,58 0,57 0,56 0,545 0,53 0,515
Kf -18 -17,25 -13 -10,5 -8,75 -7,25 -6 -5 -3,75 -3 -2,75 -2,5 -2,25 -2 -1,75
Afree 0,019 0,051 0,082 0,114 0,145 0,177 0,209 0,240 0,270 0,303 0,33 0,367 0,39 0,42 0,45
400 Kr 0,735 0,715 0,655 0,595 0,550 0,530 0,525 0,490 0,480 0,470 0,46 0,450 0,445 0,43 0,415
Kf -18 -14,5 -10,5 -9 -6,25 -4 -3,25 -2,25 -1 -0,5 -0,45 -0,4 -0,35 -0,325 -0,3
Afree 0,025 0,067 0,108 0,150 0,191 0,233 0,275 0,316 0,358 0,399 0,44 0,483 0,518 0,558 0,598
500 Kr 0,675 0,670 0,585 0,520 0,485 0,450 0,440 0,415 0,410 0,4 0,39 0,38 0,375 0,36 0,345
Kf -16 -11,75 -8,5 -6 -3,5 -2 -0,75 -0,25 0,75 2,5 2,25 2 1,75 1,5 1,25
Afree 0,031 0,083 0,134 0,186 0,237 0,289 0,341 0,392 0,444 0,495 0,54 0,599 0,643 0,693 0,742
600 Kr 0,655 0,630 0,535 0,470 0,425 0,4 0,375 0,365 0,360 0,345 0,33 0,32 0,302 0,029 0,27
Kf -14,75 -10,25 -6,5 -3,5 -2,25 -0,25 1 2 3 4 4 4 4 4 4
Afree 0,037 0,099 0,16 0,22 0,28 0,34 0,4 0,46 0,53 0,59 0,65 0,715 0,767 0,82 0,88
700 Kr 0,635 0,58 0,5 0,44 0,4 0,37 0,35 0,33 0,32 0,31 0,3 0,28 0,265 0,25 0,24
Kf -14,75 -10,25 -6,5 -3,5 -2,25 -0,25 1 2 3 4 4 4 4 4 4
Afree 0,043 0,115 0,186 0,25 0,32 0,4 0,47 0,54 0,61 0,68 0,75 0,83 0,88 0,95 1,02
800 Kr 0,605 0,56 0,49 0,42 0,38 0,35 0,32 0,31 0,3 0,29 0,27 0,26 0,245 0,23 0,22
Kf -14,75 -10,25 -6,5 -3,5 -2,25 -0,25 1 2 3 4 4 4 4 4 4
Lwa = Lwa1 + Kf
Dpt(Pa)
02/18 14
TECHNICAL DATA
FOK-EIS-120
Vf (m/s)
1 1.5 2 3 4 5 6 7 8 9 10
A free(m 2 )
1 24
Q 17 00
(m 00 0
0.8 3/h 14 0
) 12 0 0
0 0
0.6 10 00
0
80 00
0.5 00
65
0.4 55 00
0
45 0
00
0.3 35
0
30 0
00
25
0.2 0
18 0
00
16
0.15 0
13 0
00
11
0
0.1 90 0
0
70
0.08 0
50
0
0.06 40
0
0.05 30
0
0.04 20
0
0,03
0,02
100
DPt ( Pa )
80
1
Kr
60
0,8
40 0,6
55
30
0,4
) 50
20 A)
(
15 B 45
(d 0,2
=
10 a1 40
w
L
35
5
4
3
2
1
1 1.5 2 3 4 5 6 7 8 9 10
Vf (m/s)
02/18 15