0% found this document useful (0 votes)
414 views28 pages

Modbus Protocol Manual for SIL-A Relay

This document describes the Modbus protocol implementation for communicating with the SIL-A overcurrent and earth fault protection relay. It outlines the Modbus RTU packet format, supported function codes for reading and writing registers, memory map organization, and examples of Modbus frames. Communication is over RS-232, RS-485, or Ethernet using Modbus RTU or TCP/IP with default network settings provided. The memory map contains registers for states, measurements, fault reports, and settings that can be accessed via Modbus function codes 03 for reading and 16 for writing multiple registers.

Uploaded by

alvicgi_97
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
414 views28 pages

Modbus Protocol Manual for SIL-A Relay

This document describes the Modbus protocol implementation for communicating with the SIL-A overcurrent and earth fault protection relay. It outlines the Modbus RTU packet format, supported function codes for reading and writing registers, memory map organization, and examples of Modbus frames. Communication is over RS-232, RS-485, or Ethernet using Modbus RTU or TCP/IP with default network settings provided. The memory map contains registers for states, measurements, fault reports, and settings that can be accessed via Modbus function codes 03 for reading and 16 for writing multiple registers.

Uploaded by

alvicgi_97
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

SIL-A

Overcurrent & Earth


Fault Protection Relay

MODBUS PROTOCOL MANUAL

EN_FANOXTD_MANU_SIL_MODBUS_SILA_R006.Doc
1. MODBUS PROTOCOL .................................................................................................... 3
1.1. Modbus RTU pachage format ........................................................................................ 4
1.2. Function Codes............................................................................................................... 5
1.3. Exceptions Responses .................................................................................................. 5
1.4. Data type .......................................................................................................................... 6
1.5. General Memory Map ..................................................................................................... 7
1.5.1. States Map ................................................................................................................... 8
1.5.2. Measurements Map.................................................................................................... 18
1.5.3. Fault report measurements Map ................................................................................ 18
1.5.4. Settings Map .............................................................................................................. 19
1.6. Command List ............................................................................................................... 26
1.7. Setting-up the session: Password and access levels .............................................. 26
1.8. Example of Modbus Frames ........................................................................................ 27

[Link] Rev. 05 2/28


1. MODBUS PROTOCOL

Communication parameters are:


Modbus RTU:

• Address and Baudrate


• 8 data bits
• No parity
• 1 stop bit

Modbus TCP/IP:

• IP: [Link] (by default)


• Subnet: [Link] (by default)
• Gateway: [Link] (by default)
• Port number: 502
• Master Address: 1 (by default)
• Retries Number: 10 (by default)
• Confirmation time: 2000 ms (by default)

This document describes the steps to follow to read and write data on the SIL-A relay, as per the
Modbus protocol. This memory map is only valid for one piece of equipment and one version of the
memory. The positions of existing objects in the memory remain fixed from one version to the next, but
new objects will naturally have new addresses which will, in turn, remain fixed in future versions. The
memory map is described further on.
The standard Modbus protocol is used, so any program or PC can communicate easily with the
equipment.
The SIL-A always acts as a slave, which means that it never initiates communications. The master is
always responsible for initiating communications.
Only a subset of the Modbus functions is implemented:
• Reading function 3.
• Writing function 16.
The MODBUS/RTU protocol is independent from the hardware. Therefore, the physical layer can exist in
different hardware configurations: RS232, RS485, fibre optic or Ethernet.
Specifically, the relay has a front RS232 port and, as an option, a rear RS485 port. The data stream in
any of the configurations is “half-duplex”.er
Each byte of data is transmitted asynchronously and is made up of: 1 start bit, 8 data bits, 1 stop bit and
1 parity bit, if this is how it is programmed. Therefore, the data has 10 or 11 bits, depending on whether it
includes parity.
If the relay only offers with Modbus on the front port, the address (1 to 247) is configurable but the rest of
the paarmeters are fixed and equal to: baudrate 19200, No parity and stop bit 1.
If the relay offers RS485 Modbus protocol the the address (1 to 247) and the baudrate (4800, 9600,
19200 or 38400) con be but the rest of the parameters are fixed: without parity and with 1 stop bit.
The master must know the address of the slave that it is going to communicate with. No unit will act on
requests from the master if the message is not addressed to them. The exception is when the 0 address,
or “broadcast” address, is used, in which case the relay will act but will not send an answer of any type.

[Link] Rev. 05 3/28


Communications are made in packages or frames, which are groups of data that are sent
asynchronously. The master transmits a frame to the slave, and the slave then replies with another
frame (except in the case of “broadcast” messages).
The end of the frame is marked by a dead time or silence time in the communication medium. The length
of this time of silence varies depending on the transmission speed, as it is equivalent to 3 characters.
The following table shows the generic package format that is valid for transmission and reception.
However, each function has its own peculiarities, as will be described further on.

1.1. Modbus RTU pachage format


CUSTOMER 1 byte Each device on a communication bus must have a unique address, otherwise two
ADDRESS different units could reply simultaneously to the same request. All ports of the
relay will use this address which can be set a value between 1 and 247. When the
master transmits a frame with the slave address to 0 indicates a Broadcast. All
the slaves in the communications bus will carry out the requested action, but no
one will reply to the master. The Broadcast will only be accepted to write, as it
makes no sense to make a read request in the Broadcast, as no one will reply this
request.

FUNCTION 1 byte This is one of the function codes supported by the equipment. In this case, the
CODE only function codes supported are 3 to read and 16 to write. When the slave has
to reply with an exception one of these frames, it is indicated by putting 1 in the
most important bit of the correspondent function. Thus, an exception for the
function 3, will be indicated with a 83 as a function code; and an exception for the
function code 16 or 0x10 in hexadecimal, will be indicated with an 0x90.

DATA N bytes This part consists of a variable number of bytes, depending on the function code.
It may include: addresses, data lengths, settings, commands or exception codes
sent by the user.

CRC 2 bytes Control code of two bytes. The ModBus/RTU includes a 16-bit CRC in each
frame, to detect errors. If the slave detects an erroneous frame, based on a CRC
that is not correct, it won’t take any action, nor will reply anything to the master.
The management of the CRC is LSB-MSB.

DEAD TIME Necessary time A frame is terminated when nothing is received for a period of 3,5 bytes. It means:
to transmit 3,5 15 ms at 2400 bps
Bytes 2 ms at 19200 bps
...etc.

[Link] Rev. 05 4/28


1.2. Function Codes
HEX
DEC MODBUS NAME DEFINITION COMMENT
CODE

0x03 Read Holding Reading of Any Value This function allows the master to read 1 or
more consecutive addresses of a relay. The
3 Registers registers always are of 16 bits, with the most
important byte at first. The maximum number
of registers to be read in a package are 60.

HEX
DEC MODBUS NAME DEFINITION COMMENT
CODE

0x10 Preset Multiple Script This function allows to write one or more
registers that represent one or more settings.
16 Registers The registers are values of 2 bytes of length,
transmitted with the most important byte at
first. The maximum number of registers to be
written in a package is 60.

1.3. Exceptions Responses


The error codes defined by the ModBus protocol are as follows:

The slave does not support any function with the function code received in
01 ILLEGAL FUNCTION
this message.

02 ILLEGAL DATA ADDRESS The master is trying to do an operation in a wrong address.

03 ILLEGAL DATA VALUE The slave has detected that the value sent by the master is not valid.

Indicates an error occurred in the slave while trying to execute the request
04 SLAVE DEVICE FAILURE
of the master.

05 ACKNOWLEDGE Generic recognition.

06 SLAVE DEVICE BUSY The slave is busy and unable to perform the required operation.

07 NEGATIVE ACKNOWLEDGE Generic non-recognition.

When the data format takes up more than one BYTE, the most important BYTE is sent through the
communications first, and the least important BYTE is sent last.

[Link] Rev. 05 5/28


1.4. Data type
TYPE LENGTH DESCRIPTION

UCHAR 1/2 Integer without sign of 1 byte

BYTE 1/2 Integer with sign of 1 byte

BIT16 1 Gathered bits type, groups of 16.


E. g.: 0x1A41 = 0001101001000001b

BIT32 2 Gathered bits type, groups of 32.

ENUM 1 Integer without sign of 16 bits. Each of the possible values of the integer will have
a correspondence in the auxiliary list of the database. This list is the
correspondence chain which must be shown for each of the values. Memory will
only receive an integer value.
E. g.: 0, 1 Correspondence to “CLOSED”, “OPEN”

DENUM 2 Integer without sign of 4 bytes

UINT 1 Integer without sign of 2 bytes

INT 1 Integer with sign of 2 bytes

LONG 2 Integer without sign of 4 bytes

DWORD 2 Integer with sign of 4 bytes

FLOAT 2
Number in FLOAT INVERSEing decimal point “FLOAT INVERSE” of 4 bytes
INVERSE

ASCIIxx xx/2 String: In length variable character chain. Final of String marked with ‘\0’.
E. g.: “ABC” 0x41x42x43x00....

MILIS 3 Minutes (passed since 00:00 of 1/1/2000) (LONG). milliseconds (UINT)

FH 5 Year(UINT).month(UCHAR).day(UCHAR).hour(UCHAR).minutes(UCHAR).second
s(UCHAR).hundredth(UCHAR).thousandth(UINT)

CONT 13 Directory (UINT). Value (DWORD). Description (ASCII20)

EVENT 9 Criteria Directory (UINT). Event Identifier (UINT). Value (UINT). Associated
Measure (UINT).Date and Time(FH)

EVENTO 10 Antiquity (UINT). Event (EVENT)

CCRIT 6 Criteria Number (UINT). Criteria Directory (UINT). Descriptive text (ASCII8)

PEST 61 Number of States (UINT). Protection State-1(BIT16). … Protection State-60(BIT16)

PCRIT 61 Number of Criteria (UINT). Index of Criteria-1(UINT). … Index of Criteria-60(UINT).

CMED 8 Number of Measure (UINT). Descriptive text (ASCII7). Unit(ASCII3).Primary


Unit(ASCII5).Number of decimals(UCHAR)

GAJU 61 Number of Groups (UINT). Index of the Criteria-1(UINT). Index of the first setting of
the Criteria-1(UINT). … Index of the Criterion-30(UINT). Index of the first setting of
the Criteria-30(UINT).

ENUM TRIP 1 Integer without sign of 16 bits.


VOLT E. g.: 0, 1, 2 Correspondence to “12V”, “17V”, “22V”

When the data format takes up more than one BYTE, the most important BYTE is sent through the
communications first, and the least important BYTE is sent last.

[Link] Rev. 05 6/28


1.5. General Memory Map

Start Number of
Function Description Format Reference
address registries

16 Write the Directory of Event 1 1 UINT

16 Load data Profiling 2 1

16 Write the number of the Setting List 6 1 UINT

03 Read of Model and Version 100 44 ASCII88

See IP, Submask.


03 ModBus IP, Submask and Gateway 144 7
Gateway and Port

See Passwords and


16 Write access code 168 2 UCHAR4
Access Levels

03 & 16 Date and Time 170 5 FH

See IP, Submask,


03 DNP3 IP, Submask and Gateway 184 7
Gateway and Port

16 Selection of Command 200 2 UINT See Commands map

16 Confirmation of Command 201 1 UINT See Commands map

16 Direct Command 182 1 UINT See Commands map

03 & 16 Counters 202 2 CONT Opennings Number

Accumulated
03 & 16 Counters 204 2 CONT
Amperes

03 & 16 Counters 212 2 CONT Reclosings Number

03 Serial number 252 2 LONG

03 Equipment identifier 254 44 ASCII88

See States map


03 Read and Delete the oldest Event 400 11 EVENTO2
(Event Number)

See States map


03 One event reading 410 11 EVENTO2
(Event Number)

16 Delete All Events 420 1 dummy

16 Write event index 1 1

16 Write fault report index 8000 1

16 Write event index from a fault report 8002 1

03 Fault report reading 8123 11

[Link] Rev. 05 7/28


1.5.1. States Map
The function code implemented to State reading is 0x03 (Read Holding Registers).
Number of registries: 2
Event SIL-A
Address Description Bit Status Adapatation B
NO
00 01 Trip √

03 07 50 Hz

04 08 Trip Block / SHB enable

05 16 Measurement error

06 17 Ready

07 19 Change of settings

08 21 Set date/time

09 22 Local Control

10 23 Factory Settings

11 24 Error Eeprom

12 28 Eeprom changed

13 32 Events error

15 15 Reset

500 General 16 Pickup

17 Phase A Pickup

18 Phase B Pickup

19 Phase C Pickup

20 Ground Pickup

21 Phase A Trip

22 Phase B Trip

23 Phase C Trip

24 Ground Trip

25 50 Trip

26 50N/G Trip

27 Phase Trip

- 30 New DFR

- 47 Active group by input

[Link] Rev. 05 8/28


- 48 Events Erased

Event SIL-A
Address Description Bit Status Adapatation C
NO

00 01 Trip

03 07 50 Hz

04 08 Trip Block / SHB enable

05 16 Measurement error

06 17 Ready

07 19 Change of settings

08 21 Set date/time

09 22 Local Control

10 23 Factory Settings

11 24 Error Eeprom

12 28 Eeprom changed

13 32 Events error

15 15 Reset

500 General 16 49 Pickup

17 50 Phase A Pickup

18 51 Phase B Pickup

19 52 Phase C Pickup

20 53 Ground Pickup

21 54 Phase A Trip

22 55 Phase B Trip

23 56 Phase C Trip

24 - Ground Trip

25 58 50 Trip

26 59 50N/G Trip

27 - Phase Trip

- 30 New DFR

- 47 Active group by input

[Link] Rev. 05 9/28


- 48 Events Erased

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO
√ √
8200 Oscilo - 16 DFR Erased

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO
√ √
00 - Local COM.

01 - HMI Activity

17 02 Open breaker

18 03 Close breaker

19 04 79 Block
502 Local COM
20 05 79 Unblock

21 06 Local control

22 07 Remote Control

23 09 Reset

25 08 Reset TI

SIL-A SIL-A
Address Description Bit Event NO Status Adapatation B Adapatation C
√ √
00 01 50-1 Phase A Pickup

01 02 50-1 Phase B Pickup

02 03 50-1 Phase C Pickup

03 04 50-1 Pickup
504 50-1
08 05 50-1 Phase A Trip

09 06 50-1 Phase B Trip

10 07 50-1 Phase C Trip

11 08 50-1 Trip

[Link] Rev. 05 10/28


Event SIL-A SIL-A
Address Description Bit Status Adapatation B Adapatation C
NO
√ √
00 01 51 Phase A Pickup

01 02 51 Phase B Pickup

02 03 51 Phase C PIckup

03 04 51 Pickup
506 51
08 05 51 Phase A Trip

09 06 51 Phase B Trip

10 07 51 Phase C Trip

11 08 51 Trip

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO
√ √
04 01 50G-1 Pickup
508 50G-1
12 02 50G-1 Trip

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO
√ √
04 01 51G Pickup
510 51G
12 02 51G Trip

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO
√ √
00 17 Input 1

01 18 Input 2

02 19 Input 3
512 Inputs
03 20 Input 4

04 21 Input 5

05 22 Input 6

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO
√ √
08 01 Output 1

09 02 Output 2
514 Outputs
10 03 Output 3

11 04 Output 4

[Link] Rev. 05 11/28


Event SIL-A SIL-A
Address Description Bit Status Adapatation B Adapatation C
NO

00 01 Phase A Block

01 02 Phase B Block
516 Trip Block
02 03 Phase C Block

03 04 Phase Block

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO

04 01 50BF pickup
518 50BF
12 02 50BF Trip

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO
00 01 √ √
52 Start

01 02 52 Error

02 03 52 Open

03 04 52 Opening time

04 05 52 Opening error

05 06 52 Closed

520 52 06 07 52 Closing time

07 08 52 Closing error

08 09 52 Excessive total
openings
09 10 52 Excessive accumulated
amperes (I2t).
10 11 52 Excessive openings in a
time window
11 12 52 a

12 13 52 b

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO
√ √
04 01 49 Alarm
522 49
12 02 49 Trip

[Link] Rev. 05 12/28


Event SIL-A SIL-A
Address Description Bit Status Adapatation B Adapatation C
NO
√ √
00 - Remote communication

17 02 Open breaker

18 03 Close breaker

19 04 79 Block

524 Remote Modbus 20 05 79 Unblock

21 06 Local control

22 07 Remote Control

23 09 Reset

25 08 Reset TI

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO
√ √
00 01 79 Standby

01 02 79 Reclosing time

02 03 79 Is 52 Open?

03 04 79 Hold time

04 05 79 Closing time
526 79
05 06 79 Reset time.

06 07 79 Lockout

07 08 79 Safe time

08 09 79 Manual opening time

09 - 79 Enabled

[Link] Rev. 05 13/28


Event SIL-A SIL-A
Address Description Bit Status Adapatation B Adapatation C
NO
00 1 √
50-2 Phase A Pickup

01 2
50-2 Phase B Pickup

02 3
50-2 Phase C Pickup

03 4
50-2 Pickup
528 50-2
08 5
50-2 Phase A Trip

09 6
50-2 Phase B Trip

10 7
50-2 Phase C Trip

11 8
50-2 Trip

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO

04 01 50G-2 Pickup
530 50G-2
12 02 50G-2 Trip

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO
√ √
04 01 46 Pickup
532 46
12 02 46 Trip

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO
√ √
00 CLP Disable

01 52 Closed

02 52 Open

534 CLP 03 52 definitive Opening

04 Close Cold Load

05 Open Cold Load

12 02 Cold Load Pickup

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO
√ √
04 01 74TCS Pickup Configurable Fixed inputs
536 74TCS inputs
12 02 74TCS Alarm

[Link] Rev. 05 14/28


Event SIL-A SIL-A
Address Description Bit Status Adapatation B Adapatation C
NO

04 01 74CT Pickup
538 74CT
12 02 74CT Alarm

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO
√ √
00 - Remote communication Only Serial
DNP3.0
17 02 Open breaker

18 03 Close breaker

19 04 79 Block

Remote DNP3.0 20 05 79 Unblock


540 Remote
IEC60870-5-103
21 06 Local control

22 07 Remote Control

23 09 Reset

25 08 Reset TI

Event SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO
√ √
00 - Led 1

01 - Led 2

02 - Led 3

03 - Led 4
542 Leds
04 - Led 5

05 - Led 6

06 - Led 52

07 - Led 79

[Link] Rev. 05 15/28


Event SIL-A
Address Description Bit Status Adapatation B
NO

13 18 52 a

14 19 52 b

15 22 External trip

16 07 50BF Start

17 08 DFR Start

18 20 50 Block

19 21 50N/G Block

20 23 Reset

21 24 Settings group 1

544 Logic 22 25 Settings Group 2

23 06 79 Start

24 26 79 Enable

25 27 79 Level Block

26 28 79 Block

27 29 79 Unblock

28 30 74TCS Continuity A


29 31 74TCS Continuity B

30 - Logic signal 1

31 - Logic signal 2

[Link] Rev. 05 16/28


Event SIL-A
Address Description Bit Status Adapatation C
NO

00 18 52 a

01 19 52 b

02 22 External trip

13 08 DFR Start

03 20 50 Block

04 21 50N/G Block

07 23 Reset
544 Logic

05 24 Settings group 1

06 25 Settings Group 2

08 06 79 Start

09 26 79 Enable

10 27 79 Level Block

11 28 79 Block

12 29 79 Unblock

Event Associated SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO Measurement

00 1 37 Phase A Pickup IA (A)

01 2 37 Phase B Pickup IB (A)

02 3 37 Phase C Pickup IC (A)

03 4 37 Pickup Imax (A)


546 37
08 5 37 Phase A Trip IA (A)

09 6 37 Phase B Trip IB (A)

10 7 37 Phase C Trip IC (A)

11 8 37 Trip Imax (A)

Event Associated SIL-A SIL-A


Address Description Bit Status Adapatation B Adapatation C
NO Measurement
√ √
04 01 46BC Pickup I2/I1
548 46BC
12 02 46BC Trip I2/I1

[Link] Rev. 05 17/28


Event Associated SIL-A SIL-A
Address Description Bit Status Adapatation B Adapatation C
NO Measurement

00 01 Phase A Block -

01 02 Phase B Block -
552 SHB
02 03 Phase C Block -

03 04 Phase Block -

1.5.2. Measurements Map


SIL-A Adapatation B SIL-A Adapatation C
Address Description Format

300 Phase A current IA √ √

302 Phase B current IB √ √

304 Phase C current IC √ √

306 Neutral current IN √ √

308 Maximum phase current IMAX √ √

310 Thermal Image FLOAT INVERSE √ √

312 Negative sequence current I-2 √ √

314 Positive sequence current I-1 √

Phase A second harmonic


316 √
current IA-2H

Phase B second harmonic


318 √
current IB-2H

Phase C second harmonic


320 √
current IC-2H

1.5.3. Fault report measurements Map


SIL-A Adapatation B SIL-A Adapatation C
Address Description Format

350 Fault report Phase A current IA √

352 Fault report Phase B current IB √


FLOAT INVERSE NA
354 Fault report Phase C current IC √

356 Fault report Neutral current IN √

[Link] Rev. 05 18/28


1.5.4. Settings Map
SIL-A Adapatation B SIL-A Adapatation C
Settings Address Description Format Enumeration

600 (*) √ √
Identification ASCII20 -
800 (**)
610 (*) 0 → 60 Hz √ √
Frequency DENUM
810 (**) 1 → 50 Hz

612 (*) √ √
Serial Number LONG -
812 (**)

614 (*) 0 → English √ √


1 → Spanish
Language DENUM
814 (**) 2 → Depends on Relay
model
616 (*) Active Setting √ √
LONG -
816 (**) Group

618 (*) Phase √ √


1A
Nominal DENUM
current 5A
818 (**)
620 (*) Neutral 1A √ √
Nominal DENUM
820 (**) Current 5A

622 (*) CT Phase FLOAT √ √


-
822 (**) Ratio INVERSE

624 (*) CT Neutral FLOAT √ √


General -
824 (**) ratio INVERSE

626 (*) Local COM √ √


LONG -
826 (**) Address

628 (*) Remote COM √ √


LONG
828 (**) Address

630 (*) 0 → 4800 Bd √ √


Remote 1 → 9600 Bd
DENUM
830 (**) Baudrate 2 → 19200 Bd
3 → 38400 Bd
760 (*) Depending on model 0 → ModBus
Remote
DENUM -
860 (**) Protocol (***) 1 → DPN3.0/103

776 (*) DNP3.0 √


Master LONG -
976 (**) Address
778 (*) 0 → 8-N-1 √
1 → 8-N-2
2 → 8-E-1
DNP3.0 Serial 3 → 8-E-2
DENUM
978 (**) Settings 4 → 8-O-1
5 → 8-O-2
6 → 9-N-1
7 → 9-N-2
(*) Read/Write Address (FC = 03 / 16).
(**) Address for Confirmation (FC = 16)

[Link] Rev. 05 19/28


SIL-A Adapatation B SIL-A Adapatation C
Settings Address Description Format Enumeration

780 (*) DNP3.0 IB √


LONG -
980 (**) Deadband

782 (*) DNP3.0 IB √


LONG -
982 (**) Deadband
General
784 (*) DNP3.0 IC √
LONG -
984 (**) Deadband

786 (*) DNP3.0 IN √


LONG -
986 (**) Deadband

(***) Depending on model:


SIL-Axxxxx7xxxB: 0 → Modbus RTU / 1→DNP3.0 Serial
SIL-Axxxxx8xxxB: 0 → Modbus TCP/IP / 1→DNP3.0 TCP/IP

SIL-A Adapatation B SIL-A Adapatation C


Settings Address Description Format Enumeration

632 (*) 0 → Disable √ √


Function
DENUM 1 → Enable
832 (**) Enable
2 → SHB
Without SHB option

50-1 634 (*) FLOAT √ √


Tap -
834 (**) INVERSE

636 (*) FLOAT √ √


Time Delay -
836 (**) INVERSE

SIL-A Adapatation B SIL-A Adapatation C


Settings Address Description Format Enumeration

638 (*) 0 → Disable √ √


Function
DENUM 1 → Enable
838 (**) Enable Without SHB option
2 → SHB
0 → IEC Inverse √ √
1 → IEC Very Inverse
640 (*)
2 → IEC Extremely
Inverse
3 → Defined Time
Curve Type DENUM 4 → IEEE Inverse
5 → IEEE Very Inverse
51 840 (**) 6 → IEEE Extremely
Inverse
7 → IEC Long Time
Inverse
642 (*) Time Dial FLOAT √ √
-
842 (**) (TMS) INVERSE

644 (*) FLOAT √ √


Tap -
844 (**) INVERSE

646 (*) FLOAT √ √


Time Delay -
846 (**) INVERSE
(*) Read/Write Address (FC = 03 / 16).
(**) Address for Confirmation (FC = 16)

[Link] Rev. 05 20/28


SIL-A Adapatation B SIL-A Adapatation C
Settings Address Description Format Enumeration

648 (*) 0 → Disable √ √


Function
DENUM 1 → Enable
848 (**)
Enable
2 → SHB
Without SHB option

50N/G-1 650 (*) FLOAT √ √


Tap -
850 (**) INVERSE

652 (*) FLOAT √ √


Time Delay -
852 (**) INVERSE

SIL-A Adapatation B SIL-A Adapatation C


Settings Address Description Format Enumeration

654 (*) 0 → Disable √ √


Function
DENUM 1 → Enable
854 (**) Enable Without SHB option
2 → SHB
0 → IEC Inverse √ √
1 → IEC Very Inverse
656 (*)
2 → IEC Extremely
Inverse
3 → Defined Time
Curve Type DENUM 4 → IEEE Inverse
5 → IEEE Very Inverse
51N/G 856 (**) 6 → IEEE Extremely
Inverse
7 → IEC Long Time
Inverse
658 (*) Time Dial FLOAT √ √
-
858 (**) (TMS) INVERSE

660 (*) FLOAT √ √


Tap -
860 (**) INVERSE

662 (*) FLOAT √ √


Time Delay -
862 (**) INVERSE

SIL-A Adapatation B SIL-A Adapatation C


Settings Address Description Format Enumeration

664 (*) Function 0 → Disable √ √


DENUM
864 (**) Enable 1 → Enable

666 (*) FLOAT √ √


Tap -
866 (**) INVERSE

668 (*) Heating √ √


49 LONG -
868 (**) Constant
670 (*) Cooling √ √
LONG -
870 (**) Constant

672 (*) √ √
Alarm Level LONG -
872 (**)
(*) Read/Write Address (FC = 03 / 16).
(**) Address for Confirmation (FC = 16)

[Link] Rev. 05 21/28


SIL-A Adapatation B SIL-A Adapatation C
Settings Address Description Format Enumeration

674 (*) Function 0 → Disable √


DENUM
874 (**) Enable 1 → Enable
Trip
Block 676 (*) SIL-A Adapatation C
FLOAT √
Tap -
876 (**) INVERSE

SIL-A Adapatation B SIL-A Adapatation C


Settings Address Description Format Enumeration

678 (*) 0 → Disable √


Function
DENUM
Enable 1 → Enable
878 (**)

680 (*) FLOAT √


50-2 Tap -
880 (**) INVERSE

682 (*) FLOAT √


Time Delay -
882 (**) INVERSE

SIL-A Adapatation B SIL-A Adapatation C


Settings Address Description Format Enumeration

684 (*) 0 → Disable √


Function
DENUM 1 → Enable
Enable
884 (**) 2 → SHB

50N/G-2 686 (*) FLOAT √


Tap -
886 (**) INVERSE

688 (*) FLOAT √


Time Delay -
888 (**) INVERSE

SIL-A Adapatation B SIL-A Adapatation C


Settings Address Description Format Enumeration

690 (*) 0 → Disable √ √


Function
DENUM 1 → Enable
Enable Without SHB option
890 (**) 2 → SHB
0 → IEC Inverse √ √
692 (*) 1 → IEC Very Inverse
2 → IEC Extremely
Inverse
3 → Defined Time
Curve Type DENUM 4 → IEEE Inverse
5 → IEEE Very Inverse
892 (**) 6 → IEEE Extremely
46
Inverse
7 → IEC Long Time
Inverse
694 (*) Time Dial FLOAT √ √
-
894 (**) (TMS) INVERSE

696 (*) FLOAT √ √


Tap -
896 (**) INVERSE

698 (*) FLOAT √ √


Time Delay -
898 (**) INVERSE
(*) Read/Write Address (FC = 03 / 16).
(**) Address for Confirmation (FC = 16)

[Link] Rev. 05 22/28


SIL-A Adapatation B SIL-A Adapatation C
Settings Address Description Format Enumeration

700 (*) Function 0 → Disable √


DENUM
Enable 1 → Enable
900 (**)

702 (*) FLOAT √


Tap -
902 (**) INVERSE
37
704 (*) FLOAT √
Time Delay -
904 (**) INVERSE

768 (*) FLOAT √


Death tap -
968 (**) INVERSE

SIL-A Adapatation B SIL-A Adapatation C


Settings Address Description Format Enumeration

706 (*) Function 0 → Disable √


DENUM
906 (**) Enable 1 → Enable
50BF
708 (*) Adapatation B SIL-A
FLOAT √ Adapatation C
Time Delay -
908 (**) INVERSE

SIL-A Adapatation B SIL-A Adapatation C


Settings Address Description Format Enumeration

710 (*) Max Number √ √


LONG -
910 (**) of Openings

712 (*) Max √ √


Accumulated LONG -
912 (**) Amperes
714 (*) FLOAT √ √
Opening Time -
914 (**) INVERSE
52
716 (*) FLOAT √ √
Closing Time -
916 (**) INVERSE

718 (*) Excessive √ √


Repetitive LONG -
918 (**) Openings
720 (*) Repetitive FLOAT √ √
-
920 (**) Openings/Time INVERSE

(*) Read/Write Address (FC = 03 / 16).


(**) Address for Confirmation (FC = 16)

[Link] Rev. 05 23/28


SIL-A Adapatation B SIL-A Adapatation C
Settings Address Description Format Enumeration

722 (*) Function 0 → Disable √ √


DENUM
922 (**) Enable 1 → Enable

724 (*) 0 → Disable √ √


Hold Enable DENUM
924 (**) 1 → Enable

726 (*) Number of FLOAT √ √


-
926 (**) reclosings INVERSE

728 (*) Reclosing FLOAT √ √


-
928 (**) time 1 INVERSE

730 (*) Reclosing FLOAT √ √


-
930 (**) time 2 INVERSE

732 (*) Reclosing FLOAT √ √


79 -
932 (**) time 3 INVERSE

734 (*) Reclosing FLOAT √ √


-
934 (**) time 4 INVERSE

736 (*) Reclosing FLOAT √ √


-
936 (**) time 5 INVERSE

738 (*) FLOAT √ √


Hold time -
938 (**) INVERSE

740 (*) FLOAT √ √


Reset Time -
940 (**) INVERSE

742 (*) FLOAT √ √


Safe time -
942 (**) INVERSE

SIL-A Adapatation B SIL-A Adapatation C


Settings Address Description Format Enumeration

744 (*) Function 0 → Disable √ √


DENUM
944 (**) Enable 1 → Enable

746 (*) Active √ √


Settings LONG -
946 (**) Group
CLP
748 (*) FLOAT √ √
No Load Time -
948 (**) INVERSE

750 (*) Cold Load FLOAT √ √


-
950 (**) Time INVERSE

SIL-A Adapatation B SIL-A Adapatation C


Settings Address Description Format Enumeration

752 (*) Function 0 → Disable √ √


DENUM
952 (**) Enable 1 → Enable
74TCS
754 (*) FLOAT √ √
Time Delay -
954 (**) INVERSE

(*) Read/Write Address (FC = 03 / 16).


(**) Address for Confirmation (FC = 16)

[Link] Rev. 05 24/28


SIL-A Adapatation B SIL-A Adapatation C
Settings Address Description Format Enumeration

756 (*) Function 0 → Disable √


DENUM
956 (**) Enable 1 → Enable
74CT
758 (*) FLOAT √
Time Delay -
958 (**) INVERSE

SIL-A Adapatation B SIL-A Adapatation C


Settings Address Description Format Enumeration

762 (*) 0 → Disable √ √


Function
DENUM
Enable 1 → Enable
962 (**)

764 (*) FLOAT √ √


46BC Tap -
964 (**) INVERSE

766 (*) FLOAT √ √


Time Delay -
966 (**) INVERSE

SIL-A Adapatation B SIL-A Adapatation C


Settings Address Description Format Enumeration

770 (*) Function 0 → Disable √


DENUM
970 (**) Enable 1 → Enable

772 (*) FLOAT √


Current Tap -
972 (**) INVERSE
SHB
774 (*) FLOAT √
Reset Time -
974 (**) INVERSE

788 (*) Block FLOAT √


988 (**) Threshold INVERSE

(*) Read/Write Address (FC = 03 / 16).


(**) Address for Confirmation (FC = 16)

[Link] Rev. 05 25/28


1.6. Command List
SIL-A Adapatation B SIL-A Adapatation C
Index Format Description

√ √
2 UINT16 Open Breaker

√ √
3 UINT16 Close Breaker

√ √
4 UINT16 79 Block

√ √
5 UINT16 79 Unblock

√ √
6 UINT16 Local Control

√ √
7 UINT16 Remote Control

√ √
8 UINT16 Reset

√ √
10 UINT16 Reset Thermal Image

1.7. Setting-up the session: Password and access levels


The relay is provided with different passwords associated to access levels allowing the user to carry out
different actions depending on the selected password:

ACCESS Read-only Function Function Function Function Function Enable Function Enable
LEVEL Enable: Enable to: Enable to: Enable to: to: to:
Status and Change Delete Execute Change Change
measurements settings Events Commands Configuration Protected
Settings
Settings Delete DFR
Configuration
Events/DFR

2 YES YES YES NO NO NO

3 YES NO NO YES NO NO

4 YES YES YES YES NO NO

5 YES YES YES YES YES NO

[Link] Rev. 05 26/28


Four passwords and their associated levels of access are set up when the relay is configured using the SIcom
program. The password must be made up of 4 characters (passwords with more or less characters will not be
accepted). By default, the relay is programmed with the following passwords and their associated levels:

PASSWORD ACCESS LEVEL

2222 2

3333 3

4444 4

5555 5

1.8. Example of Modbus Frames


Writing the access password “5555” to equipment no. 1

Number
H Pickup L Pickup Number of Number of Checksum
Address Function of Password Checksum L
Address Address H Registers L Registers H
Bytes

0x35
0x35
0x01 0x10 0x00 0xA8 0x00 0x02 0x04 0x30 0xF4
0x35
0x35

And the SIL-A will reply OK:


Number
H Pickup L Pickup Number of L Checksum Checksum
Address Function of H
Address Address Registers H L
Registers

0x01 0x10 0x00 0xA8 0x00 0x02 0xC0 0x28

[Link] Rev. 05 27/28


[Link] Rev. 05 28/28

You might also like