This document summarizes a spring return actuator used to operate smoke dampers. It comes in 24V AC/DC or 230V AC models and is intended to safely return dampers to the closed position during a fire. The actuator motors the damper open while simultaneously tensioning a return spring. If power is lost, the spring moves the damper closed. It provides position indication and can be manually operated or overridden.

Uploaded by

K P Vignesh Rao
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
184 views1 page

Damper Datasheet

This document summarizes a spring return actuator used to operate smoke dampers. It comes in 24V AC/DC or 230V AC models and is intended to safely return dampers to the closed position during a fire. The actuator motors the damper open while simultaneously tensioning a return spring. If power is lost, the spring moves the damper closed. It provides position indication and can be manually operated or overridden.

Uploaded by

K P Vignesh Rao
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Mode 5 & 6 PTCTM Regular Spring Return Actuator

Spring return actuator with ETR


(Electro Thermal Release).
60 second reset.

24V AC/DC and 230V AC

Application
The spring-return actuator is intended for
the operation Actionair Smoke/Shield
PTCTM Hot/Shield PTCTM and Marine A-
60 dampers.

Mode of operation
Wiring Diagram
The actuator motors the damper to the
reset position whilst simultaneously
~ AC 24V BAM24-1: connect via safety
tensioning the return spring. If the power
RAMII-AA-24-1: connect via safety
- + DC 24V isolating
Isolatingtransformer
transformer supply is interrupted, the energy stored in
N L1 AC 230V ! the spring, moves the damper back to the
RAMII-AA-230-1: For disconnection from the supply, a
BAM230-1: For disconnection from the supply, a released position to give fail-safe
separate device must be incorporated in the fixed wiring (at
separate device must be incorporatet in the fixed
least 3mm contact gap in all poles)
wiring (at least 3 mm contact gap in all poles). operation
The ETR incorporates a safety feature
that ensures the fail-safe status of the
damper if the ETR is not fitted to the
1 2 S1
1 S2
2 S3
3 S4
4 S5
5 S6
6
ductwork.
The ETR probe has a replaceable 72°C
Thermal trip
5° 80° BAM24-1
MODE / 230-1
5/6 MKII An LED on the ETR housing indicates:
 Unit receiving power
ETR  ETR correctly fitted
 Thermal fuse intact
Tf1 Tf2 Tf3
[NOTE: thermal fuse (Tf1) in the ETR housing
will operate (permanently) at 71°C].
Technical Data Mode 5 MKII Mode 6 MKII
Nominal Voltage AC 24V 50/60 Hz AC 230V 50/60 Hz Signalling
- There are two fixed internal micro-
Nominal voltage range AC 19,2...28.8V AC 198...264V switches for indicating the end-positions
- of the damper.
For wire sizing 12.5 VA (Imax 8,3A @ 14 VA (0,5 A @ 5ms) Intermediate positions of the damper
5ms)
blade are visible by the use of a
Power consumption
- motoring 10 W 12 W mechanical pointer.
- holding 2W 4W
Connecting cable (LSF quality) Manual operation
- Motor 1 m 2 x 0.75 mm2 1 m 2 x 0.75 mm2 The damper can be operated manually
- Aux. switch 1 m 6 x 0.75 mm2 1 m 6 x 0.75 mm2 using the key provided, and fixed in any
Auxiliary switches 2 x SPDT 6(3)A, AC 250V required position. Release of the locking
- Switching points 5° / 80° mechanism can be achieved manually or
Torque overridden by applying the supply
- Motor Min. 20 Nm
voltage.
- Spring Min. 20 Nm
Angle of rotation 95°
Output drive coupling Form-fit 14 mm double hexagon Testing.
Direction of rotation Selected by mounting L/R A test switch is incorporated in the ETR.
Running time
- Motor <60s
- Spring ~24s (@ tamb = 20°C)
Sound power level
- Motor max. 45 dB(A)
- Spring ~ 62 dB(A)
Position indication mechanical with pointer
Protection class III II
Degree of protection IP 54
Ambient temperature range
- Normal duty -30...+ 50° C
- Safety duty -30...+ 60° C (24h)
- Non-operating temperature -40...+ 60 °C
Humidity test To EN60335-1
EMC CE according 89/336/EEC and 92/31/EEC, 93/68/EEC
Low voltage directive CE according 73/23/EEC
Service life 25,000 cycles
Weight approx. 2‘800g approx. 3‘100g
mode 5 and 6 PTC regular on infodesk updated janu08.doc