BSRIA Unsterstand Acoustic Performance Data
BSRIA Unsterstand Acoustic Performance Data
Understanding Acoustic
Performance Data
By Rebecca Hogg
BG 41/2012
ACKNOWLEDGEMENTS
This publication has been printed on Nine Lives Silk recycled paper.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system,
or transmitted in any form or by any means electronic or mechanical including photocopying,
recording or otherwise without prior written permission of the publisher.
©BSRIA 56090 July 2012 ISBN 978 0 86022 712 0 Printed by ImageData Ltd
1 INTRODUCTION 1
2 WHAT IS MEASURED? 2
2.1 What is sound? 2
2.2 Sound power vs sound pressure 2
2.3 Acoustic environments 3
2.4 Reverberation time 5
2.5 The decibel unit 5
2.6 Typical noise levels 6
2.7 Frequency and A-weighting 6
2.8 Sound reduction 8
2.9 Noise Rating curves 8
3 WHY MEASURE? 10
3.1 Common noise sources in HVAC 10
3.2 Paths of noise transmission 10
3.3 The importance of frequency data 12
3.4 Product development 13
3.5 Planning applications 14
3.6 Test standards and accreditation schemes 14
4 EXAMPLES OF ACOUSTIC PERFORMANCE DATA 15
APPENDICES
APPENDIX A: DECIBEL CALCULATIONS 18
APPENDIX B: ACOUSTIC STANDARDS 19
TABLES
Table 1: Typical sound pressure levels. 6
Table 2 : Typical sound power levels. 6
Table 3 : One third octave band centre frequencies and octave band centre
frequencies between100 Hz and 10 kHz. 7
Table 4 : Insertion loss of a silencer. 8
Table 5 : Acoustic performance data parameters. 15
FIGURES
Figure 1 : Sound power emitted by a sound source. 2
Figure 2 : Sound pressure measurements. 3
Figure 3 : Sound source located in a hard-walled plant room. 4
Figure 4 : Sound source located on a hard surface in an open space. 4
Figure 5 : Sound source located adjacent to two hard surfaces. 4
Figure 6 : Noise Rating (NR) curves. 9
Figure 7 : Paths of noise transmission. 11
Figure 8 : One third octave band centre frequency sound power levels. 12
Figure 9 : Sound power levels of an air source heat pump. 13
Figure 10 : Acoustic performance data example 1. 16
Figure 11 : Acoustic performance data example 2. 16
Figure 12 : Acoustic performance data example 3. 17
Figure 13 : Acoustic performance data example 4. 17
GLOSSARY 21
© BSRIA BG 41/2012
INTRODUCTION 1
1 INTRODUCTION
With more awareness of noise issues and many developments occurring
in already built-up areas it is essential to provide an accurate specification
of the noise emitted by building services equipment. Heat pumps located
in residential areas, kitchen extract systems in commercial premises,
pumps in plant rooms, and air conditioning units in office buildings are
just a few examples of situations where noise issues can occur.
2 WHAT IS MEASURED?
2.1 WHAT IS SOUND? Sound is any pressure variation in the air that the human ear can detect.
Noise is any sound that is undesired by the recipient. The distinction is
not strictly adhered to and the terms sound and noise are often used
interchangeably.
2.2 SOUND POWER VS A basic analogy for explaining sound is heat. An electric heater emits a
SOUND PRESSURE certain amount of heat, similar to the sound power emitted by a sound
source. In order to quantify the heat emitted by the heater, temperature
measurements may be taken around a room. The measured temperatures
vary around the room and are dependent on the thermal characteristics
of the room, much like sound pressures around a room being dependent
on the acoustic characteristics of the room.
© BSRIA BG 41/2012
WHAT IS MEASURED? 2
B C
D
A
2.3 ACOUSTIC As previously stated, sound power is independent of the specific acoustic
ENVIRONMENTS environment, but sound pressure is dependent on the specific acoustic
environment. A basic understanding of how sound is affected by a
specific acoustic environment is helpful when interpreting sound
pressure levels.
If the same sound source, emitting the same sound power is placed in
different environments then the sound pressures measured at a given
distance away from the source will vary. If sound energy is reflected
then the sound pressure measurements will include both the directly
radiated sound energy from the sound source and the sound energy
reflected from surfaces. It is therefore very important to know both the
measurement environment and the environment in which the product is
intended to be installed, allowing an accurate interpretation of acoustic
data. As sound power is independent of the specific acoustic environment
it is applicable in any environment and can be used with parameters of a
specific acoustic environment to predict the sound pressure at given
locations.
Most of the sound energy is reflected off the surfaces of the room.
© BSRIA BG 41/2012
WHAT IS MEASURED? 2
2.5 THE DECIBEL Sound power levels and sound pressure levels are stated using the
UNIT decibel (dB) unit. The decibel can be confusing as it is often assumed to
be an absolute unit, like metres or grams. The decibel is actually a
logarithm of a ratio of two quantities; a measured value and a reference
value.
One of the main reasons for using the decibel is to make the range of
Watchpoint
values easier to handle. The sound pressure that is just audible by a
Sound power levels and
person with normal hearing is approximately 20 µPa (20 millionth of a
sound pressure levels are
both stated in decibels, Pascal) so this is used as the reference pressure in all sound pressure level
but relative to different measurements. The sound pressure that is the threshold of pain for a
reference values, person is approximately a million times greater; 20 Pa.
therefore sound pressure
levels do not equal sound The reference power in all sound power measurements is 1 pW (a
power levels.
millionth of a millionth of a Watt). The sound power emitted by a jet
engine is approximately 10 kW (ten thousand Watts). This demonstrates
the enormous range of values required for sound powers and sound
pressures. Using the decibel unit provides a more convenient range of
values, which correlates well with the dynamic range of human hearing.
Further details of the formulae used to calculate sound pressure levels and
sound power levels and how to carry out decibel arithmetic are given in
Appendix A.
2.6 TYPICAL NOISE A sound pressure level of 0 dB is the threshold of human hearing and a
LEVELS sound pressure level of 120 dB is the threshold of pain. Table 1 gives
typical sound pressures and sound pressure levels for a range of sound
sources and environments. The notation Lp is often used to describe a
sound pressure level.
Table 2 gives typical sound powers and sound power levels for a range of
sound sources. The notation Lw is often used to describe a sound power
level.
Sound Power
Sound Source Sound Power
Level, Lw re 1 pW
Jet engine 10,000 W 160 dB
Loudspeaker rock 100 W 140 dB
Pneumatic hammer 1W 120 dB
Outboard motor 0.01 W 100 dB
Dishwasher 0.0001 W 80 dB
Office Equipment 0.000001 W 60 dB
Fridge 0.00000001 W 40 dB
Rustling leaves 0.0000000001 W 20 dB
Reference value 0.000000000001 W (1 pW) 0 dB
2.7 FREQUENCY AND As stated previously, sound is air pressure fluctuations that are
A-WEIGHTING perceptible by the human ear. The number of pressure fluctuations per
second, or frequency of the sound is measured in Hertz (Hz). In terms
of sound, frequency is akin to the musical idea of pitch. A bass drum
produces a sound at a low frequency (low pitch) and a triangle produces
a sound at a high frequency (high pitch).
© BSRIA BG 41/2012
WHAT IS MEASURED? 2
beneficial to state separately sound levels for different frequencies in order
to show if a particular sound source produces more noise at a certain
frequency.
The most common descriptors used are octave band centre frequencies
and one-third octave band centre frequencies. Table 3 details the
standard centre frequencies for octave bands and one-third octave bands
between 100 Hz and 10 kHz (10,000 hertz). Noise assessments, test
standards and accreditation schemes often stipulate the frequency range of
sound levels that should be stated and whether one-third octave band
centre frequencies or octave band centre frequencies are acceptable.
Table 3 : One third octave band centre frequencies and octave band centre
frequencies between100 Hz and 10 kHz.
One third octave band or octave band centre frequency noise levels are
typically unweighted. Single value noise levels are more often
A-weighted.
2.8 SOUND Sound power levels and sound pressure levels are quantities used to
REDUCTION describe the noise produced by a product. If a product, such as a louvre,
silencer or window is designed to stop the transmission of noise then
different quantities are used.
2.9 NOISE RATING Noise Rating (NR) curves are another noise descriptor that can be used.
CURVES NR values are often specified in design criteria. NR curves were
developed by the International Organisation for Standardisation (ISO)
and are outlined in ISO 1996 and originally developed by Kosten and van
Os (1962). NR curves use the 1000 Hz octave band as a reference
point. For example NR 50 has a level of 50 dB at 1000 Hz. NR curves
are predominantly utilised in Europe. In the USA Noise Criterion (NC)
curves are used. Figure 6 shows NR curves.
© BSRIA BG 41/2012
WHAT IS MEASURED? 2
Figure 6 : Noise Rating (NR) curves.
120
115
110 110
105
100 100
95
90 90
85
80
80
Octave band sound pressure level dB re. 20 µPa
75
70
70
65
60
60
55
50
50
45
40
40
35
30
30
25
20
20
15
10
10
5
0
0
31.5 63 125 250 500 1000 2000 4000 8000
3 WHY MEASURE?
3.1 COMMON NOISE The most important reason for carrying out noise measurements is to
SOURCES IN identify noise sources within a product and measure the level of noise
HVAC
produced. These noise measurements can then be used for product
development and meeting the requirements of planning and
accreditation schemes.
Any moving or vibrating part in a product can produce noise and this
noise will vary with the operation of the product. For example as a fan’s
rotational speed changes, the noise produced by the fan changes. Some
products contain one noise source and some products contain multiple
noise sources. For example, in an air source heat pump the noise sources
are a fan, a compressor and a pump.
Noise produced by a product will be transmitted through the air and this
is called airborne noise. Vibration is transmitted through structures and
may be radiated as noise by connected components; this is called
structure-borne noise.
Whilst casing and ductwork are not primary noise sources, they can
positively and negatively alter the transmission of noise from internal
sources. As an example, a well fitted and insulated product casing can
help reduce the transmission of airborne noise from internal components
into the surrounding environment. On the other hand if the casing is
poorly fitted or not vibration isolated then it may become a major
secondary radiator of noise. Anti-vibration mounts can be used to
minimise the transmission of structure-borne noise.
3.2 PATHS OF NOISE Once the noise sources of a product have been identified, it is necessary
TRANSMISSION to understand how that noise will be transmitted in a real life situation.
When a product is installed, noise can be transmitted through various
different paths. Figure 7 shows typical paths of noise transmission for an
air conditioning unit installed in a building.
© BSRIA BG 41/2012
WHY MEASURE? 3
Figure 7 : Paths of noise transmission.
Figure 7 shows a building with a plant room in the basement and offices
above. The red box shows an air conditioning unit in the plant room. It
produces noise which propagates through the room, as shown by the
blue arrows emanating away from the air conditioning unit. This noise
could cause disturbance to people working in the plant room. Airborne
noise can also be transmitted through the ceiling, causing disturbance to
the occupants of the offices above. The air conditioning unit may be
supplying air to the offices and airborne noise will propagate through the
ductwork and into the offices. This is shown by the blue arrows through
the ductwork. If the duct is lined or an attenuator is installed then the
noise will be reduced as it travels along the ductwork.
The air conditioning unit can also cause structure-borne noise, as shown
by the green arrows in Figure 7. If the unit is installed with anti-vibration
mounts structure-borne noise into the floor of the plant room will be
reduced. Depending on the installation of the ductwork, structure-borne
noise can also be transmitted through the ductwork.
3.3 THE IMPORTANCE Noise data is often given as a single value representing the overall noise
OF FREQUENCY level. Noise levels can also be given for each of the one-third octave
DATA
band centre frequencies. Figure 8 demonstrates why it is important to
provide the noise level in each frequency band rather than just an
overall single value noise level.
Figure 8 : One third octave band centre frequency sound power levels.
90
80
70
Sound power level (dB)
60
Product A
50
Product B
40
30
Product C
20
10
0
00
50
00
00
0
00
0
00
0
00
0
00
00
5
50
0
0
0
00
25
10
80
20
16
12
31
50
63
40
63
12
16
25
10
20
50
80
40
31
10
© BSRIA BG 41/2012
WHY MEASURE? 3
3.4 PRODUCT Once acoustic performance data has been obtained, it can either just be
DEVELOPMENT stated in a product brochure or utilised to develop a quieter and less
audibly disturbing product. It is beneficial to employ the services of an
acoustician during product development.
Figure 9 shows the one-third octave band centre frequency sound power
levels for a product, in this case an air source heat pump. It is clear that
the sound power level in the 200 Hz frequency band is much higher
than sound power levels in other frequency bands. The noise produced
by this product will have an audible tone at 200 Hz.
80
70
60
50
Sound power level (dB)
40
30
20
10
0
0
00
50
00
00
0
00
0
00
0
0
0
00
00
00
5
50
0
0
00
25
10
80
20
16
12
31
50
63
40
63
12
16
25
10
20
50
80
40
31
10
Determining what is causing this tone and how to stop it will lead to a
Watchpoint quieter and less audibly disturbing product. Tones can be caused by
Having accurate acoustic something as simple as a fan being unbalanced. Such problems are often
data and being able to
interpret the data leads quick and inexpensive to solve, and can easily make the product quieter
to useful product and less audibly disturbing. Having accurate acoustic data about a product
development, without and being able to interpret the data leads to useful product development,
compromising the quality without compromising the quality or performance of the product.
or performance of the
product.
If a product has multiple noise sources – such as a fan and a compressor –
it might be difficult to determine which component is causing the noise
issue. If possible, it is useful to operate each component of the product
separately so that the noise produced by each noise source can be
examined independently.
3.5 PLANNING In certain situations, planning authorities will require a noise assessment
APPLICATIONS to be carried out before a product is installed. Every authority has their
own planning policies and noise criteria, but the aim of the noise
assessment is always the same – to avoid a negative noise impact on
existing or future inhabitants. Information about local planning policies
can be found by contacting the Local planning Authority (LPA). Noise
assessments should be carried out by a qualified acoustician.
3.6 TEST STANDARDS There are many different British, European and International Standards
AND that outline test methodologies to determine the noise produced by a
ACCREDITATION
SCHEMES product. Some test standards applicable to HVAC products are described
in Appendix B. There are also a number of product specific testing
schemes, which are described in Appendix B.
© BSRIA BG 41/2012
EXAMPLES OF ACOUSTIC PERFORMANCE DATA 4
4 EXAMPLES OF ACOUSTIC PERFORMANCE DATA
Parameter Description
Noise level descriptor The sound power level, sound pressure level or a
sound insulation quantity such as sound reduction
index or insertion loss.
Measurement unit The dB or dB(A) unit.
Distance In the case of sound pressure levels, the distance the
measurement was carried out at – typically 1 m, 3 m or
10m. Note that sound power levels are stated
independently of distance from the source.
Test standard The test standard used to carry out the measurements,
and the installation and test conditions that the
measurements were carried out for.
Noise levels The overall noise level and noise level in each one-
third octave or octave band centre frequency.
Mode of operation The noise level at each operation of the product (e.g.
different fan speeds). If the noise level for only one
mode of operation is given then the operating
conditions should be clearly stated.
© BSRIA BG 41/2012
EXAMPLES OF ACOUSTIC PERFORMANCE DATA 4
Fan Speed A B C D E F
Sound Power Level
69 69 71 71 72 74
dB(A)1
1
Sound power level measured in accordance with ISO 3741
The test standard is given but there are no details Overall noise level
about the particular installation of the fan during Frequency band noise levels ×
test.
Mode of operation
More information about ISO 3741:2010 can be
found in Appendix B.
The reference value used for sound power levels and sound pressure
levels is different. For sound power levels the reference value is 1 pW
and for sound pressure levels the reference value is 20 µPa. It is important
to note which quantity is being stated in technical acoustic specifications
so that incorrect comparisons are not made.
A sound power level of 50dB does not equal a sound pressure level of
50dB.
Sound power levels and sound pressure levels can be calculated using the
following equations.
Some examples of the result of combining the sound level from two
noise sources is given in the table below.
These results are true when combining sound pressure levels or sound
power levels, but a sound pressure level and sound power level cannot be
combined directly because they have different references. To convert
from a sound power level to a sound pressure level specific formulae are
used depending on the specific acoustic environment the noise source is
located in. There are also formulae to determine sound pressure levels at
different distances from a sound source. An acoustician will be able to
assist with performing these calculations.
© BSRIA BG 41/2012
ACOUSTIC STANDARDS AND GUIDANCE B
BS 4142 Method for rating industrial noise affecting mixed residential and
industrial areas. ISBN 0 580 28300 3
This British Standard is solely for industrial noise sources and makes a
comparison between the potential noise source and the existing
background noise level at the proposed site of the industrial noise source.
The extent to which the background noise levels are exceeded is an
indication of the likelihood of annoyance to occupants in the vicinity of
the proposed noise source. Annoyance is more likely when locating a
loud industrial noise source in a quiet area and less likely when locating a
quieter industrial noise source in a louder area.
© BSRIA BG 41/2012
GLOSSARY
Anechoic chamber A room with surfaces that have a very high sound absorption.
A-weighting A frequency weighting applied to noise levels, which approximates the frequency
sensitivity of the human ear.
Decibel (dB) The logarithmic unit of the ratio of a measured quantity to a reference quantity. The
decibel is used to describe sound levels.
Frequency The number of pressure fluctuations per second, measured in Hertz (Hz). An adult with
normal hearing can hear from 20 Hz to 20 kHz.
Hertz (Hz) The SI unit of frequency.
Insertion loss A measure of the difference in the noise level at a given point in a duct with and without
the insertion of a noise control product.
Noise Any sound that is undesired by the recipient.
Noise Rating (NR) Noise Rating (NR) curves are used to assess whether indoor noise levels are likely to
cause annoyance or be detrimental to communication.
Octave band A range of frequencies whose upper frequency limit is twice that of its lower frequency
limit. For example, the 1000 Hz octave band contains sound energy at all frequencies
from 707 Hz to 1414 Hz.
Pascal (Pa) The SI unit of pressure.
Reverberation A room with a large volume and surfaces that have a very low sound absorption.
chamber
Reverberation time The time taken for the sound pressure level in a room to decrease by 60 dB after a
sound source has been stopped. The longer the reverberation time, the more
reverberant the room.
Silencer A product, often installed in a duct, which is designed to reduce the level of noise
through it.
Sound Any pressure variation in the air that the human ear can detect.
Sound insulation A measure of how good a partition material (for example wall, window, or door) is at
stopping the transmission of noise through it.
Sound power The total sound energy radiated by a source per unit of time.
Sound power level The logarithmic ratio of a sound power and a reference sound power.
Sound pressure The difference between the instantaneous pressure produced by a sound wave and the
barometric pressure at a given point in space.
Sound pressure level The logarithmic ratio of a sound pressure and a reference sound pressure.
Watt (W) The SI unit of power.
BSRIA operates a specialist thermal acoustic test facility for testing a range of HVAC products. Our thermally
controlled large reverberation chamber is suitable for carrying out:
BSRIA Test
Tel: +44 (0)1344 465600
Email: [email protected]
BG 41-12 Final_Guide Cover 03/07/2012 15:04 Page 2
Testing Troubleshooting
Modelling Information
Research Training
Consultancy Publications