HCV-2, HCV-4, HCV-8
CONVENTIONAL FIRE ALARM CONTROL PANEL
STANDARD FEATURES
• Fully compliant with & tested to BS EN54-2 and
BS EN54-4
• 2-wire Annunciator
• Fully programmable using simple menu options
• Simple, single board construction
• Installer friendly
• Compatible with wide range of detection devices
• Two monitored NAC outputs
• 3 Amp power supply
• Auxiliary power output
• Adjustable sounder delay time
• NAC configuration options
• Zonal NAC delay detectors only
DESCRIPTION • Zonal NAC delay call points only
• Coincidence input selection
• I.S. Barrier selection by zone
The HCV series is available in a 2, 4, 8 Zone
conventional panel design which is in accordance • Short circuit fire by zone
with BS EN54-2 and BS EN54-4 Detection and Fire • Non latching zones
Alarm Systems – Control and Indicating Equipment. • Silent zones
• Zone input delay
The HCV series has an integrated Power Supply and
Battery charging circuit. The control panel has
“Voltage Free” Contacts for Fire and Local Fire which
operate upon a fire condition. These are used for
local control and signaling. In accordance with BS
PRODUCT LISTING
EN54-4.
The HCV series are fully programmable using simple
menu options. The Panel is a single board
construction, which is installer friendly. Compatible
with a wide range of detection devices. Remote
control input terminals for Silence Alarm, Sound
Alarm, Trouble and Reset.
http://BaoMinhGroup.com: Chuyên phân phối Trung Tâm Báo Cháy HOCHIKI HCV-2, HCV-4, HCV-8 tại Việt Nam.
Liên hệ đặt hàng: 0909 018 089 - Email: [email protected]
Continued on back.
Specifications subject to change without notice.
Hochiki America Corporation Find latest revision at www.hochiki.com
7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or
[email protected] F0094 02/2010
Trung tâm báo cháy HOCHIKI HCV-2, HCV-4, HCV-8
SPECIFICATIONS
Supply Voltage 120VAC (50hz/60hz) or 220VAC (50hz/60hz)
Power Supply DC Rating 24V 3 Amps
Mains Supply Fuse 1.6 Amp 250V
Dimensions 385mm(W) x 310mm(H) x 92mm(D)
Weight 11.5 lbs.
Color Red
Material 1.2mm mild steel
Max. Battery Size 7Ah 12V (2 per panel)
Fault Contact Rating 30VDC 1 Amp
Local Fire Contact Rating 30VDC 1 Amp
Fire Contact Rating 30VDC 1 Amp
NAC Output Rating 0.5A per output (max 1.6A over all outputs)
Detection Zone Current 1.6mA
Detection Zone 6K8 5%
End of line resistor
Sounder Output 10K 5%
Stand by Current HCV-2: 0.065Amp, HCV-4: 0.075Amp, HCV-8: 0.093Amp
Alarm Current HCV-2: 0.1Amp, HCV-4: 0.21Amp, HCV-8: 0.55Amp
End of line resistor
Cable Capacity 2.5 mm per terminal
Operating Humidity 95% (non condensing)
Operating Temperature -5°C to +50°C
HOCHIKI AMERICA COMPATIBLE DEVICES
MODEL DESCRIPTION MAX. # PER ZONE
DETECTORS
SLR-24V/-24VN Photoelectric high velocity smoke detector 25
SLR-24H Photoelectric smoke detector 25
SLR-835H/ -835HW Photoelectric 8-35V smoke detector with Heat 25
SLR-835/-835W Photoelectric 8-35V smoke detector 25
SLR-835-BH-2W Photoelectric 8-35V smoke detector with Heat 25
SIJ-24 Ionization smoke detector 25
DFE-135 135° Fixed temperature heat detector 25
DFE-190 190° Fixed temperature heat detector 25
DCD-135 135° Fixed temperature rate of rise heat detector 25
DCD-190 190° Fixed temperature rate of rise heat detector 25
DSC-EA Rate of rise heat detector 25
SLV-24/-24N Photoelectric smoke detector 25
BASES
NS6-224 6" base, 43mA draw, 24V 25
NS4-224 4" base, 43mA draw, 24V 25
NS4-100 4" base, 24V 25
NS6-100 6" base, 24V 25
PULL STATION
HPS-SAK/HPS-DAH Conventional Manual Pull Station 32
HPS-SAH/HPS-DAK
PPE-2(JE) Call Point 32
BEAM DETECTORS
SPC-24 Beam detector 8
SRA-24 Reflective beam detector 5
NOTIFICATION DEVICES
GENTEX
GES24-1575WR Horn/Strobe 8
GEC3-24WR Horn/Strobe 8
WGEC-2475WR Horn/Strobe 10
AMSECO/POTTER
SH24W-153075R Horn/Strobe 8
SH24-75110R Horn/Strobe 8
SL24W-153075R Horn/Strobe 8
MBA-6 6" Motor Driven Bell, 24VDC 4
HOCHIKI
FBB-1501 6" Alarm Bell, 24VDC 4
Hochiki America Corporation CONVENTIONAL FIRE ALARM CONTROL PANEL Specifications subject to change without notice.