CLIMAVENETA Chiller Technical Data
CLIMAVENETA Chiller Technical Data
NECS-N /B 1816
Software version: ELCA World 1.5.3.0
Database version: 1.6.3.0
User: RADHA KRISHNAN
Print data: 01-05-2021 10:20
Calculation type: AHRI 550/590 and AHRI 551/591
Note
Outside the scope of AHRI Air-Cooled Water-Chilling Packages Certification Program, but is rated
in accordance with AHRI Standard 550/590 (I-P).
RUNNING CONDITIONS
COOLING
OUTDOOR CONDITION
Air temperature (cooling mode) °C 30.0
HEATING
OUTDOOR CONDITION
Air temperature (heating mode) °C -5.0
HEATING
Total heating capacity kW 394
Compressors power input (heating mode) kW 153.3
Fan power input (heating mode) kW 18.0
Total power input kW 171.3
COP kW/kW 2.30
The performance shown are obtained from theoretical calculations and tolerances will apply.
Rpt.version: 1.0.5.0
TECHNICAL SELECTION - AHRI 550/590 and AHRI 551/591 Page 2 / 4
NECS-N /B 1816
Software version: ELCA World 1.5.3.0
Database version: 1.6.3.0
User: RADHA KRISHNAN
Print data: 01-05-2021 10:20
Calculation type: AHRI 550/590 and AHRI 551/591
EFFICIENCIES
IPLV
Load % 100 75 50 25
Outdoor air temperature °C 35.0 26.7 18.3 12.8
Temp. evaporator inlet °C 12.22 10.83 9.44 8.06
Temp. evaporator outlet °C 6.67 6.67 6.67 6.67
Evaporator water flow l/s 20.39 20.39 20.39 20.39
Cooling capacity kW 473 355 237 118
Total power input kW 177.2 95.4 53.5 24.8
COPr kW/kW 2.67 3.72 4.42 4.77
IPLV.IP CALCULATED kW/kW 4.15
Rc (ASHRAE) kg/kW 0.20
EXCHANGERS
COOLING
Fluid inlet temperature (cooling mode) °C 12.20
Fluid outlet temperature (cooling mode) °C 6.70
Water flow l/s 21.95
Pressure drop at the heat exchanger kPa 39.3
Available unit head kPa 0.0
The performance shown are obtained from theoretical calculations and tolerances will apply.
Rpt.version: 1.0.5.0
TECHNICAL SELECTION - AHRI 550/590 and AHRI 551/591 Page 3 / 4
NECS-N /B 1816
Software version: ELCA World 1.5.3.0
Database version: 1.6.3.0
User: RADHA KRISHNAN
Print data: 01-05-2021 10:20
Calculation type: AHRI 550/590 and AHRI 551/591
HEATING
Fluid inlet temperature (heating mode) °C 40.00
Fluid outlet temperature (heating mode) °C 45.00
Water flow l/s 19.00
Pressure drop at the heat exchanger kPa 29.5
Available unit head kPa 0.0
FANS
Fans type AXIAL
Fans number N° 9
Fans power input kW 2.0
F.L.I. kW 2.0
F.L.A. A 4
COOLING
Fans number N° 9
Fans power input kW 2.0
Air flow m³/s 53.1
Available static pressure Pa 0
HEATING
Quantity N° 9
Fans power input kW 2.0
Air flow m³/s 53.1
Fan available static pressure Pa 0
COMPRESSORS
Compressor type SCROLL
Compressors nr. N° 6
No. Circuits N° 3
Refrigerant R410A
Number of capacity steps N° 6
Min. capacity step % 17
Regulation STEPS
Oil charge kg 38.0
Refrigerant charge kg 97.0
F.L.I. - Max absorbed power kW 6x35,8
F.L.A. - Max absorbed current A 6x58,9
L.R.A. - Locked rotor amperes for single compressor A 6x310
ELECTRICAL DATA
Power supply V/ph/Hz 400/3/50
F.L.I. - Max absorbed power kW 232.8
F.L.A. - Max absorbed current A 388
S.A. - Inrush current A 639
The performance shown are obtained from theoretical calculations and tolerances will apply.
Rpt.version: 1.0.5.0
TECHNICAL SELECTION - AHRI 550/590 and AHRI 551/591 Page 4 / 4
NECS-N /B 1816
Software version: ELCA World 1.5.3.0
Database version: 1.6.3.0
User: RADHA KRISHNAN
Print data: 01-05-2021 10:20
Calculation type: AHRI 550/590 and AHRI 551/591
The performance shown are obtained from theoretical calculations and tolerances will apply.
Rpt.version: 1.0.5.0