This document provides performance specifications for a chiller unit rated in accordance with AHRI 550/590 standards. It includes key details like cooling capacity, power input, efficiencies and part load performance data across a range of conditions. The unit has a cooling capacity of 505kW, COP of 3.11 and meets the ANSI/ASHRAE/IES 90.1 efficiency requirements. Part load data is provided for cooling and heating modes from 100% to 10% capacity.

Uploaded by

Rohit Sah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views4 pages

CLIMAVENETA Chiller Technical Data

This document provides performance specifications for a chiller unit rated in accordance with AHRI 550/590 standards. It includes key details like cooling capacity, power input, efficiencies and part load performance data across a range of conditions. The unit has a cooling capacity of 505kW, COP of 3.11 and meets the ANSI/ASHRAE/IES 90.1 efficiency requirements. Part load data is provided for cooling and heating modes from 100% to 10% capacity.

Uploaded by

Rohit Sah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

TECHNICAL SELECTION - AHRI 550/590 and AHRI 551/591 Page 1 / 4

NECS-N /B 1816
Software version: ELCA World 1.5.3.0
Database version: 1.6.3.0
User: RADHA KRISHNAN
Print data: 01-05-2021 10:20
Calculation type: AHRI 550/590 and AHRI 551/591

Code NECS-N /B 1816


Version B
Size 1816
Power supply V/ph/Hz 400/3/50

Note
Outside the scope of AHRI Air-Cooled Water-Chilling Packages Certification Program, but is rated
in accordance with AHRI Standard 550/590 (I-P).

PERFORMANCE AT DESIGNED CONDITIONS

RUNNING CONDITIONS

COOLING

HEAT EXCHANGER USER SIDE


Fluid inlet temperature (cooling mode) °C 12.20
Fluid outlet temperature (cooling mode) °C 6.70
Fluid type WATER
Glycol % 0
Fouling factor m²K/kW 0.044

OUTDOOR CONDITION
Air temperature (cooling mode) °C 30.0

HEATING

HEAT EXCHANGER USER SIDE


Fluid inlet temperature (heating mode) °C 40.00
Fluid outlet temperature (heating mode) °C 45.00
Fluid type WATER
Glycol % 0
Fouling factor m²K/kW 0.044

OUTDOOR CONDITION
Air temperature (heating mode) °C -5.0

COOLING (Gross value)


Cooling capacity kW 505
Compressor power input kW 144.4
Fans power input (cooling mode) kW 18.0
Total power input kW 162.4
COPr kW/kW 3.11
IPLV.IP REFERENCE kW/kW 4.15
Compliance with ANSI/ASHRAE/IES Standard 90.1 (I-P) - 2016 - Path A
Note Compliance with ANSI/ASHRAE/IES Standard 90.1 (I-P) - 2013 - Path A
Performance related to Altitude: 0 ft a.s.l.

HEATING
Total heating capacity kW 394
Compressors power input (heating mode) kW 153.3
Fan power input (heating mode) kW 18.0
Total power input kW 171.3
COP kW/kW 2.30

The performance shown are obtained from theoretical calculations and tolerances will apply.
Rpt.version: 1.0.5.0
TECHNICAL SELECTION - AHRI 550/590 and AHRI 551/591 Page 2 / 4

NECS-N /B 1816
Software version: ELCA World 1.5.3.0
Database version: 1.6.3.0
User: RADHA KRISHNAN
Print data: 01-05-2021 10:20
Calculation type: AHRI 550/590 and AHRI 551/591

EFFICIENCIES

IPLV
Load % 100 75 50 25
Outdoor air temperature °C 35.0 26.7 18.3 12.8
Temp. evaporator inlet °C 12.22 10.83 9.44 8.06
Temp. evaporator outlet °C 6.67 6.67 6.67 6.67
Evaporator water flow l/s 20.39 20.39 20.39 20.39
Cooling capacity kW 473 355 237 118
Total power input kW 177.2 95.4 53.5 24.8
COPr kW/kW 2.67 3.72 4.42 4.77
IPLV.IP CALCULATED kW/kW 4.15
Rc (ASHRAE) kg/kW 0.20

PART LOAD DATA

COOLING PARTIAL LOADS


Load % 100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0 20.0 10.0
Outdoor air temperature °C 30.0 30.0 30.0 30.0 30.0 30.0 30.0 30.0 30.0 30.0
Cooling load kW 505 454 404 354 303 253 202 152 101 51
Fans power input (cooling mode) kW 18.0 18.0 18.0 18.0 18.0 18.0 18.0 12.0 12.0 3.5
Total power input kW 162.4 142.3 122.2 103.3 89.5 75.0 59.8 44.9 30.2 16.0
Temp. evaporator inlet °C 12.20 11.65 11.10 10.55 10.00 9.45 8.90 8.35 7.80 7.70
Temp. evaporator outlet °C 6.70 6.70 6.70 6.70 6.70 6.70 6.70 6.70 6.70 6.70
Evaporator water flow l/s 21.95 21.95 21.95 21.95 21.95 21.95 21.95 21.95 21.95 21.95
COPr kW/kW 3.11 3.19 3.31 3.42 3.39 3.37 3.38 3.37 3.34 3.15

HEATING PART LOAD


Load % 100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0 20.0 10.0
Outdoor air temp. °C -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0
Heating load RT 112 101 90 78 67 56 45 34 22 11
Total power input kW 171.3 152.7 135.0 117.9 97.1 78.4 63.1 47.9 32.7 17.5
Condenser input temperature °C 40.00 40.50 41.00 41.50 42.00 42.50 43.00 43.50 44.00 44.11
Condenser output temperature °C 45.00 45.00 45.00 45.00 45.00 45.00 45.00 45.00 45.00 45.00
Condenser fluid flow l/s 19.00 19.00 19.00 19.00 19.00 19.00 19.00 19.00 19.00 19.00
COP kW/kW 2.30 2.32 2.33 2.34 2.43 2.51 2.50 2.47 2.40 2.25

EXCHANGERS

HEAT EXCHANGER USER SIDE


Typology SHELL&TUBE
Quantity N° 1
Fluid type WATER
Glycol % 0
Fouling factor m²K/kW 0.044
Type of connections VICTAULIC
Diameter of connections 5"
Min flow l/s 14.28
Max flow l/s 36.19
K pressure drop 6.30
Heat exchanger water content l 0.0
Minimum water content admitted in the plant l 1430.0

COOLING
Fluid inlet temperature (cooling mode) °C 12.20
Fluid outlet temperature (cooling mode) °C 6.70
Water flow l/s 21.95
Pressure drop at the heat exchanger kPa 39.3
Available unit head kPa 0.0

The performance shown are obtained from theoretical calculations and tolerances will apply.
Rpt.version: 1.0.5.0
TECHNICAL SELECTION - AHRI 550/590 and AHRI 551/591 Page 3 / 4

NECS-N /B 1816
Software version: ELCA World 1.5.3.0
Database version: 1.6.3.0
User: RADHA KRISHNAN
Print data: 01-05-2021 10:20
Calculation type: AHRI 550/590 and AHRI 551/591

HEATING
Fluid inlet temperature (heating mode) °C 40.00
Fluid outlet temperature (heating mode) °C 45.00
Water flow l/s 19.00
Pressure drop at the heat exchanger kPa 29.5
Available unit head kPa 0.0

FANS
Fans type AXIAL
Fans number N° 9
Fans power input kW 2.0
F.L.I. kW 2.0
F.L.A. A 4

COOLING
Fans number N° 9
Fans power input kW 2.0
Air flow m³/s 53.1
Available static pressure Pa 0

HEATING
Quantity N° 9
Fans power input kW 2.0
Air flow m³/s 53.1
Fan available static pressure Pa 0

COMPRESSORS
Compressor type SCROLL
Compressors nr. N° 6
No. Circuits N° 3
Refrigerant R410A
Number of capacity steps N° 6
Min. capacity step % 17
Regulation STEPS
Oil charge kg 38.0
Refrigerant charge kg 97.0
F.L.I. - Max absorbed power kW 6x35,8
F.L.A. - Max absorbed current A 6x58,9
L.R.A. - Locked rotor amperes for single compressor A 6x310

ELECTRICAL DATA
Power supply V/ph/Hz 400/3/50
F.L.I. - Max absorbed power kW 232.8
F.L.A. - Max absorbed current A 388
S.A. - Inrush current A 639

The performance shown are obtained from theoretical calculations and tolerances will apply.
Rpt.version: 1.0.5.0
TECHNICAL SELECTION - AHRI 550/590 and AHRI 551/591 Page 4 / 4

NECS-N /B 1816
Software version: ELCA World 1.5.3.0
Database version: 1.6.3.0
User: RADHA KRISHNAN
Print data: 01-05-2021 10:20
Calculation type: AHRI 550/590 and AHRI 551/591

WEIGHT & DIMENSIONS


A mm 5690
B mm 2260
H mm 2450
Operating weight kg 4610
R1 mm 1500
R2 mm 2000
R3 mm 1500
R4 mm 1500

The performance shown are obtained from theoretical calculations and tolerances will apply.
Rpt.version: 1.0.5.0