The AW-CSD381 is a conventional photo-electronic smoke detector that uses an optical sensing chamber for open area protection. It is designed to be used with the AW-CFP2166 conventional fire alarm panel. The detector that triggers an alarm will have its red LED and relays latched until reset by the panel. It has features like surface mounting, an LED indicator, and functional testing on activation. It meets relevant EN54-7 standards and is for indoor use only with two-wire zone connections.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
501 views1 page

AW-CSD381 Smoke Detector Overview

The AW-CSD381 is a conventional photo-electronic smoke detector that uses an optical sensing chamber for open area protection. It is designed to be used with the AW-CFP2166 conventional fire alarm panel. The detector that triggers an alarm will have its red LED and relays latched until reset by the panel. It has features like surface mounting, an LED indicator, and functional testing on activation. It meets relevant EN54-7 standards and is for indoor use only with two-wire zone connections.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Conventional Photo-electronic Smoke Detector AW-CSD381

The AW-CSD381 conventional


photo-electronic smoke detector uses
a state of the art optical sensing
chamber. This detector is designed to
provide open area protection and to be
used with the AW-CFP2166
conventional fire alarm panel.
The detector that initiated the alarm
condition will have its red LED and
relays latched until reset by panel.

Features Installation
 Surface mounting

 LED indicator

 Complete functional test with


every activation

 Meets all requirements of latest


EN54-7:2001

Technical Specification
Model AW-CSD381
Main Voltage Zone 24V or 12V
Operating current monitoring status≤120uA, alarm status≤15mA
Application For indoor use only
Wiring The promise of two bus system(Zone +, Zone -)
Protection class IP30
Smoke Alarm Sensitivity 0.1 to 0.15 dB/m
Class A temperature range: -10 to 50°C (14~122°F)
Environmental
Humidity: 5 to 95% RH, non-condensing
Materials and colors ABS, White
Mating Host AW-CFP2166 fire alarm control panel
Size 99.5mm* 99.5mm* 48.2mm
Weight about 114.5g

ASENWARE LTD