Technical Report No. 64.181.20.00804.01 Rev.
00
Date: 2020-03-10
Client: Name: NINGBO AKL HEATPUMP TECHNOLIGY CO., LTD
Address: 550 Kangzhuang South Road Ningbo Zhejiang China
Contact person: Yang Shi
Manufacturing place: Manufacturer’s name: NINGBO AKL HEATPUMP TECHNOLIGY CO., LTD
Address: 550 Kangzhuang South Road Ningbo Zhejiang China
Factory’s name: NINGBO AKL HEATPUMP TECHNOLIGY CO., LTD
Address: 550 Kangzhuang South Road Ningbo Zhejiang China
Test subject: Product: DC Inverter Air to Water Heat Pump
Type: ASH-65CHW/F1, ASH-65CHW/M1, ASH-65CHW/V1
Trade name: AKL
Test specification: EN 14825:2016
(EU) No 813/2013
Purpose of Test according to the test specification
examination:
EU 2016/2282:2016-11-30
Doc No: ITC-TTW0902.02E – Rev.4
Test result: The test results show that the presented product is in compliance with the specified
requirements
Any use for advertising purposes must be granted in writing. This technical report may only be quoted in full. This report is the result
of a single examination of the object in question and is not generally applicable evaluation of the quality of other products in regular
production. For further details please see testing and certification regulation, chapter A-3.4.
Project No: 64.181.20.00804.01
Rev.: 00
Date: 2020-03-10
Page: 1 of 13
1 Description of the test subject
1.1 Function
Manufacturer’s specification for intended use:
The appliance is air to water heat pump.
Manufacturer’s specification for foreseeable use:
According to user manual
1.2 Consideration of the foreseeable use
Not applicable
Covered through the applied standard
Covered by the following comment
Covered by attached risk analysis
1.3 Technical Data
ASH-65CHW/F1, ASH-65CHW/M1, ASH-
Model :
65CHW/V1
Rated Voltage (V) : 380-415,3N~
Rated Frequency (Hz) : 50
Rated Power (W) : 4600 for heating; 4900 for cooling
Rated Current (A) : 7.0 for heating; 7.4 for cooling
Protection Class : Class I
Protection Against Moisture : IP X4
Construction : Stationary
Supply connection : ## Non detachable cord
## Permanent connection to fixed wiring
Operation mode: ## Continuous operation;
## Intermittent operation;
## Short time operation;
R410A /4200g
Refrigerant/charge (g) :
Declared parameters : Average Warmer Colder
Sound power level dB(A) : N/A
1201911080001 for Indoor Unit; W201911080001
Series No :
for Outdoor Unit
Doc No: ITC-TTW0902.02E – Rev.4
Project No: 64.181.20.00804.01
Rev.: 00
Date: 2020-03-10
Page: 2 of 13
2 Order
2.1 Date of Purchase Order, Customer’s Reference
2020-02-22 , Yang Shi
2.2 Receipt of Test Sample, Condition, Location
2020-02-22
For Energy test:
GZ-Lans Experimental Technology Co., Ltd. Laboratory
Address: Room F2, No.10, Mubei East Road, Xintang Street, Tianhe
District,Guangzhou, Guangdong, China
2.3 Date of Testing
2020-02-22 to 2020-02-28
2.4 Location of Testing
Same as 2.2
2.5 Points of Non-compliance or Exceptions of the Test Procedure
N/A
3 Test Results
3.1 Positive Test Results
See Appendix I
4 Remark
N/A
4.1 The user manual has been examined according to the minimum requirements described
in the product standard. The manufacturer is responsible for the accuracy of further par-
ticulars as well as of the composition and layout.
4.2 When the product is placed on the market, it must be accompanied with safety Instruc-
tions written in official language of the country. The instructions shall give information re-
garding safe operation, installation and maintenance.
5 Documentation
• Appendix I Test results
• Appendix II Marking plate
• Appendix III photo documentation
• Appendix IV Construction data form
• Appendix V Test equipment list
Doc No: ITC-TTW0902.02E – Rev.4
Project No: 64.181.20.00804.01
Rev.: 00
Date: 2020-03-10
Page: 3 of 13
6 Summary
1) The appliance is DC Inverter Type Air To Water Unit , including a whole compression
type refrigerant circuit to heat water in another circuit. The appliance was for cooling and
heating water function, this report only for heating capacity test.
2) The main power is supplied by a 5-pole supply cable not with plug which not supply by
manufactory.
3) Water enthalpy method was adopted in this report.
4) Standby mode power, off mode power and thermostat-off mode power were tested
according to clause 9 of standard EN 14825:2016.
5) The models ASH-65CHW/M1, ASH-65CHW/V1 are same as ASH-65CHW/F1 except for
model’s name. And the test are carried out at models ASH-65CHW/F1.
TÜV SÜD Certification and Testing (China) Co., Ltd. Guangzhou Branch
TÜV SÜD Group
Tested by: William Liang, Project Handler
printed name, function & signature
Approved by: Tony Xie, Designated Reviewer
printed name, function & signature
Doc No: ITC-TTW0902.02E – Rev.4
Project No: 64.181.20.00804.01
Rev.: 00
Date: 2020-03-10
Page: 4 of 13
Appendix I Test results
Table 1. Heating mode(Low temperature application): P
Model ASH-65CHW/F1
Product Air to Water Heating Averag Warmer Colder
type season e
1. Test conditions:
Part Load Ratio Outdoor heat Indoor heat
Condition
in % exchanger exchanger
Formula WA Inlet dry (wet) Inlet/outlet water
bulb temperatures (°C)
temperature
°C
A (-7-16)/(Tdesignh-16) 88 N/A N/A -7(-8) a / 34
B (+2-16)/ (Tdesignh-16) 54 N/A N/A 2(1) a / 30
C (+7-16)/(Tdesignh-16) 35 N/A N/A 7(6) a / 27
D (+12-16)/(Tdesignh-16) 15 N/A N/A 12(11) a / 24
E (TOL-16)/ (Tdesignh-16) TOL a / 35.3
F (Tbivalent-16)/(Tdesignh-16) Tbiv a / 34
G (-15-16)/(Tdesignh-16) N/A N/A N/A -15 N/A
Remark: a) With the water flow rate as determined at the standard rating conditions given in EN14511-2
at 30/35 conditions.
2.Tested data/correction data(Average):
General test Unit A(-7)/W34 A2/W30 A7/W27 A12/W24 A(- A(-
conditions/ (88%) (54%) (35%) (15%) 10)/W35. 7)/W34
Part-Load 3 (88%)
(100%)
-- A B C D E F
Data hh: min:sec 3:00:00 3:00:00 2:00:00 2:00:00 3:00:00 3:00:00
collection
period
The heat -- Yes Yes No No Yes Yes
pump
defrosts
Complete -- 1 1 0 0 1 1
Cycles
Barometric kPa 101.02 101.02 101.02 101.02 101.02 101.02
pressure
Voltage V 410.2 405.6 401.9 404.7 399.2 410.2
Current input A 5.91 2.89 2.12 1.80 7.74 5.91
of the unit
Doc No: ITC-TTW0902.02E – Rev.4
Power input kW 3.767 1.678 1.158 0.964 4.972 3.767
of the unit
Test conditions indoor unit
Inlet Water °C 29.46 27.17 24.54 21.32 29.68 29.46
temperature,
DB
Outlet Water °C 33.58* 29.80 27.00 24.20 34.12* 33.58*
temperature,
DB
Project No: 64.181.20.00804.01
Rev.: 00
Date: 2020-03-10
Page: 5 of 13
Appendix I Test results
Test conditions outdoor unit
Air inlet °C -6.96 2.01 7.03 12.02 -9.96 -6.96
temperature,
DB
Air inlet °C -7.94 1.02 6.02 11.01 -10.83 -7.94
temperature,
WB
Summary of the results
Total heating kW 11.063 7.379 6.020 7.040 12.257 11.063
capacity
Effective kW 3.814 1.724 1.204 1.010 5.019 3.814
power input
Coefficient of -- 2.90 4.28 5.00 6.97 2.44 2.90
performance
(COP)
Compressor Hz 70 38 25 25 88 70
frequency
Water flow m³/h 2.10 2.10 2.10 2.10 2.10 2.10
Remark:
1. * In part condition, outlet temperature data is recorded by a full average complete cycle’s data.
3.Calculation/conclusion for SCOP(Average):
Tdesignh(°C) -10 Tbiv(°C) -7
Pdesignh(kW 12.506 TOL(°C) -10
)
Test result A, B, C, D, E, F conditions:
Condition
Part load Measured COP at Cdh CR COP at part load
capacity measured
capacity
E 12.506 12.257 2.44 0.00 1.00 2.44
Doc No: ITC-TTW0902.02E – Rev.4
F 11.063 11.063 2.90 0.00 1.00 2.90
A 11.063 11.063 2.90 0.00 1.00 2.90
B 6.734 7.379 4.28 0.00 0.91 4.28
C 4.329 6.020 5.00 0.99 0.72 4.98
D 1.924 7.040 6.97 0.99 0.27 6.79
CR: part load divided by capacity;
Project No: 64.181.20.00804.01
Rev.: 00
Date: 2020-03-10
Page: 6 of 13
Appendix I Test results
Electric power consumptions Unit Value
Thermostat-off mode [PTO] kW 0.008
Standby mode [PSB] kW 0.008
Crankcase heater [PCK] kW 0.059
Off mode [POFF] kW 0.008
Conclusions: Unit Value
SCOPon: kWh/kWh 4.30
SCOP: kWh/kWh 4.29
QH: kWh/year 25838
QHE: kWh/year 6028
ηs,h % 168.5
Seasonal space heating energy -- A++
efficiency classes: (According (EU)
No 811/2013 Table 2)
Doc No: ITC-TTW0902.02E – Rev.4
Project No: 64.181.20.00804.01
Rev.: 00
Date: 2020-03-10
Page: 7 of 13
Appendix II Marking plate
Nameplate
Model: ASH-65CHW/F1
Doc No: ITC-TTW0902.02E – Rev.4
Remark: The models ASH-65CHW/M1, ASH-65CHW/V1 are same as ASH-65CHW/F1 except for
model’s name.
Project No: 64.181.20.00804.01
Rev.: 00
Date: 2020-03-10
Page: 8 of 13
Appendix III photo documentaiton
Details of: Outdoor Unit Overall View
View:
General
Front
Rear
Right
Left
Top
Bottom
Details of: Compressor
View:
General
Front
Rear
Right
Left
Doc No: ITC-TTW0902.02E – Rev.4
Top
Bottom
Project No: 64.181.20.00804.01
Rev.: 00
Date: 2020-03-10
Page: 9 of 13
Appendix III photo documentaiton
Details of: Outdoor Fan Motor
View:
General
Front
Rear
Right
Left
Top
Bottom
Details of: Outdoor Main Control Board
View:
General
Front
Rear
Right
Left
Doc No: ITC-TTW0902.02E – Rev.4
Top
Bottom
Project No: 64.181.20.00804.01
Rev.: 00
Date: 2020-03-10
Page: 10 of 13
Appendix III photo documentaiton
Details of: Indoor Unit Overall View
View:
General
Front
Rear
Right
Left
Top
Bottom
Doc No: ITC-TTW0902.02E – Rev.4
Project No: 64.181.20.00804.01
Rev.: 00
Date: 2020-03-10
Page: 11 of 13
Appendix IV Construction data form
Part Technical data
Model: ASH-65CHW/F1, ASH-65CHW/M1, ASH-65CHW/V1
1. Compressor
Manufacture: Panasonic Wanao Appliances Compressor
(Guangzhou) Co., Ltd.
Type: H420D5VZAAJ2
Rated capacity: 4220W; R410A
Serial-number: N/A
2. Condenser
Manufacture: Ningbo Hrale Plate Heat Exchanger Co., Ltd.
Type: B3-52A-42-4.5
Heat exchanger: Plate heat exchanger
Dimension (mm): 523(L)mmX107(H)mmX115,8(D)mm
3. Evaporator
Manufacture: CHINA SHINING GROUP CO.,LTD.
Type: ASH-65CHW/F1
Heat exchanger: Compact Brazed Heat Exchanger
Dimension (mm): 680(L)mmX1243(H)mmX285(D)mm
4. Fan motor
Manufacture: ChangeZhou Yonghan Motor Co., Ltd.
Type: YDK90-6P
Fan type: 3 blade
5. Main control board
Manufacture: HangZhou Zhouju Electronic Technology Co., Ltd.
Type: HZP-BPDWRB-AKL SSPM35A-380A HZP-DWRB-
SNMAIN-AKL
Specification: 380-440V; 50Hz
Doc No: ITC-TTW0902.02E – Rev.4
Project No: 64.181.20.00804.01
Rev.: 00
Date: 2020-03-10
Page: 12 of 13
Appendix V Equipment List
Calibration Due
No. Type Manufacture Model Equipment ID
Date
R&A performance GEI 20kW - 2020-08-03
1 measuring system
Temperature and VAISALA HMD42 H5110021 2020-08-03
2 humidity meter
Platinum resistance YINUO Pt100 7430F 2020-05-22
3
4 Platinum resistance YINUO Pt100 7434F 2020-05-22
5 Flowmeter YOKOGAWA AXF015G S5M201965 2020-05-22
6 Flowmeter YOKOGAWA AXF040G S5M805005 2020-05-22
Pressure transmitter MICRO MPM489 240502 2020-08-04
7
Pressure transmitter MICRO MPM489 240503 2020-08-04
8
Water pressure MICRO MDM3051 291459 2020-08-04
9 difference transmitter
AC source Supply YANGHONG YF-3600 - 2021-01-02
10
Water pressure MICRO MDM3051 291459 2020-08-04
11 difference transmitter
AC source Supply YANGHONG YF-3600 - 2021-01-02
12
13 Temperature and H5110021 HMD42 VAISALA 2020-08-04
humidity meter
-- End of Report --
Doc No: ITC-TTW0902.02E – Rev.4
Project No: 64.181.20.00804.01
Rev.: 00
Date: 2020-03-10
Page: 13 of 13