BS EN 62305-2:2012
Part 2: Risk Management
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 1
Lightning protection standardisation
BS EN 62305-2
62305-1
General Principles
62305-2
Risk Management
62305-3 62305-4
Physical damage Electrical- and
and life hazard electronic systems
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 2
BS EN 62305 – 2 Insurance Claims
• According to the ABI figures the UK Insurance Industry pays out on average
£8.65 Billion a year in Commercial & Domestic claims (2007-2015)
• Of those claims electrical and electronic damage makes up nearly 11%
equivalent to £946M
• There is no reason to assume the UK differs that greatly from the EU figures
so 31% of this can be ‘assumed’ to lightning & surge related
• Approximately £295M in paid claims every year
• The UK lightning protection & surge protection industry generates
approximately £65m per year in turnover
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 3
Risk composition
Risk
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 4
Handling risks
Risk means suffering damage and loss
Analyse risks
Quantify risks
Total risks
Control risk Accept
risk
Prevent Reduce Insure
(take protection
measures)
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 5
Determination of the risk for a structure
Source of
damage
Type of Type of
loss damage
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 6
Sources of damage
BS EN 62305-2
Source of
Lightning current is the primary source of damage. damage
The following sources are distinguished by the strike attachment point:
S1: Flashes to a structure
S2: Flashes near a structure
S3: Flashes to a line
S4: Flashes near a line
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 7
Types of damage
BS EN 62305-2
Types of damage which may occur as a result of lightning strikes: Source of
damage
Type of
D1: Injury to living beings damage
due to touch and step voltage – electric shock
D2: Physical damage
(fire, explosion, mechanical destruction, release of
chemicals) due to lightning effects including sparking
LEMP
D3: Failure of electrical and electronic systems due to LEMP
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 8
Types of loss
BS EN 62305-2
“Each type of damage, alone or in combination with others, Source of
may produce a different consequential loss in the object to damage
be protected. The type of loss that may appear depends on the
characteristics of the object itself and its content. Type of
loss
Type of
damage
The following types of loss shall be taken into account:
L1: loss of human life;
Types of loss L1, L2
and L3 can be
L2: loss of service to the public;
Current
regarded as loss of
Water
Gas
social values, type
L3: loss of cultural heritage; of loss L4 can be
regarded as
economic loss.
L4: loss of economic value
(structure and its content, service
and loss of activity).
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 9
Risk composition
Risk
Risk Types
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 10
Risks
BS EN 62305-2
The interaction of the factors previously discussed result in the following
risk of damage. These have to be evaluated for a structure
R1: risk of loss of human life; 10-5
current
water
10-4
gas
R2: risk of loss of service to the public;
R3: risk of loss of cultural heritage; 10-4
R4: risk of loss of economic value.
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 11
Risk components
Risk
Risk Types
Risk components
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 12
Risk components
Risk
Current
Water
Gas
Human life Service to the public Cultural heritage Economic loss
R1 R2 R3 R4
Each risk consists of several risk components
= = = =
R1 = RA+ RB+ RC R2 = RB+ RC+ R3 = RB+ RV R4 = RA+ RB+ RC
+ RM+ RU+ RM+ RV + + RM+ RU+
RV+ RW+ RZ RW+RZ RV+ RW+ RZ
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 13
Overview of risk component RX
LEMP
RA RB RC
S1
RZ S4 RM
Rx S2
LEMP
S3
RW RV RU
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 14
Risk component RB - Fire
Source of damage S1
S1
RB =fire
Physical damage due to
dangerous sparking inside
the structure causing fire
and explosion.
Possible types of loss:
L1: Loss of human
life
L2: Service to the
public
L3: Cultural
heritage
L4: Economic loss
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 15
Risk component RM - Overvoltage (LEMP)
Source of damage S2
RM=overvoltage
(LEMP)
Failure of internal systems
caused by LEMP.
Electromagnetic effects of
the lightning current.
LEMP Possible types of loss:
S2 L1: Loss of human life
(structures with risk of
explosion, hospitals)
L2: Service to the
public
L4: Economic loss
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 16 30.09.08 / S6215e
Risk component RV - Fire
Source of damage S3
RV = fire
Physical damage due to
lightning current injected
in supply lines entering
the structure.
S3
Possible types of loss:
L1: Loss of human life
L2: Service to the
public
L3: Cultural heritage
L4: Economic loss
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 17
Risk component RZ - Overvoltage
Source of damage S4
RZ = overvoltage
Failure of internal systems
caused by overvoltages
induced on incoming lines
and transmitted to the
structure.
S4
Possible types of loss:
L1: Loss of human life
(structures with
risk of explosion,
hospitals)
L2: Service to the
public
L4: Economic loss
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 18 30.09.08 / S6219e
Risk composition
Risk
Risk types
Risk components
Number of dangerous events Nx
Probability of damage Px
Consequent loss Lx
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 19
Parameters affecting risk components
Risk of damage
RX = NX • PX • LX
NX PX LX
Number of dangerous Probability of Consequent loss
events damage
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 20 30.09.08 / S6220e
Lightning Ground Flash Density (NG)
per square kilometre per year
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 21
Selection of protection measures for buildings
Identify the structure to be protected
Identify the types of loss relevant for the structure
Define and calculate the risk components for
each type of loss RA, RB, RC, RM, RU, RV, RW, RZ
No
R > RT Structure protected
Yes
Yes Yes
LPS installed? SPM installed?
Calculate new values
of risk components No
No No
RA+B+U+V > RT
Yes
Install relevant Install relevant Install other
type of LPS SPM protection
measures
© 2013 DEHN + SÖHNE / protected by ISO 16016 2 - BS EN 62305 Risk Management 22
DEHNsupport
Demonstration
Risk assessment calculation using DEHNsupport Toolbox