Pdvsa: Engineering Design Manual
Pdvsa: Engineering Design Manual
ENGINEERING SPECIFICATION
PDVSA N° TITLE
APPD.BY Youhad Kerbaje DATE JUN.02 APPD.BY Raúl Rivero DATE JUN.02
Index
1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.1 Purpose (Modify) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 REFERENCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.0 Petróleos de Venezuela PDVSA (Addition) . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2 Industries Codes and Standards (Modify) . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.3 Government Regulation (Modify) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 DEFINITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5 ENVIRONMENTAL CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . 7
6 INSTRUMENT SIGNAL COMPATIBILITY . . . . . . . . . . . . . . . . . . . . . . 7
7 WIRE AND CABLE SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7.2 Instrument Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7.3 Segregation / Separation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7.4 Cable Tray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7.5 Conduit Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8 TERMINATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8.2 Milliamp Signals -- Typically 4 -- 20 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
9 INSTRUMENT POWER SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
9.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
9.2 Branch Circuits Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
10 GROUNDING AND SURGE PROTECTION (MODIFY) . . . . . . . . . . . 14
11 INTRINSICALLY SAFE INSTRUMENT SYSTEMS . . . . . . . . . . . . . . 14
12 NON--INCENDIVE SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
13 CONTROL PANEL AND CABINET WIRING . . . . . . . . . . . . . . . . . . . . 16
14 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
15 DATA LINKS AND FIELDBUSES (MODIFY) . . . . . . . . . . . . . . . . . . . . 16
16 QUALITY ASSURANCE / QUALITY CONTROL (ADDITION) . . . . . 16
ENGINEERING SPECIFICATION PDVSA K–334
REVISION DATE
INSTRUMENTATION ELECTRICAL
PDVSA REQUIREMENTS 1 JUN.02
Page 2
1 INTRODUCTION
1.1 Purpose (Modify)
The purpose of this document is to provide criteria for the design, specification,
installation and commissioning of electrical systems for instrumentation.
Guidelines of PDVSA K–300, Instrumentation Introduction shall also be explicitly
followed.
Since PDVSA has decided to adopt the Process Industries Practices (PIP)
document PCCEL001 “Instrumentation Electrical Requirements” as an integral
part of the Engineering Design Manual (MID), the requirements in this document
are additions or modifications to PCCEL001. The section/paragraph numbers and
the associated headings used in this document correspond to the ones used in
PCCEL001.
The previous version of this document was titled “Instrumentation and
Thermocouple Extension Cables” The present version includes and extends the
scope of the previous version.
1.2 Scope
(Modify) This Document provides criteria for equipment and accessory selection,
design, and installation of electrical supply, grounding and wiring to support
process measurement and control systems.
Electrical requirements for telecommunication systems are not within the scope
of this Practice.
2 REFERENCES
(Modify) Applicable requirements in the latest editions of the PDVSA documents
listed below shall be considered as an integral part of this Practice. Other industry
codes and standards listed below shall be used as reference unless otherwise
indicated within this document.
3 DEFINITIONS
(Modify) AC Safety Ground: The grounding system required by NEC Article 250
to provide protection for personnel and electrical equipment. The Signal
Reference System is connected to the Safety Ground per the NEC requirements
and IEEE 1100, 1999 recommendations. See also Equipment Grounding
Conductor.
(Add) Electrical/Instrumentation Interface Box or Panel: An interface box or
cabinet (see Junction Box), which houses the equipment and accessories
necessary to physically separate the instrumentation system signal wiring from the
electrical control system signal wiring corresponding to signals for monitoring and
control of electrical equipment.
(Add) Equipment Grounding Conductor (EGC): The conductor(s) used to connect
the non–current–carrying parts of conduits, raceways and equipment enclosures
to the AC Safety Ground. The EGC insulation cover is green colored.
(Add) Fieldbus: A digital, two–way, multi–drop communication link among
intelligent measurement and control devices. It serves as a Local Area Network
(LAN) for advanced process control, remote input/output and high speed factory
automation applications.
(Add) Ground Grid: A system of interconnected bare conductors arranged in a
pattern over a specified area on, or buried below, the surface of the earth.
Normally, it is bonded to ground rods driven around and within the perimeter to
increase its grounding capabilities and provide convenient connection points for
grounding devices. The primary purpose of the ground grid is to provide safety for
workmen by limiting potential differences within its perimeter to safe levels in case
of high currents that could flow if the circuit being worked on became energized
for any reason, or if an adjacent energized circuit faulted. Metallic surface mats
and gratings are sometimes utilized for this same purpose. It is sometimes also
referred to as the Plant Grid. Note: This term should not be used when referring
to a signal reference structure, which is defined below.
ENGINEERING SPECIFICATION PDVSA K–334
REVISION DATE
INSTRUMENTATION ELECTRICAL
PDVSA REQUIREMENTS 1 JUN.02
Page 5
4 GENERAL
4.1 (Add) The method of protection to be used, i.e., intrinsic safety, explosion–proof,
non–incendive, etc., shall be defined in specific project design guidelines.
4.2 (Modify): All techniques used to comply with electrical area classification
requirements shall comply with PDVSA 90619.1.101.
ENGINEERING SPECIFICATION PDVSA K–334
REVISION DATE
INSTRUMENTATION ELECTRICAL
PDVSA REQUIREMENTS 1 JUN.02
Page 6
4.4 (Modify) Instruments shall not be installed in Zone 0, Zone 1, or Division 1 areas
unless approved by PDVSA. See PDVSA 90619.1.101 for area classification and
equipment selection guidelines.
4.10 (Modify) All electrical equipment including instrumentation shall be designed and
installed in accordance with NEC, OSHA 1910 Subpart S and IEEE 1100, 1999
4.14.2 (Modify) Control building cabinets and consoles shall be designed so that at
design completion there are a minimum of 20% installed and connected spare
I/O’s as well as space to accommodate a minimum of 20% additional equipment.
This installed spare capacity and additional space shall be proportionately
distributed among the different types of I/O and processor modules. For control
building cabinet and console fabrication requirements, refer to PDVSA K–330.
4.14.5 (Modify).Cable tray from the process area into the control room and instrument
buildings shall be sized as per NEC 318 including a minimum of 20% future
additions.
4.14.7 (Add) Percent occupancy for conduits shall be as per NEC Chapter 9, Table 1.
4.15 (Modify) Individual signal input/output circuits that are not current limited shall be
protected by fuses.
4.17 (Add) Control room cabinets, consoles and field junction boxes of Safety
Instrumented Systems shall be dedicated to SIS circuits. For additional
requirements, refer to PDVSA K–336 and PDVSA 90620.1.118.
4.18 (Add) Signal input/output circuits shall be segregated by signal type: Discrete,
analog, pulse, etc. and by energy level: mV, 24 VDC, 125 VAC, 125 VDC, etc.
Inside control or equipment rooms, either dedicated cabinets or clearly marked
and separated terminal boards within cabinets shall be used. Field junction boxes
shall be dedicated to only one type of signal. Exceptions require PDVSA approval.
4.19 (Add) Instrumentation signals dedicated to the remote control and monitoring of
electrical equipment shall not be directly connected to the motor control cells.
They will be routed to an interface box or panel located in the motor control center.
The function of this panel is to convert the low power level (24 VDC or logic) of
instrumentation signals to the required power levels of electrical control (either 125
VDC or 120 VAC). This will be effected either through the use of interposing relays
or electro–optic isolators for individually wired signals, or through the use of
remote I/O modules dedicated to the control of electrical equipment. The interface
equipment between electrical system SCADA and instrumentation system shall
also be installed inside the electrical/instrumentation interface panel. See
appendix “A” for a more detailed specification of the E/I interface panel.
5 ENVIRONMENTAL CONSIDERATIONS
5.3 (Add) Specific corrosive agents shall be specified.
5.4 (Add) Purging for environmental purposes shall be effected through a standard
instrument air supply set–up: root valve, filter regulator (set at 0.2 to 0.4 bar – 2.5
to 5 psi), and needle valve.
6.4 (Add) pulse train signals for specialty flow meters shall be applied in cases where
uncertainty of measurement is an important issue.
6.5 (Add) ON–OFF signals from field sensors and actuators shall be 24 VDC. 120
VAC or 120 VDC for solenoid valves, relays and other electro–mechanical devices
may be used only after PDVSA approval.
ENGINEERING SPECIFICATION PDVSA K–334
REVISION DATE
INSTRUMENTATION ELECTRICAL
PDVSA REQUIREMENTS 1 JUN.02
Page 8
7.1.2 (Modify) For fire protection of instrument cable, refer to PDVSA IR–C–03, Section
7.8, or to PDVSA supplied procedure.
7.1.3 (Add) Intrinsic safety wiring routed inside control rooms shall utilize dedicated
conduits or enclosed metallic cable trays in order to guarantee segregation with
other electrical circuits.
7.1.5 (Modify) For Safety Instrumented Systems refer to PDVSA K–336 and the design
guidelines in PDVSA 90620.1.118.
7.1.7 (Add) Entrance of cables to control room or field instrument rooms may be either
through underground trenches or specially designed wall penetration cable or
conduit frames. Design shall comply with water–tightness, gas tightness, fire
resistance, blast resistance, area classification and EMC requirements
established in PDVSA IR–C–02 and specific project requirements.
7.2.1.6 In general, cables shall meet the design criteria listed below and shall be selected
in accordance with Table 1.
a. Single Pair Instrument Signal Cable with an Overall Shield (SPISCO)
(Add) May also be used on some process fieldbus network wiring.
c. Single Triad Instrument Signal Cable with an Overall Shield (STISCO)
ENGINEERING SPECIFICATION PDVSA K–334
REVISION DATE
INSTRUMENTATION ELECTRICAL
PDVSA REQUIREMENTS 1 JUN.02
Page 9
Type: (modify) The cable shall be individually twisted triads with an overall
shield. Each triad shall be 3 copper conductors with an individual shield
insulated from other triads’ shields. Conductor wire gauge shall be selected
based on voltage drop vs. distance calculations, with a minimum of 20 AWG
(note 3 of Table 1).
7.2.1.7 (Add) All of the above cables described in 7.2.1.6 may be specified with metallic
armour, for direct burial and/or installation in open (ladder type) cable trays in lieu
of conduits or enclosed cable trays. For direct burial armor shall be continuous
welded impervious corrugated aluminum. See PDVSA N–261 and PDVSA N–262.
7.2.1.8 (Add) For intrinsic safety wiring, outer protective jacket shall be light blue in color.
7.2.1.9 (Add) For intrinsic safety and nonincendive wiring, vendor shall certify the
following electrical parameters: resistance, capacitance and inductance per unit
length, and L/R ratio.
7.2.1.10 (Add) For critical applications where fire resistant cables are specified, certification
in compliance with IEC 60331 circuit integrity tests and IEEE 383 flame tests is
required.
7.2.1.11 (Add) For downhole applications, specially designed cables with longitudinal
traction force protection shall be used.
7.2.1.12 (Add) For burner or pilot igniter, flame rod detector wiring and other applications
exposed to high temperature, specially designed cable with fire–proof outer
protective jacket shall be used.
7.2.2 Circuit Impedance
7.2.2.1 (Modify second paragraph) Where multiple devices are wired in series in a 4 – 20
mA loop, total circuit impedance shall be evaluated for proper operation.
(Add) For process fieldbus networks, appropriate circuit impedance and voltage
drop calculation shall be done for each particular fieldbus network requirement.
7.2.2.4 (Add) Comment: special applications may require more stringent voltage drop
allowances, i.e., loading arm electrohydraulic systems.
7.2.2.6 (Add) For intrinsically safe and nonincendive circuits, distributed parameters
capacitance per unit length, inductance per unit length and L/R ratio are required
for the calculations to ensure safety of the installation, as indicated in Chapters
11 and 12.
(Add) Comment: Intrinsically safe circuits located inside non intrinsically safe
cabinets must be clearly segregated and isolated by physical means such as
grounded metal barriers. PDVSA approval is required.
7.3.5 (Add new paragraph) For Protective Systems (SIS, Fire and Gas), additional
requirements are:
a. All wiring between initiating contacts and individual protective systems shall
be isolated from ground.
b. Protective systems shall use dedicated junction boxes or barriers within
junction boxes of the BPCS to clearly segregate wiring of the protective
system.
c. All wiring shall be clearly separated on a system by system basis. Where
multiple sensors (voting) are used, sensor signals may be segregated to
isolate failures.
d. A ground fault detector system shall be provided for each protective system
that will identify a faulted circuit while the system is in the normal operation.
The detector shall identify the specific protection system or circuit causing a
faulted condition. Electronic fault finding devices or power transfer switching
to an additional isolated power supply are acceptable methods to satisfy this
requirement.
7.4.2 (Add) Cable tray systems shall be grounded in accordance with NEC Table
318–7(b) (2) and following requirements of Chapter 10, Grounding.
7.4.4 (Add) Cable rails may be utilized to route individual signals to field instruments.
7.4.5 (Add) Cable tray systems may be utilized to route instrument power supply cables
powering instruments or equipment.
7.4.6 (Add) Cable trays shall be either hot dip galvanized steel or aluminum, solid or
perforated bottom. Where corrosive atmospheres are present, hot dip galvanized
steel with baked epoxy coating may be considered.
7.4.7 (Add) Cable trays carrying multicables shall be covered throughout their entire
outdoor routes in cases where mechanical or environmental protection are
required (corrosion, sunlight, lightning, etc).
ENGINEERING SPECIFICATION PDVSA K-- 334
REVISION DATE
INSTRUMENTATION ELECTRICAL
PDVSA REQUIREMENTS 1 JUN.02
Page 12
7.4.8 (Add) Open (ladder type) cable trays shall be used in conjunction with armored
cable.
7.4.9 (Add new paragraph) Cable tray systems carrying instrument power cables shall
be filled as per the requirements of NEC Table 318--9
7.6 (Modify) Field junction boxes shall meet the requirements of PDVSA K--329
8 TERMINATIONS
8.1 General
8.1.7 (Modify) Substitute signal reference grid (SRG) for IGB
ENGINEERING SPECIFICATION PDVSA K-- 334
REVISION DATE
INSTRUMENTATION ELECTRICAL
PDVSA REQUIREMENTS 1 JUN.02
Page 13
12 NON--INCENDIVE SYSTEMS
12.1 (Modify) In general, nonincendive systems shall not be used. They may be used
for special applications after PDVSA approval.
12.3 (Add) Nonincendive systems shall be applied only for Class I and II, Div. 2 and
Class III, Divs. 1 and 2 hazardous (classified) areas.
12.4 (Add) All field Instruments and associated apparatus included in a nonincendive
circuit shall be approved as required for the area classification and surface
temperature limits, according to NFPA 70, Articles 497M and 500 to 504.
Certification shall be either by FM, UL, or equivalent in country of origin.
12.5 (Add) Instrument wire and cable to be used in nonincendive circuits shall be
certified by supplier for its relevant physical and electrical parameters: insulation
material, insulation thickness, resistance, capacitance and inductance per meter,
and L/R ratio.
ENGINEERING SPECIFICATION PDVSA K-- 334
REVISION DATE
INSTRUMENTATION ELECTRICAL
PDVSA REQUIREMENTS 1 JUN.02
Page 16
12.6 (Add) The nonincendive system design shall be guaranteed by EPC contractor.
An engineering document, titled Nonincendive System Document of
Compliance, shall be emitted for review and approval by PDVSA. See Appendix
”C” for a description of the contents of this engineering certificate of compliance.
14 INSTALLATION
(Modify) For instrumentation wiring installations, PIP PCIEL000 may be used as
a referential document. Installation details shall be approved by PDVSA. All type
B circuits shall use Instrument Tray Cable (ITC).
APPENDIX A (ADDITION)
REQUIREMENTS FOR ELECTRICAL/INSTRUMENTATION (E/I) INTERFACE
PANEL
1. Instrumentation signals (24 VDC, wiring level 1) shall be physically separated from
power control signals (120 VAC/125 VDC, wiring level 3) by means of separate
raceways (panduits) and separate termination boards. See table 2, page 18 of PIP
PCCEL001, tray to tray spacing.
2. Cabinet and components shall be clearly identified, as per PDVSA K--330, Control
Panels and Consoles
3. Signals in termination boards, isolating relay boards and PLC I/O cards shall be
grouped as per electrical equipment. In general, each piece of electrical equipment
(e.g. motor) may have some or all of the following monitoring and control signals:
S ON command
S Off command
S ON/OFF status
S LOCAL/REMOTE status
S Electrical failure indication
4. Electrical separation of signals shall be effected by means of interposing relays or
electro--optic isolators, or by the use of dedicated remote I/O modules with high
power level I/O’s (120 VAC, 125 VDC and higher), inside the E/I interface panel.
5. The Instrument/Electrical interface panel may also be used to house the digital
interface between the BPCS and the electrical supervisory system.
6. For a typical equipment distribution of the Electrical/Instrumentation Interface
Panel, see figure A--1.
ENGINEERING SPECIFICATION PDVSA K-- 334
REVISION DATE
INSTRUMENTATION ELECTRICAL
PDVSA REQUIREMENTS 1 JUN.02
Page 18
APPENDIX B (ADDITION)
GUIDELINES FOR GROUNDING OF ELECTRONIC EQUIPMENT
The following guidelines may be applied in the design of instrumentation
grounding systems. The standard of reference is IEEE 1100, 1999,
Recommended Practice for Powering and Grounding Electronic Equipment
1. Grounding system consists of four (4) distinct, solidly (e.g.: galvanically)
interconnected functional subsystems. They are as follows:
a. NEC 250 described fault and personnel protection grounding subsystems,
including the earth--grounding conductors (green wires), earth grounding
electrodes (generally in the form of a plant--wide grounding grid) and related
grounding electrode conductors. This subsystem is also called the power
system ground or the AC safety ground, and is installed following the
guidelines of PDVSA 90619.1.091, Puesta a Tierra yProtección contra
Sobre tensiones. Outside the scope of this specification.
b. Signal reference structure (SRS), consisting either of a signal reference
grounding plane (SRGP) or a signal reference grounding grid (SRGG), and
installed following the original equipment manufacturers instructions and the
recommendations made in chapter 8 of IEEE 1100, 1999. The function of the
SRS is to provide an effective high frequency grounding system for
protection of electronic equipment against damage or interference caused
by power system faults or lighting strikes.
c. Lightning protection subsystem, installed per PDVSA electrical guidelines.
This subsystem is outside the scope of this specification.
d. Telecommunications, data transmission and signaling circuit surge
protection grounding subsystem, as installed per the original equipment
manufacturer’s instructions, the requirements of the NEC and
recommendations made in chapters 8 and 9 of IEEE 1100, 1999. Outside
the scope of this specification.
2. SRS shall be installed as per IEEE, 1100, chapter 8.5.4. See below a summary list
of recommended practices for installing a Signal Reference Ground Grid, extracted
from IEEE 1100, 1999, par. 8.5.4.8
a. Follow the NEC and other related applicable codes and standards for safe
grounding. There is no conflict between personal safety grounding and
effective higher--frequency grounding for electrical systems and their
associated electronic equipment.
b. Select a suitable signal reference grid approach and assure that it is
engineered, installed and maintained properly.
c. Permanently and effectively bond the signal reference grid to all accessible
building steel and to each metallic path (e.g.: conduits, raceways, cable
ENGINEERING SPECIFICATION PDVSA K-- 334
REVISION DATE
INSTRUMENTATION ELECTRICAL
PDVSA REQUIREMENTS 1 JUN.02
Page 20
trays, pipes and ducts) that cross into the SRG in any plane or within 1.8 m
(6 ft) of the SRG.
d. If a single point of entry for power, grounding cables and other metallic items
into the space exists (e.g.: physical ground window or bulkhead), then
single--point grounding of the SRG is acceptable. The electronic load
equipment installed on the SRG may be multipoint grounded or single point
grounded to the SRG, depending on the signal frequency of interest.
e. Bond the signal reference grid to each piece of electronic equipment and to
any other electrical or mechanical equipment located on the SRG.
f. Bonding connections to the SRG should be as short as practical with no
sharp folds or bends. Flexible flat straps are preferred to the use of round
conductors.
g. Where in accordance with manufacturer requirements, more than one
bonding conductor for each piece of equipment should be used. These
conductors should be connected to opposing corners of the equipment and
to the nearest, but separate points on the SRG. These conductors should
be short (less than 0.5 m) and of different lengths (at least 20%).
h. Electronic equipment should not be installed nearest to the outer edges of
the SRG if practicable. Instead, this equipment should be installed one or
more SRG conductor intersections (about 1 m) towards the center of the
SRG . . . HVAC equipment and panelboards should be connected to any SRG
conductor, or to the outermost SRG conductor. Where feasible, critical
equipment should be located and bonded to the SRG greater than 1.8 m (6
ft) away from building steel or other potential lightning current or sideflash
paths.
i. All separatedly derived systems serving equipment located on the SRG
should have their power grounding point (i.e.: neutral--to--ground bond)
connected to the SRG by a suitable bonding strap, This connection is in
addition to the required connection of the grounding electrode conductor to
the grounding electrode (AC safety ground).
j. All HVAC equipment, its associated piping, panelboards, switchboards,
transformers and similar electrical or mechanical equipment within the
protected area should be bonded to the signal reference grid.
k. No special or supplementary grounding connections should be made to
remote or dedicated earth grounding points, nor should there be any similar
attempt to provide any form of separate earth ground paths to or from the
SRG or any equipment installed upon it.
l. All interconnecting communications, data and power cables should lay on or
very close to the SRG.
ENGINEERING SPECIFICATION PDVSA K-- 334
REVISION DATE
INSTRUMENTATION ELECTRICAL
PDVSA REQUIREMENTS 1 JUN.02
Page 21
APPENDIX C (ADDITION)
TABLE OF CONTENTS OF THE INTRINSICALLY SAFE
DOCUMENT OF COMPLIANCE
(Note: For nonincendive installations, the guidelines below apply as noted)
As a minimum, the Intrinsically Safe (or Nonincendive) System Document of
Compliance shall be provided with the following sections:
1. Frontispiece, including a box with the history of revisions/approvals.
2. Scope, indicating the scope of the document which is, basically, the show of proof
of the correct design, installation and verification of the intrinsically safe and/or
nonincendive equipment and circuits designed, procured and installed within the
scope of the specific project under consideration.
3. List of Applicable Standards. Including PDVSA K--334 and those listed in
paragraphs 11.2 and 12.2.
4. General Statement of Compliance. In this section, the EPC contractor shall
declare that the instrumentation electrical installation is effectively designed as
an intrinsically safe and/or nonincendive system, indicating its compliance
with each and all sections of the above mentioned mandatory standards and
PDVSA requirements. Where alternatives are allowed, the document shall
describe the specific way in which compliance was obtained. Also, the intent and
extent of the approved exceptions, if any, shall be described.
5. Calculations: This section shall include the Control Drawing for each distinctive
type of intrinsically safe or nonincendive circuit, as defined in Section 504--10 of
the NEC. The Control Drawing for each type of circuit shall use the greater length
(worst case), of interconnecting wire for the calculations proving that the safety
parameters are within acceptable range. A list of all instrument loops for which
each Control Drawing applies shall be included. For nonincendive circuits, control
drawings shall be similar in form to those for intrinsic safety circuits, but calculations
shall follow general guidelines as stated in ISA S12.12.
6. Certificates of Approval for Intrinsically Safe and Associated Apparatus:
This section shall present the official certificates of approval for each and every
intrinsically safe apparatus and associated apparatus installed in the plant,
issued by an internationally recognized certifying authority: FM, UL, CSA,
BASEEFA, PTB, CESI, etc. The apparatus shall be approved for the specific
hazardous area classification where they are to be installed, according to the NFPA
70 Articles 500 to 503 hazardous location classification scheme and the NFPA
497M group and auto--ignition temperature (AIT) classification. Each certificate
shall be accompanied with the corresponding list of instrument tags covered by the
certificate.
ENGINEERING SPECIFICATION PDVSA K-- 334
REVISION DATE
INSTRUMENTATION ELECTRICAL
PDVSA REQUIREMENTS 1 JUN.02
Page 23