Portland Cement I-II Mill Cert

This cement mill test report summarizes the chemical and physical analysis of a Type IIII(MH) Portland cement produced in July 2010 at Lafarge's Ravena, New York plant. The cement met all ASTM C150-09 and AASHTO M85-09 specifications for composition and properties, including limits for silica, alumina, iron oxide, lime, magnesia, and loss on ignition. Test results are provided for air content of mortar, fineness, strength, setting time, and expansion. The cement is certified to meet requirements for Type IIII(MH) portland cement.

Uploaded by

Firas Ashraf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
1K views1 page

Portland Cement I-II Mill Cert

This cement mill test report summarizes the chemical and physical analysis of a Type IIII(MH) Portland cement produced in July 2010 at Lafarge's Ravena, New York plant. The cement met all ASTM C150-09 and AASHTO M85-09 specifications for composition and properties, including limits for silica, alumina, iron oxide, lime, magnesia, and loss on ignition. Test results are provided for air content of mortar, fineness, strength, setting time, and expansion. The cement is certified to meet requirements for Type IIII(MH) portland cement.

Uploaded by

Firas Ashraf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

L,LAFARGE

~ NSF-51
CEMENT

Cement Mill Test Report


Month of Issue: August-10
Plant: Ravena, New York
Product: Portland Cement Type IIII(MH)
Manufactured: JUly-10

ASTM C 150-09 and AASHTO M 85-09 Standard Requirements

CHEMICAL ANALYSIS PHYSICAL ANALYSIS

Item Spec limit Test Result tlem Seec limit Test Result
Rapid Method. X-Ray (C 114)
SI02(%) - 19.7 Air content of mortar (%) (C 185) 12 max 8.0
Al203 (%) 6.0 max 4.7
Fe203 (%) 6.0 max 3.0 Blaine Fineness (m2lkg) (C 204) 28o-420~· 38.
caO(%) - 62.1
MgO(%) 6.0 max 3.7 -328 (%) (e 430) - 92.9
803(%) 3.0 max· 2.•
NaEq (%) - 0.89 Autoclave expansion (%) (C 151) 0.80 max 0.04
Loss on ignition (%) 3.0 max 2.29
Insoluble residue (%) 0.75 max 0.57 Compressive strength Mpa (PSI) (C 109)
cement C02 (%) - 1.05
Limestone (%) 5.0 max 2.68 3 days 12.0 (1740) min 24.5 ( 3550)
caC03 in limestone (%) 70 min 89.1 7 days 19.0 (2760) min 31.0 (4500)
28 days (Previous Month) 42.0 (6090)
Adjusted Potential Phase Composition (C 150)
C3S (%)
C3A (%) 8max
- 54.1
7.4
Time of setting (minutes)
Vicat Initial (C 191) 45- 375 130
C3S+4.75-C3A (%) 100 max 89.1
Heat of Hydration (calfg) (C 186yH
Optimum 803 (%) (C 563) 2.90 7 days (for information only) - 82.0
Expansion in Water (%) (C 1038) 0.020 max 0.010

• May exceed 3.1)%503 maltimum based on our C1038 results of <OJI2%expanslon at 14 days. Data avallabk! upon request.
·"'he max Blaine does not apply if the Sum of C3S ... 4.7S·C3A Is Jess than or equal 10 90
••• Current Production run not available· most recenl provided

We certify that the above described cement, atlhe time of shipment, meets the chemical and physical reqUirements
for Type I-II(MH) portland cement as specified in the American Society of Testing and Materials (ASTM) Specification C 150-09
and the American Association of State Highway and Transportation Officials (AASHTO) Specificalion M 85-09.

US East au ~ Ravena Plant


P.O. Box3· Ravena, NY 12143
ftltZ
Phone: HIOO-631~2777 Jason Shoemaker
Quality Manager
Dale Repon CJl!8te<!: 81912010