Principles of Illumination
Principles of Illumination
Objective:
1. Selection of the most efficient light source possible to minimize power costs and energy
consumption.
2. Matching the proper lamp type, to the intended work task or aesthetic application, consistent
with color, brightness control and other requirements.
3. Establishing adequate light levels to maintain productivity improve security and increase
safety.
Definition of Terms
Estimating Illumination and Brightness
Coefficient of Utilization Factor
Measuring Foot-candle
Uniformity of Light
Lighting Control
Definition of Terms
Foot-candle (fc) is the amount of light flux density. It is the unit of measure used when describing the
amount of light in a room and is expressed in lumens per square foot.
Footlambert (fl) is defined as “the luminance of a surface reflecting. Transmitting or emitting one lumen
(lm) of illumination per square foot of area in the direction being viewed or the conventional unit of
brightness or luminance. In the same manner, the lumens (lm) is the light output generated
continuously by a standard wax candle
In our study of light, we are interested in the amount of light that fall on the areas that we want to
illuminate. We also want to know the lumens per square foot or square meter in a space.
This quantity called Light Flux Density is the common term Foot-candle (fc) represented by the formula:
Foot-candle = Lumens
Area
Example 1
A 40 – watt fluorescent lamp 120 centimeters long produces 3,200 lumens of light in a room having a
general dimension of 10 x 20ft. Find the illumination on the floor.
SOLUTION
Foot-candle = Lumens
Area
fc = 3,200 lm. = 16 footcandle
10 x 20 ft.
The foot-candle is an important unit of measure in calculating the desired illumination and layout of
fixtures. In the absence of Tables of equivalent foot-candles for a fixture, a rule of thumb of 10-30-50
illumination level is here presented.
However, providing an adequate quantity of light alone is not a guarantee for an efficient and
comfortable vision. In fact, the quality of light is very important especially where difficult visual needs
are required. The luminance or brightness of a diffusely reflecting surface is equal to the product of the
illumination and the reflectance. Thus;
Example 2
From example 1, find the luminance if the reflectance factor of the wall is 40%.
SOLUTION
1. Footlambert = foot-candle x Reflectance factor
= 16 x 40% = 6.4
Meanwhile, Lumens flux remains in Lumens, but illumination or light flux is expressed in Lux. Thus:
Lux = Lumens
Area (sq. m.)
In the metric system, Luminance or Brightness is expressed in Lambert which is defined as “the
luminance or brightness of a surface reflecting, transmitting or emitting one lumen per square
centimeter. Millilambert is more conveniently used than the lambert because the value of lambert is
greater than what is usually encountered.
SOLUTION
1. Luminance = Total lumens x transmission factor
Area of diffuser
= 2pcs. x 3,200 x .6
1’ x 4’
= 960 footlambert
1. To obtain the metric equivalent, multiply:
Millilambert = Footlambert x 1.076
= 960 x 1.076
= 1032.96 millilambert
Depending upon the size of the room, color of wall and ceiling, types of lighting units and methods of
lighting used, the watts per square meter method is may produce 50 to 100 lux which is approximately
5 to 10 foot-candles.
1. Twenty watts (20) per square meter will provide an illumination of 100 to 150 lux which is
approximately 10 to 15 fc in industrial areas.
2. For commercial areas, two (2) watts per square foot or 22 watts per square meter is will
provide from 80 to 120 lux when used with standard quality equipment.
3. Forty (40) watts per square meter will provide about 200 lux which is approximately 20 fc
wherein greater illumination is required
4. Sixty (60) watts per square meter will provide about 300 lux or approximately 30 fc which is
recommended for many conventional, industrial, and commercial requirements.
5. Eighty (80) watts per square meter will provide from 300 to 350 lux and more than
supplementary lighting is necessary.
The usable Initial foot-candle or lux is equal to the foot-candle produced by the coefficient of utilization
(cu).
Initial was emphasized because the output is of a light fixture is reduced with time as the lamp fixture
is becomes old and dirty. Lamp output normally drops and is termed as Maintenance factor (mf). And
to find the average-maintained illumination, we reduce the initial illumination by the maintenance
factor.
The usable initial foot-candle is equal to the foot-candle produced by the coefficient of utilization (cu).
EXAMPLE 5
A school classroom with a general dimension of 24 x 30 ft. is lighted with 10 fluorescents of 4F 40 T12
WW rapid start lamp. Calculate the initial and maintained illumination in foot-candles (English) and Lux
(Metric) assuming that (cu) is 0.35 and (mf) is 0.70.
EXAMPLE 6
An office room having a general dimension of 8 x 20 meters is to be lighted at an averaged
maintained foot-candle of 50 fc, How many 3-lamp fixtures of 120 centimeters long F40 T12 WW rapid
start fluorescent lamps are required assuming the cu is 0.38 and the mf is 0.75?
SOLUTION
1. Lamp lumens = maintained foot-candle x area
cu x mf
= 50 fc x (8m. x 20 m.)
0.38 x 0.75
= 28,070 lumens
2. Each 40-watt fluorescent lamp has an output of 3,200 lumens, the number of lamps will be:
Number of lamps = 28,070
3,200
= 8.77 lamps
3. Since there are 3 lamps for each fixture, divide:
8.77 = 2.93 say 3 lamps in ach fixture
3
Calculation involving a wide area is more confusing than by computing the number of lamp
fixtures per bay or per row which is more meaningful and interesting.
This could be done easily by using the following formula:
Number of Fixtures = Illumination x area _
Lamp per fixture x lumens x cu x mf
MEASURING FOOT-CANDLE
The unit measure of illumination is the foot-candle or lux in the Metric System which is
frequently used when describing the amount of light in a room. It is not enough to know how to
calculate the illumination level, but it is also equally important to know how to measure them in
enclosed space. In measuring illumination level, the foot-candle meter is held horizontally with its
sensitive surface at least 30 centimeters from the body of the person holding the meter, The meter
could be placed on a table and read from a distance to avoid obstruction of the light.
In conducting a general illumination check inside a room, the meter is held at least 80 centimeters
above the floor. Reading is undertaken throughout the room and the results are recorded on the
plan of the room.
Uniformity of Light
The purpose of lighting calculations, by the foot-candle or lux, is to determine the average
illumination in a room or lux, is to determine the average illumination in a room to a working level
condition. This working level condition refers to the height of 75 centimeters above the floor being the
approximate height of the table. The average illumination at the working level is directly related to the
maximum spacing of the light to the mounting height ratio represented by the formula.
EXAMPLE 8
A room with a ceiling height of 3 meters is to be lighted with direct concentrating fluorescent light.
What are the maximum fixtures spacing?
SOLUTION:
1. For spacing and mounting ratio, refer to table 8. The mounting height ratio of direct
concentrating light is 0.40.
Therefore:
2. Substituting the given values, wherein mh is the ceiling height,
S = 0.40 x 3.00
Spacing: S = 1.20 meters maximum side to side of the fixtures.
EXAMPLE 9
A warehouse will install pendant dome incandescent lamps at a mounting ratio of 1.50 meters. The
lamp will be mounted on a grid measuring 5.00 x 5.00 meters. What is the minimum mounting height
of the lamps?
Solution:
Mounting height is; mh = Spacing
Ratio
mh = 5.00 m. = 3.30 meters
1.50
Semi-Direct Lighting. When the predominant light on the illuminated area is fed directly from the
lighting units wherein the greater amount of light is obtained from the ceiling through the reflection.
Semi-Indirect Lighting. A lighting arrangement wherein 5% to 25% of the light is directed downward
with more than half of the light focused upward and reflected from the ceiling.
Indirect Lighting. When the light is diffused and reflected from a wide ceiling area. This kind of lighting
produces a soft and subdued effect due to low brightness and absence of sharp shadows.
Maximum Light Utilization – In order to attain the maximum utilization of light from the fixtures, the
luminaires should be mounted under the following specifications.
Where:
E=The illumination in lux
Al=Average lumens with a typical value of:
20 500 lumens for 40 watts
11 500 lumens for 250 watts
5 400 lumens for 125 watts
The value of Al varies depending upon the type of lamp specified.
mf- is the maintenance factor which depends on the following:
a). Maintenance practice of the company
b). Operation of light sources at rate current and voltage
c). Regular replacement of depreciated lamp
d). Periodic cleaning of the luminaires either 0.8-0.9
w = Width of the roadway
d = Distance between luminaires
cu = Coefficient of utilization, which is dependent on the type of fixture, mounting height, width of
roadway and the length of mast arm or outreach.
EXAMPLE 10
Considering the data as presented on Figure 6-7 when the night pedestrian traffic is estimated
to be light and the night vehicular traffic is to be medium, determine the required lumens if theroad
concrete is a pavement.
SOLUTION
1. Referring to Table 9, E= 6.46 for light pedestrian medium traffic classifications. For concrete
road, the reflectance will be higher but let us accept the value of 6.46 lumens.
2. Determine the average pole distance.
E= 6.46 lumens per sq.m.
w= 7.00 meters
d= 50 meters
mf= 0.9
cu= 0.29 (type A fixture)
Under the Working Voltage, the mean lamp lumens of a 250 watts lamp is 11, 500 lumens, this is the
nearest value to 8,662.83 average lumens. Therefore, a 250 watts lamp is acceptable.
Computing for the new actual illumination E