Bulletin 40
Bulletin 40
D. Low Pressure Drop: The heat load or heat exchanged may also be expressed as the
x Bare tube exchangers offer least pressure drop product of mass flowrate, specific heat, and temperature
among most exchangers change in each stream.
Eq. 2 Q = m x Cp x (T₂-T₁)
E. Adopting New Application: Q = Heat exchanged, BTU/hr
x Hairpin for process that might be modified or m = Mass flow rate, lb/hr
completely changed Cp = Specific heat, BTU/lb-°F
x Accommodate these changes simply by T₁ = Inlet temperature, °F
rearranging the sections. T₂ = Outlet temperature, °F
x One or more sections might be added or removed
2. FINNED DOUBLE PIPE & FINNED MULTITUBE *Table 1 shows the approximate U limits that have been
(Table 3 & 5) calculated under different conditions. Please note that
A. High Pressure: these values are based on 4 ft/sec shellside and 6 ft/sec
x Offers same advantages for high pressure as bare tubeside velocity. An overall fouling factor of 0.004 and 5-
tube Hairpin 10 psi pressure drop on each stream has been assumed .
B. High Surface Requirements: A is the effective heat transfer surface; which is found from
x More advantageous when shell side heat transfer Table 2, 3, 4 and 5 for different types of Hairpin
coefficient is low exchangers. To estimate surface for lengths that are not
x Finned Hairpin has two to five times heat transfer listed, simply use the following formula:
surface than bare tube Hairpin ͳͲᇱ ݂ܵ݁ܿܽݎݑ
ܵ ݂݁ܿܽݎݑൌ ݄ݐ݈݃݊݁݀݁ݎ݅ݑݍ݁ݎݔሺ݂ݐሻ
ͳͲ
5
Example: Using Table 3 to find the 10’ surface, an 8” shell with
44 U-tubes, 3/4” OD, 23’ nominal length has a surface of: CHART A
ͳʹǤͻ݂ ݐଶ APPROXIMATE FRICTION FACTOR
ܵ ݂݁ܿܽݎݑൌ ͵ʹݔሺ݂ݐሻ ൌ ͵ͻǤሺ݂ ݐଶ ሻ Reynolds f f
ͳͲ݂ݐ
Number Commercial Commercial
Re pipe tubes
ΔT isbiggest
the log mean temperature difference. One of the
advantages of Hairpin exchangers is the ability
0.2
0.3
0.35
0.23
0.35
0.23
to have a true counter-current flow of streams. This
0.4 0.17 0.17
allows the hottest portion of the hot stream to be in
0.8 0.082 0.082
contact with the hottest portion of the cold stream at
1.0 0.07 0.07
any given time. This eliminates the need for any
2.0 0.04 0.04
temperature correction factor.
3.0 0.029 0.029
6.0 0.011 0.011
Example: Let’s assume that fluid A enters the shellside at 300°F .
10.0 0.0068 0.0068
Fluid B enters the tubeside at 450°F and is to be cooled
20.0 0.0056 0.0053
down to 350°F.
Hot Fluid Cold Fluid Diff.
40.0 0.005 0.0047
B A 100.0 0.0042 0.0038
450 High Temp 310 140 DT₂ 200.0 0.0038 0.0033
350 Low Temp 300 50 DT₁ 400.0 0.0034 0.0029
90 DT₂-DT₁ 1000.0 0.0029 0.0025
2000.0 0.0026 0.0021
ઢࢀ ିઢࢀ 10,000.0 0.002 0.002
Eq. 4 DT = ઢࢀ 100,000.0 0.002 0.002
ࡵ
ઢࢀ
ଽ ଽ ࡸ
Using Eq. (4) ΔT = భరబ = = 87.4 ࢌሺࡳƮሻ ሺ ሻ
ூ
ఱబ
ଵǤଶଽ Eq. 5 DP =
ࡰࢋ࣋ࣘ
Where DP is pressure drop, psi
Now that all the parameters of Eq. (1) have been defined, a ௫ீƮ
concept called UA analysis should also be defined . Let’s refer to Re’ = Reynolds No. =
௩
Eq. (1): f = Friction Factor
(1) Q = U x A x DT G’ = Mass velocity, lb/sec-ft²
ொ Z = viscosity, cP
Solving for UA, UA = L = total travel path, ft
Δ்
De = equivalent diameter, in.
ߩ = density, lb/ft³
Q is easily found by using Eq. (2), DT is calculated using Eq. (4)
௩ Ǥଵସ
Please refer to the guidelines in the selection of bare vs. fin ߶ = viscosity correction factor, ቀ ቁ
௪
tube. For average viscosity less than
1 cP Use a correction of 1.0
IF UA < 10,000
doublepipe or multitube 4” shell or under
Step 1: Check the heat load of heat exchanged In Table 3, a 4” unit with 12 u-tubes, ¾” OD, 0.083” wall and
Eq. (2): Q=m Cp (T₂-T₁) 20’ nominal length has 94.3 sq. ft surface which would be a
suitable section. The model number is 4B12-20-00-SS.
Shellside Q = 9700 lb/hr x 0.579 BTU/lb-°F x (150-105)
= 252733 BTU/hr Step 6: Pressure Drop Calculation
Tubeside Q = 24537 lb/hr x 1 BTU/lb-°F x (97.3-87) Pressure drop usually is one of the most important
= 252731 BTU/hr controlling factors that influence the size and cost of an
The two heat loads are almost identical . exchanger. The higher the allowable pressure drop, the
Therefore Q = 252733 BTU/hr lower the cost. Now let’s check to see if the pressure drop
remains within the specified limits in the selected
Step 2: Calculate the DT exchanger.
Using counter current flow and Eq. (4) Model No. 4B12-20-00-SS
Hot Fluid Cold Fluid Temp Diff. Using mechanical data listed:
150 High Temp 97.3 52.7 DT₂ 25NFA = 185.6
105 Low Temp 87 18 DT₁
Shellside
De = equivalent diameter = 0.725 in.
34.7 DT₂ - DT₁ 25NFA = 80.3
Tubeside ID = 0.584
Δ்మ ିΔ்భ
Using Eq. (4) DT = Δమ
ூ
Δభ
ଷସǤ
DT = ఱమǤళ = 32.3
ூ
భఴ
Step 3: Calculate UA
Eq. (1) Q = UA DT
ொ ଶହଶଷଷ்Ȁ
UA = = = 7824
Δ் ଷଶǤଷǏி
The UA result is less than 10,000 which suggest the
exchanger will be one or more double pipes or a 4” or
smaller multitube hairpin.
U = 81 BTU/hr-ft²-°F