RCS-931 V4.0 Instruction Manual en MY General X R2.01
RCS-931 V4.0 Instruction Manual en MY General X R2.01
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Documentation for equipment ordered from NR is dispatched separately from manufactured goods
and may not be received at the same time. Therefore, this guide is provided to ensure that printed
information normally present on equipment is fully understood by the recipient.
Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason, only qualified personnel may work on or operate the equipment.
z Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
z Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
z Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
DANGER means that death, severe personal injury, or considerable equipment damage will
occur if safety precautions are disregarded.
WARNING means that death, severe personal, or considerable equipment damage could occur
if safety precautions are disregarded.
CAUTION means that light personal injury or equipment damage may occur if safety
precautions are disregarded. This particularly applies to damage to the device and to
resulting damage of the protected equipment.
WARNING!
The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.
WARNING!
During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.
In particular, the general facility and safety regulations for work with high-voltage equipment must
be observed. Noncompliance may result in death, injury, or significant equipment damage.
DANGER!
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING!
z Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous
z Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.
CAUTION!
z Earth
z Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
z Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.
Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.
z External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
z Connection cable
Copyright
Software Version: RCS-931_MY V4.00 NR ELECTRIC CO., LTD.
Release: R2.01 69 Suyuan Avenue. Jiangning, Nanjing 211102,China
Tel: 86-25-87178185, Fax: 86-25-87178208
P/N: EN_XLBH0104.0060.1204
Website: www.nari-relays.com
Copyright © NR 2010. All rights reserved
Email: [email protected]
Table of Contents
Preface ....................................................................................................................................... i
Introduction ............................................................................................................................ i
1.2 Function........................................................................................................................... 2
3.4.2 Deviation of operation voltage fault phase selection element ........................... 52
4.3.1 Voltage and current drift monitoring and auto adjusting .................................... 72
6.2.7 Opto-coupler module (DC 220/110 Option) (#7 BI) .............................................. 92
Chapter 1 Introduction
1.1 Application
The RCS-931 relay is a digital EHV line differential protection with the main and back-up protection
functions, which is mainly designed for transmission line of 132KV and higher voltage class.
The main protection of RCS-931 relay comprises of segregated phase current differential
protection and zero-sequence current differential protection, which can clear the fault without
delay for the whole line. DPFC distance protection can reach to extremely fast speed for the fault
near the busbar.
The back-up protection of RCS-931 relay comprises of three zones phase-to-phase and
phase-to-ground distance protection, four stages directional zero-sequence overcurrent protection
and two stage of non-directional phase overcurrent protection. Specially, one zone reversal
distance protection and inverse-time overload for alarming and tripping are also provided.
RCS-931 relay can implement single-phase or three-phases trip and configure auto-reclosing that
can implement 1-pole reclosing, 3-poles reclosing and 1/3-pole reclosing for single busbar and
double-busbar.
Where:
79: Auto-reclosing
25: Synchrocheck
Note!
1.2 Function
1. Main protection
Note!
in the power system, the fault current consists of three parts: the power frequency
components before the fault, the power frequency variables during the fault and the
transient variables during the fault. DPFC is the power frequency variables during the
fault.
2. Backup protection
3. Additional function
synchro-checking (25)
Fault Recorder including 256 event reports and 6 oscillograms (The format of recorded
oscillogram is compatible with international COMTRADE file.)
Fault locator
GPS clock synchronization - second pulse, minute pulse, RS-485 difference level and IRIG-B
synchronization
High-speed 64 Kbit/s PCM channel or dedicated optical fiber channel for differential protection
data exchanging
CTS
VTS
Line VTS
4. COMMUNICATIONS
1 RS-232 or RS-485 (can be set by jumper) communication rear ports for printer
1.3 Features
Quickly clearing the internal fault for whole line,
Two independent data acquisition paths, one for fault detector element and another for
protections and logic functions, to prevent any undesired trip.
The CT ratio of two terminals could be different. Different ratio of various CT on each terminal
can be regulated by configurable coefficients in software.
The communication channel can be monitored automatically. Bit error rate could be displayed
online. Differential protection will be blocked during channel failure.
The relay can receive tripping command from the opposite terminal protection and transmit
tripping command to the opposite terminal protection via fiber optical channel.
Friendly HMI interface with LCD and 9-button keypad on the front panel.
24 samples per cycle, all task including data measurement, protection calculation, logic
discrimination, event recording and protection logic calculation can be done within one
sampling period.
2. Analog current
2.5 Terminals
AC Current
1.5mm2~2.5mm2 lead
Heavy duty terminal block
Threated M4 terminals, for crimp terminals
CT inputs have integral safety shorting, upon removal of the terminal block
AC Voltage
1.0mm2~2.5mm2 lead
Threated M4 terminals, for crimp terminals
upon removal of the terminal block
General input/output: Power supply, Output contacts, Binary input and RS485
Threated M4 terminals, for jointing terminals
1.5mm2~2.5mm2 lead
Case Protective Earth Connections
Two rear BVR type yellow and
Green stub connections threated M4
Musted be grounded for safety
Wiring size 4.0mm2 lead
Jointing terminal
Spot frequency
Radiated amplitude-modulated
Radiated pulse-modulated
2.7 Certifications
z ISO9001: 2000
z ISO14001:2004
z OHSAS18001: 1999
z CMMI L3
z ISO10012:2003
Voltage : 0.4V~100V
Note!
Operating time of stage 2 of differential protection: <65ms (the fixed 35ms time delay is
included)
0.05Ω~200Ω (In=1 A)
Tolerance will be higher in case of single-phase fault with high ground resistance or extremely
short line.
2.8.15 Auto-reclosing
Phase difference setting range: 0~90
Item Accuracy
Voltage setting Max(0.01Un,5.0%)
Frequency difference 0.01Hz
Phase difference 2.0Deg
Voltage difference Max(0.01Un,5.0%)
Operating time of synchronism check ≤1%Setting+20ms
Operating time of energizing check ≤1%Setting+20ms
t_1P_AR
t_3P _AR
t_PW_AR
t_CBClsd_AR ≤1%Setting+20ms
t_Wait_SynChk_AR
t_Unsuc_AR
t_Reclaim_AR
If any of the above fault detection elements operates, the GFD will operate to provide DC power
supply to the output relays to enable the output circuit.
If operating condition is met, the DPFC overcurrent FD element will operate to provide DC power
supply for output relay, and pickup signal will be kept for 7 seconds after the DPFC overcurrent
element drops out.
where:
3I0: zero-sequence current derived at the neutral current circuit from three-phase currents
3I0Cal: zero-sequence current calculated depending on the summation of IA, IB and IC (i.e.,
3I0Cal=IA+IB+IC)
If operating condition is met, the zero-sequence overcurrent FD element will operate to provide DC
power supply for output relay, and pickup signal will be kept for 7 seconds after the zero-sequence
overcurrent FD element drops out.
When CT circuit failure is detected (i.e. [Alm_CTS] issued), this element will be disabled.
Note!
If operating condition is met, the circuit breaker pole discrepancy FD element will operate to
provide DC power supply for output relay, and pickup signal will be kept for 15 seconds after the
circuit breaker pole discrepancy FD element drops out.
If operating condition is met, the auxiliary voltage FD element will operate to provide DC power
supply for output relay, and pickup signal will be kept for 7 seconds after auxiliary voltage FD
element drops out.
Note!
Here Un is the rated secondary phase voltage of VT. Unn is the rated secondary
Figure 3.3-1 shows the operation characteristic of the DPFC distance relay on R-X plane when a
forward fault occurs, which is the circle with the –Zs as the center and the │Zs+Zzd│ as the radius.
When measured impedance Zk is in the circle, the DPFC distance relay will operate. The DPFC
distance relay has a large ability to endure fault resistance. When there is infeed current from the
power source on the other end in the fault resistance, the phase of ΔIn is the same as ΔI and the
phase of voltage of fault resistance is the same as ΔI, so the fault resistance appears resistive and
is in parallel with R axes. The overreaching problem that results from infeed current can be
prevented.
jX
Z’s
Zzd
-Zk
Figure 3.3-2 shows the operation characteristic of the DPFC distance relay on R-X plane when a
reverse fault occurs, which is the circle with the Z’s as the center and the │Z’s-Zzd│ as the radius.
The region of operation is in the quadrant 1 but the measured impedance –Zk is always in the
quadrant 3, so the DPFC distance relay has the definite directionality to prevent from
mal-operation.
Note!
The DPFC distance protection can be disabled by setting virtual binary input [VEBI_DistP]
as “0” and can be enabled by setting virtual binary input [VEBI_DistP] as “1” and setting
Note!
DPFC current differential relay and steady-state current differential relay can all
Φ: Phase A, B or C
Operation criteria :
Where:
1.5U N
IM : Max([I_L_Diff], 1.5 ICap , )
XC1L
0.6UN
IL : Max([I_ROC_FD], 0.6ICap , )
XC1L
1. Stage 1
Operation criteria :
Where:
4UN
IH : Max([I_H_Diff], 4ICap , )
XC1L
Note!
The real capacitive current is the differential current not compensated under normal
condition.
Note!
Xc1 is the real positive sequence capacitive impedance of line for long transmission line.
4UN
For short transmission line, the real capacitive current and are all small, so the
XC1L
DPFC current differential relay has a high sensitivity. The sensitivity can be decreased by
2. Stage 2
Operation criteria :
Where:
2.25UN
IQ : Max([I_L_Diff], 2.25ICap , )
XC1L
When the above criterion is met, the stage 2 of DPFC current differential element will operate after
35ms.
1. Stage 1
Operation criteria :
Where:
4UN
IH : Max([I_H_Diff], 4ICap , )
XC1L
2. Stage 2
Operation criteria :
Where:
1.5UN
IM : Max([I_L_Diff], 1.5ICap , )
XC1L
When the above criterion is met, the stage 2 of steady-state differential current relay will operate
after 40 ms.
operation criteria :
Where:
0.6UN
IL : Max([I_ROC_FD], 0.6ICap , )
XC1L
If the alarm, [Alm_VTS] or [Alm_Xc], is issued, the capacitive current compensation will be
disabled automatically. The operation criterion is changed to:
1.5UN
IM : max([I_L_Diff], 1.5ICap , )
XC1L
IDiff0 , IBias0 , IDiffΦ and IBiasΦ are the same to those mentioned above
When the above criterion is met, the zero sequence differential current relay will operate after 100
ms.
For the long transmission line, because capacitive current of line is very large, the sensitivity of
zero-sequence current differential element is not enough for the ground fault associated with fault
resistance. In order to increase the sensitivity, the capacitive current compensation is applied in
the zero-sequence current differential element. The compensative capacitive current is
⎡ U − UM0 UM0 ⎤ ⎡ UNΦ − UN0 UN0 ⎤
ICΦ = ⎢ MΦ + ⎥ +⎢ + Equation 3.3-8
⎣ 2XC1L 2XC0L ⎦ ⎣ 2XC1L 2XC0L ⎥⎦
UMΦand UM0 are phase voltage and zero sequence voltage in the M terminal. UNΦand UN0 are
phase voltage and zero sequence voltage in the N terminal. [XC1L] and [XC0L] are positive
sequence capacitive impedance and zero sequence capacitive impedance of the whole line.
The compensative capacitive current calculated based on the equation mentioned above is
suitable to normal condition or external fault.
3.3.2.6 CT supervision
If CT circuit failure occurs, delayed alarm will be issued. When CT circuit failure occurs on an end,
the FD and current differential protection on this end might operate at once. However FD on
another end will not operate and not send any permissive signal of current differential relay. So the
current differential protection will not maloperate. Meanwhile the healthy end will issue alarm
signal [Alm_Diff] which will be treated as the same as the alarm [Alm_CTS].
However, if CT circuit failure associated with internal fault or pickup due to system disturbance is
detected, the protective device will show two kinds of behavior.
If logic setting [En_CTSBlkDiff] (differential protection being blocked during CT circuit failure)
is set as “1”, the differential protection will be blocked.
If logic setting [En_CTSBlkDiff] is set as “0” and the differential current of the faulty phase is
more than the differential current setting [I_Diff_CTS] during CT circuit failure, the differential
protection will operate with alarm signal being issued at the same time.
3.3.2.7 CT saturation
The incorrected operationg of current differential protection would occur due to transient CT
saturation at the moment when external fault occurs. Hence, the protective device adopts high
restraint coefficient and self-adaptive floating restraint threshold, which can prevent current
differential protection from mal-operation even in serious saturation case.
Sampling of the currents on both ends shall be synchronized. One end should be configured as
the master end and the other as the slave end. The end of which setting [ID_Local] is greater than
[ID_Remote] is chosen as a master. The master end sends sampling information to the slave end
in fixed intervals while the slave adjusts its sampling intervals at any time. The slave end sends
three-phase current sampling value to the master if the synchronism condition is met and if not
then the synchronism program is initiated until the synchronism condition is met.
1) The routine of both direction shall be the same, so the time delays for both directions are the
same.
2) The maximum one-way channel propagation delay shall be less than 15 ms.
Depending on the difference of the amount of optic fibre core and the distance permitted to
transmit, RCS-931 relay can select two modes including dedicated optical fibre channel and
multiplex channel. The multiplex channel is not recommended unless the receiver power does not
meet the requirement.
Data exchange is very important to digital differential protection. RCS-931 relay can use multiplex
PCM (pulse code modulation) channel or dedicated optical fiber channel for data exchanging.
The differential relay sends and receives data based on respective clock, which are called transmit
clock (i.e. clock Tx) and receive clock (i.e. clock Rx) respectively. Clock Rx is fixed to be extracted
from data frame, which can ensure no drop-out data code generated and no receive error data
code received. Clock Tx has two options:
1) Use internal crystal clock, which is called internal clock. (master clock)
Depend on the difference of the clock used by the differential relays of the two terminals, there are
three modes.
1. Master-master mode
The RCS-931 relay line differential relays of both the two terminals use internal clock.
clock Tx clock Tx
64 kbit/s 64 kbit/s
clock Rx clock Rx
2. Slave-slave mode
The RCS-931 relay line differential relays of both the two-terminals use external clock.
3. Master-slave mode
One of them uses internal clock, the other uses external clock. (Not recommended)
Depending on the logic setting [En_InnClock], RCS-931 line differential relay selects the
communication clock mode. The inner clock is enabled automatically when the logic setting
[En_InnClock] is set to “1”. Contrarily, the outer clock is enabled automatically when the logic
setting [En_InnClock] is set to “0”.
If RCS-931 uses multiplex PCM channel, logic setting [En_InnClock] should be set as “0”. If
RCS-931 uses dedicated optical fibre channel, logic setting [En_InnClock] should be set as “1”.
The option for optic fibre communication is 1310 nm single-mode. The sending power of optic fibre
interface depends on the option of jumpers.
Note!
When using dedicated optical fibre channel, if the transmission distance is longer than
50km, the sending power must be enhanced to make receiver power larger than receiver
Note!
When transmission distance is longer than 80KM using dedicated optical fibre channel,
please declare it before ordering and it will be considered as special project using
Note!
When using multiplex channel, jumper needn’t be set and sending power is default.
The current differential protection will be enabled only if virtual binary input [VEBI_DiffP] and logic
setting [En_DiffP] are both set as “1”.
IDiff>[I_Diff_CTS]
[En_CTSBlkDiff] &
≥1
&
[Alm_CTS]
≥1
[Alm_Diff]
Channel abnormality
[VEBI_DiffP]
&
[En_DiffP]
&
VEBI_DiffP_R
≥1 Differential current condition 1
& DiffP_Rmt
En_DiffP_R
&
Common current differential element (Phase A) & Differential current condition 2 (Phase A)
&
Common current differential element (Phase B) & Differential current condition 2 (Phase B)
&
Common current differential element (Phase C) & Differential current condition 2 (Phase C)
Where:
VEBI_DiffP_R: the value is equal to the virtual binary input [VEBI_DiffP] of the remote end. This
signal can be received through optic fiber.
En_DiffP_R: the value is equal to the logic setting [En_DiffP] of the remote end. This signal can be
When virtual binary input [VEBI_DiffP] and logic setting [En_DiffP] of the remote end are both set
as “1”, the value of the signal “DiffP_Rmt” will be “1”.
[En_Stdy_Diff1]
[En_Comp_REF]
&
Capacitive current compensation &
VTS
&
UMin>40V
The zero-sequence current differential element referred to herein (Phase A, phase B and phase C)
has been compensated by capacitive current. (Please refer to Equation 3.3-7)
The condition of capacitive current compensation is met when the following conditions are all met
at the same time.
[En_REF]
&
VTS
&
UMin>40V
The zero-sequence current differential element referred to herein (Phase A, phase B and phase C)
has not been compensated by capacitive current. (Please refer to Equation 3.3-8)
3U0>1V
≥1
3U2>6V
UA<0.65UN
UB<0.65UN ≥1 ≥1
&
UC<0.65UN ≥1 Auxiliary voltage condition
UAB<0.65UNN
UBC<0.65UNN ≥1
UCA<0.65UNN
VTS
4Ia<Ioa
4Ib<Iob ≥1
4Ic<Ioc
30ms 0
[Alm_Diff] &
≥1
[Alm_CTS]
No current (Phase A)
&
[BI_52b_Pha]=1
CB is open (Phase A)
No current (Phase B)
CB is open (Phase B)
& ≥1 52b
CB is open (Phase C)
[BI_52b_Phb]=1
No current (Phase C)
&
[BI_52b_Phc]=1
52b ≥1
Fault detector
Besides differential current condition 1 must be met, sending permissive signal is determined by
any of conditions below.
Ioa>4Ia or Iob>4Ib or Ioc>4Ic (Ia, b, c is local current, Ioa, ob, oc is remote current), and
2) 52b
3) Pickup
52b
≥1 Fault detector
Differential current condition 1 &
&
Permissive signal from remote end
They have differential logic settings used to enabled or disable corresponding differential element.
Please to refer Chapter 7 about enabling and disabling of these differential elements. When
operating condition of the differential element is met and relevant logic setting is set as “1”, the
relevant differential element operates and sends a tripping signal.
When a tripping signal is issued by the differential element, in addition to tripping the local circuit
breaker, the protective device will send a intertripping signal to the remote device. This will ensure
tripping of both ends of the protected line, even for marginal fault conditions.
In order to avoid protective devices on the both ends are relcosed into the fault when a
single-phase permanent earth fault occurs, the protective device at the end of the line, which is
reclosed into the faulty line earlier, trips local circuit breaker at once and transfers the three-phase
intertripping signal to the other device at the opposite end of line, which simultaneously trips the
circuit breaker and blocks auto-reclosing after receiving three-phase intertripping signal.
Phase-segregated intertripping
When a fault associated with high resistance occurrs in the outlet of long transmission line, the
protective device at the end of line, which is near the fault, can pick up immediately, but,
considering the influence of a considerable power source, the other device at opposite end of line,
which is far from the fault, can not pick up due to inapparent fault component. In order to avoid this
case, the protective device at the end of the line, which is near the fault, operates (such as
directional zero-sequence overcurrent protection operating, distance protection operating and so
on) and transfers phase-segregated intertripping signal to the other device at opposite end of line,
which trips corresponding phase of circuit breaker associated with permissive signal and logic
setting [En_RTrValid] set as “1” after receiving phase-segregated intertripping signal.
At one end, CT circuit failure is detected, which maybe leads to fault detector element and
differential element operating, but, on the other end, fault detector element does not operate so
that no permissive signal is issued, which prevents current differential protection maloperation.
However, if CT circuit failure associated with internal fault or pickup due to system disturbance is
detected, the protective device will show two kinds of behavior.
If logic setting [En_CTSBlkDiff] (differential protection being blocked during CT circuit failure)
is set as “1”, the differential protection will be blocked.
If logic setting [En_CTSBlkDiff] is set as “0” and the differential current of the faulty phase is
more than the differential current setting [I_Diff_CTS] during CT circuit failure, the differential
protection will operate with alarm signal being issued at the same time.
&
3I0Cal > [I_ROC_FD] & Zero sequence forward element
[En_Dir_ROC1]
≥1
&
Stage 1 of Zero sequence
3I0 > [I_ROC1] & overcurrent protection operation
&
[En_Dir_ROC2]
≥1
&
Stage 2 of Zero sequence
3I0 > [I_ROC2] & [t_ROC2]
overcurrent protection operation
&
[En_Dir_ROC3]
≥1
&
Stage 3 of Zero sequence
3I0 > [I_ROC3] & [t_ROC3]
overcurrent protection operation
&
[En_Dir_ROC4]
≥1
&
3I0 > [I_ROC4] & Stage 4 of Zero sequence
[t_ROC4]
overcurrent protection operation
&
[En_ROC_VTS]
& [t_ROC_VTS]
3I0 > [I_ROC_VTS]
[En_OC_VTS]
1. There are four stages zero-sequence directional overcurrent elements. Whether it is under
the control of the directional element or not can be decided by setting the logic setting
[En_Dir_ROC1], [En_Dir_ROC2], [En_Dir_ROC3] and [En_Dir_ROC4] for corresponding
stage.
or not.
3. When bus VT circuit failure happens, the distance protection will be disabled. As a substitute,
phase overcurrent protection and zero sequence overcurrent protection will be put into
operation automatically in this case if virtual binary inputs [VEBI_DistP] and [VEBI_ROC] are
set as “1”. It can be disabled by setting logic setting [En_OC_VTS] and [En_ROC_VTS] as
“0”.
The inverse-time characteristic complies with the following formula (based on IEC60255-3
standard).
k
t(I p ) = TMS × ( + c)
Ip α
( ) −1
I set
Where:
k, α, c: a certain constant
According to the different value of k, α and c, different inverse-time characteristic are available.
TMS: Time constant, i.e. the setting [t_OC1] if inverse-time characteristic is chose for stage 1 of
phase overcurrent protection
Iset : Reference current, i.e. the setting [I_OC1] if inverse-time characteristic is chose for stage 1 of
phase overcurrent protection
For stage 1 of phase overcurrent protection, definite-time characteristic and seven kinds of
inverse-time characteristics can be choose from. According to the specification of IEC60255-3,
four kinds of IEC inverse-time characteristics and three kinds of ANSI/IEEE inverse-time
characteristics are provided to choose from. It can be shown in the following table.
Opt_Curve_OC1 k α c
0: definite-time - - -
1: IEC Normal Inverse-time characteristic 0.14 0.02 0
2: IEC Very Inverse-time characteristic 13.5 1 0
3: IEC Extremely Inverse-time characteristic 80 2 0
The distance protection provides a fast and reliable protection for overhead lines and underground
cables in various power networks. For each independent distance element zone, an individual
impedance measuing element is equipped within it. Full scheme design provides continuous
measurement of impedance separately in three independent phase-to-phase measuring loops as
well as in three independent phase-to-ground measuring loops.
Phase-to-phase distance element is suitable as a basic protection function against two- and
three-phase faults in various networks, regardless of the treatment of the neutral point.
Independent setting for each zone separately makes it possible to create fast and selective
protection in power systems.
Phase-to-ground distance element serves as basic earth fault protection in networks with solid or
low impedance grounded networks. Separately, independent setting for each zone makes it
possible to create fast and selective protection in power systems.
Polarized positive sequence voltage is used to improve performance of distance protection against
high fault resistance. Moreover, in the case of short lines, in order to enhance performance against
high fault resistance, the impedance characteristic of the zone 1 and zone 2 could be inclined
toward quadrant 1.
Zero sequence reactance character is used for phase-to-ground distance element so that the
overreach due to resistance earth fault can be avoided.
If the positive sequence polarized voltage is high enough, directionality of the distance protection
using positive sequence polarized voltage is very good. However, when close-in three phase fault
happens, the positive sequence voltage may reduce to 15% or less of the rated voltage, this will
lead the distance protection to go to a low voltage program (please refer to 3.3.5.1) in which a
memorized positive sequence polarized voltage is used instead.
Threshold will be set forward for zones 1 and 2 of distance element before its operation, so that
directionality could be assured during busbar three phase fault. And this threshold will be changed
to reverse direction after operation of the protection, so that forward close-in three phase fault can
be fully cleared. As to the zone 3 of the distance element, the direction of the threshold is always
reverse, because it acts as a backup protection for busbar.
Note!
When VT circuit failure happens, the alarm [Alm_VTS] is displayed, and all distance
1. General description
Distance element with memorized polarization is an algorithm used when positive sequence
voltage reduces to 15% or less. There are only two possibilities for this condition: power swing or
three phase short circuit fault.
As the power swing, distance element will be blocked and power swing blocking for distance
element is not released if PSBR element does not operate. Thus, only three-phase short-circuit
fault should be considered and discussed herein.
Impedance of all three phase are usually equal. But in order to ensure fast tripping even in the
case of transition from bus fault to three phase line fault, all of the three phase impedance are
calculated and operation of any phase element will lead to three phase tripping.
2. Design
Distance element with memorized polarization compares phasor angle of operating voltage and
polarized voltage.
Generally the phasor angle of bus voltage of the faulty line is almost equal to be phasor angle of
EM , (i.e. δ=0), the transient operation characteristic can be shown as Figure 3.3-17.
Operation characteristic of Z K on R-X plane is a circle with line connecting ends of Z ZD and
This does not mean it will operate incorrectly during reverse fault but means it will operate
correctly during forward fault even if the fault occurs just on the outlet because that is derived
supposing forward fault. δ is not equal to 0, the circle with the line connecting ends of Z ZD and
Z S as a chord will move toward quadrant 1or 2.
jX
ZZD
ZK
ZS
Figure 3.3-18 shows operation characteristic of measured impedance − Z K on R-X plane. This
Z 'S as the diameter. It will
characteristic is a circle with line connecting ends of Z ZD and
operate only when − Z K is in the circle. Therefore directionality of the protection is explicit.
jX
Z'S
ZZD
R
ZK
The conditions mentioned above are before fading of memorized voltage: the transient
characteristic.
When the memorized voltage fade, Figure 3.3-19 shows operation characteristic of measured
impedance Z K on R-X plane for forward fault as well as that of ‘ − Z K ’ for reverse fault. Since the
circle covers the origin, the equipment will be just on the margin of operation for fault on the bus or
line outlet. In order to prevent the mal-operation for bus fault, especially the three phase bus fault
with arc resistance, zone1 and 2 of distance element is equipped with a positive threshold. Voltage
value of the threshold is equal to maximum voltage drop of the arc. Moreover, when zone 1 or 2 of
distance element operates, phase of the threshold voltage will be inverted so that the origin can be
enclosed in the characteristic circle to ensure the fault can be fully cleared. In order to ensure
backup protection of zone 3, phase of threshold voltage is always inverted and the origin is always
enclosed in the characteristic circle.
jX
ZZD
ZK
Figure 3.3-19 Steady state characteristic of three phase short circuit fault
In short line case, in order to improve the relay performance against high fault resistance, phase
shift θ1 is used for polarized voltage. This phase shift could move the directional impedance
characteristic toward quadrant 1 as is shown in Figure 3.3-20. Value of θ1 can be set to 0°, 15° or
30°.
Because of using phase shift characteristic, the permformance of this relay against high fault
resistance is improved. However, if there is a considerable power source in remote end, an
overreach caused by infeed from remote end during resistance earth fault may occur. In order to
prevent overreach, the following zero sequence reactance relay is introduced.
Typical zero-sequence reactance characteristic is shown as the straight line A in Figure 3.3-20.
Therefore, directional impedance characteristic integerating with the zero sequence characteristic
are adaptive with the fault resistance.
The no-memorized positive sequence voltage is used as polarized voltage because during earth
fault, positive sequence voltage is mainly formed by healthy phase and the phase of positive
sequence voltage is kept as it was before the fault. So characteristic of zone 3 of phase–to-earth
distance element is the same as the transient characteristic of distance element with memorized
polarization and have a very good directionality.
The sensitivity of phase-to-ground distance element with Mho characteristic may be not enough
during ground fault with extreme high resistance. So additional three-zone distance element with
quadrilateral characteristic is adopted in the equipment to compensate the sensitivity of Mho
characteristic. The logic relationship between quadrilateral distance element and Mho distance
element is OR. It means that any ground fault in one of the two operation zones will be cleared.
The quadrilateral phase-to-ground distance element can significantly improve the sensitivity to
clear ground fault with extreme high resistance. The three zones of quadrilateral characteristic can
be enabled or disabled by the logic setting [En_ZPG1_Quad], [En_ZPG2_Quad] and
[En_ZPG3_Quad] respectively.The operation characteristic of quadrilateral distance element is
shown in Figure 3.3-21 :
jX
Φ Φ
R
Where,
[Z_PG1], [Z_PG2] or [Z_PG3] are the impedance setting of corresponding zone of Mho distance
protection.
Phase shift θ2 is introduced here for polarized voltage in zones 1 and 2 just like θ1 in case of
phase-to-ground distance element. It is used also for improving performance against high fault
resistance in short line case. Value of θ2 can be set as 0° or 15°or 30°.
Reactance element
Combination of the directional impedance element and reactance element increases tolerance on
high fault resistance in short line application.
If three-phase short circuit fault occurs, since the polarized voltage has not been memorized, its
operation characteristic is a circle passing through the origin (Please refer to Figure 3.3-19). If the
positive sequence voltage is low, the fault will be measured by impedance element with
memorized polarization. There is neither problem about dead zone nor loss of directionality for bus
fault in this case.
When a reversal fault occurs in backside busbar, reversal distance element is provided to clear it
and is taken as backup protection for reversal busbar fault. Its operation characteristic is shown as
follow.
Where:
The blinder characteristic shown in Figure 3.3-23 can be used to restrict the reach of a distance
relay on a long line or during heavy load conditions. The distance relay will be allowed to trip only
when both blinders are operated (i.e., the apparent impedance must be between the two
characteristics).
In order to ensure distance relay not affected by load impedance, the phase-to-phase and
phase-to-ground blinders are used. As shown in Figure 3.3-23, the slope of blinder is same to the
positive sequence sensitivity angle Φ, RZD is the setting [R_Blinder]. The operation region is
between line A and line B. The logic setting [En_Blinder] can decide whether the blinder is enabled
or not.
When power swing occurs on the power system, the impedance measured by the distance
measuring element may vary from the load impedance area into the operating zone of the
distance element. The operation of the distance measuring element due to the power swing
occurs in many points of interconnected power systems. To keep the stability of whole power
system, tripping due to operation of the distance measuring element during a power swing is
generally not allowed. RCS-931 adopts releasing power swing blocking to avoid maloperation of
distance protection resulting from power swing. In another word, distance protection is blocked all
along under the normal condititon and power swing. Only if fault (internal fault or power swing with
internal fault) is detected, power swing blocking for distance protection is released by PSBR
element.
Power swing blocking for distance element will be released if any of the following PSBR elements
operate.
If any of the following condition is matched, FD PSBR will operate for 160ms.
1) Positive sequence current is lower than the setting [I_OC_PSBR] before general fault detector
element operates.
2) Positive sequence current is higher than the setting [I_OC_PSBR] before general fault
detector element operates, but the duration is less than 10ms.
The “m” is a internal fixed coefficient which can ensure UF PSBR operate during power swing with
internal unsymmetrical fault, while not operate during power swing or power swing with external
fault
If a three-phase fault occurs and FD PSBR is invalid (160ms after GFD operates), neither FD
PSBR nor UF PSBR will be able to operate to release the distance protection. Thus, SF PSBR is
provided for this case specially. This detection is based on measuring the voltage at power swing
center:
Where:
1) when − 0.03U N < U OS < 0.08U N , the SF PSBR element will operate after 150ms.
2) when − 0.1U N < U OS < 0.25U N , the SF PSBR element will operate after 500ms.
If the rate of change of voltage at power swing center is great than a certain value, and the DPFC
overcurrent fault detector picks up, the PSCVR PSBR element will operate.
Figure 3.3-24 Logic diagram of PSBR for zone 1 and zone 2 of distance element
The logic setting [En_PSBR_Z1/2] is common for zone 1 and zone 2 of distance element. If the
logic setting [En_PSBR_Z1/2] is set as “0”, zone 1 and zone 2 of distance element is not blocked
by PSBR. PSBR for zone 1 and zone 2 of distance element will operate right now (i.e., output state
of [PSBR_Z1/2] is “1”).
If the logic setting [En_PSBR_Z1/2] is set as “1”, zone 1 and zone 2 of distance element is
controlled by PSBR. After zone 2 of distance element operates and PSBR condition is also met,
PSBR for zone 1 and zone 2 of distance element will operate (i.e., output state of [PSBR_Z1/2] is
“1”).
The logic setting [En_PSBR_Z3] is only for zone 3 used to enable or disable power swing blocking
for zone 3 of distance element. If the logic setting [En_PSBR_Z3] is set as “0”, zone 3 of distance
element is not blocked by PSBR.PSBR for zone 3 of distance element will operate right now (i.e.,
output state of [PSBR_Z3] is “1”).
If the logic setting [En_PSBR_Z3] is set as “1”, zone 3 of distance element is controlled by PSBR.
After zone 3 of distance element operates and PSBR condition is also met, PSBR for zone 3 of
distance element will operate (i.e., output state of [PSBR_Z3] is “1”).
ZPP_Rev operates
[En_ZPP_Rev] &
Reversal distance
VT circuit failure ≥1 [t_Rev] element operating
[En_ZPG_Rev] &
ZPG_Rev operates
distance element
1. If distance protection is required to be enabled, virtual binary input setting [VEBI_DistP] shall
be set as 1.
2. If the logic setting [En_BI_Z1_Vld] is set as “1”, zone 1 of distance element is enabled when
the binary input [BI_En_Z1] is energized and channel abnormality is detected by the device
(or differential protection is disabled). If the logic setting [En_BI_Z1_Vld] is set as “0”, zone 1
of distance element is enabled all along and is not controlled by the binary input [BI_En_Z1].
Shown as below:
If duplicated line protection configuration is adopted, the wiring scheme between two devices is as
below:
P1 P2
En_BI_Z1_Vld >=1
Watchdog
Comm_fail >=1 & Z1 is Released
Where:
In order to prevent existing dead zone in the protected zone, the origin in the operation
characteristic diagram is included in the operation zone of reversal distance element.
5. If the logic setting [En_Blinder] is set to “1”, the reach of distance relay will be restricted on a
long line or during heavy load condition.
6. Power swing blocking for zone 1 and zone 2 of distance element can be enabled or disabled
by logic setting [En_PSBR_Z1/2]. Power swing blocking for zone 3 of distance element can
be enabled or disabled by logic setting [En_PSBR_Z3].
7. Zone 2 and 3 of distance element have corresponding logic setting [En_Z2_Blk_AR] and
[En_Z3_Blk_AR] to or not to block auto-reclosing.
For thermal overload protection without consideration of the preload current, the following tripping
characteristic is applied. For different thermal time constants τ , the operating time T is calculated
in accordance with the following equation:
I2
T = τ ⋅ ln 2
I − (k ⋅ I B ) 2
The thermal overload protection with consideration of preload current constantly updates the
thermal model calculation regardless of the magnitude of the phase currents. The operating time T
is calculated in accordance with the following equation (complete memory in accordance with IEC
60255-8).
I 2 − I p2
T = τ ⋅ ln
I 2 − (k ⋅ I B ) 2
RCS-931 is equipped with IEC60255-8 “heat” curve to make up thermal overload protection,
where:
T: operating time
I: overload current
RCS-931 calculates real-time temperature rise curve every time. When thermal capacity of
temperature rise is larger than setting [ThM_OvLd_Alm] (shown as percentage), protective device
sends overload alarm signal. When heat quantity of temperature rise is larger than setting
[ThM_OvLd_Trp] (shown as percentage), protective device trips circuit breaker or sends overload
alarm signal.
element, current differential fault phase selection element and I 0 and I 2 A fault phase selection
element. The logic makes the relay ideal for single-phase tripping applications.
If ΔU OPΦMAX is several times higher than the other two deviation of phase operation voltages, the
ΔU OPA A phase
ΔU OPB B phase
ΔU OPC C phase
ΔU OPAB AB phase
ΔU OPBC BC phase
ΔU OPCA CA phase
The phase selection algorithm uses the angle relation between I 0 and I 2 A of the relay currents.
I0 I
When − 60 < Arg < 60 o , region A is selected, 60 o < Arg 0 < 180 o , region B is selected,
o
I2A I2A
I0
180 o < Arg < 300 o , region C is selected.
I2A
I0
Table 3-3 The relation between Arg and fault phase
I2A
I0
Arg Fault phase
I2A
00 A phase or BC phase
1200 B phase or CA phase
0
240 C phase or AB phase
Note:
The operation of the contact based pole discordance logic is based on checking the position of the
circuit breaker through its auxiliary contacts: three parallel connected normally open contacts are
connected in series with three parallel connected normally closed contacts.
Pole disagreement procedure comprises of the protection of pole disagreement state and switch
onto fault protection. When the following conditions are met, pole disagreement state is ensured a
delay of 30ms.
1) Trip confirmation
Trip confirmation means that tripping signal is issued and any phase current is smaller than 0.06IN
4) When trip phase current I Φ > 0.06 I n or 52b=0, SOTF protection is initiated for 400ms
1) When I A , I B or I C > 0.06 I n or three phase 52b=0, SOTF protection is initiated for 400ms
>=1
&
Single pole tripping &
Fault Detector
Any tripping
>=1
BI_52b_Pha >=1 &
BI_52b_Phb & 0 400ms Single pole reclosing (For SOTF)
BI_52b_Phc
&
&
>=1
Fault Detector 0 400ms Three poles reclosing (For SOTF)
&
Three pole tripping >=1
&
Any tripping
BI_52b_Pha &
BI_52b_Phb
&
BI_52b_Phc
0 400ms Manual closing (For SOTF)
Fault Detector
1. Zero-sequence overcurrent element for SOTF can be enabled or disabled by logic setting
[En_ROC_SOTF]. Distance element for SOTF can be enabled or disabled by logic setting
[En_Z_SOTF].
2. Zero-sequence overcurrent element for SOTF will operate to trip three-phase circuit breaker
delay 60ms when 1-pole auto-reclosing.
3. Zone 2 of distance element which is blocked by power swing for SOTF will operate to trip
three-phase circuit breaker delay 25ms when 1-pole auto-reclosing.
4. Zero-sequence overcurrent element for SOTF will operate to trip three-phase circuit breaker
delay 100ms if 3I0 is greater than setting [I_ROC_SOTF] when 3-pole auto-reclosing or
reclosing manually.
5. When protective device is reclosed to faulty line, zone 2 and 3 of distance element which is
not blocked by power swing will operate to trip three-phase circuit breaker if logic setting
[En_Z2SOTF_AR3P] and [En_Z3SOTF_AR3P] are set as “1” when 3-pole auto-reclosing. If
logic setting [En_Z2SOTF_AR3P] and [En_Z3SOTF_AR3P] are set as “0”, zone 2 of distance
element which is blocked by power swing will operate to trip three-phase circuit breaker when
3-pole auto-reclosing.
6. Zone 3 of distance element will operate to trip three-phase circuit breaker when reclosing
manually.
≥1
PSBR_Z1/2
&
&
Z < [Z_PP2]
[En_Z_SOTF]
[En_Z3SOTF_AR3P]
≥1
Zone 3 of Quadrilateral distance element
&
[En_ZPG3_Quad]
≥1 &
Z < [Z_PG3] ≥1
Z < [Z_PP3]
&
IA>0.06In
& &
≥1
Select Phase A ≥1 Trip Phase A
IB>0.06In
&
Select Phase B & ≥1
≥1 Trip Phase B
IC>0.06In
≥1
& 200ms 0
&
IP>0.06In
Op_OC1
≥1
Op_OC2
Op_Ovld_Trip
Op_TT ≥1
Op_OC_VTS
Op_3P_RecvTT
Op_Z1
&
≥1
Op_Z2
&
[En_Z2_Blk_AR]
Op_Z3
&
[En_Z3_Blk_AR]
Op_ROC1
&
[En_Inst_Blk_AR]
Op_ROC2
&
[En_ROC2/3_Blk_AR] ≥1
Op_ROC3
&
Op_ROC4
&
[En_ROC4_Blk_AR]
≥1
Op_PDP
&
[En_PDF_Blk_AR]
Initiating blocking relay for auto-reclosing
≥1
Op_PhSelFail
&
[En_PhSF_Blk_AR]
[VEBI_LockOut]
Trip phase A
Trip phase C
[En_3P_Trip]
& 150ms 0 Fail in single pole tripping
[VEBI_LockOut]
&
Enable Auto-Reclosing
&
Three-Pole Auto-Reclosing
2. If phase segregated differential relay operates, corresponding phase selection element will
operate.
3. When DPFC distance element and pilot differential element operate, it will trip single phase by
phase selection element. If phase selection element fails and operation element can not drop
off, three-pole tripping command caused by phase selection failure will be sent after 200ms
delay.
4. If any of the following conditions is matched, three-phase tripping signal will be sent directly.
5. After receiving single phase tripping signal, if the current of this phase is still larger than 0.06In,
three-phase tripping signal will be sent after 150ms delay.
6. Three poles trip will be used if two or three phases are selected by the phase selection
element.
7. Any fault occurs under following conditions, three-pole trip element will operate
8. When a serious fault occurs, auto-reclosing will be blocked under the following conditions:
9. For zone 1 of distance protection and stage 1 of zero sequence overcurrent protection,
whether three-pole trip and auto-reclosing blocked are adopted or not will be decided by logic
setting [En_Inst_Blk_AR]. For zone 2 and zone 3 of distance protection, whether
auto-reclosing blocked is adopted or not will be decided by logic setting [En_Z2_Blk_AR] and
[En_Z3_Blk_AR]. For stage 2, stage 3 and stage 4 of zero sequence overcurrent protection,
whether auto-reclosing blocked is adopted or not will be decided by logic setting
[En_ROC2/3_Blk_AR] and [En_ROC4_Blk_AR].
10. Three-pole trip with auto-reclosing blocked can be selected by logic setting
[En_PhSF_Blk_AR], [En_PDF_Blk_AR] and [En_MPF_Blk_AR].
11. If logic setting [En_FD_Ctrl_TT] is set as “1”, three-pole trip is adopted and auto-reclosing is
blocked after receiving transfer trip and fault detector element operating. If logic setting
[En_FD_Ctrl_TT] is set as “0”, three-pole trip is adopted and auto-reclosing is blocked after
receiving transfer trip.
12. If only reversal distance protection and overload protection operate, the relay will not select
faulty phase and locate where the fault occurs.
3.8 Auto-Reclosing
3.8.1 General description
To maintain the integrity of the overall electrical transmission system, protective relays are
installed on the transmission system to isolate faulted segments during system disturbances.
Faults caused by lightning, wind, or tree branches could be temporary in nature and may
disappear once the circuit is de-energized. Automatic reclosing systems are put into place to
re-energize and restore the faulted section of the transmission system once the fault is
extinguished (providing it is a temporary fault). For certain transmission systems, reclosing is used
to improve system stability by restoring critical transmission paths as soon as possible.
3.8.2 Design
Auto-reclosing of RCS-931 is one shot mode, which can implement 1-pole auto-reclosing, 3-pole
auto-reclosing and 1-pole/3-pole auto-reclosing.
In any case, auto-reclosing is performed only once. If the fault still exists after reclosing, the line
will be tripped without any future reclosing, in other words, lockout. Only single shot auto-reclosing
during the time from auto-reclosing initiated to dropped off.
The synchronising scheme consists of synchronism check relay element and a voltage check
element. The synchronising scheme monitor the condition of the bus voltage and line voltage. The
voltage settings for distinguishing between “live” and “dead” conditions can be determined by
taking into account an induced voltage from the self-line and the adjacent line:
The synchronism check will compare the AC voltage from line VT and the AC voltage from busbar
VT. The checking voltage inputs can adopt phase voltage of any phase or phase-to-phase voltage
of any phase from line VT. The relay is self-adaptive to the checking voltage inputs.
Phase voltage of phase A is used for the busbar voltage of the synchronism check. During normal
running condition, the relay remembers the angle difference between phase A busbar voltage and
checking voltage. And the mnemonic angle difference is compensated during synchronism check.
For dead line check, auto-reclosing is performed if busbar voltage or checking voltage is less than
the setting i.e. [V_Dead].
For synchronism check, auto-reclosing is performed if busbar voltage and checking voltage are
both higher than the setting i.e. [V_Live] and the phase difference, frequency difference and
voltage difference between them are all within the setting range.
The energizing check function measures the bus and line voltages and compares them to both
“live” and “dead” threshold detectors. The condition is only given when the actual measured
conditions match the set conditions.
The following figures show the synchrocheck and energizing check scheme logic.
3.8.7 Lockout
Under the following conditions, the auto-relcosing will be locked out.
breaker control circuit failure, either trip or closing coils are unhealthy
stage 2 or 3 ROC operates to trip three phases and logic setting [En_ROC2/3_Blk_AR]
reclosing conditions are not met yet till the incomplete sequence time expires.
Whenever all of the listed events disappear, the auto-relcosing will resume normal function.
The synchronising scheme consists of synchronism check element and voltage check element.
The synchronising scheme monitors the condition of the bus voltage and line voltage. The voltage
settings for distinguishing between “live” and “dead” conditions to be determined taking account of
an induced voltage from the self-line and the adjacent line:
The synchronism check will compare the AC voltage from line VT and the AC voltage from busbar
VT. The checking voltage inputs can adopt phase voltage of any phase or phase-to-phase voltage
of any phase from line VT. The relay is self-adaptive to the checking voltage inputs.
For dead line check, auto-reclosing is performed if busbar voltage or line checking voltage is less
than [V_Dead].
For synchronism check, auto-reclosing is performed if busbar voltage and checking voltage are
both higher than [V_Live] and the phase difference, frequency difference and voltage difference
between them are all within the setting range.
The energizing check function measures the bus and line voltages and compares them to both
“live” and “dead” threshold detectors.
The following figures show the synchrocheck and energizing check scheme logic.
[En_SynChk_AR]
UBusHigh
Udiff<V_Diff_SynChk
FreqDiff<f_Diff_SynChk
PhaseDiff<phi_Diff_SynChk
13) t_CBClsd_AR: The time a breaker must be closed before AR becomes ready for a reclosing
cycle (proposed setting 25s)
14) t_VoltChk: Supervision time for dead/live voltage check (internal setting 20ms)
15) t_SynChk: Synchronism check operation time delay (internal setting 20ms)
If no blocking signal for reclosing is received and all three phase circuit breakers have been closed
for [t_CBClsd_AR], the reclosing will be ready for one-shot reclosure. When binary input for
blocking reclosing is received, protective device will output contact for blocking reclosing.
CB Closed ≥1
& [t_CBClsd_AR]
Any trip
AR ON CB Ready
&
Device abnormal
AR lock Input
Lock element ≥1
AR Pulse
AR Unsuccess
&
Single pole AR
Reset Logic
&
≥1
Three Pole Trip
Any trip
& 3 Pole ARInitiate
3 Pole AR
CB Ready
≥1
AR Pulse
& [t_Unsuc_AR]
CB closed
CB Ready
200ms AR Fail
& ≥1
Any trip
SynChk ok
&
[En_SynChk]
≥1
Energe ok
& [t_Wait_SynChk] SynChk Fail
&
[En_deadvChk]
&
& ≥1
& AR3 Pulse ready
[En_NoChk_AR]
Any trip: tripping signal from local protective device or remote protective device
t_CBClsd_AR: time delay of circuit breaker in closed state before reclosing;
t_1P_AR: Dead time for 1-pole AR;
t_3P_AR: Dead time for 3-pole A;
t_Unsuc_AR: CB Check time before unsuccessful;
t_Wait_SynChk: Maximum wait time for synchonism;
En_SynChk:Enable synchronism check
En_DeadvChk:Enable dead voltage check (including En_DdB_DdL_AR, En_LvB_DdL_AR,
En_DdB_LvL_AR)
For transient fault, the fault will be cleared after protection device operates to trip. After the
reclosing command is issued, AR will drop out with time delay [t_Reclaim_AR], and can carry out
next reclosing. When the reclosing is unsuccessful or the reclosing condition is not met after AR
initiated, the reclosing will be considered as unsuccessful, including the following cases.
1. If the tripping command is received again after the reclosing pulse is issued, the reclosing
shall be considered as unsuccessful.
2. The tripping command is received before AR is ready, the reclosing shall be considered as
unsuccessful.
3. If CB is still in open state with a time delay [t_Unsuc_AR] after the reclosing pulse is issued,
the reclosing shall be considered as unsuccessful.
For this case, the protection device will issue signal “AR Fail” to indicate the reclosing is
unsuccessful, and this signal will drop out after “Reset Command”. After AR unsuccess is
confirmed, AR will be blocked. AR will not enter into the ready state unless the circuit breaker
position drops out.
RCS-931 can exchange not only current but also binary inputs via communication channel
between two ends of line.
RX
TX
702 +110/220V
A02
Optical fibre
Transfer trip
TJA-1
A05
TJB-1
A07
RX
TX
720 Transfer trip TJC-1
A09
RCS-931 RCS-931
M N
&
[En_FD_Ctrl_TT]
& ≥1 Op_TT
[BI_Recv_TT]
Transfer signal 1
RX
TX
RX
TX
Transfer signal 2
Figure 3.9-3 The sketch diagram of transfer signal
The numerical relay based on the microprocessor operations is suitable for implementing this
automatic supervision function of the protection system.
In case a fault is detected during initialization when DC power supply is provided to the equipment,
the equipment will be blocked out, which means relay is out of service. Therefore you must
re-energize the relays or reset CPU module by restarting equipment to get relay back into service.
When a failure is detected by the automatic supervision, it is followed with an LCD message, LED
indication and alarm contact outputs. At the same time event recording will record the failure alarm
which can be viewed in event recording report and be printed.
When any DPFC fault detector picks up for longer than 10s, an alarm will be issued
[Alm_PersistFD] without the equipment getting blocked.
summation error of all setting groups, an alarm [Alm_EEPROM] will be issued, equipment is also
blocked.
If these 15 setting groups are not all set, when the equipment is provided DC power supply first, an
alarm [Alm_InvalidGrp] will be issued. If any equipment settings is changed and the protection
settings is not confirmed or some settings in protection settings exceed setting range, an alarm
[Alm_InvalidGrp] will be issued.
If either of the binary input [BI_ExTrp1P_AR] or [BI_ExTrp3P_AR] is energized and the duration
exceed 10s, an alarm [Alm_BI_ExTrp] will be issued.
If binary input [BI_52b] is energized ,which indicates circuit breaker is open and no current is
detected in the line, the line will be considered to be out of service. Switch onto fault (SOTF)
protection will be enabled.
If binary input [BI_52b]=1 that indicates circuit breaker is open but current can still be detected in
the line, an alarm signal [Alm_52b] will be issued after 10 seconds.
If control circuit of circuit breaker is broken, the alarm signal [Alm_TCCS] will be issued.
In normal operation program of the RCS-931, the phasor summation of bus three phase voltage is
checked frequently, if this phasor summation detected is higher than 8.8V and fault detection
element does not operate, VTS will, after 1.25s, output an alarm [Alm_VTS].
If the phasor summation detected is lower than 8.8V but the bus positive voltage U1 is less than
33V, VTS will also issue an alarm [Alm_VTS] after 1.25s when logic setting [En_LineVT] is set to
“0”, otherwise, VTS will also issue an alarm [Alm_VTS] after 1.25s when circuit breaker is closed
([BI_52b]=0) or there is current existing on line.
3U0>8.8V
1.25s 10s
U1<0.3UN ≥1
&
[En_LineVT] ≥1
& ≥1 VTS
CB Closed
[En_VTS]
to enable phase overcurrent protection and zero sequence overcurrent protection especially
for this case as a substitute (Please refer to 3.3.3 for detail)
to disable stage 3 zero sequence overcurrent element if logic setting [En_Dir_ROC3] is set to
“1”
Resetting of all the above measures and resetting of the display and alarm are automatically
performed 10s after all three phases voltage resume to normal condition.
If the auto-reclosing mode is not 1-pole AR, and the line circuit breaker is in closed state which is
indicated by binary input [BI_52b]=0, but the line voltage is lower than the setting i.e. [V_Dead], it
is concluded that “line voltage transformer circuit failure” has occurred and an alarm
[Alm_VTS_Usyn] will be issued after 10s.
If auto-reclosing is disabled, or the logic settings [En_SynChk_AR] and [En_DeadChk_AR] are set
to “0”, line voltage is not needed to be connected and line voltage transformer circuit failure
supervision will be disabled.
When line voltage transformer circuit failure is detected, function of synchronism check and dead
line check in auto-reclosing logic will be disabled.
After line voltage resumes to normal condition, the alarm and its subsequences will be reset
automatically after 10s.
The equipment measures zero sequence current from two sources, which is either calculated
depending on the summation of IA, IB and IC (3I0Cal) or derived at the neutral current circuit from
three-phase currents (3I0).
If 3I0Cal is less than 0.75 times 3I0 or 3I0 is less than 0.75 times 3I0Cal, after 200 ms, an alarm
[Alm_CTS] will be issued.
If 3I0Cal exists (3I0Cal>0.1In) but 3U0 is nearly zero (3U0<3V) and there is a phase whose current is
zero at least, after 10s, an alarm [Alm_CTS] will be issued.
10s 10s
3I0Cal>0.1IN &
≥1 [Alm_CTS]
3U0<3V
3I0>0.1IN
≥1
200ms 10s
3I0Cal>0.1IN &
3I0>0.75×3I0Cal
≥1
3I0Cal>0.75×3I0
When CT circuit failure is detected, CTS will have the following influence on protection.
3U0: zero-sequence voltage calculated depending on the summation of UA, UB and UC. (i.e.,
3U0=UA+UB+UC)
When differential protection is disabled and persists for 400ms, an alarm [Alm_Ch] will be issued
and persist for 3s.
If no correct data is received within 100ms, after that, an alarm [Alm_Data_Ch] will be issued and
persist for 1s.
If 40 frame messages are failed in CRC check within 1s, an alarm [Alm_CRC_Ch] will be issued.
If differential current is greater than 0.1In and 80 percent of differential current is greater than
capacitive current calculated , an alarm [Alm_Xc] will be issued after 400ms delay.
If the protection device is under the state of communication test (The setting [En_CommTest] of
communication parameters is set as “1”), the alarm signal [Alm_CommTest] will be issued.
If the differential current is higher than low current setting of current differential protection [I_L_Diff]
for 10s, an alarm [Alm_Diff] will be issued and persist for 10s.
A common abnormality may block a certain number of protections functions while the other
functions can still work. However, if serious hardware failure or abnormality were detected, all
protection functions will be blocked and the LED “HEALTHY” will be extinguished and blocking
signal will be given by contacts output BSJ. The protective device then cannot work normally and
maintenance is required to eliminate the failure.
Note!
If the protective device is blocked or alarm signal is sent during operation, please do find
out its reason with the help of self-diagnose record. If the reason can not be found at site,
please notice the factory NR. Please Do not simply re-power on the protective device.
REPORT FD MEASUREMENT
CLOCK BI STATE
VERSION BO STATE
Measured directly
Magnitude of phase current coming from the other end (Ioa, Iob, Ioc)
Calculated by DSP
Event recording
Fault recording
These records are displayed on the LCD of the relay front panel or on the local or remote PC.
Navigate the menu to view the report through LCD screen. Access path in menu is:
MainMenu VALUES
VERSION
LANGUAGE
TEST MODE
The protection device is under automatic supervision all the time. If there are any failure or
abnormal condition detected, such as, chip damaged, VT circuit failure and so on, it will be logged
in event recorder.
When there is binary input is energized or de-energized, i.e., its state has changed from “0” to “1”
When there is binary output is energized or de-energized, i.e., its state has changed from “0” to “1”
or from “1” to “0”, it will be logged as an event recorder.
Once the protection device detects some cases, such as reboot protection device, modify setting,
clear the report and so on, they will be logged in event recorder.
Disturbance recording is consisted of fault operation report recording and fault waveform recording.
Disturbance recording is initiated by fault detection.
The protective device can store up to 256 records of fault report in non-volatile memory. If a new
fault occurs when 64 faults have been stored, the first type of fault report will be overwritten, and
then the oldest fault report will overwritten by the latest one if another new fault report is generated
againt.
Sequence number
Each operation will be recorded with a sequence number in the report and displayed on LCD
screen.
The time resolution is 1ms using the relay internal clock synchronized via GPS if connected.
Initiating date and time is when a protective fault detection operates.
Operating time
An operating time (not including the operating time of output relays) is recorded in the report.
Faulty phase
Fault location
To get accurate result of fault location, the following settings shall be set correctly:
protective elements
The protective device can save 6 pieces of fault waveform. If a new fault occurs when 6 fault
waveform records have been stored, the oldest waveform of the type-A fault report will be
overwritten at first, if no the type-A fault report exist then the oldest waveform of the type-B fault
report will be overwritten.
6.1 General
RCS-931 relay is made of a 4U height 19” chassis for panel flush mounting. Components mounted
on its front include a 320×240 dot matrix LCD, a 9 button keypad, 10 LED indicators, a 9 pin
connector for communication with PC and a 15 pin connector for analog inputs by HELP-90A
during commissioning. A monolithic micro controller is installed in the protective device for these
functions. The front view is shown as Figure 6.1-1.
GRP
ESC
The 10 LED indicators are, from top to bottom, “HEALTHY” (Operation indicator), “ALARM”
(Alarm indicator), “TRIP A, TRIP B and TRIP C” (Three-phase tripping indicators), “RECLOSE”
(Auto-reclosing indicator), and “LED 1, LED2, LED3 and LED4” (User-defined indicators). The
LED1~LED4 can be set freely by user based on the project requirement. As to buttons of the
keypad, “ENT” (Enter/Execute), “GRP” (Group number) and “ESC” (Cancel/Exit).
RCS-931 comprises following 13 plug-in modules. Figure 6.1-2 is rear view of the equipment and
shows disposition of these modules.
1
PWR
DC POWER 101
+
DC POWER 102
-
DC 101
103 From DC power supply 5V
DC 102
DC/DC ±12V
Opto-
coupler 104 24V
+24V
Note!
When ordering, please mark the input voltage class of DC power supply.
I A , I B , I C and 3I 0 are phase current and zero sequence current input to AC input module
separately with rating 5 A or 1 A. Terminal 201, 203, 205 are polarity marks. It is assumed that
polarity mark of CT installed on line is at line side.
3I 0 shall be connected to the equipment, otherwise all relevant zero sequence current protection
will be disabled. Maximum linear range of the current converter is 30 In. Figure 6.2-2 shows rear
view and typical connection of AC input module.
2
A
AI TA
B 52
IA 201 IA’ 202 C
VT
IB 203 IB’ 204
CURRENT
Isolating Transformer
Isolating Transformer
201
IA Ux
I0 207 I0' 208 UA 213
209 To LPF
202 214
UA 209 UB 210
203
IB
210
UB To LPF
To LPF
204
VOLTAGE
UC 211 UN 212
205
IC
211
UC
Ux 213 Ux’ 214 206
207
3I0
212
215 Ground
208
U A , U B , and U C are phase voltage input to AC input module. U X is the line voltage, it could
be any phase-ground voltage or phase-phase voltage, and terminal 213 is the polarity mark. If the
auto-reclosing is disabled or enabled but without any check, the voltage U X could be
disconnected. Terminal 215 is ground point. It shall be connected to ground bus.
RX RX
TX TX
RX
TX
Event recorder, fault oscillograph recorder (could be printed via serial port)
Sampling rate of the equipment is 24 point per cycle. Parallel real time data is calculated for
algorithm and logic of protection at every sampling point. So very high inherent reliability and
security are ensured to the equipment.
An optical transceiver is installed in this module. It exchanges AC current data and status signal
with remote end via 64 kbit/s or 2048kbit/s dedicated optical channel or multiplex PCM equipment.
Figure 6.2-5 Rear view of type A and external connections of COM module
Figure 6.2-6 Rear view of type B and external connections of COM module
Figure 6.2-7 Rear view of type D and external connections of COM module
RS-485/
Type Ethernet Ethernet Ethernet Ethernet RS-485 RS-485
RS-232
1 RS-485A
To local PC for debugging
2 RS-485B
Twisted pair Twisted pair Twisted pair Twisted pair Twisted pair Twisted pair Twisted pair
3 RS-485GND Physical Layer
wire wire wire wire wire wire wire
4 RS-485A
To GPS for clock synchronism
5 RS-485B
6 RS-485GND
7 Printer RX
To printer or controller
8 Printer TX
9 Printer Ground
Type E
Figure 6.2-8 Rear view of type E and external connections of COM module
All ports used to communicate with the SCADA system or RTU support IEC60870-5-103 protocol,
moreover, Ethernet port in COM modules of type E also supports IEC61850. From Figure 6.2-5 to
Figure 6.2-8 shows rear view of these types and their external connections.
All types are equipped with a RS-485 port for debugging and it can be connected with local PC for
setting and testing via the software RCSTool_900 (need an additional converter to make the
RS-485 port be changed into RS-232 port).
All types are equipped with a RS-485 port for receiving second pulse signal (PPS-pulse per
second) from GPS and a port for printer. Printer port could be configured as RS-232 or RS-485 by
setting corresponding jumpers on the PCB (RS-232 default). If logic setting [En_Net_Print] is set to
“1” , printer port must be set as RS-485. Transmission rate of printer port can be set by the setting
[Printer_Baud] and should be the same with baud rate of the printer.
Note:
For the port used to printer or controller, it can be configured as RS-485 or RS-232 by setting
corresponding jumper of module COM. The port is configured as RS-232 by shorting PIN 1 and
PIN 2 and as RS-485 by shorting PIN 2 and PIN 3. As shown in Figure 6.2-9
1. Receiving PPS (pulse per second) and PPM (pulse per minute) via external contact
It is used to trigger printing latest report when the equipment is configured as manual printing
mode by logic setting [En_Auto_Print]=0. The printer button is located on the panel usually. If the
equipment is configured as automatic printing mode ([En_Auto_Print]=1), report will be printed
automatically as soon as it is formed.
It is used to receive clock synchronism signal from GPS or other equipment used clock
synchronism. When setting [GPS_Pulse] is set to “1”, the equipment receives PPM (pulse per
minute), otherwise, receives PPS (pulse per second). Clock synchronism via RS485 bus is
recommended. Only one of them can be selected. If clock synchronism via RS485 bus is selected,
terminal 604 need not be connected.
It is used to reset latching signal relay. It can be done by pressing a button on the panel or by
remote command via communication channel.
It is used to block monitoring direction communication. A link located on the panel is used for that.
When the equipment is in maintenance or commissioning status, this link should be closed. All of
the reports will not be sent via communication port then, but local displaying and printing are still
working. This link should be open during normal operation condition.
Table 6-2 shows the relation between the state of binary input and AR mode.
Note!
When logic setting [En_SetOpt_AR] is set to “1”, the binary inputs [EBI_Opt1_AR] and
It is used to initiate blocking auto-reclosing and tripping three-phase circuit breaker even if
single-phase fault occurs in the line.
It is auxiliary switch contact of phase A circuit breaker, which is provided by interposing relay. (For
example, CZX-12R)
Note!
contacts, which will drop off after external protection returning immediately. If AR of the
protection equipment is disabled or 52b is used to initiate AR, the two terminals need not
be connected.
Figure 6.2-10 shows rear view and external connections of BI(#6) module.
It is auxiliary switch contact of phase B circuit breaker, which is provided by interposing relay. (For
example, CZX-12R)
It is auxiliary switch contact of phase B circuit breaker, which is provided by interposing relay. (For
example, CZX-12R)
It is used to block auto-reclosing when low pressure for reclosing. If auto-reclosing of protective
device is disabled, the terminal need not be connected.
It is used to send transfer trip to remote protective device to inter-trip remote circuit breaker
through the channel.
Terminals 714, 716, 718, 720, 722, 724and 726 are reserved binary input.
Figure 6.2-11 shows rear view and external connections of BI(#7) module.
8 LOCAL SIGNAL
SIG 02
BSJ_1
COM1 802 801 04
BJJ_1
BSJ_1 804 803 06
BJJ_1 806 805 REMOTE SIGNAL
COM2 808 807 08
BSJ_2
BSJ_2 810 809 10
BJJ_2
BSJ_2 812 811 12
COM3 814 813 BREAKER FAILURE INITIATION
BO_BFI_A_1 816 815 14
BO_BFI_A_1
BO_BFI_B_1 818 817 16
BO_BFI_B_1
BO_BFI_C_1 820 819 18
BO_BFI_C_1
COM4 822 821 20
BO_BFI_A_2 824 823 22
BO_BFI_A_2
BO_BFI_B_2 826 825 24
BO_BFI_B_2
BO_BFI_C_2 828 827 26
BO_BFI_C_2
830 829 28
9 TRIP/CLOSING TRIP
BO 02 20
TJA_1 TJA_4
COM2 902 COM1 901 05 19
TJB_1 TJB_4
COM3 904 903 07 21
TJC_1 TJC_4
906 TJA_1 905 09 22
TJA_2 908 TJB_1 907 04 TRIP
TJA_2
TJB_2 910 TJC_1 909 08 24
TJB_2 TJA_5
TJC_2 912 HJ_1 911 10 23
TJC_2 TJB_5
914 913 12 25
TJC_5
COM4 916 TJA_3 915 01 26
HJ_1
TJC_3 918 TJB_3 917 11 REMOTE SIGNAL
COM5 920 TJA_4 919 CLOSING 2 16
TJA_3
TJC_4 922 TJB_4 921 15
TJB_3
COM6 924 TJA_5 923 17
TJC_3
TJC_5 926 TJB_5 925 18
HJ_2 928 HJ_2 927 29 27
HJ_3 HJ_2
HJ_3 930 HJ_3 929 30 28
The first BO module provides five groups of phase-segregated trip contacts and three groups of
auto-reclosing contacts, which are all instantaneous operating contact. The normally open contact
902~905, 902~907, 902~909 and 901~911, are connected with the first group of tripping coil and
closing coil of interposing relay to trip and close circuit breaker respectively, for example, CZX-12R.
Others are used as remote signal, to initiate fault recorder and to initiate circuit breaker failure
protection. If there are two circuit breakers needed tripped, for example, 3/2 breaker arrangement,
the normally open contact 904~908, 904~910 and 904~912 are used to trip the second circuit
breaker.
TJ is an auxiliary tripping relay. It operates when the equipment trips (single-pole tripping or
three-pole tripping). It can be connected to binary input [BI_ExTrp1P_AR] of other protection
equipment to initiate AR.
TDGJ is channel alarm relay with normally closed contacts. When the equipment does not receive
the signal from remote end, data frame is abnormal during transmitting, the settings related with
channel of equipments on two ends are wrong (including [Equip_ID], [ID_Local], [ID_Remote] and
[En_InnClock]) or error rate of channel is higher than 0.1 percent, 2 TDGJ contacts are all closed.
YC1 and YC2 are remote status signal relay. They will operate if remote status signal is received.
At local terminal, when binary input [BI_Send_TS1] or [BI_Send_TS2] is energized, a binary signal
will be sent to remote terminal. At remote terminal, when such a binary signal received, binary
input state of [BI_Recv_TS1] or [BI_Recv_TS2] will change to 1, and corresponding binary output
contacts [YC] will close.
TJABC is an auxiliary tripping relay. It operates when the equipment 3-pole tripping. It can be
connected to binary input [BI_ExTrp3P_AR] of other protection equipment to initiate AR.
BCJ is an auxiliary blocking closing relay. It operates when the equipment trips and the condition
of blocking AR is met at the same time.
TJ, TJABC and BCJ all output two sets of contacts to other protection equipments.
At present, the last group (two pairs) of output contacts ( BO25_1, BO25_2) are configurable.
Extended #C BO module can provides 7 groups of normally open contacts and 2 contacts without
common terminal for each group. Extended #D BO module can provides 6 groups of normally
open contacts and 2 contacts without common terminal for each group. All the contacts are
configurable.
Chapter 7 Settings
The protection device has 15 setting groups for protection to coordinate with the different mode of
power system operation, one of which is assigned to be active. However, the equipment
parameters and the communication parameters are common for all protection setting groups.
Note!
All current settings in this chapter are secondary current converted from primary current
by CT ratio. Zero sequence current or voltage setting is configured according to 3I0 or 3U0 and
negative sequence current setting according to I2 or U2.
1. Active_Grp
This setting means current active group of setting. Fifteen setting groups are provided to select,
group number from 0 to 14. Equipment parameters are shared for 15 setting groups.
2. Language
This setting is used to select the LCD display language. User can select “0”-Chinese, “1”-English
and “2”-the third-party language (local language of the area used).
3. Equip_ID
This setting means the identity of substation or plant. It can be set as a character string which is
made of 16 characters at most.
4. En_Remote_Cfg
This setting is used to determine whether the protection settings can be modified remotely via
SCADA or RTU. “1” means that settings can be remotely configured via SCADA or RTU, otherwise,
it should be set to “0”.
1. Comm_Addr
It is the communication address between the protection device with the SCADA or RTU via
RS-485.
2. COM1_Baud
3. COM2_Baud
The baud rate of rear RS-485 communication port 2. It is recommended that the baud rate of rear
RS-485 communication port 2 is set as “57600” which will be connected with local PC via an
additional converter for debugging.
4. COM1_Protocol
2: Modbus protocol
3: DNP protocol
5. COM2_Protocol
6. Printer_Baud
It is the baud rate of printer port, which should be as same as the baud rate of printer.
7. Debug_Baud
It is the baud rate of front communication port for setting and testing via the software
RCSTool_900.
8. TimeZone
It is applied to communication function of IEC 61850, which should be set according to the time
zone of Greenwich Mean Time.
9. ID_SourceStation_Net
It is the communication address between the protection device with the SCADA or RTU via
Ethernet based on IEC 60870-5-103 protocol.
10. ID_Server_SNTP
It is the communication address of SNTP server which provides time reference based on IEC
61850 protocol.
11. IP_Addr_Net1/IP_Addr_Net2/IP_Addr_Net3/IP_Addr_Net4
They are IP address of Ethernet 1, Ethernet 2, Ethernet 3 and Ethernet 4 respectively. They are
applied to communication based on IEC 60870-5-103 protocol via Ethernet or IEC 61850 protocol.
12. Subnet_Mask_Net1/Subnet_Mask_Net2/Subnet_Mask_Net3/Subnet_Mask_Net4
They are subnet mask of Ethernet 1, Ethernet 2, Ethernet 3 and Ethernet 4 respectively.
13. GateWay_Local_Net1/GateWay_Local_Net2/GateWay_Local_Net3/GateWay_Local_Net
They are gateway of Ethernet 1, Ethernet 2, Ethernet 3 and Ethernet 4 of local substation
respectively. When the protection device communicates with master station of relay protection
directly not via protection management unit, they are applied to communication based on IEC
60870-5-103 protocol via Ethernet.
14. GateWay_Remote_Net1/GateWay_Remote_Net2/GateWay_Remote_Net3/GateWay_Re
mote_Net4
They are gateway of Ethernet 1, Ethernet 2, Ethernet 3 and Ethernet 4 of remote substation
respectively. When the protection device communicates with master station of relay protection
directly not via protection management unit, they are applied to communication based on IEC
60870-5-103 protocol via Ethernet.
15. En_Router_Net1/En_Router_Net2/En_Router_Net3/En_Router_Net4
When the protection device communicates with master station of relay protection directly not via
protection management unit, they are used to determine whether communication route pass a
router based on IEC 60870-5-103 protocol via Ethernet.
16. En_Iec103_Inf
When spontaneous events are sent via generic services based on IEC 60870-5-103 protocol, this
setting should be setting as “0”. When spontaneous events are sent in the format of FUN and INF
based on IEC 60870-5-103 protocol, this setting should be set as “1”.
17. En_Auto_Print
When this setting is set as “1”, the protection device will print automatically the latest fault report
generated after the protection device forms a new disturbance recorder.
18. En_CommTest
1. Fn
2. U1n
3. U2n
4. I1n
5. I2n
6. En_LineVT
If three-phase voltage used for protection measurement comes from line side (for example, 3/2
breaker), it should be set as “1”. If three-phase voltage comes from busbar side, it should be set as
“0”.
Default
No. Parameter Setting Range Notes/Comments
Setting
Setting of DPFC current fault
detector
1 Ipp_Incr_FD 0.02~30 A×IN 0.2In
(Detects the magnitude change of
Phase-Phase Current)
Setting of zero sequence current
2 I_ROC_FD 0.02~30 A×IN 0.2In
fault detector
Impedance setting of DPFC
3 Z_DPFC 0.5~37.5Ω/IN 5
distance element
Current ratio factor of CT
Larger CT Ratio used as Reference
4 K_CT 0.25~1.00 1 CT
K_CT = 1
K_CT (Remote) = CT Ratio
Default
No. Parameter Setting Range Notes/Comments
Setting
(Remote) Reference CT
High setting of differential current
element
5 I_H_Diff 0.04~30 A×IN 2In
(Setting for Stage 1 DPFC &
Steady State Diff Elements)
Low setting of differential current
element
6 I_L_Diff 0.04~30 A×IN 0.9In
(Setting for Stage 2 DPFC &
Steady State Elements)
Differential current for CT circuit
failure
7 I_Diff_CTS 0.04~30 A×IN 3In (Only activated when Alm_CTS OR
Alm_Diff is asserted and with
En_CTSBlkDiff = 0
The ID of local equipment
8 ID_Local 0~65535 1
(Local Relay Address)
The ID of remote equipment
9 ID_Remote 0~65535 2
(Remote Relay Address)
Zero sequence compensation
10 K0 0~10 0.6
factor
Current setting for power swing
11 I_OC_PSBR 0.02~30 A×IN 1In
detecting
Zone 1 of phase-to-ground
12 Z_PG1 0.05~200Ω/IN 5
distance element
Time delay of zone 1
13 t_Z1 0.0~100s 0 phase-to-ground and
phase-to-phase distance element
Zone 2 of phase-to-ground
14 Z_PG2 0.05~200Ω/IN 8
distance element
Time setting of zone 2 of
15 t_PG2 0.0~100s 0.5
phase-to-ground distance element
Zone 3 of phase-to-ground
16 Z_PG3 0.05~200Ω/IN 12 distance element
(Not Used)
Time setting of zone 3 of
17 t_PG3 0.0~100s 2
phase-to-ground distance element
Zone 1 of phase-to-phase distance
18 Z_PP1 0.05~200Ω/IN 5
element
Zone 2 of phase-to-phase distance
19 Z_PP2 0.05~200Ω/IN 8
element
Time setting of zone 2 of
20 t_PP2 0.0~100s 0.5
phase-to-phase distance element
Zone 3 of phase-to-ground
21 Z_PP3 0.05~200Ω/IN 12
distance element
Time setting of zone 3 of
22 t_PP3 0.0~100s 2
phase-to-ground distance element
Forward impedance setting of
23 Z_Fwd_Rev 0.05~200Ω/IN 1
reversal distance element
Default
No. Parameter Setting Range Notes/Comments
Setting
Reverse impedance setting of
24 Z_Rev_Rev 0.05~200Ω/IN 2
reversal distance element
Time setting of reverse distance
25 t_Rev 0.0~100s 2
element
15 Restrict impedance of the reach of
26 R_Blinder 0.05~200Ω/IN
distance element
Resistance setting of zone 1 of
27 R1_Quad 0.05~200Ω/IN 8 quadrilateral characteristic distance
element
Resistance setting of zone 2 of
28 R2_Quad 0.05~200Ω/IN 20 quadrilateral characteristic distance
element
Resistance setting of zone 3 of
29 R3_Quad 0.05~200Ω/IN 30 quadrilateral characteristic distance
element
Phase angle of positive sequence
30 phi1_Reach 45°~90° 78
line impedance
Phase angle of zero sequence line
31 phi0_Reach 45°~90° 78
impedance
Phase shift of zone 1 and 2
32 phi_Shift_ZPG 0°~30° 0
phase-to-ground distance element
Phase shift of zone 1 and 2
33 phi_Shift_ZPP 0°~30° 0
phase-to-phase distance element
Stage 1 of zero sequence
34 I_ROC1 0.02~30 A×IN 1.3 In
overcurrent element
Time delay of stage 1 of
35 t_ROC1 0.0~100s 0.01
zero-sequence overcurrent element
Stage 2 of zero sequence
36 I_ROC2 0.02~30 A×IN 1.2 In
overcurrent element
Time setting of stage 2 of zero
37 t_ROC2 0.01~100s 0.5
sequence overcurrent element
Stage 3 of zero sequence
38 I_ROC3 0.02~30 A×IN 0.8 In
overcurrent element
Time setting of stage 3 of zero
39 t_ROC3 0.01~100s 2
sequence overcurrent element
Stage 4 of zero sequence
40 I_ROC4 0.02~30 A×IN 0.6 In
overcurrent element
Time setting of stage 4 of zero
41 t_ROC4 0.01~100s 5
sequence overcurrent element
Accelerated stage of zero
42 I_ROC_SOTF 0.02~30 A×IN 1 In
sequence overcurrent element
Threshold multiple of overload
43 ThM_OvLd_Alm 1.00~3.00 1.05
element for alarming
Threshold multiple of overload
44 ThM_OvLd_Trp 1.00~3.00 1.1
element for tripping
45 Ib_OvLd 0.02~10 A×IN 5 In Basic current of overload element
46 t_Disspt_OvLd 0.1~100s 6 Time constant of inverse-time
Default
No. Parameter Setting Range Notes/Comments
Setting
overload element
Phase overcurrent for VT circuit
47 I_OC_VTS 0.02~30 A×IN 2 In
failure
Time setting of phase overcurrent
48 t_OC _VTS 0.01~100s 0.5
element for VT circuit failure
Zero sequence overcurrent for VT
49 I_ROC_VTS 0.02~30 A×IN 1 In
circuit failure
Time setting of zero sequence
50 t_ROC_VTS 0.01~100s 0.5 overcurrent element for VT circuit
failure
Current setting of stage 1 of phase
51 I_OC1 0.02~30 A×IN 1.3In
overcurrent element
Time setting of stage 1 of phase
52 t_OC1 0.01~100s 0.5
overcurrent element
Time characteristic setting of stage
1 of phase over-current protection
0:definite-time
1: IEC Normal inverse-time
2: IEC Very Inverse
53 Opt_Curve_OC1 0~7 0
3: IEC Extremely Inverse
4: IEC Long-time Inverse
5: ANSI Moderately Inverse
6: ANSI Very Inverse
7: ANSI Extremely Inverse
Current setting of stage 1 of phase
54 I_OC2 0.02~30 A×IN 1.0In
overcurrent element
Time setting of stage 2 of phase
55 t_OC2 0.01~100s 0.5
overcurrent element
Default
No. Parameter Setting Range Notes/Comments
Setting
Voltage threshold for live line/bus
check (phase voltage or
61 V_Live 5V~110V 40
phase-to-phase voltage depends
on the synchronism voltage)
62 t_1P_AR 0.01~600s 1 Time setting of single-pole AR
63 t_3P_AR 0.01~600s 0.8 Time setting of three-pole AR
Time delay of circuit breaker in closed
64 t_CBClsd_AR 0.01~600s 5
state before reclosing
This value should be bigger than maximum variation of load current and typically 0.2 In. For line
with wide variation of load current like those for electric railway, heavy rolling mill or
aluminum-smelting, the setting should be increased properly so that frequent pickup of the
equipment could be avoided.
2) I_ROC_FD
It shall be greater than maximum zero-sequence unbalance current. Setting it based on same
primary current on both ends.
3) Z_DPFC
The setting of DPFC distance element: it shall be 80~85% impedance of whole line.
4) K_CT
CT ratio correction
The ratio of CTs on two terminals of the line could be different. it could be corrected by the setting
[k_CT].
Setting principle: Suppose CT ratio, Terminal M: kM=IM1n : IM2n; Terminal N: is and kN=IN1n : IN2n
IM1n: primary rated current of terminal M, IM2n: secondary rated current of terminal M
IN1n: primary rated current of terminal N, IN2n: secondary rated current of terminal N
Terminal M: [K_CT]=1.00
For example:
5) I_H_Diff
Set it not less than 4 times of capacitive current and usually not less than 0.2 In. Sensitivity of this
setting should be checked by short circuit current of internal fault. Setting it based on same
primary current on both ends.
6) I_L_Diff
Set it not less than 1.5 times of capacitive current and usually not less than 0.1 In. Sensitivity of
this setting should be checked by minimum short circuit current of internal fault. Setting it based on
same primary current on both ends.
7) I_Diff_CTS
The operating value of the differential protection when it is not blocked by CTS.
Used to confirm that equipments at both ends of line are compatible. The end of which setting
[ID_Local] should be same as the [ID_Remote] of the other and the greater [ID_Local] between
the two ends is chosen as a master end for sampling synchronism, the other is a slave end. If the
setting [ID_Local] is set as same as [ID_Remote], that means the equipment in loopback testing
state.
9) K0
Setting principle: K0 = (Z0L–Z1L)/3Z1L, where Z0L and Z1L are zero and positive sequence
impedance of the line respectively. Actual measurement value is suggested adopted, but
calculated value with 0.05 subtracted from can also be used if there is not actual measurement
value.
10) I_OC_PSBR
This current setting should be greater than maximum load current of the line.
11) Z_PG1
Setting of this zone should be 0.8~0.85 times the impedance of the line and should be decreased
properly for line with mutual inductance.
12) Z_PP1
Setting of this zone should be 0.8~0.85 times the impedance of the line.
13) Z_PG2, Z_PG3, Z_PP2, Z_PP3, t_PG2, t_PG3, t_PP2 and t_PP3
Setting of the impedance and time delay of these zones should meet requirements between
various zones and operation should be ensured even for fault at end of the line.
14) Z_Rev
15) t_Rev
Setting principle: it should meet requirement between zone 3 distance element and busbar
protection.
16) R_Blinder
It should be less than the minimum impedance measured during heavy load conditions
17) phi_Shift_ZPG
Phase shift of zone 1 and 2 phase-to-ground distance element. Recommended value: 30°for
length of the line < 10 km, 15°for length ≥10 km and 0°for length ≥40 km.
18) phi_Shift_ZPP
Phase shift of zone 1 and 2 phase-to-phase distance element. Recommended value: 30°for length
of the line < 2 km, 15°for length ≥2 km and 0°for length ≥10 km.
Phase angle of positive and zero sequence impedance of the line. Set as they should be.
21) I_ROC_SOTF
This setting should ensure sufficient sensitivity to ground fault at end of the line.
22) ThM_OvLd_Alm
23) ThM_OvLd_Trp
When line is overload, if percentage of allowable thermal capacity is greater than [ThM_OvLd_Trp],
overload protection operates to trip circuit breaker. For example, 1.1 (corresponding with 110%)
24) Ib_OvLd
It is allowable overload current, i.e., IB of IEC 60255-8 thermal characteristic (please refer to 3.3.6).
It is critical value corresponding with maximum thermal capacity which can be permitted to be in
service for a long time.
25) t_Disspt_OvLd
26) I_OC_VTS
27) I_ROC_VTS
28) t_OC/ROC_VTS
Time setting of phase and zero sequence overcurrent elements for VTS.
29) I_OC1
30) t_OC1
31) Opt_Curve_OC1
Time characteristic setting for stage 1 of phase overcurrent protection while definite-time
characteristic and seven kinds of inverse-time characteristics can be chose. According to
IEC60255-3 standard, four kinds of IEC inverse-time characteristics and three kinds of ANSI/IEEE
inverse-time characteristics are provided to choose from. It can be shown in the following table.
Opt_Curve_OC1 k α c
0: definite-time - - -
1: IEC Normal Inverse-time characteristic 0.14 0.02 0
2: IEC Very Inverse-time characteristic 13.5 1 0
3: IEC Extremely Inverse-time characteristic 80 2 0
4: IEC Long-time Inverse-time characteristic 120 1 0
5: ANSI Moderately Inverse-time characteristic 0.0515 0.02 0.114
6: ANSI Very Inverse-time characteristic 19.61 2 0.0185
7: ANSI Extremely Inverse-time characteristic 28.2 2 0.1217
32) I_OC2
Current setting of stage 2 of phase overcurrent protection element
33) t_OC2
Time setting of stage 2 of phase overcurrent protection element
34) phi_Diff_SynChk
35) f_Diff_SynChk
36) V_Diff_SynChk
38) t_Unsuc_AR
39) t_Wait_SynChk
40) t_PW_AR
Positive sequence and zero sequence reactance and resistance of the line. Parameter of the
transmission line, used for calculation of fault location.
For EHV long line, capacitive current of line is very great, so capacitive current compensation must
be adopted. It is worth of attention that XC1L must be less than XC0L. Table 7-3 can be as a
reference.
Table 7-3 Capacitive impedance and current of overhead per 100KM based on different
voltage
However, when capacitive current of line is less than 0.1In, capacitive current compensation is
disabled automatically. XC1L and XC0L can be set according to the following rule.
X C1 = 580Ω ( I N = 1A ), X C 0 = 840Ω ( I N = 1A ) or
X C1 = 116Ω ( I N = 5 A ), X C 0 = 168Ω ( I N = 5 A )
If the ratio of CTs on two terminals of the line are different, the terminal setting [K_CT] set to “1”
according to the above rule and the other terminal can be calculated according to CT ratio.
43) LineLength
Total length of the line. The actual total length of the line km, used for calculation of fault location.
Note!
All zero sequence current settings should be greater than that of zero-sequence current
Setting Default
No. Parameter Notes/Comments
Range Setting
0/1 0 Enable DPFC distance protection
1 En_Z_DPFC
(Not Used)
2 En_DiffP 0/1 1 Enable current differential current
Setting Default
No. Parameter Notes/Comments
Range Setting
protection
0/1 1 Enable stage 1 of DPFC current
3 En_DPFC_Diff1
differential element
0/1 1 Enable stage 2 of DPFC current
4 En_DPFC_Diff2
differential element
0/1 1 Enable stage 1 of steady-state current
5 En_Stdy_Diff1
differential element
0/1 1 Enable stage 2 of steady-state current
6 En_Stdy_Diff2
differential element
0/1 1 Enable zero-sequence current
7 En_REF
differential element
0/1 1 Enable zero-sequence current
8 En_CompREF differential element with capacitive
current compensation
0/1 0 Enable differential protection blocked
9 En_CTSBlkDiff during CT circuit failure
(No Blocking when CT Fail)
0/1 1 Enable inner clock
10 En_InnClock - Set to 0 for G.703
- Set to 1 for Direct Fiber
0/1 0 Transfer tripping controlled by local fault
detector
11 En_FD_Ctrl_TT (For local relay fault detector check
when receive transfer trip from remote
end)
0/1 1 Transfer tripping signal from remote end
12 En_RTrValid is valid
(To Enable transfer trip function)
0/1 1 Enable power swing blocking for zone
13 En_PSBR_Z1/2
1,2 of distance element
0/1 0 Enable power swing blocking for zone 3
14 En_PSBR_Z3
of distance element
0/1 1 Enable zone 1of phase-to-ground
15 En_ZPG1
distance element
0/1 1 Enable zone 2 of phase-to-ground
16 En_ZPG2
distance element
0/1 1 Enable zone 3 of phase-to-ground
17 En_ZPG3
distance element
0/1 1 Enable zone 1of phase-to-phase
18 En_ZPP1
distance element
0/1 1 Enable zone 2 of phase-to-phase
19 En_ZPP2
distance element
Setting Default
No. Parameter Notes/Comments
Range Setting
0/1 1 Enable zone 3 of phase-to-phase
20 En_ZPP3
distance element
0/1 Enable phase-to-ground reversal
21 En_ZPG_Rev 1
distance element
0/1 Enable phase-to-phase reversal
22 En_ZPP_Rev 1
distance element
0/1 Enable restrict impedance measured of
23 En_Blinder 1
line load
0/1 Enable zone 1 of quadrilateral
24 En_ZPG1_Quad 1
phase-to-ground distance protection
0/1 Enable zone 2 of quadrilateral
25 En_ZPG2_Quad 1
phase-to-ground distance protection
0/1 Enable zone 3 of quadrilateral
26 En_ZPG3_Quad 1
phase-to-ground distance protection
0/1 Enable the function of binary input for
27 En_BI_Z1_Vld 1 enabling/disabling zone 1 of distance
protection
28 En_Z_SOTF 0/1 1 Enable distance element for SOTF
0/1 0 Enable zone 2 of distance element for
29 En_Z2SOTF_AR3P SOTF is not blocked by power swing
when 3-pole auto-reclosing.
0/1 0 Enable zone 3 of distance element for
30 En_Z3SOTF_AR3P SOTF is not blocked by power swing
when 3-pole auto-reclosing.
0/1 0 Enable stage 1 of zero sequence
31 En_ROC1
overcurrent element
0/1 0 Enable stage 2 of zero sequence
32 En_ROC2
overcurrent element
0/1 1 Enable stage 3 of zero sequence
33 En_ROC3
overcurrent element
0/1 1 Enable stage 4 of zero sequence
34 En_ROC4
overcurrent element
0/1 1 Enable direction controlling function to
35 En_Dir_ROC1 stage 1 of zero sequence overcurrent
element
0/1 1 Enable direction controlling function to
36 En_Dir_ROC2 stage 2 of zero sequence overcurrent
element
0/1 1 Enable direction controlling function to
37 En_Dir_ROC3 stage 3 of zero sequence overcurrent
element
38 En_Dir_ROC4 0/1 1 Enable direction controlling function to
Setting Default
No. Parameter Notes/Comments
Range Setting
stage 4 of zero sequence overcurrent
element
0/1 1 Enable zero-sequence element for
39 En_ROC_SOTF
SOTF
0/1 1 Enable stage 1 of thermal overload
40 En_OvLd1_Alm
element for alarming
0/1 1 Enable stage 2 of thermal overload
41 En_OvLd2_Alm
element for alarming
0/1 0 Enable stage 2 of thermal overload
42 En_OvLd2_Trp
element for tripping
0/1 1 Enable phase overcurrent element only
43 En_ROC_VTS
if VT fails
0/1 1 Enable phase overcurrent element only
44 En_OC_VTS
if VT fails
0/1 0 Enable alarming function when VT
45 En_VTS
circuit fails
0/1 0 Enable stage 1 of phase overcurrent
46 En_OC1
protection
0/1 0 Enable stage 2 of phase overcurrent
47 En_OC2
protection
0/1 0 Enable three-pole tripping mode
48 En_3P_Trip Set to 1 for 132kV and below
Set to 0 for 275kV and above
0/1 0 Enable synchronism check
49 En_SynChk_AR
(Set 1 for internal SYNC)
0/1 0 Enable dead line and dead bus (DLDB)
50 En_DdB_DdL_AR
check
0/1 0 Enable Dead line and live bus (DLLB)
51 En_LvB_DdL_AR
check
0/1 0 Enable live line and dead bus (LLDB)
52 En_DdB_LvL_AR
check
0/1 1 Enable AR without Voltage and
53 En_NoChk_AR
Syncheck
0/1 1 Enable auto-reclosing(AR)
54 En_AR
(Set 1 for internal AR)
0/1 0 Enable position of circuit breaker to
55 En_CB_Init_AR
initiate AR if no fault detected
0/1 0 Enable AR blocking when Z1 Distance
56 En_Inst_Blk_AR element and Stage 1 Zero Sequence
Overcurrent element operate
0/1 0 Enable auto-reclosing blocked when
57 En_Z2_Blk_AR
zone 2 of distance element operating
0/1 1 Enable auto-reclosing blocked when
58 En_Z3_Blk_AR
zone 3 of distance element operating
Setting Default
No. Parameter Notes/Comments
Range Setting
En_ROC2/3_Blk_A 0/1 0 Enable recloser blocked when stage 2,3
59 zero-sequence overcurrent element
R operating
0/1 1 Enable recloser blocked when stage 4
60 En_ROC4_Blk_AR zero-sequence overcurrent element
operating
0/1 1 Enable auto-reclosing blocked when
61 En_PhSF_Blk_AR
fault phase selection fails
0/1 1 Enable auto-reclosing blocked in pole
62 En_PDF_Blk_AR
discrepancy condition
0/1 1 Enable auto-reclosing blocked when
63 En_MPF_Blk_AR
multi-phase fault happens
0/1 1 Enable select auto-reclosing mode by
logic setting
- Set 0 for AR mode selection using
external switch
- Set 1 for AR mode selection using
settings.
Refer to table below for logic setting:
Binary [EBI_Opt1 [EBI_Opt
64 En_SetOpt_AR input _AR] 2_AR]
1-pole
0 0
AR
3-pole
1 0
AR
1-pole/3
-pole 0 1
AR
OFF 1 1
0/1 1 Enable 1-pole auto-reclosing mode
65 En_1P_AR
(Only use when En_SetOpt_AR = 1)
0/1 0 Enable 3-pole auto-reclosing mode
66 En_3P_AR
(Only use when En_SetOpt_AR = 1)
0/1 0 Enable 1/3-pole auto-reclosing mode
67 En_1/3P_AR
(Only use when En_SetOpt_AR = 1)
1: enable
0: disable
For short transmission line, if the secondary value of line impedance is less than 1/IN, DPFC
distance protection should be disabled.
2) En_DiffP
1: enable
0: disable
3) En_DPFC_Diff1
4) En_DPFC_Diff2
1: enable
0: disable
5) En_Stdy_Diff1
1: enable
0: disable
6) En_Stdy_Diff2
1: enable
0: disable
7) En_REF
8) En_CompREF
1: enable
0: disable
Note!
invalid.
9) En_CTSBlkDiff
If this setting is set as “1”, current differential protection shall be blocked during CT circuit failure.
10) En_InnClock
If the setting is set as “1”, inner clock is used. Please refer to 3.3.2.10.
11) En_FD_Ctrl_TT
If the setting is set as “1”, transfer tripping controlled by local fault detector. Local trip circuit could
be active by remote command (i.e. [BI_Recv_TT]=1) only when local fault detector initiates. if do
not use transfer tripping, the setting should be set to “1”.
12) En_RTrValid
If it is set as “1”, after tripping signal from remote end is received, associated with low percentage
differential criterion and low threshold value, local protective device will operate. If it is set as “0”,
tripping signal from remote end does not affect local protective device.
13) En_PSBR_Z1/2
The function of power swing blocking for zone 1,2 distance element;
“0”: disable; zone 1,2 of distance element is not controlled by PSBR element, and power swing
blocking for zone 1,2 of distance element is released all along.
14) En_PSBR_Z3
“0”: disable; zone 3 of distance element is not controlled by PSBR element, and power swing
blocking for zone 3 of distance element is released all along.
The zone 1(2, 3) of phase-to-ground distance element enabled and zone 1(2, 3) of
phase-to-phase distance relay enabled, if these setting are set to “1”, in the same time, virtual
binary input [VEBI_DistP] should be set as “1”. If none of them is met, the distance protection shall
be disabled.
16) En_ZPG_Rev
“1”: enable;
“0”: disable;
17) En_ZPP_Rev
“1”: enable
“0”: disable
18) En_Blinder
“1”: enable
“0”: disable
19) En_Z_SOTF
“1”: enable;
“0” disable;
If the setting is set as “1”, zone2 or 3 of distance element for auto-reclosing SOTF is not blocked
by power swing. If logic setting [En_Z2SOTF_AR3P] and [En_Z3SOTF_AR3P] are set as “0”,
zone 2 of distance element which is blocked by power swing will operate to trip three-phase circuit
breaker when 3-pole auto-reclosing.
If these settings are set as “1”, stage 1, 2, 3 and 4 of zero sequence overcurrent protection can be
enabled.
If the setting is set as “1”, the direction controlling function to stage 1 ~ 4 of zero sequence
overcurrent element is enabled.
23) En_ROC_SOTF
“1”: enable;
“0”: disable;
24) En_OvLd1_Alm
“1”: enable;
“0”: disable;
25) En_OvLd2_Alm
“1”: enable;
“0”: disable;
26) En_OvLd2_Trp
“1”: enable;
“0”: disable;
27) En_OC_VTS
“0”: disable;
28) En_ROC_VTS
“0”: disable;
29) En_VTS
“1”: enable;
“0”: disable;
30) En_OC1
If this setting is set as “1”, stage 1 of phase overcurrent protection can be enabled.
31) En_OC2
If this setting is set as “1”, stage 2 of phase overcurrent protection can be enabled.
32) En_3P_Trip
If it is set as “1”, three-pole tripping will be implemented for any fault but AR is not blocked.
33) En_AR
If the setting is set as “1”, and all conditions of lockout auto-reclosing are not met, auto-reclosing
enabled.
34) En_SynChk_AR:
1: enable
0: disable
35) En_LvB_DdL_AR:
1: enable
0: disable
36) En_DdB_LvL_AR:
1: enable
0: disable
37) En_DdB_DdL_AR:
1: enable
0: disable
38) En_CBInit_AR
If the setting is set as “1”, AR will be initiated by position of circuit breaker. Please refer to 3.1.3.
39) En_INTS_Blk_AR
Enable AR blocking when Z1 Distance element and Stage 1 Zero Sequence Overcurrent element
operate
“1”: enable
“0”: disable
40) En_Z2_Blk_AR
“1”: enable;
“0”: disable;
41) En_Z3_Blk_AR
“1”: enable;
“0”: disable;
42) En_ROC2/3_Blk_AR
The function of auto-reclosing blocked when stage 2,3 of zero-sequence overcurrent element
operating;
“1”: enable;
“0”: disable;
43) En_ROC4_Blk_AR
“1”: enable
“0”: disable
44) En_PhSF_Blk_AR
If the settings is set as “1”, AR should be blocked when fault phase selection fails.
45) En_PDF_Blk_AR
46) En_MPF_Blk_AR
47) En_SetOpt_AR
When the setting is set as “1”, AR mode can be selected by logic settings [En_1P_AR], single-pole
AR, [En_3P_AR], three-pole AR, and [En_1/3P_AR], single-pole and three-pole AR. Conversely, if
it is set as “0”, AR mode can be selected by switch on the panel. Please refer to Table 6-2.
If these setting are set as “1”, corresponding AR mode is selected. Please refer to setting
[En_SetOpt_AR].
Except for virtual binary input [VEBI_LockOut], logic relation between these virtual binary inputs
mentioned in the table and corresponding logic setting is AND. If it is set as 1, auto-reclosing will
be locked out. It should be set as 0 generally.
This chapter will introduce the human machine interface, the menu tree structure and the LCD
display, and other related functions, as well as how to realize the setting input, browse the
message and other operations by the keyboard operation.
8.1 Overview
The human machine interface function is undertaken by a dedicated human machine interface
module, which can extract some information that users shall pay attention to, or illuminate some
indicator lights or display the information in the LCD. Users can locate some interesting
information by the keyboard navigation.
LCD Display
The device is equipped with a LCD display with the dot matrix 320×240, used for the observation,
monitoring, failure analysis and setting of the settings. If there is the tripping report and alarm
information, the responding message will be displayed in the LCD.
Indicators
Keyboard
GRP
ESC
1. LCD display
2. Signal indicators
8.1.1 Keyboard
1. ”ESC”
Escape operation
2. ”ENT”
Execute operation
3. ”Group number”
Page up/down
Page up/down
After the protection device is powered on to activate, if the device works normally, the “HEALTHY”
indicator light shall always be in the lighting status. Only when serious failures are incurred (for
example, the chip is damaged, the error takes place for the setting check, etc.), the “HEALTHY”
indicator light will go out, and the protection device will be blocked.
After the protection device is powered on to activate, the “ALARM” indicator light shall not be lit under
normal condition. Only when the device detects the abnormality, this signal indicator light will be lit.
When the abnormal condition disappears, this signal indicator light will go out automatically.
After the protection device is powered on to activate, the “TRIP A” indicator light shall not be lit under
normal condition. Only when the protection sends the TRIP A signal, this signal indicator light will be lit.
After the protection device is powered on to activate, the “TRIP B” indicator light shall not be lit under
normal condition. Only when the protection sends the TRIP B signal, this signal indicator light will be lit.
After the protection device is powered on to activate, the “TRIP C” indicator light shall not be lit under
normal condition. Only when the protection sends the TRIP C signal, this signal indicator light will be lit.
After the protection device is powered on to activate, the “RECLOSE” indicator light shall not be lit
under normal condition. Only when the protection issues the RECLOSE signal, this signal indicator
light will be lit.
The four signal indicator lights “LED1-LED4”are of the configurable signal indicator lights, which can
be defined according to the project requirements.
1 2
No. Items
DB9-pin RS232 interface, which communicates with local PC by the assistant
1
software.
2 DB15-pin interface, which is used to connect with the HELP-90A tester.
After the protection device is powered on again, there is no record in shortcut menu. Press “▲” to
go to the main menu as shown in the below Figure:
Main menu
VALUES SETTINGS
FD MEASUREMENT
LOCAL CTRL
PORT MEASUREMENT
RESET TARGET
REPORT
CLEAR CH STATE
CTRL REPORT
CLOCK
BO CHG REPORT
VERSION
BI CHG REPORT
LANGUAGE
ALM REPORT
TEST MODE
TRP REPORT
103 ACC INFO
PRINT
103 GS GROUP
TEST BO REPORT
SETTINGS
TEST BI REPORT
NODE SETTINGS
TEST ALM REPORT
LATEST MODIFIED
TEST TRP REPORT
UNACTIVE SETTING
CTRL REPORT
BO CHG REPORT
BI CHG REPORT
ALM REPORT
TRIP INFO
REPORT LIST
TRP REPORT
ORGNL WAVE
PRESENT WAVE
VALUES
EQUIP DESCRIPTION
Press “▲” to go to the main menu under main screen status, and select the submenu by “▲”, “▼”
and “ENT”. The command menu uses the tree-shape directory structure. The above Figure shows
the whole structure and all submenus of the menu trees for the protection device.
8.2.2 VALUES
This menu is mainly used to show the real-time sampling value and input status of the current and
voltage for the protection device, and can completely reflect the operation environment of the
protection device. If only the display value of these inputs conforms to the actual operation, the
protection device can basically properly operate. The setting of this menu can facilitate to the
debugging and maintenance for the field personnel.
8.2.3 REPORT
This menu is used to show the protection tripping report, self-supervision report, binary input
change report, binary output change report and control report, facilitate the operators to invoke
and view, and take it as the foundation of the accident analysis and the device maintenance. Since
the protection device can provide the power-off holding function, it can still record the protection
action report even though the protection device is powered off. The device can store 256 records
of each type of report.
8.2.4 PRINT
This menu is used to print the device description, self-supervision report, binary input change
report, binary output change report and the information related with settings, fault report and 103
protocol, and so on.
8.2.5 SETTINGS
This menu is used to view all settings of the protection device, including the device parameters,
system parameters, communication parameters, protection setting and enabling binary input
setting, and so on. Furthermore, user can modify any above setting items, and carry out the setting
copy among different setting groups in this submenu.
8.2.7 CLOCK
This menu is used to show or modify current date and time of the protection device.
8.2.8 VERSION
This menu is used to view the program version of various intelligent modules within the protection
device, the program generation time, etc.
8.2.9 LANGUAGE
This menu is used to select the LCD display language. User can select Chinese, English and the
Under normal running condition, LCD will show the screen as follows. LCD takes white color as
the background light. Once there is any keyboard operation, the background light will be activated,
and delay for 60 seconds without action, and then the background light will go out automatically.
1. Current date and time of the protection device with the format YY-MM-DD HH:MM:SS
3. Device address
7. Magnitude of frequency
2. Report name
5. Fault information (faulty phase selection, fault location, maximum fault current, maximum
zero-sequence current and variable impedance coefficient, and so on)
2. Report name
4. Alarm element
2. Report name
3. Time of the binary input change report (format: YY-MM-DD HH:MM:SS: MS)
2. Report name
3. Time of the binary output change report (format: YY-MM-DD HH:MM:SS: MS)
immediately after any control behavior is executed during the running process of the protection
device.
2. Report name
2. Press “▲” or “▼” to move the cursor to the menu “VALUES”, and press “ENT” or “►” to enter
this menu
3. Press “▲” or “▼” to move the cursor to any command menu, and press “ENT” to enter the
selected command menu
4. Press “▲” or “▼” to turn the page (if all information cannot be shown in one screen, one
screen can show 14 rows of information at most)
2. Press “▲” or “▼” to move the cursor to the menu “REPORT”, and press “ENT” or “►” to enter
this menu
3. Press “▲” or “▼” to move the cursor to any command menu, and press “ENT” to enter the
selected command menu
2. Press “▲” or “▼” to move the cursor to the menu “PRINT”, and press “ENT” or “►” to enter
this menu
3. Press “▲” or “▼” to move the cursor to any command menu, and press “ENT” to enter the
selected command menu
4. If the submenu “TRP INFO” is selected, according to the different protection function config,
there are four command menus “REPORT LIST”, “TRP REPORT” and “ORGNL WAVE”
Select the command menu “TRP REPORT”, and press “ENT”, LCD will show the following
interface:
Press “+” or “-” to select previous or next record. If you press “ENT”, LCD will show “Printing…”.
Then it will exit automatically, and return to “PRINT” menu. Press “ESC” to exit, and return to the
menu “PRINT”.
If no report is stored in the protection device, press “ENT” and LCD will display “No Report”.
5. If the command menu “ALM REPORT”, “BI CHG REPORT”, “BO CHG REPORT”, or “CTRL
REPORT” are selected, press “▲” or “▼” to move the cursor and press “ENT”, LCD will show
the following interface:
Press “+” or “-” to select the start and end sequence number of the printed report. Press “ENT”,
LCD will show “Printing…”. Then it will exit automatically, and return to the menu “PRINT”. Press
“ESC” to exit, and return to the menu “PRINT”.
The menu “PRINT” is also provides the command menus “EQUIP DESCRIPTION”, “VALUES”,
“PRESENT WAVE”, “103 PROTOCOL”, “CH A SELF-CHECK” and “CH A STATISTIC” to print
corresponding information, and the operation steps are similar with above.
2. Press “▲” or “▼” to move the cursor to the menu “PRINT”, and press “ENT” or “►” to enter
this menu
3. Press “▲” or “▼” to move the cursor to the submenu “SETTINGS INFO”, and press “ENT” to
enter this submenu
4. Select the command menus “NODE SETTINGS” and “LATEST MODIFIED” to print the node
settings and latest modified settings
5. If the command menu “UNACTIVE SETTINGS” is selected, LCD will show the following
interface:
Press “+” or “-” to select the setting group to be printed, and press “ENT”, LCD will show
“Printing…”. Then it will exit automatically, and return to the menu “PRINT”. Press “ESC” to exit,
and return to the menu “PRINT”.
2. Press “▲” or “▼” to move the cursor to the menu “SETTINGS”. Press “ENT” or “►” to enter
this menu
3. Press “▲” or “▼” to move the cursor to any command menu, and press “ENT” to enter the
selected command menu
8. Press “▲” or “▼” to move the cursor to the menu “SETTINGS”. Press “ENT” or “►” to
enter this menu
9. Press “▲” or “▼” to move the cursor to any command menu, and press “ENT” to enter
the selected command menu
13. If the command menu “EQUIP SETTINGS” is selected, move the cursor to the setting
item to be modified, and then press “ENT”
Press “+” or “-” to modify the value (if the modified value is more than one, press “◄” or “►” to
move the cursor to the digit bit to be modified. Press “+” or “-” to modify the value). Press “ESC”
to cancel the modification, and return to the command menu “EQUIP SETTINGS” display screen.
Press “ENT” to exit automatically, and return to the command menu “EQUIP SETTINGS” display
screen. Move the cursor to continue to modify other setting items. Press “ESC” after all setting
items to be modified are modified completely, LCD will show whether you want to save it? Press
“ESC” directly, or press “◄” or “►” to move the cursor, select “Cancel”, and then press “ENT”, it
will exit automatically and return to the command menu “EQUIP SETTINGS” display screen. Press
“◄” or “►” to move the cursor, select “No”, and then press “ENT”, all modified setting items will
restore its original value, and return to the “SETTINGS” menu. Press “◄” or “►” to move the
cursor, and select “Yes”, and then press “ENT”, LCD will show the following interface:
Password:
____
Enter 4-bit password (“+”, “◄”, “▲” and “-”). If the password is not correct, continue to enter it.
Press “ESC” to exit the password entry screen, and return to the command menu “EQUIP
SETTINGS” display screen. If the password is correct, LCD will show “Saving Setting…”. Then exit
and return to the command menu “EQUIP SETTINGS” display screen, all modified setting items
adopts the modified values.
Note!
For different setting items, the screen shown will vary slightly, but the modification method
is the same. The following is the same as it.
Note!
After the setting of the system parameters is modified, it will cause the “HEALTHY”
indicator light of the protection device goes out, you need to enter the command menu
“NODE SETTINGS” or “PROT SETTINGS” and confirm the protection setting have been
modified correspondingly. and then the protection device will restart automatically.
14. If the command menu “PROT SETTINGS” is selected, LCD will display the following
interface:
4. PROT_SETTINGS
Active Group: 01
Selected Group: 02
Press “+” or “-” to modify the value of “Selected Group”, and press “ENT” to enter. Move the
cursor to the setting item to be modified, and press “ENT” to modify the value.
2. Press “▲” or “▼” to move the cursor to the menu “SETTINGS”. Press “ENT” to enter this
menu
3. Press “▲” or “▼” to move the cursor to the command menu “COPY SETTINGS”, and press
“ENT”, LCD will display the following interface:
Press “+” or “-” to modify the value. Press the “ESC”, and return to the menu “SETTINGS”.
Press “ENT”, LCD will show password entry interface. If the password is incorrect, continue
inputting it, press the “ESC” to exit password entry interface and return to the menu “SETTINGS”.
If the password is correct, the LCD will display “Set Copying…”, and exit this menu (return to the
menu “SETTINGS”).
Press “+” or “-” to modify the value, and press “ESC” to exit, and return to main menu. Press
“ENT”, and LCD will show password entry interface. If the password is not correct, continue to
enter it. Press “ESC” to exit the password entry interface, and return to the initial status. If the
password is correct, the “HEALTHY” indicator light of the protection device will go out, and the
protection device will recheck the protection setting. If the check is not qualified, it will block the
device. If the check is qualified, LCD will return to the initial status.
2. Press “+”, “-”, “+”, “-” and “ENT”, LCD will show the following interface:
Press “ESC” to exit, and return to the initial status. Press “ENT” to clear.
Note!
The operation of deleting the device report will delete all reports saved in the protection
device, including the tripping reports, self-supervision reports, binary input change reports,
binary output change reports and control reports, and theses reports cannot be restored
once it is deleted. Please use this operation carefully!
3. Press “▲” or “▼” to move the cursor to the data or time to be modified
4. Press “+” or “-” to modify the value, and press “ENT” to save the modification and return to
the main menu
5. Press “ESC” to cancel the modification and return to the main menu
2. Press “▲” or “▼” to move the cursor to the menu “VERSION”, and press “ENT” to enter it
2. Press “▲” or “▼” to move the cursor to the menu “LANGUAGE”, and press “ENT” to enter this
menu
3. Press “▲” or “▼” to move the cursor to corresponding language, and press “ENT” to carry out
the language change, and then return to the main menu, and the language shown will change
4. Press “ESC” to cancel the selection, and return to the main menu
3. Press the “▲” or “▼” to move the cursor to the menu “TEST MODE”, and then press the
“ENT” or “►”to enter this menu
4. Press the “▲” or “▼” to move the cursor to the command menu, and then press the “ENT” to
enter the selected command menu
5. Press the “+” or “-” to page up/down, and then press the “▲” or “▼” to move the scroll bar.
(taking the command menu “TEST TRP REPORT” as an example):
Move the cursor to select the corresponding protection elements. Press the “ENT” to execute the
communication test one by one, SCADA will receive the corresponding fault report.
6. Press the “ESC” to exit this menu to return to the menu “TEST MODE”
Note!
If the communication parameter i.e. [En_CommTest] is set as “0”, the protection device will
display the prompt message “Not in Test Mode” when excuting any command menu
among “TEST TRP REPORT”, “TEST ALM REPORT”, “TEST BI REPORT” and “TEST BO
REPORT” .
Note!
All LCD interfaces provided in this chapter is a mere reference and available for explaining
specific definition of LCD. The displayed interface of the actual protection device may be
different from it, so you shall be subject to the actual protection device.
Chapter 9 Communications
The rear EIA RS-485 interface is isolated and is suitable for permanent connection of whichever
protocol is selected. The advantage of this type of connection is that up to 32 protective devices
can be “daisy chained” together using a simple twisted pair electrical connection.
It should be noted that the descriptions contained within this section do not aim to fully detail the
protocol itself. The relevant documentation for the protocol should be referred to for this
information. This section serves to describe the specific implementation of the protocol in the relay.
The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the
product. The connection is polarized and whilst the product’s connection diagrams indicate the
polarization of the connection terminals it should be borne in mind that there is no agreed
definition of which terminal is which. If the master is unable to communicate with the product, and
the communication parameters match, then it is possible that the two-wire connection is reversed.
The EIA RS-485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end
across the signal wires (refer to Figure 9.2-1). Some devices may be able to provide the bus
terminating resistors by different connection or configuration arrangements, in which case
separate external components will not be required. However, this product does not provide such a
facility, so if it is located at the bus terminus then an external termination resistor will be required.
The EIA RS-485 standard requires that each device be directly connected to the physical cable
that is the communications bus. Stubs and tees are expressly forbidden, such as star topologies.
Loop bus topologies are not part of the EIA RS-485 standard and are forbidden by it too.
Two-core screened cable is recommended. The specification of the cable will be dependent on the
application, although a multi-strand 0.5mm2 per core is normally adequate. Total cable length must
not exceed 500m. The screen must be continuous and connected to ground at one end, normally
at the master connection point; it is important to avoid circulating currents, especially when the
cable runs between buildings, for both safety and noise reasons.
This product does not provide a signal ground connection. If a signal ground connection is present
in the bus cable then it must be ignored, although it must have continuity for the benefit of other
devices connected to the bus. At no stage must the signal ground be connected to the cables
screen or to the product’s chassis. This is for both safety and noise reasons.
9.2.1.4 Biasing
It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal
level has an indeterminate state because the bus is not being actively driven. This can occur when
all the slaves are in receive mode and the master is slow to turn from receive mode to transmit
mode. This may be because the master purposefully waits in receive mode, or even in a high
impedance state, until it has something to transmit. Jabber causes the receiving device(s) to miss
the first bits of the first character in the packet, which results in the slave rejecting the message
and consequentially not responding. Symptoms of these are poor response times (due to retries),
increasing message error counters, erratic communications, and even a complete failure to
communicate.
Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1V. There
should only be one bias point on the bus, which is best situated at the master connection point.
The DC source used for the bias must be clean; otherwise noise will be injected. Note that some
devices may (optionally) be able to provide the bus bias, in which case external components will
not be required.
Note!
It is extremely important that the 120Ω termination resistors be fitted. Failure to do so will
result in an excessive bias voltage that may damage the devices connected to the bus.
As the field voltage is much higher than that required, NR cannot assume responsibility for
any damage that may occur to a device connected to the network as a result of incorrect
application of this voltage.
Ensure that the field voltage is not being used for other purposes (i.e. powering logic inputs)
as this may cause noise to be passed to the communication network.
It is recommended to use twisted screened eight-core cable as the communication cable. A picture
is shown bellow.
Each equipment is connected with an exchanger via communication cable, and thereby it forms a
star structure network. Dual-network is recommended in order to increase reliability. SCADA is
also connected to the exchanger and will play a role of master station, so the every equipment
which has been connected to the exchanger will play a role of slave unit.
To use the rear port with IEC60870-5-103 communication, the relevant settings of the protective
device must be configured. To do this use the keypad and LCD user interface. In the submenu
“COMM SETTINGS”, set the parameters [COM1_Protocol] as “0”, [COM1_Baud] as “9600”. For
using the Ethernet port with IEC60870-5-103 communication, the IP address and submask of
each Ethernet port can be set in the submenu “COMM SETTINGS”.
Initialization (reset)
Time synchronization
General interrogation
General commands
Disturbance records
The link layer strictly abides by the rules defined in the IEC60870-5-103.
9.3.2 Initialization
Whenever the protective device has been powered up, or if the communication parameters have
been changed, a reset command is required to initialize the communications. The protective
device will respond to either of the two reset commands (Reset CU or Reset FCB), the difference
is that the Reset CU will clear any unsent messages in the transmit buffer.
The protective device will respond to the reset command with an identification message ASDU 5,
the COT (Cause Of Transmission) of this response will be either Reset CU or Reset FCB
depending on the nature of the reset command.
If the protective device clock is synchronized using the IRIG-B input then it will not be possible to
set the protective device time using the IEC60870-5-103 interface. An attempt to set the time via
the interface will cause the protective device to create an event with the current date and time
taken from the IRIG-B synchronized internal clock.
When this setting [En_Iec103_Inf] is set as “1”, all spontaneous events are sent in the format of
FUN and INF based on IEC 60870-5-103 protocol. Non disturbance report are sent via the
message with time-stamp ASDU1 and disturbance report are sent via the message with relative
time-stamp ASUD2.
All spontaneous events can be gained by printing, implementing submenu “103 PROTOCOL” in
the menu “PRINT”.
Refer the IEC60870-5-103 standard can get the enough details about general interrogation.
When this setting [En_Iec103_Inf] is set as “0”, all spontaneous events are sent via generic
services based on IEC 60870-5-103 protocol.
All general classification service group numbers can be gained by printing, implementing submenu
“103 PROTOCOL” in the menu “PRINT”.
The disturbance records are stored in uncompressed format and can be extracted using the
standard mechanisms described in IEC60870-5-103.
All channel numbers (ACC) of disturbance data can be gained by printing, implementing submenu
“103 PROTOCOL” in the menu “PRINT”.
IEC 61850-5: Communications and requirements for functions and device models
IEC 61850-7-1: Basic communication structure for substation and feeder equipment–
Principles and models
IEC 61850-7-2: Basic communication structure for substation and feeder equipment - Abstract
communication service interface (ACSI)
IEC 61850-7-3: Basic communication structure for substation and feeder equipment–
Common data classes
IEC 61850-7-4: Basic communication structure for substation and feeder equipment–
Compatible logical node classes and data classes
IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO
9506-1 and ISO 9506-2) and to ISO/IEC 8802-3
IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over
serial unidirectional multidrop point to point link
IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over
ISO/IEC 8802-3
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC 61850 implementation obtain this document set.
1. MMS protocol
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. Actual IEC 61850-7-2 abstract services and objects are mapped to MMS protocol
services in IEC61850-8-1.
2. Client/server
This is a connection-oriented type of communication. The connection is initiated by the client, and
communication activity is controlled by the client. IEC61850 clients are often substation computers
running HMI programs or SOE logging software. Servers are usually substation equipment such
as protection relays, meters, RTUs, transformer, tap changers, or bay controllers.
3. Peer-to-peer
A substation configuration language is a number of files used to describe IED and communication
system realized according to IEC 61850-5 and IEC 61850-7. Each configured device has an IEC
Capability Description (ICD) file and a Configured IED Description (CID) file. The substation single
line information is stored in a System Specification Description (SSD) file. The entire substation
configuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the
combination of the individual ICD files and the SSD file, moreover, add communication system
parameters (MMS, GOOSE, control block, SV control block) and the connection relationship of
GOOSE and SV to SCD file.
Each IED represents one IEC61850 physical device. The physical device contains one or more
logical device(s), and the logical device contains many logical nodes. The logical node LPHD
contains information about the IED physical device. The logical node LLN0 contains information
about the IED logical device.
The GGIO logical node is available in the RCS-900 series relays to provide access to digital status
points (including general I/O inputs and warnings) and associated timestamps and quality flags.
The data content must be configured before the data can be used. GGIO provides digital status
points for access by clients. It is intended that clients use GGIO in order to access digital status
values from the RCS-900 series relays. Clients can utilize the IEC61850 buffered reporting
features available from GGIO in order to build sequence of events (SOE) logs and HMI display
screens. Buffered reporting should generally be used for SOE logs since the buffering capability
reduces the chances of missing data state changes. All needed status data objects are transmitted
to HMI clients via buffered reporting, and the corresponding buffered reporting control block
(BRCB) is defined in LLN0.
Most of analog measured values are available through the MMXU logical nodes, and metering
values in MMTR, the else in MMXN, MSQI and so on. Each MMXU logical node provides data
from a IED current/voltage “source”. There is one MMXU available for each configurable source.
MMXU1 provides data from CT/VT source 1(usually for protection purpose), and MMXU2 provides
data from CT/VT source 2 (usually for monitor and display purpose). All these analog data objects
are transmitted to HMI clients via unbuffered reporting periodically, and the corresponding
unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical nodes provide the
following data for each source:
MMXU.MX.Hz: frequency
The following list describes the protection elements for all RCS-900 series relays. The specified
relay will contain a subset of protection elements from this list.
PTUC: undercurrent
PTOC: phase overcurrent, zero sequence overcurrent and overcurrent when CTS
PTUV: undervoltage
PTUF: underfrequency
RSYN: Synchronism-check
The protection elements listed above contain start (pickup) and operate flags, instead of any
element has its own start (pickup) flag separately, all the elements share a common start (pickup)
flags “PTRC.ST.Str.general”. The operate flag for PTOC1 is “PTOC1.ST.Op.general”. For the
RCS-900 series relay protection elements, these flags take their values from related module for
the corresponding element. Similar to digital status values, the protection trip information is
reported via BRCB, and it also locates in LLN0.
Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address
common issues for Logical Devices. Most of the public services, the common settings, control
values and some device oriented data objects are available here. The public services may be
BRCB, URCB and GSE control blocks and similar global defines for the whole device; the
common settings include all the setting items of communication settings. System settings and
some of the protection setting items, which can be configured to two or more protection elements
(logical nodes). In LLN0, the item Loc is a device control object, this Do item indicates the local
operation for complete logical device, when it is true, all the remote control commands to the IED
will be blocked and those commands make effective until the item Loc is changed to false. In
RCS-900 series relays, besides the logical nodes we describe above, there are some other logical
nodes below in the IEDs:
LPHD: Physical device information, the logical node to model common issues for physical
device.
PTRC: Protection trip conditioning, it shall be used to connect the “operate” outputs of one or
more protection functions to a common “trip” to be transmitted to XCBR. In addition or
alternatively, any combination of “operate” outputs of protection functions may be combined to
a new “operate” of PTRC.
RDRE: Disturbance recorder function. It triggers the fault wave recorder and its output refers
to the “IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System”
(IEC 60255-24). All enabled channels are included in the recording, independently of the
trigger mode.
IEC61850 buffered and unbuffered reporting control blocks locate in LLN0, they can be configured
to transmit information of protection trip information (in the Protection logical nodes), binary status
values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and MSQI). The
reporting control blocks can be configured in CID files, and then be sent to the IED via an
IEC61850 client. The following items can be configured.
- Bit 1: Data-change
- Bit 4: Integrity
- Bit 1: Sequence-number
- Bit 2: Report-time-stamp
- Bit 3: Reason-for-inclusion
- Bit 4: Data-set-name
- Bit 5: Data-reference
- Bit 8: Conf-revision
- Bit 9: Segmentation
MMS file services are supported to allow transfer of oscillography, event record or other files from
a RCS-900 series relay.
9.5.4.3 Timestamps
The timestamp values associated with all IEC61850 data items represent the time of the last
change of either the value or quality flags of the data item.
IEC61850 specifies that each logical node can have a name with a total length of 11 characters.
The name is composed of:
Complete names are of the form xxxxxxPTOC1, where the xxxxxx character string is configurable.
Details regarding the logical node naming rules are given in IEC61850 parts 6 and 7-2. It is
recommended that a consistent naming convention be used for an entire substation project.
IEC61850 specifies the type of peer-to-peer data transfer services: Generic Object Oriented
Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support,
Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and
priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be
given a higher priority than standard Ethernet traffic, and they can be separated onto specific
VLANs. Devices that transmit GOOSE messages also Devices that transmit GOOSE messages
also function as servers. Each GOOSE publisher contains a “GOOSE control block” to configure
and control the transmission.
The transmission is also controlled via device setting “GOOSE Group ID” in the setting submenu
“EQUIP SETUP”. The “GOOSE Group ID” setting item defines a definite IED group in which the
IED can communicate with each other via GOOSE protocol, and if GOOSE Group ID is configured
to “0”, GOOSE service is blocked in this IED. IEC61850 recommends a default priority value of 4
for GOOSE. Ethernet traffic that does not contain a priority tag has a default priority of 1. More
details are specified in IEC61850 part 8-1. IEC61850 recommends that the Ether-type Application
ID number be configured according to the GOOSE source.
The RCS-931 series relays support IEC61850 Generic Object Oriented Substation Event
(GOOSE) communication. All GOOSE messages contain IEC61850 data collected into a dataset.
This dataset is transferred using GOOSE message services. The GOOSE related dataset is
configured in the CID file and it is recommended that the fixed GOOSE be used for
implementations that require GOOSE data transfer between RCS-900 series relays.
IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must be
correct to achieve the successful transfer of data. It is critical that the configured datasets at the
transmission and reception devices are an exact match in terms of data structure, and that the
GOOSE addresses and name strings match exactly.
RCS-900
Services Client Server
Series
Client-Server Roles
Server side (of Two-party
B11 - C1 Y
Application-Association)
Client side (of Two-party
B12 C1 - N
Application-Association)
SCSMS Supported
B21 SCSM: IEC 61850-8-1 used N N Y
B22 SCSM: IEC 61850-9-1 used N N N
B23 SCSM: IEC 61850-9-2 used N N N
B24 SCSM: other N N N
Generic Substation Event Model (GSE)
B31 Publisher side - O Y
B32 Subscriber side O - Y
Transmission Of Sampled Value Model (SVC)
B41 Publisher side - O N
B42 Subscriber side O - N
Where:
C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
M: Mandatory
Where:
C2: Shall be "M" if support for LOGICAL-NODE model has been declared
C3: Shall be "M" if support for DATA model has been declared
C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has
been declared
C5: Shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory
The RCS-900 series relays support IEC61850 logical nodes as indicated in the following table.
Note that the actual instantiation of each logical node is determined by the product order code.
10.1 Introduction
The chapter contains instructions on how to install, commission and maintenance the protection
equipment. It can also be used as a reference if a periodic test is performed. The chapter covers
procedures for mechanical and electrical installation, energizing and checking of external circuitry,
setting and configuration as well as verifying settings and performing a directionality test.
1) The “Safety information” presents warning and note signs, which the user should draw
attention to.
2) The “Overview” gives an overview over the major task when installing and
commissioning the protection equipment.
4) The “Installing the protection equipment” contains instructions on how to install the
protection equipment.
5) The “Checking the external circuitry” contains instructions on how to check that the
protection equipment is properly connected to the protection system.
6) The “Energizing the protection equipment” contains instructions on how to start-up the
protection equipment.
10) The “Final Check” contains instructions on make sure that everything associated with
the device is well.
The chapter is addressing the installation, commissioning and maintenance personnel responsible
for taking the protection into normal service and out of service. The installation personnel must
have a basic knowledge in handling electronic equipment. The commissioning and maintenance
personnel must be well experienced in using protection equipment, test equipment, protection
functions and the configured functional logics in the protection.
This section contains safety information. Warning signs are presented which attend the user to be
careful during certain operations in order to avoid human injuries or damage to equipment.
Warning signs
Warning!
Strictly follow the company and country safety regulations. Working in a high voltage
environment requires serious approach to avoid human injuries and damage to
equipment.
Do not touch circuitry during operation. Potentially lethal voltages and currents are
present.
Always avoid to touch the circuitry when the cover is removed. The product contains
electronic circuitries which can be damaged if exposed to static electricity (ESD). The
electronic circuitries also contain high voltage which is lethal to humans.
Always use suitable isolated test pins when measuring signals in open circuitry.
Potentially lethal voltages and currents are present.
Never unmount the front or back cover from a powered equipment or from a protection
equipment connected to powered circuitry. Potentially lethal voltages and currents are
present.
Caution signs
Caution!
Always transport modules using certified conductive bags. Always handle modules using
a conductive wrist strap connected to protective ground and on a suitable antistatic
surface. Electrostatic discharge (ESD) may cause damage to the module.
Do not connect live wires to the protection equipment. Internal circuitry may be damaged.
Always use a conductive wrist strap connected to protective ground when replacing
modules. Electrostatic discharge (ESD) may damage the module and protection
equipment circuitry.
Take care to avoid electrical shock if accessing wiring and connection protection
equipment when installing and commissioning.
Note signs
Note!
Changing the active setting group will inevitably change the protection equipment’s
operation. Be careful and check regulations before making the change.
The protection assembly is designed for a maximum continuous current of four times
rated value.
Activating the other setting group without proper configuration may seriously affect the
protection equipment’s operation.
10.3 Overview
The settings for each function must be calculated before the commissioning task can start. A
configuration, made in the configuration and programming tool, must also be available if the
protection equipment does not have a factory configuration downloaded.
The protection equipment is unpacked and visually checked. It is preferably mounted in a cubicle.
The connection to the protection system has to be checked in order to verify that the installation
was successful.
The installation and commissioning task starts with configuring the digital communication modules,
if included. The protection equipment can then be configured and set, which means that settings
and a configuration has to be applied if the protection equipment does not have a factory
configuration downloaded. Then the operation of each included function according to applied
settings has to be verified by secondary injection. A complete check of the configuration can then
be made. A conformity test of the secondary system has also to be done. When the primary
system has been energized a directionality check should be made.
Carefully examine the protection panel, protection equipment inside and other parts
inside to see that no physical damage has occurred since installation.
Panel wiring:
Check the conducting wire used in the panel to assure that their cross section meet the
requirement. Carefully examine the wiring to see that they are no connection failure exists.
Label:
Check all the isolator links, terminal blocks, ferrules, indicators, switches and push buttons to
make sure that their labels meet the requirements of this project.
Check each plug-in module of the equipments on the panel to make sure that they are well
installed into the equipment without any screw loosened.
Earthing cable:
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator links and push buttons work normally
and smoothly.
3) Check that all items are included in accordance with the delivery documents.
The user is requested to check that all software functions are included according to the delivery
documents after the terminal has been energized.
These product checks cover all aspects of the protection, which should be checked to ensure that
the protection not only has not been physically damaged prior to commissioning but also functions
correctly and all input quantity measurements are within the stated tolerances.
Sufficient space must be available in front of and at rear of the protection panel to allow access for
maintenance and future modifications. Flush mounted protection equipment should be mounted
so that equipment modules can be added and replaced without excessive demounting.
10.5.2 Dimensions
The equipment adopts IEC standard chassis and is rack with modular structure. It uses an integral
faceplate and plug terminal block on backboard for external connections. RCS-931 is IEC 4U high
and 19” wide. Figure 10.5-1 shows its dimensions and Figure 10.5-2 shows the panel cut-out.
GRP
101.6
177.0
ESC
465.0
101.6
179.0
4-
Ф6.8
450.0
All these influences can influence the operation of electronic apparatus. On the other hand,
electronic apparatus can transmit interference that can disrupt the operation of other apparatus.
In order to minimize these influences as far as possible, certain standards have to be observed
Note!
All these precautions can only be effective if the station ground is of good quality.
Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non-corroding.
Note!
If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of it
forming a resonant circuit at certain frequencies that would amplify the transmission of
interference by the devices installed and also reduce their immunity to induced
interference.
Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (refer to Figure 10.5-3).
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
Note!
For metallic connections please observe the voltage difference of both materials according
to the electrochemical code.
The cubicle ground rail must be effectively connected to the station ground rail by a grounding strip
(braided copper).
There are some ground terminals on some connectors of the relays, and the sign is “GND”. All the
ground terminals are connected in the cabinet of this relay. So, the ground terminal on the rear
panel (refer to Figure 10.5-4) is the only ground terminal of this device.
The grounding strips must therefore be of (preferably tinned) braided copper and not round copper
conductors, as the cross-section of round copper would have to be too large.
Data of braided copper strip: threaded M4, 4.0mm2. Proper terminations must be fitted to both
ends (press/pinch fit and tinned) with a hole for bolting them firmly to the items to be connected.
The surfaces to which the grounding strips are bolted must be electrically conducting and
non-corroding.
When using screened cabling always use 360° full screen cable bushing to ensure screen
coupling. Ensure that all signals of the single circuit are in the same single cable. Avoid mixing
current and voltage measuring signals in the same cable. Also use separate cables for control and
measuring circuits.
Heavy-duty terminal block, M4 threaded terminal ends. VT circuit must be connected with the
protective device through an MCB.
Auxiliary power cords cross can be directly screwed fixed on the rear panel of DC board. Refer to
section 6.2.1.
Welding terminals. Those devices are supplied with sufficient M4 screws for making connections
to the rear mounted terminal blocks using ring terminals, with a recommended maximum of two
ring terminals per relay terminal.
To meet the insulation requirements of the terminal block, for the sake of safety, an insulating
sleeve should be fitted over the ring terminal after crimping.
The wire used for all connections to the welding terminal blocks and heavy duty terminal blocks,
except the EIA(RS)485 port, should have a minimum voltage rating of 300Vrms.
It is recommended that the auxiliary power circuit wiring should be protected by using a 16A high
rupture capacity (HRC) fuse of type NIT or TIA. For safety reasons, current transformer circuits
must never be open.
Connect the unit to the grounding bar of the cubicle with green/yellow conductor; connected to the
protective Earthing terminal at the back of the DC board. Refer to section 6.2.1. Attend that the
earth wire must be as short as possible. All cautions have to be taken to ensure the best electrical
conductivity, particularly the contact quality, stainless conductor. The impedance between the relay
Earthing terminal and the Earth must be less than 20mΩ under 12Volt, 50Hz. What matters is that
the device has to be only grounded at one point. Loop grounding from unit to unit is not allowed.
Connectors are generally color coded; connect blue or dark grey cable connectors to blue or dark
grey (receive) back-side connectors. Connect black or grey cable connectors to black or grey
(transmit) back-side connectors.
Fiber optical cables are sensitive to handling. Do not bend too sharply. The minimum curvature
radius is 15 cm for plastic fibers and 25 cm for glass fibers. If cable straps are used, apply with
loose fit.
Note!
Always hold the connector, never the cable, when connecting or disconnecting optical
fibres. Do not twist, pull or bend the fibre. Invisible damage may increase fibre damping
thus making communication impossible.
When using galvanic connection between protective relay and communication equipment or
point-to-point galvanic connection between two protective relays it is essential that the cable
installation is carefully done. This is true regardless of type of module used, only the possible
length of the cable differs. The factors that must be taken into account is the susceptibility for noise
disturbance, due to that the levels of the communication signal are very low. For a best result, a
cable with twisted pairs with screen should be used.
9 BO Binary output
A BO Binary output
B BO Binary output
C BO Binary output (optional)
D BO Binary output (optional)
612 EBI_Opt2_AR +
616 BI_En_Z1 +
Cls_1 911 TrpA-1 905
618 BI_ExTrP1P_AR + Cls_3 929
TrpB-1 907
620 BI_ExTrp3P_AR + Cls_3 930
TrpC-1 909
622 BI_MCB_VT_Syn + Cls_2 927
712 BI_Send_TS2 +
TDGJ-1 A01 TJ-1 A09
714 Reserved +
TDGJ-1 A02 TJ-1 A10
716 Reserved +
TDGJ-2 A03 TJ-2 A11
718 Reserved +
TDGJ-2 A04 TJ-2 A12
720 Reserved +
TDGJ-3 A05 TJABC-1 A13
102 DC-
BCJ-1 A17 YC2-1 A25
103
BCJ-1 A18 YC2-1 A26
104 OPTO+
BCJ-2 A19 YC2-2 A27
105 OPTO-
BCJ-2 A20 YC2-2 A28
106 GROUND
GROUND BUS
Syn_Fail-1 B09 AR_INP-1 B13
505 RS485B 5 5
506 GND 6 6
507 RS485A 7 7
508 RS485B 8 8
FIBRE R
509 GND 9 9
510 RS485A/RS232R
FIBRE T RS232 DB 9
511 RS485B/RS232T
ETHERNET DB 15
512 GROUND
AI FOR TEST
Check that the wiring is in strict accordance with the supplied wiring diagram.
Polarity check
Grounding check
The polarity check verifies the integrity of the circuits and the phase relationship. The check should
be performed as close as possible to the relay. The primary injection test verifies the CT ration and
the wiring all the way through from the primary system to the relay. Injection must be performed for
each phase-to-neutral circuit and each phase-to-phase pair. In each case currents in all phases
and the neutral line are measured.
Check that the value of the auxiliary supply voltage remains with the permissible range under all
operating conditions. Check that the polarity is correct according to the instruction manual on the
rear plate of DC board. Refer to section 6.2.1.
Preferably, disconnect the binary input connector form the binary input cards. Check all connected
signals so that both input level and polarity are in accordance with the relay’s specifications.
Note!
The binary inputs may be energized from an external dc auxiliary supply (e.g. the station
battery) in some installations. Check that this is not the case before connecting the field
voltage otherwise damage to the protection may result. The status of each binary input can
be viewed using either RCSTool_900 software installed in a portable PC or by checking
the front man-machine interface LCD. When each binary input is energized the display will
change to indicate the new state of the inputs.
Preferably, disconnect the binary output connector form the binary output cards. Check all
connected signals so that both load and polarity are in accordance with the relay’s specifications.
Before the procedures in this section can be carried out the connection to external circuitry must
have been checked which ensures that the installation was made correctly.
The user must energies the power supply to the relay to start it up. This could be done in a
numerous of ways, from energizing a whole cubicle to energizing a single relay. The user should
reconfigurate the relay settings. The relay time must be set. The self-supervision function should
also be checked to verify that the relay unit operates properly. The user could also check the
software version, the relay’s serial number, the installed modules, and their ordering number to
ensure that the relay is according to delivery and ordering specifications.
The liquid crystal display (LCD) is designed to operate in a wide range of substation ambient
temperatures. For this purpose, this relay has an automatic “LCD contrast” adjusting feature,
which is capable to adjust LCD contrast automatically according to the ambient temperature.
Connect the relay to DC power supply correctly and turn the relay on. Check program version and
forming time displayed in command menu to ensure that are corresponding to what ordered.
If the time and date is not being maintained by substation automation system, the date and time
should be set manually.
Set the date and time to the correct local time and date using menu item “CLOCK”. Refer to
section 8.4.10 for detailed procedures.
In the event of the auxiliary supply failing, with a battery fitted on CPU board, the time and date will
be maintained. Therefore when the auxiliary supply is restored the time and date will be correct
and not need to set again.
To test this, remove the auxiliary supply from the relay for approximately 30s. After being
re-energized, the time and date should be correct.
On power up, the green LED “HEALTHY” should have illuminated and stayed on indicating that
the protective device is healthy.
The relay has latched signal relays which remember the state of the trip, auto-reclose when the
relay was last energized from an auxiliary supply. Therefore these indicators may also illuminate
when the auxiliary supply is applied. If any of these LEDs are on then they should be reset before
proceeding with further testing. If the LED successfully reset, the LED goes out. There is no testing
required for that that LED because it is known to be operational.
It is likely that alarms related to voltage transformer supervision will not reset at this stage.
behave as intended. A default value is provided for each parameter from factory.
Download from a PC or laptop with RCSTool_900 software or remotely by SCADA. Front port
communication has to be established before the settings can be downloaded.
To change settings through the local HMI need a password which is “+”, “◄”, “▲” and “-”
keyboard on the front panel.
Unless previously agreed to the contrary, the customer will be responsible for determining the
application-specific settings to be applied to the protection and for testing of any scheme logic
applied by external wiring and/or configuration of the protection’s internal programmable scheme
logic.
It is not the intention of the test to verify the operation of the complete system from the relay to the
remote location, just the protection’s rear communications port and any protocol converter
necessary.
Multifunctional dynamic current and voltage injection test set with interval timer.
Multimeter with suitable AC current range and AC/DC voltage ranges of 0-440V and 0-250V
respectively.
Note!
Modern test set may contain many of the above features in one unit.
Optional equipment:
An electronic or brushless insulation tester with a DC output not exceeding 500 V (for
insulation resistance test when required).
A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).
EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested).
At the same time, the calculated settings, substation configuration diagram, the protective device
diagram and the instruction manual is essential to test the protective device.
The relay has to be set before the testing can start. Only the functions that are used should be
tested.
All used setting groups should be tested. The user can release the functions to be tested and
prevent other functions from operation by setting the corresponding parameters. The user could
also energize the binary input [BI_BlkComm] to disable communication function to ensure that no
events are reported to remote station during the test.
The setting checks ensure that all of the application-specific protection settings (i.e. both the
protection’s function and programmable scheme logic settings), for the particular installation, have
been correctly applied to the protection.
Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, The circuits need to be tested should include:
DC power supply
Output contacts
Communication ports
Test method:
To unplug all the terminals sockets of this protective device, and do the Insulation resistance test
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected
to the protection
This test verifies that the accuracy of current measurement is within the acceptable tolerances.
Checking its magnitude using a multimeter. The corresponding reading can then be checked
either in the protection’s submenu “PORT MEASUREMENT column or a portable computer
connected to the front communication port with software RCSTool_900.
The measurement accuracy of the protection is ± 5%. However, an additional allowance must be
made for the accuracy of the test equipment being used.
This test verifies that the accuracy of voltage measurement is within the acceptable tolerances.
Checking its magnitude using a multimeter. The corresponding reading either in the protection’s
submenu “PORT MEASUREMENT or a portable computer connected to the front communication
port with software RCSTool_900.
The measurement accuracy of the protection is ±5%. However, an additional allowance must be
made for the accuracy of the test equipment being used.
Note!
The trip circuit should remain isolated during these checks to prevent accidental operation
of the associated circuit breaker.
Ensure that the voltage applied on the binary input must be within the operating range. The status
of each binary input can be viewed using menu item “BI STATE”. Sign “1” denotes an energized
input and sign “0” denotes a de-energized input. Refer to section 6.2.6 and section 6.2.7.
3) Self-check and the transition of binary input in the process of devices start
1) Confirm the external wiring to the current and voltage inputs is correct.
However, these checks can only be carried out if there are no restrictions preventing the
tenderization of the plant being protected.
Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has
been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the protection in order to
perform any of the foregoing tests, it should be ensured that all connections are replaced in
accordance with the relevant external connection or scheme diagram. Confirm current and voltage
transformer wiring.
If the protection is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. If a test block is installed, remove the
test plug and replace the cover so that the protection is put into service.
Ensure that all event records, fault records, disturbance records and alarms have been cleared
and LED’s has been reset before leaving the protection.
Chapter 11 Maintenance
NR numerical relay RCS-931 is designed to require no special maintenance. All measurement and
signal processing circuit are fully solid state. All input modules are also fully solid state. The output
relays are hermetically sealed.
Since the device is almost completely self-monitored, from the measuring inputs to the output
relays, hardware and software defects are automatically detected and reported. The
self-monitoring ensures the high availability of the device and generally allows for a corrective
rather than preventive maintenance strategy. Therefore, maintenance checks in short intervals are
not required.
Operation of the device is automatically blocked when a hardware failure is detected. If a problem
is detected in the external measuring circuits, the device normally only provides alarm messages.
2. It is only allowed to plug or withdraw relay board when the supply is reliably switched off.
Never allow the CT secondary circuit connected to this equipment to be opened while the
primary system is live when withdrawing an AI module. Never try to insert or withdraw the
relay board when it is unnecessary.
3. Check weld spots on PCB whether they are well soldered without any rosin joint. All dual
inline components must be well plugged.
When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the event record.
Failures detected by supervision are traced by checking the “ALM REPORT” screen on the LCD.
Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.
Check that the replacement module has an identical module name (AI, PWR, CPU, SIG, BI, BO,
etc.) and hardware type-form as the removed module. Furthermore, the CPU module replaced
should have the same software version. And the AI and PWR module replaced should have the
same ratings.
The module name is indicated on the top front of the module. The software version is indicated in
LCD menu “VERSION”.
Caution!
When handling a module, take anti-static measures such as wearing an earthed wrist band
and placing modules on an earthed conductive mat. Otherwise, many of the electronic
components could suffer damage. After replacing the CPU module, check the settings.
1) Replacing a module
Short circuit all AC current inputs and disconnect all AC voltage inputs
Warning!
Hazardous voltage can be present in the DC circuit just after switching off the DC power
supply. It takes approximately 30 seconds for the voltage to discharge.
Unplug the ribbon cable on the front panel by pushing the catch outside.
After replacing the CPU module, input the application-specific setting values again.
Warning!
Units and modules may only be replaced while the supply is switched off and only by
appropriately trained and qualified personnel. Strictly observe the basic precautions to
guard against electrostatic discharge.
Warning!
When handling a module, take anti-static measures such as wearing an earthed wrist
band and placing modules on an earthed conductive mat. Otherwise, many of the
electronic components could suffer damage. After replacing the CPU module, check the
settings.
Danger!
After replacing modules, be sure to check that the same configuration is set as before the
replacement. If this is not the case, there is a danger of the unintended operation of
switchgear taking place or of protections not functioning correctly. Persons may also be
put in danger.
11.5 Cleaning
Before cleaning the relay, ensure that all AC/DC supplies, current transformer connections are
isolated to prevent any chance of an electric shock whilst cleaning.
Front panel cleaning: use a smooth cloth. Do not use abrasive material or detergent chemicals.
11.6 Storage
The spare relay or module should be stored in a dry and clean room. Based on IEC standard
60255-6 the storage temperature should be from –25oC to 70oC, but the temperature of from 0oC
to 40oC is recommended for long-term storage.
12.1 Decommissioning
1. Switching off
To switch off the RCS-931, switch off the external miniature circuit breaker of the power supply.
2. Disconnecting Cables
Disconnect the cables in accordance with the rules and recommendations made by relational
department.
Danger!
Before disconnecting the power supply cables that connected with the PWR module of the
RCS-931, make sure that the external miniature circuit breaker of the power supply is
switched off.
Danger!
Before disconnecting the cables that are used to connect analog input module with the
primary CTs and VTs, make sure that the circuit breaker for the primary CTs and VTs is
switched off.
3. Dismantling
The RCS-931 rack may now be removed from the system cubicle, after which the cubicles may
also be removed.
Danger!
When the station is in operation, make sure that there is an adequate safety distance to
live parts, especially as dismantling is often performed by unskilled personnel.
12.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste.
Note!
Strictly observe all local and national regulations when disposing of the device.
Software Manual
Source Documentation
Release Release
R4.00 R2.00 R1.01 RCS-931_MY Line Differential Relay
R4.01 R2.01 R2.00 RCS-931_MY Line Differential Relay
Manual
Section Page No. Description of change Note
Version
R1.00 Original Release
PSB is change into PSBR, and
3.3.2.12 29~37 Amended
corresponding description is re-writen.
The logic scheme of current differential
3.3.5.6 46~48 Amended
protection is amended.
The logic scheme of VT circuit failure
R1.01 4.4.3 73 Added
detection is added.
The logic scheme of CT circuit failure
4.4.5 74 Added
detection is added.
The logic scheme of differential
4.6 75 Added
protection supervision is added.
Chapter 2 5~14 Technique data Amended
15~17,
Chapter 3 Protection Description Amended
37~51, 54~68
Chapter 4 71~76 Automatic Supervision Amended
Chapter 5 79~82 Metering and recording Amended
R2.00 Chapter 6 83~98 Hardware Description Amended
Chapter 7 101~124 Settings Amended
Chapter 8 127~147 Human Machine Interface Amended
Chapter 9 153~164 Communications Amended
Chapter 10 175~178 Installation and Commissioning Amended
Chapter 13 191 Manual Version History Amended
3.3.4 38 Phase overcurrent protection Added
3.3.6 51 Thermal overload Amended
3.3.5 46~48 PSCVR PSBR element Added
R2.01 6.2.5 87~89 Communication interface module Amended
Settings about phase overcurrent
7.4 105~114 Added
protection
7.5 114~124 Logic settings about phase overcurrent Amended