s
Datasheet for
Siemens HydroRanger 200 Ultrasonic level controller for up to six pumps that provides control, differential control and open channel flow
monitoring.
Ordering data: 7ML50344BA21
General
Manufacturer Siemens
Supplier Siemens
Product designation Ultrasonic transducer
Brand name HydroRanger 200
Type designation Electronica de medida de nivel mediante sensor ultrasonico para liquidos,
lodos y polvos, de Siemens Milltronics, modelo HydroRanger
Net weight 1,4 kg
Single or dual point level monitor/controller
Mode of operation and application
Measuring principle ultrasonic
44 kHz
Input
1
Analog input
1
Signal range at the analog input 0 ... 20 mA, 4 ... 20 mA
Digital input
Number of outputs 2
Input voltage, DC 0 V...50 V
Input voltage signal 0, DC (minimum) 0,5 V
Input voltage signal 1, DC (minimum) 10 V
Input voltage signal 1, DC (maximum) 50 V
Input current (maximum) 3 mA
Measuring range
Measuring range 0,3 m...15 m
-50 °C
150 °C
Output
Current output
Number of outputs 2
Signal range 0 ... 20 mA, 4 ... 20 mA
Failure signal (minimum) 3,8 mA
Failure signal (maximum) 22 mA
Load, at active output (maximum) 750 Ohm
Digital output
relais
This is only an extract from the technical data. For more details, see the FI 01 catalog or the Industry Mall.
Creation date: 21.06.2019 Page 1 of 3
s
Datasheet for
Siemens HydroRanger 200 Ultrasonic level controller for up to six pumps that provides control, differential control and open channel flow
monitoring.
Ordering data: 7ML50344BA21
...Relay output
Number of outputs 6
Type 1 Normally Open (NO)
Number of outputs 1 4
Type 2 Change-over (NO/NC)
Number of outputs 2 2
Rated conditions
Degree of pollution Pollution degree 4
IEC 61010-1
Overvoltage class Installation category II
IEC 61010-1
Environmental conditions
Ambient temperature during operation -20 °C...+50 °C
Ambient temperature during storage -20 °C...+50 °C
Electromagnetic compatibility EMC
Standard for EMC EN 61326-1
Design
Mechanical design
Design of the housing separated version, sensor separated
...Material
....Housing
Material of the transmitter Polycarbonate (PC)
....Cable entry & cable gland
Material of the cable entry polyamide (PA)
Electrical connections
Connection technology 4-wire technology
Potential insulation galvanic
Potential insulation to all communications interfaces, to all inputs, to all outputs, to all supplies
Number of cable entries 4
Design of the cable entry Cutout opening
Length of the connection cable 365 m
Display and controls
Display with display
Controls Membrane key
Number of controls 4
Power supply
This is only an extract from the technical data. For more details, see the FI 01 catalog or the Industry Mall.
Creation date: 21.06.2019 Page 2 of 3
s
Datasheet for
Siemens HydroRanger 200 Ultrasonic level controller for up to six pumps that provides control, differential control and open channel flow
monitoring.
Ordering data: 7ML50344BA21
Electrical
Voltage type DC
Nominal voltage, DC 24 V
Supply voltage, DC 12 V...30 V
Power consumption effective power 20 W
Communication
Interface RS 485
RJ11 jacket
Protocol Profibus DP
Profile version DP-V0
SIMATIC PDM Software, with infrared hand programmer
Certificates and approvals
Verification of suitability C-Tick (RCM), CE, CSA, FM, MCERTS Class 3 (flow measurement in open
channels), UL
ENV1, ENV2, ENV3, ENV5
62 Years
SN 29500
calculation with component load
40 °C
Measuring device
The information provided in this data sheet contains descriptions or characteristics of performance which in case of actual use do not
always apply as described or which may change as a result of further development of the products. An obligation to provide the
respective characteristics shall only exist if expressly agreed in the terms of contract. Availability and technical specifications are subject
to change without notice.
This is only an extract from the technical data. For more details, see the FI 01 catalog or the Industry Mall.
Creation date: 21.06.2019 Page 3 of 3