CONDITION M3/HR M
RATED 454 125 10x8x23A SSC
150% 681 81.25
1500 GPM 138 to 285 psi, (319' to 658')
2000 GPM 127 to 282 psi, (293' to 651')
IMPELLER C02-80618
PATTERSON PUMP COMPANY NOL (MAX) POWER
A Gorman-Rupp Company Phone: (706) 886-2101 291 KW CURVE No. EPC72262
Post Office Box 790 www.pattersonpumps.com
Toccoa, Georgia 30577 U.S.A.
1780 RPM
597 MM
UL / FM APPROVED 700
210 54% 59% 64% 69%
74%
76.5% 600
180
PUMP TOTAL HEAD (M)
74%
150 500
* 494 MM 69%
PUMP TOTAL HEAD (FT)
64%
120 400
59%
441 MM
90 MINIMUM FLOW 300
71.2%
60 200
* ACTUAL IMPELLER DIAMETER
& SHUT-OFF HEAD DETERMINED
30 16 BY TESTING. 100
NPSHR (M)
8 NPSHR
PUMP INPUT POWER (KW)
PUMP INPUT POWER (HP)
1000 0
1200
800
500
597 MM 400
0 441 MM 0
M3/HR 0 200 400 600 800 1000 1200
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
GPM
* SHUT-OFF HEAD = 137.5 M
SPECIFIC GRAVITY = 1.000
140% RATED HEAD = 175 M