User Manual KW9M
User Manual KW9M
Read the manual carefully before installing, running and maintenance for proper operation.
Before using, master the knowledge of the equipment, safety information and all of other
notes.
This manual uses two safety flags to indicate different levels of danger.
A handling error could cause serious physical injury to an
WARNING operator and in the worst case could even be fatal.
●Apply appropriate personal protective equipment (PPE) and follow safe electrical work
practices. In the USA, see NFPA 70E.
●Always take precautions to ensure the overall safety of your system, so that the whole
system remains safe in the event of failure of this product or other external factor.
●Do not use this product in areas with inflammable gas. It could lead to an explosion.
●Exposing this product to excessive heat or open flames could cause damage to the
lithium battery or other electronic parts.
●Do not open the secondary side of CT during power on the primary side current.
It might cause electric shock or CT breakdown.
■ Installation environment
◇Do not use the Unit in the following environments.
・Where the unit will be exposed to direct sunlight and where the ambient temperature is outside
the range of -25 to 55 °C.
・Where the ambient humidity is outside the range of 30 to 85 % RH (at 20℃), non-condensing
and where condensation might occur by sudden temperature changes
・Where inflammable or corrosive gas might be produced
・Where the unit will be exposed to excessive airborne dust or metal particles
・Where the unit will be exposed to water, oil or chemicals
・Where organic solvents such as benzene, paint thinner, alcohol, or strong alkaline solutions
such as ammonia or caustic soda might adhere to the product
・Where direct vibration or shock might be transmitted to the product, and where water might wet
the product
・Where the place near high-voltage cable, high-voltage device, power line, power device.
・Where the place near a machinery with transmission function such as amateur radio.
・Where the place near a machinery which occurs the big switching serge
◇Please use the Unit according to the specifications described in this manual. Otherwise, it
may malfunction or cause fire and an electric shock.
・Connect to the power supply in compliance with the rating.
・Refer to the wiring diagram to ensure proper wiring for the power supply, input and output.
・Do not perform wiring or installation with a live line. It may also lead to circuit burnout or fire by
way of the secondary CT side opening.
■ Installation
・Eco-POWER METER is designed to be used in a control panel.
・The power supply terminal and voltage input terminal of the main unit is common. Therefore if
additional noise effects the power supply line, incorrect measurements may result.
・Installation and wiring must be performed by expert personnel for electrical work or electric
piping.
・Never remove the terminal block under applying current to load.
It might cause electric shock or CT breakdown.
・Do not add an excess power to the display. It might break the inner liquid crystal.
・Although the case is made from fireproof resin, do not mount it next to flammable materials. Also,
avoid placing it directly on top of materials that catch fire easily.
・If the operating power supply surge exceeds the following value, the internal circuit could be
destroyed, so be sure to use a surge absorption element.
Surge wave form
Surge voltage 6,000V [± (1.2/50) μs single-polarity full-wave voltage]
Standard surge waveform
The above value is the surge-voltage 100
resistance at ± (1.2/50) μs of 90
Surge voltage (%)
30
0 1.2
0 50
Time (μs)
i
・External noise up to the level shown below is treated as noise voltage, but levels higher than this
could lead to malfunctioning or damage to the internal circuit. Although the case is made from
fireproof resin, do not mount it next to flammable materials.
Note) Accurate measurement may not be possible if excessive noise gets added to the input line.
■ As to measurement
・If there is some distortion by harmonic or waveform, it may not measure correctly.
Please check with the actual system before adopts it.
・It might not measure an instantaneous current such as an inrush current or an welding machine.
・When measuring the below loads, it might not satisfy with the accuracy guarantee.
Out of rating current, Load with low power factor,
Load with winding current, Load with ferromagnetic field
・Power factor operation is a method assuming balanced load. The error might be big when it
measures unbalanced load.
■ Static electricity
・Discharge static electricity touching the grounded metal etc. when you touch the unit.
・Excessive static electricity might be generated especially in a dry place.
■ Cleaning
・Wipe dirt of the main unit with soft cloth etc. When thinner is used, the unit might deform or be
discolored.
■ Power supply
・Connect a breaker to the voltage input part for safety reasons and to protect the device.
The breaker that connects to the voltage input part must arrange at the position easily reached,
and display shows it is the breaker of the equipment.
・Do not turn on the power supply or input until all wiring is completed.
■ Before power on
Please note the following points when turning on power at the first time.
・Confirm there are neither wiring rubbish nor especially an electrical conduction when installed.
・Confirm neither the power supply wiring, the I/O wiring nor the power-supply voltage are wrong.
・Tighten the installation screw and the terminal screw surely.
・Use an electric wire applicable to the rated current.
ii
KW9M Eco-POWER METER
・Demand
Item Unit Display data range
Active kW
Reactive kvar
Apparent kVA
Present demand 0.000 to 99999
Active (export) kW
Reactive (export) kvar
Current A
* Please use this demand function as your standard.
The demand value calculated with this function is not guaranteed.
<Glossary>
Eco-POWER METER defines as below.
THD
Ratio of harmonic distortion (voltage or current) for the fundamental frequency.
(total harmonic
Lower the value shows that the distortion is less.
distortion)
Demand by Based on IEC61557-12 Performance measuring and monitoring devices (PMD)
IEC61557-12
It calculates by measured power via CT with setting interval.
Sliding block interval Set power interval by 1 to 60(min.) (every 1-min.). It calculates demand
demand during latest finished interval and displays.
One interval is started every setting time.
It calculates by measured power via CT with setting interval.
fixed block interval Set power interval by 1 to 60 (min.) (every 1-min.) It calculates demand
demand during latest finished interval and displays. After one interval finishes, the
next interval starts.
It calculates based on a thermal demand meter.
Current demand It measures an average current (current demand) within setting interval and
the max. value is considered as max. current demand.
2
KW9M Eco-POWER METER
<Front> <Back>
4 9
1 5
10 11 12
*1 Auxiliary mark [LEAD] [LAG] indicates the phase difference between voltage and current.
When current phase delays to voltage phase, [LAG] is indicated.
When current phase leads to voltage phase, [LEAD] is indicated.
When power factor is ‘1’, ‘0’ and ‘-1’, it doesn’t display [LEAD] nor [LAG].
3
KW9M Eco-POWER METER
Key Functions
Measuring mode Shift to setting mode
<MODE> Setting mode Shift to setting confirmation mode and measuring mode
Logging mode
Shift to setting mode
Demand mode
<SET> Setting mode Set setting items and setting values
Measuring mode
<SET> Logging mode All keys locked
(continuous 3-sec) Demand mode
Lock mode Release the lock mode
Measuring mode Select measuring item to display
<SHIFT/▽> Setting mode Select a setting value
Demand mode Select demand item to display
Measuring mode Select measuring item to display
Setting mode Select a setting value
<ITEM/△>
Logging mode Select logging item to display
Demand mode Select demand item to display
Measuring mode Shift to logging mode
<MODE>+<SHIFT/▽> Logging mode Shift to demand mode
Demand mode Shift to measuring mode
●Lock mode
It is the mode makes all keys unable. In this mode, you can not input by any keys.
When you press <SET> continuously for about 3sec., lock mark is displayed.
Press <SET> continuously for about 3sec. again to release Lock mode.
When it set to use auto-display functions, the display items are changed automatically.
Refer to 4.4.3 setting for optional functions for auto-display functions.
4
KW9M Eco-POWER METER
5
KW9M Eco-POWER METER
Chapter 3 Wiring
Be sure to wire correctly according to the terminal arrangement and wiring diagrams.
Please connect a fuse or a breaker to power supply part for safety reasons and to protect the device.
This has no built-in power switch, circuit breaker or fuse for measured voltage input parts.
Therefore it is necessary to install them in the circuit near this unit.
Do not turn on the power supply or input until all wiring is completed.
Stripping length: 7 to 8 mm
6
KW9M Eco-POWER METER
Grounding the secondary side of VT (Voltage transformer) and CT (Current transformer) is not
necessary with low-voltage circuit.
*When using several CTs, set each CT approximately 1m apart. If the two CTs are set too close each
other, it may not measure accurately due to magnetic field interference.
7
KW9M Eco-POWER METER
8
KW9M Eco-POWER METER
DANGER
●Never open the secondary circuit of CT under applying current to load.
●Never remove the terminal block under applying current to load.
Will cause electric shock or breakdown CT
・Use CT that the secondary side current is 5A or 1A, the rated burden 0.5VA or more.
・One CT is needed for 1 unit when measuring 1P2W (2 CTs for 2-circuit, 3CTs for 3-circuit). Two CTs
are needed when measuring 1P3W/3P3W. Three CTs are needed when measuring 3P4W.
Using all CTs for one unit should be the same.
・Use the applicable wire, or it might cause a breakdown, burnout or electric shock.
・When connecting CT, connect the secondary side to the terminal of the main unit first, and after that
wire the primary side to a load electric wire. Incorrect order might cause an electric shock or break CT.
・The CT has polarity. Wire correctly according to the K and L marks. Wrong direction can’t measure
correctly.
・If there is some distortion by harmonic or waveform, it may not measure correctly.
Please check with the actual system before adopts it.
・Separate the wiring (strong electric part) of the measured voltage input terminal (operating power
supply terminal) from the CT cable. It may not satisfy the accuracy due to noise.
9
KW9M Eco-POWER METER
◆How to connect CT
(1) Power off the measured devices.
(2) Install applicable CT.
(3) Remove terminal block of KW9M.
(4) Connect CT to the terminal block.
(5) Insert terminal stand surely.
(6) After confirm all wiring correct, turn on the power of the load and KW9M.
Power supply
Ammeter etc.
Breaker
K Secondary current
k
Load
10
KW9M Eco-POWER METER
(Fig.1)
Terminal Terminal
(Fig.2) station station
Correct wiring
○
Incorrect wiring
×
◆How to connect KW9M and the other devices with 2-wire system
11
KW9M Eco-POWER METER
When using in the application conforming to EN61010-1/IEC61010-1, make sure to satisfy the following
conditions.
1) Pulse output part secure only basic insulation. In order to secure reinforced (double) insulation
demanded by EN 61010-1/ IEC61010-1, secure basic insulation or more with load side and
reinforced (double) insulation with RS485 communication system side.
2) Provide the voltage input part with an EN60947-1 or EN60947-3 compliant circuit breaker.
3) Use a wire with basic insulation or more for a wire cramped (or connected) CT.
4) Vn terminal should be connected to N-phase which is grounded.
【Environmental conditions】
・Overvoltage category Ⅱ, Pollution degree 2
・Indoor use
・An ambient temperature of -25 to +55℃
・An ambient non-condensing humidity of 30 to 85%RH (at 20℃)
・Altitude of 2000m or less
【Mount the product in a place with】
・A minimum of dust, and an absence of corrosive gases
・No flammable, explosive gasses
・Few mechanical vibrations or shocks
・No exposure to direct sunlight
・No large capacity electromagnetic switches or cables through which large current is flowing
DC Voltage
CE Mark
Confirmation of conformity of the product with the applicable EU directives
and compliance with the essential requirements contained in these directives
Protective insulation, device with protection class II
Products with this mark comply wit both the Canadian and the American
requirements
12
KW9M Eco-POWER METER
Chapter 4 Settings
You can set parameters for measuring and the other functions using the keys on Eco-POWER METER.
After wiring Eco-POWER METER and CT, power on and set the parameter for power measurement,
Eco-POWER Meter can measure the electric power. In order to use the other functions, set other
parameters according to your use.
13
KW9M Eco-POWER METER
◆Password
Item Range Initial value
Password change 0000 to 9999 0000
14
KW9M Eco-POWER METER
Measuring value
display
Enter password
Setting mode
【Power 【Optional
【Demand】 【Communication】 【Password】
measurement】 functions】
Power demand
CT type Device number Luminance
interval 1
Reset all
Version
integral value
15
KW9M Eco-POWER METER
Increase
16
KW9M Eco-POWER METER
30 seconds
17
KW9M Eco-POWER METER
CT type
Select using CT type (secondary side current).
Increase
decrease
18
KW9M Eco-POWER METER
VT ratio
Select the voltage input method, input voltage directly or uses a voltage transformer
(VT: secondary side rating 110V) and set VT ratio.
increase
decrease
Input directly without VT: [1.00]
Use VT : [1.01 to 600.00]
*When input voltage is under 3V (VT ratio = 1), [0.0] is displayed and it doesn’t measure.
increase
decrease
increase
decrease
19
KW9M Eco-POWER METER
[Set list]
Slide (sliding block),
Fixed (fixed block) (initial: Slide)
Increase
Decrease
Increase
decrease
Increase
Decrease
20
KW9M Eco-POWER METER
[Set list]
Start, Stop (initial: Stop)
21
KW9M Eco-POWER METER
Device number
Set an individual device number for each unit when two or more units are connected to
communicate via serial communication (RS485).
decrease
[Set list]
1200, 2400, 4800, 9600, 19200, 38400 [bps]
(initial: 19200)
22
KW9M Eco-POWER METER
Transmission format
*Select [8b-E] when [645] is set for the protocol.
Select serial communication (RS485) transmission format (Data length, Parity).
Define the transmission format according to the master’s (PLC etc.).
[Set list] 8b-o (8bit odd), 8b-n (8bit none), 8b-E (8bit even) (initial: 8b-o)
Stop bit
*Select [1] when [645] is set for the protocol.
Select serial communication (RS485) stop bit.
Response time
*Select 50 or more when [645] is set for the protocol.
Set serial communication (RS485) response time of main unit.
When command is received, it sends response after setting response time passes.
increase
decrease
23
KW9M Eco-POWER METER
increase
decrease
Always turn on : [0]
Turn off after setting time: [1~99]
After turns off the LCD, any key operation makes it turns on.
Luminance
Adjust the display luminance.
Update cycle
Set update cycle for measuring window.
It updates the display of measured values every setting time.
Increase
decrease
24
KW9M Eco-POWER METER
Auto-display
It shifts items of each integral value automatically.
When it passes the setting time after key operation, the integral value is shifted automatically.
increase
decrease
Display cycle
*It skips this item when [0] is set for auto-display.
Set each display cycle during auto-display.
increase
decrease
Shift every 1second: [1]
*Any key operation during auto-display makes the display shift to instantaneous active power.
Temperature correction
The measured temperature can be corrected to display.
increase
decrease
25
KW9M Eco-POWER METER
Reset : [YES]
Not reset : [NO]
Reset : [YES]
Not reset : [NO]
Reset : [YES]
Not reset : [NO]
26
KW9M Eco-POWER METER
Reset : [YES]
Not reset : [NO]
Version
You can check the software version.
27
KW9M Eco-POWER METER
Increase
Confirm: [YES]
Not confirm: [NO]
28
KW9M Eco-POWER METER
29
KW9M Eco-POWER METER
・According to IEC61557-12
1. Sliding block interval demand
2. Fixed block interval demand
3. Current demand
Please use this simple demand function as your standard. The value is not guaranteed.
Caution
(1)Definition of Demand
It is demand measurement in order to use by yourself as your standard.
Sliding block
Set power interval by 1 to 60(min.) (every 1-min.). It calculates demand during latest finished interval
and displays.
One interval is started every time that set for ‘power demand interval 2’.
0 1 2 3 4 ・ ・ 1 1 1 1 1 [min.]
・・ ・・ 5 6 7 8 9
Fixed block
Set power interval by 1 to 60 (min.) (every 1-min.) It calculates demand during latest finished interval
and displays. After one interval finishes, the next interval starts.
1 3 [mi
0 5 0 n.]
30
KW9M Eco-POWER METER
Current demand =
(Average of current – last current demand value) × 90%(fixed) + Last current demand value
In case of that a stable current flows for interval time, 90% of current value is displayed.
(%)
90
time
interval
31
KW9M Eco-POWER METER
initial
Power monitoring
<MODE>
mode
<MODE>+<SHIFT/▽>
<MODE>
Log mode Setting mode
<MODE>+<SHIFT▽/>
Demand mode
<MODE>
<MODE>+<SHIFT/>
32
KW9M Eco-POWER METER
To next page
33
KW9M Eco-POWER METER
Current
Voltage
Power factor
Frequency
Current THD
Voltage THD
Temperature
*1) When 2nd circuit and 3rd circuit are not measured, [0] are displayed.
34
KW9M Eco-POWER METER
To next page
35
KW9M Eco-POWER METER
Current
Voltage
Phase-voltage Line-voltage
Power factor
Frequency
Current THD
Voltage THD
Phase-voltage THD Line-voltage THD
Temperature
36
KW9M Eco-POWER METER
Current
Line-voltage
Power factor
Frequency
Current THD
Voltage THD
Conversion value -P
(integral export power)
Temperature
37
KW9M Eco-POWER METER
To next page
38
KW9M Eco-POWER METER
Current
Voltage
Phase-voltage Line-voltage
Power factor
Frequency
Current THD
Voltage THD
Phase-voltage THD Line-voltage THD
Temperature
39
KW9M Eco-POWER METER
40
KW9M Eco-POWER METER
<1P2W/1P3W/3P4W>
Active Reactive Apparent
<3P3W>
Active Reactive Apparent
41
KW9M Eco-POWER METER
<1P2W/1P3W/3P4W>
Phase 1/ 1st circuit Phase 2/ 2nd circuit Phase 3/ 3rd circuit
<1P2W/1P3W/3P4W>
Active Reactive Apparent
<3P3W>
Active Reactive Apparent
・Total integral power is measured and displayed from 0.000 to 29999999 (kWh/kvarh/kVAh).
・The decimal point is changed automatically.
(After reach the full scale, 29999999, the value reverts to 0.000 but continues to measure.)
*At this window, present total integral power is displayed even if integral powers of each phase/ each
circuit return to ‘0’ after measuring to full-scale or reset. Therefore the total value of displayed integral
power of each phase/each circuit is different from the value at this window.
42
KW9M Eco-POWER METER
<1P2W/1P3W/3P4W>
Active Reactive
<3P3W>
Active Reactive
・Total integral power is measured and displayed from 0.000 to 29999999 (kWh/kvarh/kVAh).
・the decimal point is changed automatically.
(After reach the full scale, 29999999, the value reverts to 0.000 but continues to measure.)
*At this window, present total export power is displayed even if integral powers of each phase/ each
circuit return to ‘0’ after measuring to full-scale or reset. Therefore the total value of displayed integral
power of each phase/each circuit is different from the value at this window.
43
KW9M Eco-POWER METER
<1P2W/1P3W/3P4W>
Phase 1/ 1st circuit
Active Reactive Apparent
(After reach the full scale, 9999999.9, the value reverts to 0.000 but continues to measure.)
44
KW9M Eco-POWER METER
<1P2W/1P3W/3P4W>
Phase 1/ 1st circuit
Active Reactive
(After reach the full scale, 9999999.9, the value reverts to 0.000 but continues to measure.)
How to reset integral power (active/reactive/apparent) and integral export power (active/reactive)
・You can reset the value at the optional functions settings.
Refer to 4.4.3 setting for optional functions in detail.
45
KW9M Eco-POWER METER
6.2.7 Current
・The present current value is displayed.
6.2.8 Voltage
・The present voltage is displayed.
・Press <SHIFT/▽> to change phase voltage and line voltage.
(Line voltage is not displayed for 1P2W system. Phase voltage is not displayed for 3P3W system.
Phase voltage Line voltage
・When input voltage is under 3V (when VT ratio is 1.), it displays “0.0” and doesn’t measure.
・When input voltage exceeds 600V or the display range, it displays “- - - - -“.
Check and confirm the measurement environment.
・Voltage measuring points
Eco-POWER METER measures the voltage as below.
Display 1P2W 1P3W 3P3W 3P4W
R-voltage (L1-N)
1 R-voltage (L1-N) R-voltage (L1-N)
or 1st circuit R-voltage
None or
2 None No display S-voltage (L2-N)
2nd circuit R-voltage
None or
3 T-voltage (L3-N) T-voltage (L3-N)
3rd circuit R-voltage
12 R-voltage (L1-N) RS-voltage (L1-L2) RS-voltage (L1-L2)
46
KW9M Eco-POWER METER
*Power factor operation is a method assuming balanced load. The error might be big when it
measures unbalanced load.
6.2.10 Frequency
・The present frequency is displayed.
<1P2W/1P3W/3P4W> <3P3W>
47
KW9M Eco-POWER METER
<1P2W/1P3W/3P4W>
Total Phase 1 (1st circuit) Phase 2 (2nd circuit) Phase 3 (3rd circuit)
<3P3W>
Total
<1P2W/1P3W/3P4W>
Total Phase 1 (1st circuit) Phase 2 (2nd circuit) Phase 3 (3rd circuit)
<3P3W>
Total
48
KW9M Eco-POWER METER
6.2.15 Temperature
・The present temperature is displayed.
・Temperature measuring function is the simple function Use this only to check temperature trend
and do not use for control.
・It measures by built-in thermistor, therefore it differs the measuring value according to the internal
circuit conditions (communication, input current). Use it for your reference.
・When the temperature of the front is much different from the temperature of installed panel, when
it cools inside the panel, it is impossible to measure correctly. Use the temperature correction
function in order to adjust the temperature and use only to check temperature trend.
49
KW9M Eco-POWER METER
Item indicator
Peak demand
Lighting
[DEMAND]
50
KW9M Eco-POWER METER
Present demand
Active power Reactive power Apparent power
51
KW9M Eco-POWER METER
52
KW9M Eco-POWER METER
Chapter 7 Communications
7.1 Communication Procedures
Communication starts with command transmission from the host computer (hereafter Master) and ends
with the response of Eco-POWER METER (hereafter Slave).
Master Slave
Command • Acknowledgement
When master sends setting command, slave responds by sending
Acknowledgement the acknowledgement.
• No response
Command Slave will not respond to master in the following cases.
• Global address “FF” (MEWTOCOL) is set.
• Broadcast address “00H” (Modbus protocol) is set.
No response • Communication error (framing error, parity error)
• CRC-16 discrepancy (Modbus RTU mode)
• CS discrepancy (DL/T645)
53
KW9M Eco-POWER METER
②Responses
◆Command and response formats
Command message
Des- Check Termi- (To next command)
(Host computer) Header Text
tination code nator
Check Termi-
(Eco-POWER METER) Header Source Text
code nator
Normal response message
◇Control codes
Name Character ASCII code Explanation
Header % 25H Indicates the beginning of a message.
Indicates that the data comprises a command
Command # 23H
message.
Normal Indicates that the data comprises a normal response
$ 24H
response message.
Error Indicates that the data comprises a response message
! 21H
response when an error occurs.
Terminator CR 0DH Indicates the end of a message.
◇Destination and source AD (H), (L)
Two-digit decimal 01 to 99 (ASCII codes)
Command messages contain a station number for Eco-POWER METER that receives the message.
When FF (ASCII code table) is used, however, the transmission is a global transmission (sent to all
stations at once).
Note) When a global transmission is sent, no response to the command message is returned.
◇Block check code Bcc (H), (L)
Two- digit hexadecimal 00 to FF (ASCII codes)
These are codes (horizontal parity) that are used to detect errors in the transmitted data.
If “**” is entered instead of “Bcc”, however, messages can be transmitted without the Bcc. In this case,
the Bcc is included with the response
◇Error code Err (H), (L)
Two- digit hexadecimal 00 to FF (ASCII codes)
These indicate the content if an error occurs.
◆Bcc (Block Check Code)
-The Bcc is a code that carries out an error check using horizontal parity, to improve the reliability of
the data being sent.
-The Bcc uses an exclusive OR from the header (%) to the final character of the text, and converts the
8- bit data into a 2-character ASCII code.
Example) % 0 1 # R T 0 1 CR
↑ ↑ ↑ ↑ ↑
Header Station No.1 Command RT 2-character
Command Bcc
% 0 1 # R T 0 1
25H 30H 31H 23H 52H 54H Bcc(H)=0(30H)
Bcc(L)=1(31H)
①Takes exclusive OR ②Converts to ASCII format
54
KW9M Eco-POWER METER
DT00095 Auto display start 1min Unsigned 16bit 0 to 99 (0: fix display item) R/W
55
KW9M Eco-POWER METER
56
KW9M Eco-POWER METER
57
KW9M Eco-POWER METER
58
KW9M Eco-POWER METER
59
KW9M Eco-POWER METER
60
KW9M Eco-POWER METER
61
KW9M Eco-POWER METER
7.3.4 Command
Eco-POWER METER has 5 kinds of commands.
Command name Code Explanation
Read data area RD Reads the contents of data area.
Write data to data area WD Writes data to a data area.
Resister or Reset data monitored MD Resisters the data to be monitored.
Monitoring start MG Monitors a registered data.
Read status RT Reads the specifications of Eco-POWER METER and error code
if an error occurs.
◇Error response (lower word) (higher word) (lower word) (higher word)
Destination Starting word No. Ending word No. First writing data
% # W D D 5 characters 5 characters 4 characters ⇒
×101 ×100 ×104 ×103 ×102 ×101 ×100 ×104 ×103 ×102 ×101 ×100 ×161 ×160 ×163 ×162
62
KW9M Eco-POWER METER
◆[MD]: Register or Reset data monitored (Registers the data to be monitored.) *Up to 16 points can be registered for one unit.
◇Command (Register) Data specification ① Data specification n
Word No. Word No.
Destination Bcc
% # M D D 5 characters D 5 characters CR
1 0 4 3 2 1 0 4
×10 ×10 ×10 ×10 ×10 ×10 ×10 ×10 ×103 ×102 ×101 ×100 ×161 ×160
Destination Bcc
% # M D F F F F F F CR
×101 ×100 ×161 ×160
Source BCC
% $ M D CR
×101 ×100 ×161 ×160
Destination Bcc
% # M G CR
×101 ×100 ×161 ×160
◇Normal response (Monitoring successful) No. of characters
No. of characters
Source in data line Data ① Data n
Bcc
% $ M G 0 0 0 2 characters 4 characters 4 characters CR
×101 ×100 ×161 ×160 ×161 ×160 ×163 ×162 ×161 ×160 ×163 ×162 ×161 ×160
*With this unit, it responses "99" for Model code1, "16" for Model code2. (lower word) (higher word)
Note) The maximum number of reading slaves is 26 (57 bytes), the maximum number of writing
slaves is 23 (55 bytes).
63
KW9M Eco-POWER METER
◆Message configuration
RTU mode is configured to start after idle time processing of more than 3.5 character transmissions
and end after idle time processing of more than 3.5 character transmissions.
Master judges the transmission complete after no command for 4-characters idle time and process the
command.
*Transmission speed and judgment time to complete transmission
Transmission speed (bps) Judgment time to complete (ms)
38,400 about 1
19,200 about 2
9,600 about 4
4,800 about 8
2,400 about 16
1,200 About 32
◇Slave address:
Slave address is an individual instrument number on the slave side and is set within the range 1 to
247 (01H to F7H) for Modbus communication. Master identifies slaves by the slave address of the
requested message.
Slave informs master which slave is responding to master by placing its own address in the response
message. Slave address 0 (00H, broadcast address) can identify all slaves connected. However
slaves do not respond.
◇Function code: Function code is command code for the slave to undertake the following action types.
Function code Contents
03(03H) DT Read
06(06H) DT1 word write
16(10H) DT several data write
Function code is used to discern whether the response is normal (acknowledgement) or if any error
(negative acknowledgement) has occurred when slave returns response message to master.
When acknowledgement is returned, slave simply returns original function code. When negative
acknowledgement is returned, MSB of original function code is set as 1 for response.
For example, when the master sends request message setting 00H to function code by mistake, slave
returns 80H by setting MSB to 1, because the former is an illegal function.
For negative acknowledgement, the exception codes below are set to data of response message and
returned to master in order to inform it of what kind of error has occurred.
Exception code Contents
1(01H) Illegal Function (Non-existent function)
3(03H) Illegal data value (Value out of the devise numbers)
note1) Even if it commands to write (06H.10H) to non-existent data address, slave response with
acknowledgement. However, it doesn’t write.
note2) Even if it commands to write the value out of the setting range, slave response with
acknowledgement. However, it doesn’t write.
note3) The maximum number of reading slaves is 26 (57-byte), the maximum number of writing slaves
is 23 (55-byte).
64
KW9M Eco-POWER METER
◇Error check: 16-bit data to detect communication errors. Refer to the next.
◇Acknowledgement response
When command is to write 1 point, same massage of command is responded.
When command is to write several points, part of command message (6-byte) is responded.
◆Error check
After calculating CRC-16 (Cyclic Redundancy Check) from slave address to the end of data, the
calculated 16-bit data is appended to the end of message in sequence from low order to high order.
<How to calculate CRC>
In CRC system, the information is divided by the polynomial series. The remainder is added to the end
of the information and transmitted. The generation of polynomial series is as follows.
(Generation of polynomial series: X16 + X 15 + X 2 + 1)
1) Initialize the CRC-16 data (assumed as X) (FFFFH).
2) Calculate exclusive OR (XOR) with the 1st data and X. This is assumed as X.
3) Shift X one bit to the right. This is assumed as X.
4) When a carry is generated as a result of the shift, XOR is calculated by X of 3) and the fixed
value (A001H). This is assumed as X. If a carry is not generated, go to step 5).
5) Repeat steps 3) and 4) until shifting 8 times.
6) XOR is calculated with the next data and X. This is assumed as X.
7) Repeat steps 3) to 5).
8) Repeat steps 3) to 5) up to the last data.
9) Set X as CRC-16 to the end of message in sequence from low order to high order.
◆Message example
<1> Reading conversion rate (P) (005DH) of address 1
・Command
Slave Function Data item Number of Error check
3.5 idle 3.5 idle
address code data CRC-16
characters characters
(01H) (03H) (005DH) (0001H) (15D8H)
1 1 2 2 2 ←character
number
・Response message from slave in normal status (When Rate=1000(10.00) [03E8H])
Slave Function Number of Number of Error check
3.5 idle 3.5 idle
address code response byte data CRC-16
characters characters
(01H) (03H) (02H) (03E8H) (B8FAH)
1 1 1 2 2 ←character
number
<2> Setting conversion rate (P) (005DH) of address 1 (When rate is set to 20.00(2000) [07D0H])
・Command
Slave Function Data item Number of Error check
3.5 idle 3.5 idle
address code data CRC-16
characters characters
(01H) (06H) (005DH) (07D0H) (1BB4H)
1 1 2 2 2 ←character
number
・Response message from slave in normal status
Slave Function Data item Number of Error check
3.5 idle 3.5 idle
address code data CRC-16
characters characters
(01H) (06H) (005DH) (07D0H) (1BB4H)
1 1 2 2 2 ←character
number
65
KW9M Eco-POWER METER
66
KW9M Eco-POWER METER
Function
Data register Name Unit Kind of data Range: Hexadecimal
code
Mewtocol: 1H to 64H
Unsigned 03H/
0032H RS485 Device number - Modbus: 1H to F7H
16bit 06H/10H
DL/T645: 0H to 270FH
0H: 1200 1H: 2400 2H: 4800
RS485 Unsigned 03H/
0033H - 3H: 9600 4H: 19200
Transmission speed 16bit 06H/10H
5H: 38400
RS485 Unsigned 0H: 8bit-o 1H: 8bit-n 03H/
0034H -
Transmission format 16bit 2H: 8bit-E 06H/10H
Unsigned 03H/
0035H RS485 Stop bit - 1H, 2H
16bit 06H/10H
Unsigned 03H/
0036H RS485 Response time 1ms 1H to 63H
16bit 06H/10H
Unsigned 0H: 1P2W 1H: 1P3W 03H/
0037H Phase/Wire -
16bit 2H: 3P3W 3H: 3P4W 06H/10H
nd Rated A Unsigned 03H/
0038H CT type (2 ) 1H, 5H
(rms) 16bit 06H/10H
Primary side current Unsigned 03H/
0039H 1A 1H to FFFFH
of CT 16bit 06H/10H
Unsigned 03H/
003AH VT ratio 0.01 64H to EA60H
16bit 06H/10H
Temperature correction 03H/
003BH 0.1℃ Signed 16bit FC18H to 3E8H
value 06H/10H
Unsigned 03H/
0041H Update cycle 100ms 1H to AH
16bit 06H/10H
Unsigned 03H/
0046H Auto-off 1min 0H to 63H (0H: always ON)
16bit 06H/10H
Unsigned 03H/
0057H Conversion rate (-P) 0.01 0H to 270FH
16bit 06H/10H
Unsigned 03H/
005DH Conversion rate (P) 0.01 0H to 270FH
16bit 06H/10H
Unsigned 03H/
005EH Password - 0H to 270FH
16bit 06H/10H
Unsigned 03H/
005FH Auto display start 1min 0H to 63H (0H: fix display item)
16bit 06H/10H
Unsigned 03H/
0060H Display cycle 1sec 1H to 63H
16bit 06H/10H
Unsigned 03H/
0061H Luminance - 1H to 5H
16bit 06H/10H
Unsigned 0H: MEWTOCOL, 1H: MODBUS, 03H/
0062H Protocol -
16bit 2H: DL/T645 06H/10H
Unsigned 03H/
759CH Power demand type - 1H:sliding block, 2H:fixed block,
16bit 06H/10H
Power demand Unsigned 03H/
759DH 1min, 0H to 3CH
interval1 16bit 06H/10H
Power demand Unsigned 03H/
759EH 1min, 0H to 3CH
interval2 16bit 06H/10H
Current demand Unsigned 03H/
759FH 1min, 0H to 3CH
interval 16bit 06H/10H
Demand measurement Unsigned 03H/
75F8H - 0H: Start 1H: Stop
status 16bit 06H/10H
Unsigned 03H/
765CH Reset all integral value - 0H:No 1H:Yes
16bit 06H/10H
Unsigned 03H/
765DH Reset integral value 1 - 0H:No 1H:Yes
16bit 06H/10H
Unsigned 03H/
765EH Reset integral value 2 - 0H:No 1H:Yes
16bit 06H/10H
Unsigned 03H/
765FH Reset integral value 3 - 0H:No 1H:Yes
16bit 06H/10H
Unsigned 03H/
7662H Reset logging data - 0H:No 1H:Yes
16bit 06H/10H
Unsigned 03H/
7663H Cut off current 0.1% 1H to 1F4H
16bit 06H/10H
67
KW9M Eco-POWER METER
Function
Data register Name Unit Kind of data Range: Hexadecimal
code
0064H <LSB> Unsigned
Integral active power (1) 0.01kWh 0H to 3B9AC9FFH 03H/10H
0065H <MSB> 32bit
0066H <LSB> Unsigned
Integral active power (2) 0.01kWh 0H to 3B9AC9FFH 03H/10H
0067H <MSB> 32bit
0068H <LSB> Unsigned
Integral active power (3) 0.01kWh 0H to 3B9AC9FFH 03H/10H
0069H <MSB> 32bit
006AH <LSB> Total integral active Unsigned
0.01kWh 0H to B2D05DFDH 03H
006BH <MSB> power 32bit
006CH <LSB> Integral Unsigned
0.01kvarh 0H to 3B9AC9FFH 03H/10H
006DH <MSB> reactive power (1) 32bit
006EH <LSB> Integral Unsigned
0.01kvarh 0H to 3B9AC9FFH 03H/10H
006FH <MSB> reactive power (2) 32bit
0070H <LSB> Integral Unsigned
0.01kvarh 0H to 3B9AC9FFH 03H/10H
0071H <MSB> reactive power (3) 32bit
0072H <LSB> Total integral Unsigned
0.01kvarh 0H to B2D05DFDH 03H
0073H <MSB> reactive power 32bit
0074H <LSB> Integral Unsigned
0.01kVAh 0H to 3B9AC9FFH 03H/10H
0075H <MSB> apparent power (1) 32bit
0076H <LSB> Integral Unsigned
0.01kVAh 0H to 3B9AC9FFH 03H/10H
0077H <MSB> apparent power (2) 32bit
0078H <LSB> Integral Unsigned
0.01kVAh 0H to 3B9AC9FFH 03H/10H
0079H <MSB> apparent power (3) 32bit
007AH <LSB> Total integral Unsigned
0.01kVAh 0H to B2D05DFDH 03H
007BH <MSB> apparent power 32bit
007CH <LSB> Integral export active Unsigned
0.01kWh 0H to 3B9AC9FFH 03H/10H
007DH <MSB> power (1) 32bit
007EH <LSB> Integral export active Unsigned
0.01kWh 0H to 3B9AC9FFH 03H/10H
007FH <MSB> power (2) 32bit
0080H <LSB> Integral export active Unsigned
0.01kWh 0H to 3B9AC9FFH 03H/10H
0081H <MSB> power (3) 32bit
0082H <LSB> Total integral Unsigned
0.01kWh 0H to B2D05DFDH 03H
0083H <MSB> export active power 32bit
0084H <LSB> Integral export Unsigned
0.01kvarh 0H to 3B9AC9FFH 03H/10H
0085H <MSB> reactive power (1) 32bit
0086H <LSB> Integral export Unsigned
0.01kvarh 0H to 3B9AC9FFH 03H/10H
0087H <MSB> reactive power (2) 32bit
0088H <LSB> Integral export Unsigned
0.01kvarh 0H to 3B9AC9FFH 03H/10H
0089H <MSB> reactive power (3) 32bit
008AH <LSB> Total integral export Unsigned
0.01kvarh 0H to B2D05DFDH 03H
008BH <MSB> reactive power 32bit
008CH <LSB> Instantaneous active
0.01kW Signed 32bit FA0A1F01H to 5F5E0FFH 03H
008DH <MSB> power (1)
008EH <LSB> Instantaneous active
0.01kW Signed 32bit FA0A1F01H to 5F5E0FFH 03H
008FH <MSB> power (2)
0090H <LSB> Instantaneous active
0.01kW Signed 32bit FA0A1F01H to 5F5E0FFH 03H
0091H <MSB> power (3)
0092H <LSB> Total instantaneous
0.01kW Signed 32bit EE1E5D03H to 11E1A2FDH 03H
0093H <MSB> active power
0094H <LSB> Instantaneous reactive
0.01kvar Signed 32bit FA0A1F01H to 5F5E0FFH 03H
0095H <MSB> power (1)
0096H <LSB> Instantaneous reactive
0.01kvar Signed 32bit FA0A1F01H to 5F5E0FFH 03H
0097H <MSB> power (2)
0098H <LSB> Instantaneous reactive
0.01kvar Signed 32bit FA0A1F01H to 5F5E0FFH 03H
0099H <MSB> power (3)
009AH <LSB> Total instantaneous
0.01kvar Signed 32bit EE1E5D03H to 11E1A2FDH 03H
009BH <MSB> reactive power
009CH <LSB> Instantaneous apparent Unsigned
0.01kVA 0H to 5F5E0FFH 03H
009DH <MSB> power (1) 32bit
009EH <LSB> Instantaneous apparent Unsigned
0.01kVA 0H to 5F5E0FFH 03H
009FH <MSB> power (2) 32bit
00A0H <LSB> Instantaneous apparent Unsigned
0.01kVA 0H to 5F5E0FFH 03H
00A1H <MSB> power (3) 32bit
* ’Range’ is not the measurement range, it shows the data range.
68
KW9M Eco-POWER METER
Function
Data register Name Unit Kind of data Range: Hexadecimal
code
00A2H <LSB> Total instantaneous Unsigned
0.01kVA 0H to 11E1A2FDH 03H
00A3H <MSB> apparent power 32bit
00A4H <LSB> Unsigned
Voltage 1 0.1V 0H to 3B9AC9FFH 03H
00A5H <MSB> 32bit
00A6H <LSB> Unsigned
Voltage 2 0.1V 0H to 3B9AC9FFH 03H
00A7H <MSB> 32bit
00A8H <LSB> Unsigned
Voltage 3 0.1V 0H to 3B9AC9FFH 03H
00A9H <MSB> 32bit
00AAH <LSB> Unsigned
Voltage average 0.1V 0H to 3B9AC9FFH 03H
00ABH <MSB> 32bit
00ACH <LSB> Unsigned
Line voltage 1-2 0.1V 0H to 3B9AC9FFH 03H
00ADH <MSB> 32bit
00AEH <LSB> Unsigned
Line voltage 2-3 0.1V 0H to 3B9AC9FFH 03H
00AFH <MSB> 32bit
00B0H <LSB> Unsigned
Line voltage 3-1 0.1V 0H to 3B9AC9FFH 03H
00B1H <MSB> 32bit
00B2H <LSB> Unsigned
Line voltage average 0.1V 0H to 3B9AC9FFH 03H
00B3H <MSB> 32bit
00B4H <LSB> Unsigned
Current (1) 0.01A 0H to 3B9AC9FFH 03H
00B5H <MSB> 32bit
00B6H <LSB> Unsigned
Current (2) 0.01A 0H to 3B9AC9FFH 03H
00B7H <MSB> 32bit
00B8H <LSB> Unsigned
Current (3) 0.01A 0H to 3B9AC9FFH 03H
00B9H <MSB> 32bit
00BCH <LSB> Unsigned
Current average 0.01A 0H to 3B9AC9FFH 03H
00BDH <MSB> 32bit
Unsigned
00BEH Frequency (1) 0.1Hz 0H to 3E8H 03H
16bit
Unsigned
00BFH Frequency (2) 0.1Hz 0H to 3E8H 03H
16bit
Unsigned
00C0H Frequency (3) 0.1Hz 0H to 3E8H 03H
16bit
Unsigned
00C1H Frequency average 0.1Hz 0H to 3E8H 03H
16bit
00C2H PF (1) 0.001 Signed 16bit FC18H to 3E8H 03H
00C3H PF (2) 0.001 Signed 16bit FC18H to 3E8H 03H
00C4H PF (3) 0.001 Signed 16bit FC18H to 3E8H 03H
00C5H PF average 0.001 Signed 16bit FC18H to 3E8H 03H
00C6H <LSB> 0.001 Unsigned
Integral active power (1) 0H to 3B9AC9FFH 03H/10H
00C7H <MSB> kWh 32bit
00C8H <LSB> 0.001 Unsigned
Integral active power (2) 0H to 3B9AC9FFH 03H/10H
00C9H <MSB> kWh 32bit
00CAH <LSB> 0.001 Unsigned
Integral active power (3) 0H to 3B9AC9FFH 03H/10H
00CBH <MSB> kWh 32bit
00CCH <LSB> Total integral active 0.001 Unsigned
0H to B2D05DFDH 03H
00CDH <MSB> power kWh 32bit
00CEH <LSB> Integral 0.001 Unsigned
0H to 3B9AC9FFH 03H/10H
00CFH <MSB> reactive power (1) kvarh 32bit
00D0H <LSB> Integral 0.001 Unsigned
0H to 3B9AC9FFH 03H/10H
00D1H <MSB> reactive power (2) kvarh 32bit
00D2H <LSB> Integral 0.001 Unsigned
0H to 3B9AC9FFH 03H/10H
00D3H <MSB> reactive power (3) kvarh 32bit
00D4H <LSB> Total integral 0.001 Unsigned
0H to B2D05DFDH 03H
00D5H <MSB> reactive power kvarh 32bit
00D6H <LSB> Integral 0.001 Unsigned
0H to 3B9AC9FFH 03H/10H
00D7H <MSB> apparent power (1) kVAh 32bit
00D8H <LSB> Integral 0.001 Unsigned
0H to 3B9AC9FFH 03H/10H
00D9H <MSB> apparent power (2) kVAh 32bit
00DAH <LSB> Integral 0.001 Unsigned
0H to 3B9AC9FFH 03H/10H
00DBH <MSB> apparent power (3) kVAh 32bit
00DCH <LSB> Total integral 0.001 Unsigned
0H to B2D05DFDH 03H
00DDH <MSB> apparent power kVAh 32bit
* ’Range’ is not the measurement range, it shows the data range.
69
KW9M Eco-POWER METER
Function
Data register Name Unit Kind of data Range: Hexadecimal
code
00DEH <LSB> Integral export active 0.001 Unsigned
0H to 3B9AC9FFH 03H/10H
00DFH <MSB> power (1) kWh 32bit
00E0H <LSB> Integral export active 0.001 Unsigned
0H to 3B9AC9FFH 03H/10H
00E1H <MSB> power (2) kWh 32bit
00E2H <LSB> Integral export active 0.001 Unsigned
0H to 3B9AC9FFH 03H/10H
00E3H <MSB> power (3) kWh 32bit
00E4H <LSB> Total integral 0.001 Unsigned
0H to B2D05DFDH 03H
00E5H <MSB> export active power kWh 32bit
00E6H <LSB> Integral export 0.001 Unsigned
0H to 3B9AC9FFH 03H/10H
00E7H <MSB> reactive power (1) kvarh 32bit
00E8H <LSB> Integral export 0.001 Unsigned
0H to 3B9AC9FFH 03H/10H
00E9H <MSB> reactive power (2) kvarh 32bit
00EAH <LSB> Integral export 0.001 Unsigned
0H to 3B9AC9FFH 03H/10H
00EBH <MSB> reactive power (3) kvarh 32bit
00ECH <LSB> Total integral export 0.001 Unsigned
0H to B2D05DFDH 03H
00EDH <MSB> reactive power kvarh 32bit
00EEH <LSB> Instantaneous active 0.001
Signed 32bit FA0A1F01H to 5F5E0FFH 03H
00EFH <MSB> power (1) kW
00F0H <LSB> Instantaneous active 0.001
Signed 32bit FA0A1F01H to 5F5E0FFH 03H
00F1H <MSB> power (2) kW
00F2H <LSB> Instantaneous active 0.001
Signed 32bit FA0A1F01H to 5F5E0FFH 03H
00F3H <MSB> power (3) kW
00F4H <LSB> Total instantaneous 0.001
Signed 32bit EE1E5D03H to 11E1A2FDH 03H
00F5H <MSB> active power kW
00F6H <LSB> Instantaneous reactive 0.001
Signed 32bit FA0A1F01H to 5F5E0FFH 03H
00F7H <MSB> power (1) kvar
00F8H <LSB> Instantaneous reactive 0.001
Signed 32bit FA0A1F01H to 5F5E0FFH 03H
00F9H <MSB> power (2) kvar
00FAH <LSB> Instantaneous reactive 0.001
Signed 32bit FA0A1F01H to 5F5E0FFH 03H
00FBH <MSB> power (3) kvar
00FCH <LSB> Total instantaneous 0.001
Signed 32bit EE1E5D03H to 11E1A2FDH 03H
00FDH <MSB> reactive power kvar
00FEH <LSB> Instantaneous apparent 0.001 Unsigned
0H to 5F5E0FFH 03H
00FFH <MSB> power (1) kVA 32bit
0100H <LSB> Instantaneous apparent 0.001 Unsigned
0H to 5F5E0FFH 03H
0101H <MSB> power (2) kVA 32bit
0102H <LSB> Instantaneous apparent 0.001 Unsigned
0H to 5F5E0FFH 03H
0103H <MSB> power (3) kVA 32bit
0104H <LSB> Total instantaneous 0.001 Unsigned
0H to 11E1A2FDH 03H
0105H <MSB> apparent power kVA 32bit
0106H <LSB> Unsigned
Voltage 1 0.01V 0H to 3B9AC9FFH 03H
0107H <MSB> 32bit
0108H <LSB> Unsigned
Voltage 2 0.01V 0H to 3B9AC9FFH 03H
0109H <MSB> 32bit
010AH <LSB> Unsigned
Voltage 3 0.01V 0H to 3B9AC9FFH 03H
010BH <MSB> 32bit
010CH <LSB> Unsigned
Voltage average 0.01V 0H to 3B9AC9FFH 03H
010DH <MSB> 32bit
010EH <LSB> Unsigned
Line voltage 1-2 0.01V 0H to 3B9AC9FFH 03H
010FH <MSB> 32bit
0110H <LSB> Unsigned
Line voltage 2-3 0.01V 0H to 3B9AC9FFH 03H
0111H <MSB> 32bit
0112H <LSB> Unsigned
Line voltage 3-1 0.01V 0H to 3B9AC9FFH 03H
0113H <MSB> 32bit
0114H <LSB> Unsigned
Line voltage average 0.01V 0H to 3B9AC9FFH 03H
0115H <MSB> 32bit
70
KW9M Eco-POWER METER
Function
Data register Name Unit Kind of data Range: Hexadecimal
code
0116H <LSB> Unsigned
Current (1) 0.001A 0H to 3B9AC9FFH 03H
0117H <MSB> 32bit
0118H <LSB> Unsigned
Current (2) 0.001A 0H to 3B9AC9FFH 03H
0119H <MSB> 32bit
011AH <LSB> Unsigned
Current (3) 0.001A 0H to 3B9AC9FFH 03H
011BH <MSB> 32bit
011EH <LSB> Unsigned
Current average 0.001A 0H to 3B9AC9FFH 03H
011FH <MSB> 32bit
Unsigned
0120H Frequency (1) 0.01Hz 0H to 2710H 03H
16bit
Unsigned
0121H Frequency (2) 0.01Hz 0H to 2710H 03H
16bit
Unsigned
0122H Frequency (3) 0.01Hz 0H to 2710H 03H
16bit
Unsigned
0123H Frequency average 0.01Hz 0H to 2710H 03H
16bit
0131H<LSB> Present demand Unsigned
0.001kW 0H to 5F5E0FFH 03H
0132H<MSB> (active power) 32bit
0133H<LSB> Present demand Unsigned
0.001kvar 0H to 5F5E0FFH 03H
0134H<MSB> (reactive power) 32bit
0135H<LSB> Present demand Unsigned
0.001kVA 0H to 5F5E0FFH 03H
0136H<MSB> (apparent power) 32bit
0137H<LSB> Present demand Unsigned
0.001kW 0H to 5F5E0FFH 03H
0138H<MSB> (active power (export)) 32bit
0139H<LSB> Present demand Unsigned
0.001kvar 0H to 5F5E0FFH 03H
013AH<MSB> (reactive power (export)) 32bit
013BH<LSB> Present demand Unsigned
0.001A 0H to 5F5E0FFH 03H
013CH<MSB> (current①) 32bit
013DH<LSB> Present demand Unsigned
0.001A 0H to 5F5E0FFH 03H
013EH<MSB> (current②) 32bit
013FH<LSB> Present demand Unsigned
0.001A 0H to 5F5E0FFH 03H
0140H<MSB> (current③) 32bit
Unsigned
0144H PF status - 0H: even, 1H: Lag, 2H: Lead 03H
16bit
0145H<LSB> Total integral active Unsigned
0.01kWh 0H~3B9AC9FFH 03H
0146H<MSB> power 32bit
0147H<LSB> Total integral Unsigned
0.01kvarh 0H~3B9AC9FFH 03H
0148H<MSB> reactive power 32bit
0149H<LSB> Total integral Unsigned
0.01kVAh 0H~3B9AC9FFH 03H
014AH<MSB> apparent power 32bit
014BH<LSB> Total integral Unsigned
0.01kWh 0H~3B9AC9FFH 03H
014CH<MSB> export active power 32bit
014DH<LSB> Total integral export Unsigned
0.01kvarh 0H~3B9AC9FFH 03H
014EH<MSB> reactive power 32bit
014FH<LSB> Total integral active 0.001 Unsigned
0H~3B9AC9FFH 03H
0150H<MSB> power kWh 32bit
0151H<LSB> Total integral 0.001 Unsigned
0H~3B9AC9FFH 03H
0152H<MSB> reactive power kvarh 32bit
0153H<LSB> Total integral 0.001 Unsigned
0H~3B9AC9FFH 03H
0154H<MSB> apparent power kVAh 32bit
0155H<LSB> Total integral 0.001 Unsigned
0H~3B9AC9FFH 03H
0156H<MSB> export active power kWh 32bit
0157H<LSB> Total integral export 0.001 Unsigned
0H~3B9AC9FFH 03H
0158H<MSB> reactive power kvarh 32bit
Signed
01A2H Temperature 0.1℃ FC18H to 3E8H 03H
16bit
0298H<LSB> Signed
Phase voltage THD① 0.001% FFF9E580H to 61A80H 03H
0299H<MSB> 32bit
029AH<LSB> Signed
Phase voltage THD② 0.001% FFF9E580H to 61A80H 03H
029BH<MSB> 32bit
029CH<LSB> Signed
Phase voltage THD③ 0.001% FFF9E580H to 61A80H 03H
029DH<MSB> 32bit
71
KW9M Eco-POWER METER
Function
Data register Name Unit Kind of data Range: Hexadecimal
code
029EH<LSB> Phase voltage THD Signed
0.001% FFF9E580H to 61A80H 03H
029FH<MSB> average 32bit
02A0H<LSB> Signed
Line voltage THD 1-2 0.001% FFF9E580H to 61A80H 03H
02A1H<MSB> 32bit
02A2H<LSB> Signed
Line voltage THD 2-3 0.001% FFF9E580H to 61A80H 03H
02A3H<MSB> 32bit
02A4H<LSB> Signed
Line voltage THD 3-1 0.001% FFF9E580H to 61A80H 03H
02A5H<MSB> 32bit
02A6H<LSB> Line voltage THD Signed
0.001% FFF9E580H to 61A80H 03H
02A7H<MSB> average 32bit
02A8H<LSB> Signed
Current THD① 0.001% FFF9E580H to 61A80H 03H
02A9H<MSB> 32bit
02AAH<LSB> Signed
Current THD② 0.001% FFF9E580H to 61A80H 03H
02ABH<MSB> 32bit
02ACH<LSB> Signed
Current THD③ 0.001% FFF9E580H to 61A80H 03H
02ADH<MSB> 32bit
02AEH<LSB> Current THD Signed
0.001% FFF9E580H to 61A80H 03H
02AFH<MSB> average 32bit
13B0H <LSB> Export power Unsigned
0.01 0H to 3B9AC9FFH 03H
13B1H <MSB> conversion value (1) 32bit
13B2H <LSB> Export power Unsigned
0.01 0H to 3B9AC9FFH 03H
13B3H <MSB> conversion value (2) 32bit
13B4H <LSB> Export power Unsigned
0.01 0H to 3B9AC9FFH 03H
13B5H <MSB> conversion value (3) 32bit
13B6H <LSB> Total export power Unsigned
0.01 0H to B2D05DFDH 03H
13B7H <MSB> conversion value 32bit
13E2H <LSB> Unsigned
Conversion value (1) 0.01 0H to 3B9AC9FFH 03H
13E3H <MSB> 32bit
13E4H <LSB> Unsigned
Conversion value (2) 0.01 0H to 3B9AC9FFH 03H
13E5H <MSB> 32bit
13E6H <LSB> Unsigned
Conversion value (3) 0.01 0H to 3B9AC9FFH 03H
13E7H <MSB> 32bit
13E8H <LSB> Unsigned
Total conversion value 0.01 0H to B2D05DFDH 03H
13E9H <MSB> 32bit
7C9FH<LSB> Max. demand value 0.001 Unsigned
0H to B2D05DFDH 03H
7CA0H<MSB> active power kW 32bit
7CA4H<LSB> Max. demand value 0.001 Unsigned
0H to B2D05DFDH 03H
7CA5H<MSB> reactive power kvar 32bit
7CA9H<LSB> Max. demand value 0.001 Unsigned
0H to B2D05DFDH 03H
7CAAH<MSB> apparent power kVA 32bit
7CAEH<LSB> Max. demand value 0.001 Unsigned
0H to B2D05DFDH 03H
7CAFH<MSB> active power (export) kW 32bit
7CB3H<LSB> Max. demand value 0.001 Unsigned
0H to B2D05DFDH 03H
7CB4H<MSB> reactive power (export) kvar 32bit
7CB8H<LSB> Max. demand value Unsigned
0.001A 0H to 3B9AC9FFH 03H
7CB9H<MSB> current1 32bit
7CBDH<LSB> Max. demand value Unsigned
0.001A 0H to 3B9AC9FFH 03H
7CBEH<MSB> current2 32bit
7CC2H<LSB> Max. demand value Unsigned
0.001A 0H to 3B9AC9FFH 03H
7CC3H<MSB> current3 32bit
72
KW9M Eco-POWER METER
◆Frame format
Frame start number 68H
A0
A1
A2
Address field
A3
A4
A5
Frame start symbol 68H
Control code C
Data field length L
Data field DATA
Check code CS
End symbol 16H
73
KW9M Eco-POWER METER
Item Contents
Transmission direction (D7) 0 Command frame from master
1 Response frame from slave
Slave response flag (D6) 0 Slave response is correct.
1 Slave response is wrong.
Subsequent frame flag (D5) 0 No subsequent data
1 With subsequent data
Function code (D4 to D0) 00000 Vacant
01000 Not support
10001 Read out data
10010 Not support
10011 Read out transmission address (device number)
10100 Write data
10101 Write transmission address (device number)
10110 Not support
10111 Change transmission speed
11000 Change password
11001 Not support
11010 Reset integral power
11011 Not support
Ex.) In case of the receiving data is ‘45 34 (N1 N0’. (Receive voltage 112V)
Code Value Calculation
N1 12 = 45-33
N0 01 = 34-33
It receives from the lower, it is ‘N0 N1’ and the voltage is 112V.
(It receives with hexadecimal but it doesn’t convert the value subtract 33 to decimal.)
74
KW9M Eco-POWER METER
⇒ A0 A1 A2 A3 A4 A5 CS 16H
continue Transmission address read out from slave
*No response when slave is abnormal.
75
KW9M Eco-POWER METER
Write data
It is available only with pressing <MODE> key (programming key).
Without pressing programming key, it doesn’t response.
For data writing, authorization level (PA0) should be designated, but only ‘0’ is supported.
For workers code, it doesn’t record and the code is fixed to ‘0’.
⇒ C0 C1 C2 C3 N1 ・・・ Nm CS 16H
continue Workers code (33H fix) Writing data
A0 A1 A2 A3 A4 A5 CS 16H
⇒
Transmission address to write slave
continue
(Add 33H to transmission address value)
76
KW9M Eco-POWER METER
Change password
It changes password.
It is available only with pressing <MODE> key (programming key).
Without pressing programming key, it doesn’t response.
For changing password, authorization level (PA0) should be designated, but only ‘0’ is supported.
・Command from master; Control code 18H
68H A0 A1 A2 A3 A4 A5 68H 18H 0CH ⇒
Transmission address Control code continue
77
KW9M Eco-POWER METER
⇒ PA P0 P1 P2 ⇒
continue Authorization level (33H fix) Password (P2: 33H fix) continue
⇒ C0 C1 C2 C3 CS 16H
continue Workers code (33H fix)
Programming key
Programming key is <MODE> key.
With every display, it is possible to change the settings only when pressing <MODE> key.
78
KW9M Eco-POWER METER
79
KW9M Eco-POWER METER
*For signed data, the upper bit shows the sign. ‘0’ shows plus and ‘1’ shows minus.
80
KW9M Eco-POWER METER
It is necessary to install USB driver (kw9musb_vxxx.inf) for connecting KW9M Eco-POWER METER
via USB communication.
* Once installing USB driver, it is not necessary to install from the second time.
* When you change the using port, install the driver again.
81
KW9M Eco-POWER METER
[PROG] on the upper line and the current version [x.xx] on the middle
line are displayed.
This is ready to update the firmware of Eco-POWER METER.
82
KW9M Eco-POWER METER
83
KW9M Eco-POWER METER
Click [Version] and it displays the current version. After it shows the version, you need to
update the firmware if it is not necessary. If not, Eco-POWER METER can’t be used.
When you have used KW Version Upgrade Tool before, it displays the last updated
firmware. If the firmware was moved, the error window will be appeared.
Select firmware again and update it.
6) When it starts updating, the indicator is appeared and it updates to the selected firmware.
84
KW9M Eco-POWER METER
7) When it completes updating the firmware, the complete window will be appeared.
Click [OK].
85
KW9M Eco-POWER METER
Chapter 9 Specifications
9.1 Main unit
100 to 240V AC
Rated supply voltage
100 to 300V DC
Rated frequency 50/60Hz
Approx. 5VA (240V AC at 25℃)
Nominal power consumption
Approx. 3W (240V DC at 25℃)
Inrush current 30A or less (240V AC/DC at 25℃)
Allowable supply voltage 85 to 264V AC (85 to 110% of rated supply voltage)
Allowable momentary
10ms
power-off time
Accuracy guarantee -10 to + 55℃
Ambient temperature Operation -25 to + 55℃
Storage -25 to + 70℃
Ambient humidity 30 to 85%RH (at 20℃) non-condensing
a) enclosure ⇔ all terminals
Between the isolated b) between insulated circuits
Breakdown voltage (initial)
circuits: 2000V/1min ・power supply terminals
⇔other terminals
・RS485 terminals
Between the isolated ⇔other terminals
Insulation resistance (initial)
circuits: 100 MΩ or more ・measured current input terminals
⇔ other terminals
10 to 150Hz (7.5 minutes/cycle)
Vibration resistance single amplitude:0.075mm (1h on 3 axes)
10 to 55Hz (1 minute/cycle)
single amplitude:0.375mm (1h on 3 axes)
Shock resistance Min. 294m/s2 (5 times on 3 axes)
Display method LCD with backlight
Display updated cycle 100 to 1000ms (set with setting mode)
Power failure memory method Internal memory (overwrite 1010 or more)
Degree of protection Front: IP51 Back: IP20
Sea level altitude Under 2,000m
96 x 96 x 56 mm (without terminal block)
Dimensions W/H/D
96 x 96 x 68 mm (with terminal block)
Weight Approx. 450g
Cable conductor cross section
Single wire / stranded cable 1pc.
0.5 to 4mm2 (AWG20to 12)
Single wire/ stranded cable 2pcs.
Terminal connection 0.5 to 2 mm2 (AWG20 to 14)
Stripping length 7-8mm
Connection method Screw M2.5
Tightening torque 0.4 to 0.5 N m
86
KW9M Eco-POWER METER
87
KW9M Eco-POWER METER
<RS485>
Interface Conforming to RS485
Communication method Half-duplex
Synchronous system Synchronous communication method
Isolation status Isolated with the internal circuits
MEWTOCOL, MODBUS(RTU), DL/T645-2007 *1
Protocol
(select with setting mode)
Number of connected unit 99 (max.) *2
Transmission distance 1200m *3
38400, 19200, 9600, 4800, 2400, 1200bps
Transmission speed
(select with setting mode)
Data length 8bit (fixed)
Transmission Not available / odd number / even number
Parity
format (select with setting mode)
Stop bit 1bit, 2bit (select with setting mode)
*1 MEWTOCOL is the protocol for PLC from Panasonic.
DL/T645 is the China power-meter standard. Only DL/T645-2007 is supported.
*2 For RS485 converter on the computer side, we recommend SI-35 and SI-35USB (from LINE EYE
Co.,Ltd.). When using SI-35,SI-35USB or PLC from our company (which can be connected up to 99
units), up to 99 can be connected. In case using this system with the other devices, up to 31 can be
connected.
*3 Please check with the actual devices when some commercial devices with RS485 interface are
connected. The number of connected devices, transmission distance, and transmission speed may
be different according to using transmission line.
88
KW9M Eco-POWER METER
*Includes the possibility that the internal memory life has expired.
89
KW9M Eco-POWER METER
Chapter 10 Mounting
10.1 Dimensions
10.1.1 Main unit
(Unit: mm)
(Clearance: ±1.0)
90
KW9M Eco-POWER METER
Revision History
Issue Date Manual No. Content of revision
November, 2012 WUME-KW9M-01 First edition