G Cem4000 Ops B
G Cem4000 Ops B
020038
G-CEM 4000
Multi-Gas Analyser
OPS. 080
Issue : B
Revision :
Date : September 2002
CODEL
Doc i/d : 0080/6
CODEL
OPS. 080
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
While every effort has been made to ensure that this manual is free from errors,
CODEL supply all information without warranty.
OPS. 080
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
OPS. 080
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Table of Contents
1. CODEL G-CEM4000 Analyser – Introduction 1
1.1. Foreword 1
1.2. Basic Principles 3
1.3. Emission Monitoring and the G-CEM4000 6
1.4. User Interface 7
1.5. Analogue and Logic Inputs and Outputs 7
1.6. CDC Serial Port - for use with the CODEL IEM system 8
1.7. Analyser Protection 9
2. Summary Specification 10
3.1. Unpacking. 13
3.2. Additional Materials 15
3.3. Ancillary/Additional Equipment 17
3.4. Services 18
4. Installation 19
OPS. 080
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
5. Commissioning 39
6. Analyser Records 68
7.1. Introduction 70
7.2. Factory Calibration 70
7.3. Verification 70
7.4. Re-calibration 73
8. Maintenance 74
9. Fault Finding 75
OPS. 080
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Please take a few minutes to read this section before proceeding with
installation. It is designed to provide an overview of the analyser and its
capabilities so that the information given later will be more easily
understood.
1.1. Foreword
At the heart of this concept is the SmartCEM station containing all the analysers
and monitors to provide comprehensive stack emission monitoring. The
SmartCEM Station Control Unit (SCU) provides power to and communicates
with the analysers and monitors within that station.
OPS. 080 1
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
OPS. 080 2
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
The G-CEM4000 analyser uses an in-situ probe set into a duct to measure the
concentration of gases of interest. Figure 2 illustrates the arrangement. The in-
situ tube includes a section that allows the diffusion of flue gases into the
measurement zone or the dispersion of purge or calibration gas out of the tube
and into the duct. This section of the tube is the analysers’ measurement cell.
The analyser is capable of simultaneous measurement of up to six different
gases (plus water vapour as a seventh measurement if required).
OPS. 080 3
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
OPS. 080 4
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
The transceiver unit containing the infrared source and detector system,
required to measure the received light energy after its passage through the gas,
is totally isolated from the flue gas. There is, therefore, no contact between the
analyser electronics and the flue gas. Correctly installed and commissioned,
this provides the opportunity to achieve very low maintenance factors and
totally eliminates any possibility of altering the composition of the flue gases to
be measured.
• The Gas Control Unit (GCU) that controls the input of zero and span
calibration gases into the analyser. It contains the necessary
compressed air filtration and drying equipment to ensure high quality air
supply for the zero calibration and probe purge functions. The analyser
power supply and Station Control Unit (SCU) are also housed within the
GCU. The function of the SCU is as an emissions data processing unit,
communications centre for the monitor and controller of the zero and
span calibration functions. The SCU also acts as a data logging device
in which hours emission and diagnostic data is stored for retrieval in the
case of loss of main data logging in the remote pc or DCS system.
• A Junction Box through which is routed the cabling from the transceiver
and the temperature, pressure and oxygen sensors and the cable to the
GCU. The unit should be mounted local to the analyser.
OPS. 080 5
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Although G-CEM4000 analysers can be used for process gas analysis, they
have been primarily designed to monitor pollutant emissions from industrial
stacks. Legislation governing such emissions usually requires data to be
reported in very specific formats. G-CEM4000 analysers are therefore
designed to fulfil this requirement without the need for external data
manipulation. Although differing in detail from country to country, the essential
demands of legislation are common world-wide.
1.3.1. Normalisation
This basic ppm measurement is always corrected for the duct pressure and
presented as vpm by the analyser. G-CEM4000 analysers have the capability
for the outputs and display to be configured in vpm (or %) or mg/m3 (which is a
mathematical conversion depending on the molecular weight of the gas being
measured and the flue gas temperature), or in mg/Nm3 (i.e. ’normalised’ to the
required standard conditions).
OPS. 080 6
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
1.3.2. Verification
Volt-free contact outputs (250V/10A) are provided for data valid and
measurement alarm level (common output for all measurement channel
alarms).
OPS. 080 7
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
1.6. CDC Serial Port - for use with the CODEL IEM system
The CDC is equipped with a 2-way serial communications port for use with the
CODEL IEM system. On a plant where more than one CODEL analyser is
installed, this is the preferred method and, even for a single analyser
installation, can provide significant benefits. The main ones are:
• All real time and historical data and diagnostics can be accessed
remotely via a MODEM.
OPS. 080 8
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
G-CEM4000 analysers are designed for outdoor installation and all units are
constructed to IP65 (NEMA 4) standards and are designed for ambient
temperatures from -20o to +55oC. For outdoor installation, an optional weather
shield is recommended for the transceiver.
OPS. 080 9
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
2. Summary Specification
Measurements
Measurement Spans
Note that although very low spans can be configured, this should not be
done without consideration of the measurement uncertainty.
Measurement Uncertainty
• CO2 ± 0.2%
• H 2O ± 0.2%
• Other gases ± 10vpm or ±2% of measurement (whichever
is the greater).
Measurement Units
OPS. 080 10
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Display
• real-time measurements
• operating parameters
• diagnostic information
• set-up menus
Outputs
• Logic
(located in SCU)
Inputs
OPS. 080 11
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Dimensions
• CDC
• Junction Box
OPS. 080 12
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
3.1. Unpacking.
The analyser and any other items are normally protected for transportation by
an expanded foam packing material. When unpacking, please ensure that
smaller items are not discarded with the packing material.
If any items are missing please inform CODEL or your local CODEL agent
immediately.
OPS. 080 13
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
The transceiver, GCU and SCU, are supplied with blanking plugs fitted in the
cable gland entry holes. Cable Glands are packed separately.
OPS. 080 14
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
• Cables
Note that screened cables should have the screen terminated as described in
Section 4. Installation. If steel wire armoured cable is used, the steel wire
sheath should be earthed at the analyser end only.
• Other Materials
OPS. 080 15
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
- Compressed air supply (10 l/mincleaned and dry to -20°C) for (a)
measurement cell purge (2 l/sec on demand) and (b) purging of
the neutral zone (0.5 l/min/sec continuous). 10mm o/d. PTFE
tube is required.
OPS. 080 16
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
The 4000 analyser is rarely supplied alone. It is usually associated with other
equipment that makes up an emission monitoring system. In planning
installation, consideration should be given to the requirements of other
equipment by consulting the specific manuals so that the whole system may be
installed in the most cost effective and efficient way. If the complete system
has been engineered by CODEL, detailed contract specific information and
schematics will have been provided.
- Non-CODEL monitors/analysers
OPS. 080 17
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
3.4. Services
OPS. 080 18
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
4. Installation
Installation of the several units that make up a 4000 Series analyser may be
carried out in any order. However, the recommended order, reflected in this
manual, is:
The next factor to consider is that of flue gas pressure. Choosing a position
where the flue gas is at negative pressure, compared with ambient pressure, is
not as important as it is for conventional open path cross-duct analysers.
However, it is advantageous in reducing pressure and flow requirements, to
ensure complete flooding of the measurement cell, of both zero and calibration
gases. Under normal operating conditions negative flue gas pressure exists
from 10-15m after the ID fan outlet to stack exit. If possible, open any existing
port near the selected measurement position to confirm.
OPS. 080 19
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Take care to ensure that duct vibration at the selected mounting point is
minimal as severe vibration may cause malfunctioning of the instrument or at
worst a catastrophic failure of the duct wall due the effects of vibrating 84kg
continuously.
Take care in doing this. Use suitable protective clothing, including eye
protection. Positive pressure in the duct will cause hot flue gases to be
vented from the open port.
Conditions vary from plant to plant but, in general, the following guidelines
should be followed:
OPS. 080 20
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
The measurement tube should always be on the centre line of circular ducts.
On square or rectangular ducts, the axis may be displaced from the centre line.
Figure 8 shows the recommended displacement limit.
OPS. 080 21
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
OPS. 080 22
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Cut 'slip-fit' holes in the duct at the chosen position; note that the assembly
should be installed at a 50 downward angle to the horizontal to allow
condensate to flow into the stack
Before proceeding, note that the total weight of the measurement probe and
transceiver assembly is approximately 84kg. The duct or stack should be
appropriately strengthened if necessary (see Figure 10).
OPS. 080 23
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Tack-weld the inner end of the stub-pipe to the duct/stack. Ensure that it is
aligned at least 50 downward from the horizontal.
If the analyser is not being fitted immediately it is advisable to close the stub-
pipe with a blanking plate (not supplied) cut and drilled to suit the fitted flange.
OPS. 080 24
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Double skin stacks are often designed to allow movement between the inner
and outer skins, to accommodate thermal expansion or contraction when plant
operation changes. This can cause unacceptable movement of stub-pipes if
mounting arrangements are not designed to maintain alignment. There are too
many structural variations to provide a single solution but, if in doubt, consult
CODEL before commencing installation.
OPS. 080 25
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
The G-CEM4000 requires air supplies for the pre-measurement zone and to
purge the measurement cell for zero verification. This supply should pass
through a proprietary filter unit prior to entering the GCU for further distribution.
a) Plan how the job is to be done and have all necessary lifting and
safety equipment available.
b) Ensure that all personnel involved know the plan, are adequately
protected and that there is no risk to others working nearby.
d) Remember that as the tube is inserted further into the duct, the
weight and moment exerted by the tube within the duct will increase,
whilst the available length of tube (outside the duct) with which to
control this will decrease.
OPS. 080 26
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
e) Remember that, if the plant is operating, the tube will get hot with
time. Take all necessary precautions to deal with this.
The measurement tube is supplied fully assembled but without the transceiver
or air purge units fitted.
The tube is now ready for insertion into the duct or stack, through the previously
fitted stub-pipe and site mounting-flange. Note that when finally positioned the
diffuser section of the tube should be rotated so that the four rows of diffuser
disks are positioned as shown in Figure 2 in relation to the general gas flow. As
these are out of sight when the tube is inserted, mark one end of the tube so
that the correct orientation can be achieved after installation. When installing
the measurement tube, ensure that the pressure sensor is mounted above the
centre line of the probe
OPS. 080 27
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Use the mark previously made to rotate the tube so that the diffusion disks are
oriented to the general gas flow as shown in Figure 2. This is important!
OPS. 080 28
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
The Transceiver may now be attached to the probe assembly using the six off
M6 x 25 setscrews provided. It is advisable to support the weight of the
analyser on the two mounting pins on the mounting flange while fitting the
setscrews.
Cabling from the transceiver and the temperature, pressure and oxygen
sensors are routed through the junction box. The junction box should be
mounted local to the analyser using 4 x M6 bolts. Mounting hole details are
shown in Figure 3.
The GCU, shown below, is suitable for outdoor installation. The power supply
and SCU within the GCU are sealed to IP67. Permissible ambient temperature
range is –20 to +55oC.
power
SCU
supply
purge gas
zero/span
filtration &
calibration
drying
gas equipment
equipment
Figure 14 : GCU
OPS. 080 29
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Mount the GCU to a suitable load bearing surface wall using 4 x M8 bolts.
Mounting hole details are shown in Figure 3. Connect the compressed air input
line to the input connector and the air lines from the GCU to the neutral zone
and measurement zone of the probe. Connect any span gases to the span
inputs of the GCU.
Connect the nylon/PTFE tube to the GCU input and the outputs to the probe
(see Figure 15). When the tubes have been connected to the probe, turn on
the compressed air. Set the regulator to the neutral zone to 10psi and a flow
rate to the measurement zone of 10 l/min. The regulators are actuated by lifting
the black cap and turning; to lock, press the cap down. The compressed air
must be clean and dry as detailed in the Section 2. Summary Specification.
flow rotometer
span 2
solenoid
OPS. 080 30
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
The GCU is supplied with all internal cables fitted. External cables supplied by
the customer should be connected in accordance with the connection schedule
Figure 16.
Decide routing for all non-power cables (both those supplied by CODEL and
those sourced locally). Use common routing wherever possible and install
leaving sufficient free-end length to make final connections.
OPS. 080 31
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Fit the required number of cable glands. Maximum overall cable diameter is
15mm.
Connect the 10-core transceiver cable (only 9 cores used), together with the
temperature and pressure (and if used oxygen) sensor cables, to the terminal
connectors in the junction box as shown in Figure 18. Connect the cable
screen in the cable gland as illustrated in Figure 19. At the same time, if not
already set, set the address switch in the SCU to 01 (Figure 21).
Connect the 4-core local bus cable (customer supply) between the junction box
(Figure 18) and the terminal rail in the GCU (Figure 16 and Figure 20).
OPS. 080 32
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
OPS. 080 33
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
OPS. 080 34
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
temperature
2-core
red orange
pressure blue pink link 10 (9) core
2-core red orange cable from
blue grey transceiver
oxygen +ve yellow
2-core -ve white
0V green
MISO black
local bus to GCU MOSI blue
4-core +V brown
OPS. 080 35
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
cable
connection
block
address switch
OPS. 080 36
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Connect the 4-20mA outputs from the oxygen sensor to the Junction Box as
shown in Figure 18.
Any of these inputs will accept independently powered current loop inputs.
Input impedance is 237Ω and the common mode voltage range is ±200V DC.
The pressure and temperature inputs are also able to provide power for either
two- or three-wire transducers requiring a 24V DC supply.
All cable screens should either be connected to the cable glands as illustrated
in Figure 19 or terminated at the transducer. Screens must NOT be earthed
at more than one point.
If required, span verification may be carried out using certified test gases. This
is achieved by flooding the measurement cell with the required gas as shown in
Figure 22.
OPS. 080 37
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
OPS. 080 38
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
5. Commissioning
The analyser should now be fully installed and ready to be commissioned. This
involves the following basic procedures that can be carried out with the plant on
or off :
• zero calibration
Finally
Check that the neutral zone air purge is functioning. If not, take corrective
action.
OPS. 080 39
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
5.2. Power On
Switch on the power supply. The order in which these units are switched on is
not important.
If final connection of power supplies has been left until the commissioning
stage, note that the requirements are :
The following commissioning instructions are provided in detail and are written
for the first time user.
Connect the special interface cable between the pc serial port and the screw
connector on the GCU.
Start SmartCOM software and you will see the screen below. Set the correct pc
comms port identity in the 'Comms validity indicator'.
OPS. 080 40
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Set sensor selector to SCU. Insert address of SCU at Address selector (this
will probably be 1).
Set sensor selector to GCEM 4000, set Function selector to 'Read'. Click on
'read data control' and ensure the 'message received indicator' turns green and
that data is deposited in the 'Data access window' (Figure 24), where a binary
stream should be visible in the data window. If not, try again, but if after several
attempts nothing happens, check for good communications between the pc and
SCU.
OPS. 080 41
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
OPS. 080 42
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
The following procedure will ensure that the sensor head is in optimal alignment
with the measurement probe, but before proceeding, allow 4-hour warm-up time
after power-up.
Switch on the purge air using the following procedure. Select 'Calibration' in the
Function selector and the screen below should appear.
Set 'Working Set Cal data' in the type box, click on 'Read' and ensure that the
green 'message received' LED is activated. The required data will now fill the
appropriate boxes.
OPS. 080 43
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Select 'Activate calibration' in the 'Type' box and the following screen should
appear.
Set Calibrate to 'Off'. Set manual purge air to ‘On’; click on the 'Lock tick' to
release it and click on 'Apply'.
At this point check that the flow meter on the air line to the measurement zone
is showing 10 l/min. If not, adjust it so that it is. If the flow meter is unable to
show sufficient flow, open the air control valve to allow more through. A value
of less than 10 l/min is unacceptable and will lead to a poor zero calibration and
consequently poor accuracy from the analyser.
Before alignment can be carried out the following parameters must be checked
to see if the Target and Measured values are within range. If this is not the
case then allow more time for the analyser to warm-up.
OPS. 080 44
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Select 'Thermistor Control' at the Function selection and the following screen
will appear.
OPS. 080 45
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Some of the data displayed is in hexadecimal (base 16) notation, not decimal
(base 10). Check the values against the table below and change any that are
incorrect.
The 'Thermistor measured value' and 'Cooler current' should now display at
values close to those selected.
OPS. 080 46
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Select Source Temp Control in the Function selector and the following screen
should appear.
Click ‘Read’ to update the display values. Ensure that the green ‘message
received’ LED illuminates to confirm that the data is current. Check these
values against those shown in the following table and adjust if necessary.
OPS. 080 47
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Select 'Cell oven control' in Function selector and click on 'Read' to update the
displayed values. Ensure that the green 'message received' LED activates to
confirm that the data is current. Check these values against those shown in the
following table and adjust if necessary. Please note that some are in
hexadecimal and some in decimal notation.
To upload any new values, change the variable in the white box, ensure that
'Auto control' is set to 'On' and click on 'Apply'. Ensure the 'message received'
LED goes to green.
OPS. 080 48
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Now, with purge air on align the transceiver in relation to the probe.
b) Select detector 6.
c) Set auto update rate to 3 seconds and click on 'Auto read stop/start
control'.
d) Using the alignment and locking nuts on the four alignment studs (Figure
25)adjust the position of the transceiver mount such that the gap between
it and the alignment flange is equal all the way round. Watching the
alignment display in SmartCEM start to adjust the alignment on the
vertical plane by adjusting both the alignment and the locking nuts, until
the maximum signal strength is achieved.
alignment flange
OPS. 080 49
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Important Note:
plateau
maximum signal
strength
Lock position
OPS. 080 50
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
e) Select detector wave forms in the Function box and the following
screen should be displayed.
2)
3)
1)
4)
Sample 3
6) Sample 2 start start
5)
Sample 3
7)
end
Sample 2 end
Comms. lights Sample 1 start Sample 1 end
OPS. 080 51
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
5) The displayed signal should look as shown below, with the six
lines protruding form it. These lines denote the three start and
three stop points of the sampling. At this point the sampling
positions made, need to be adjusted; this can be checked as
follows:
1
2
OPS. 080 52
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
8) Now re-check that spaces (1) and (2) are equal and if not, repeat
step 7) until this is the case.
9) Take the valve for sample 2 achieved from step 8) and from this
value subtract 2360 and enter the result as the sample 1 value.
Then take the sample 2 value and add 2760 and enter the result
as the sample 3 value; transmit these values by pressing the
‘apply’ button as described in step 7).
Note: On some analysers there will be no signals and a straight line will be
displayed for the detector wave form. This is related to gas channels which the
analyser is measuring.
Compare the background colour of the display against the colour check box
beneath to check if the detector level is good, saturated or there is a comms.
error. Detector levels should be 13000 to 16000.
OPS. 080 53
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
To view the analyser detector levels select 'Detector Levels' in the Function
selector and click on 'Read' to update the information. Finally, ensure the green
'message received' LED is activated.
The detector values represent the amount of energy received at the photo-
detector as the gas wheel rotates. There may be zero values dependent on the
number of detection channels the analyser is set-up for. Where there are
values shown >0 they should be at least 15000 (decimal) ±2000 (if the purge air
is on). If not, or if any of the saturation LEDs are red, first check the alignment
and if this does not rectify the situation, contact your local CODEL Distributor or
CODEL direct for further advice. To view the smoothed detector output, select
'smoothed' in the 'Type' box.
OPS. 080 54
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Set 'Working Set Cal data' in the 'Type' box, click on 'Read' and ensure the
green 'message received' LED is activated. The required data will now fill the
appropriate boxes. To receive a continuous update set the 'Auto Update rate'
and press 'Start'.
The data shown in the final boxes is crucial to the performance of the analyser
during calibration and must be equal to or greater than the data given below. If
it is not, wait until the analyser warms to this temperature. If it fails to do so,
contact the CODEL Distributor or CODEL International direct.
OPS. 080 55
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
When the transceiver has achieved the correct temperature, select 'Activate
calibration' in the 'Type' box and the following screen should appear.
Set the 'Purge time' to 180 seconds, set 'Number of Cal cycles' to 240, set
'Calibrate' to 'On', click on the 'Lock' tick to release it and click on 'Apply'.
Clicking on 'Auto update' will show a clock decrementing through the remaining
Cal cycles.
To stop a calibration, which is not advisable, set 'Calibrate' to 'Off' and click on
'Apply'.
OPS. 080 56
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
OPS. 080 57
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
To view the 'Y' values, select this in the Function selector, click on 'Read' to
update them and ensure the green 'message received' LED is activated. The
'Y' values should be in the region of 10000 (if the purge air is on). If they vary
significantly from these values, check the alignment and if does not rectify the
problem, contact your CODEL Distributor or CODEL direct.
OPS. 080 58
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
The G-CEM4000 and GCU are equipped to enable the performing of span
verification checks. This is achieved by connecting the required span gas bottle
to the span gas input of the GCU (see Figure 15). Note that some GCUs may
have more that one input.
Set the pressure on the relevant regulator to the same pressure indicated on
the zero purge regulator.
The control of span verification can be carried out either from SmartCOM or via
the IEM for WindowsR software (if using IEM for WindowsR software refer to the
IEM manual).
Note: Before performing a span check it is good practice to carry out a zero
calibration first as described in Section 5.3.6. Zero Calibration.
Note that not all these functions are applicable to the G-CEM4000
span check and therefore should not be used.
OPS. 080 59
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
2) 3) 10)
1)
4)
8)
Comms.
light
5)
6) 9) 7)
4) Read back the stored parameter data from the SCU by clicking
‘Read’.
7) Click ‘Apply’.
9) Select ‘ON’.
10) Click ‘Apply’ and make sure that the comms. Light turns green.
OPS. 080 60
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
This will now switch on zero air for 5 minutes to check the zero condition of the
analyser. The zero air will then switch off and the span gas will switch on. At
this point the flow must be checked on the flow rotometer; make sure that it is
≈10 l/min and adjust if required using the span gas regulator.
Switch to the ‘Data File’ in the Function box and the following screen will be
displayed.
Make sure that G-CEM4000 is selected and adjust the Auto update time to ≈20
seconds and click ‘Start’. The relevant gas channel value should start to
increase to the value indicated on the span gas bottle (within tolerances). If this
is not the case please contact CODEL or your local representative.
OPS. 080 61
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
To receive a continuous update set the 'Auto Update rate' and press 'Start'.
OPS. 080 62
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
The analogue outputs and alarm relay set points should be configured if
required. On some systems using IEM for WindowsR, this may be handled by
the pc. Select SCU in the 'Sensor' selector and then select Outputs and the
following screen will appear. Click on "Read" to update the displayed data.
The data displayed now relates to the complete output set for a particular
channel and is configured at the factory. At this point you should
understand that this section is factory set and should be left alone under
nearly all circumstances. If you do need to make changes, you will need to
refer to the Memory map in Appendix 2 - Output Memory Map.
OPS. 080 63
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Current output
Abs. data location : the memory location of the source of the current
output data
0 - 4mA : selects the starting value (in mA) for zero output
Averaging value : the time period over which the output data is
averaged in 0 - 256 steps. Each step is 3 seconds
and is input in hexadecimal. Some key values are
shown below.*
Relay output
Abs. data location : the memory location of the source of the alarm
output data
Averaging value : the time period over which the output data is
averaged as described above
Source : 2 byte
OPS. 080 64
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Time in Hexadecimal
minutes value
1 0014
2 0028
3 003C
4 0050
5 0064
6 0078
7 008C
8 00A0
9 00B4
10 00C8
11 00DC
12 00FO
Refer to Appendix 2 - Output Memory Map for output location memory map.
To deduce what the factory settings for the analyser channels are, employ the
following method. Select 'Read' in the 'Function' box to view the following
screen. Select 'Master' in the 'Target destination' box, type 7EF8 in the 'Start
address' box and type 7 in the 'Number of bytes box. Click on 'Read' and data
should appear in the Data Access Window. If not, click on 'Read' until it does.
The data displayed in two number blocks relates to the species at each
channel.
01 CO
02 CO2
03 NO
04 NO2
05 not used
06 SO2
07 not used
08 UHC/CH4
09 not used
0A H2O
0B HCL
OPS. 080 65
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
7EF8; 03 02 01 06 0A 0B FF
Channel 1 NO
Channel 2 CO2
Channel 3 CO
Channel 4 SO2
Channel 5 H20
Channel 6 HCL
Channel 7 Not used
OPS. 080 66
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Return to the output configuration screen, input the required address to both
boxes marked 'Abs. data location' and click on 'Read'. The current
configuration should now display. Change the required parameter and click on
'Apply'.
OPS. 080 67
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
6. Analyser Records
Transceiver :
Gas Control Unit :
Station Control Unit :
Completion Date :
OPS. 080 68
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
OPS. 080 69
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
7.1. Introduction
4000 Series analysers use very tightly controlled infrared wavebands that are
specific to each of the gases measured. The scale-shape for each
measurement (i.e. the relationship between concentration and output) is
therefore uniquely defined and the output, at any measurement level, is only
dependent on gas concentration, gas temperature and any system zero error.
Flue gas temperature is a continuous measured input. Any zero error detected
during commissioning is corrected as part of the commissioning procedure
(Section 5. Commissioning) and any subsequent zero drift is automatically
detected, measured and corrected (Section 7.3.1. Automatic Zero Calibration).
7.3. Verification
Even though 4000 Series analysers are designed to maintain their calibration
stability almost indefinitely, it is often necessary to verify measurement
performance. This may be a routine check after an extended period of
operation, to confirm unusual measurements or as an audit requirement by
some external authority.
OPS. 080 70
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
This automatic procedure is carried out by the analyser itself and provides
regular checking and, if necessary, adjustment of the zero for each
measurement. The automatic zero calibration procedure provides a regular
check on analyser performance without the need for operator intervention. The
operation of this is covered in the IEM for WindowsR manual.
The zero of all measurement channels can be verified manually at any time
after being powered-up for at least four hours.
Important! The purge air must be dry to the specified level (-20°C). Any water
vapour in the measurement path will show an offset not only on the water
vapour measurement itself, but also on any other measurements that the
analyser automatically corrects for cross-sensitivity to water vapour. Any
calibration subsequently initiated to correct these apparent offsets will be
incorrect.
Ensure that the solenoid valve controlling the purge is powered and the control
cable connected as described in Section 4. Installation.
If an analyser error is still suspected, contact CODEL or the local service agent,
but first consult Section 9. Fault Finding to establish what information to
provide.
OPS. 080 71
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
If the analyser is working correctly and the comparative testing is carried out to
the prescribed procedure, it is rare for such exercises to be other than a routine
confirmation of performance. However, to ensure that any discrepancies can
be easily resolved, it is recommended that the following precautions be taken :
OPS. 080 72
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
7.4. Re-calibration
Note : The laws of physics determine that the scale shape (i.e. the
relationship between gas concentration and analyser output)
is absolutely fixed for a defined measurement waveband.
If re-calibration cannot wait until the next scheduled automatic zero calibration
(Section 7.3.1. Automatic Zero Calibration), a manual zero calibration may be
implemented (Section 7.3.2. Manual Zero Verification).
Consider and check all other possibilities before assuming an analyser fault.
Analyser faults are rare, are usually detected by the analyser itself (initiating an
automatic data invalid state) and likely to produce very large errors.
OPS. 080 73
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
8. Maintenance
This version of the 4000 series requires no routine maintenance other than care
of the air purge supplies. Ensure that all filters, dryers and automatic drain units
are serviced and maintained according to the manufacturers' instructions.
Ensure that the compressor is properly serviced and does not inject more oil
into the air supply than the filter system can remove.
The probe and fittings are designed, by choice of materials and construction, to
be corrosion resistant and to provide many years of trouble-free operation.
However, it is good practice to take the opportunity of plant shutdown periods to
visually examine components that are not accessible during normal operation.
OPS. 080 74
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
9. Fault Finding
To obtain current values for data recorded in Tables 3 and 4 follow the
procedure described in Section 5. Commissioning.
OPS. 080 75
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
The need to reset gains after manufacture and testing is very rare, but if
necessary, there are a number of methods that depend on the analysers'
configuration and its date of manufacture. Consult CODEL to check that gain
resetting is necessary and to obtain instructions for the appropriate method.
The analysers' serial number should be quoted at this time.
Note that gain setting requires access to the circuit boards within the
receiver and should only be undertaken by a trained instrument
technician.
OPS. 080 76
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
Location Description
0180 } Ch1 ]
0181 } ]
0182 } Ch2 ]
0183 } ]
0184 } Ch3 ] 3min (Analyser response)
0185 } ]
0186 } Ch4 ]
0187 } ]
0188 } Ch5 ]
0189 } ]
018A } Ch6 ]
018B } ]
018C } Ch7 ]
018D } ]
018E } Opacity ]
018F } ]
0190 } Ch1 ]
0191 } ]
0192 } Ch2 ]
0193 } ]
0194 } Ch3 ] x Minute response
0195 } ]
0196 } Ch4 ]
0197 } ]
0198 } Ch5 ]
0199 } ]
019A } Ch6 ]
019B } ]
019C } Ch7 ]
019D } ]
019E } Opacity ]
019F } ]
OPS. 080 77
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM01A0
Location Description
01A0 } Ch1 ]
01A1 } ]
01A2 } Ch2 ]
01A3 } ]
01A4 } Ch3 ] 3min (Analyser response)
01A5 } ]
01A6 } Ch4 ]
01A7 } ]
01A8 } Ch5 ]
01A9 } ]
01AA } Ch6 ]
01AB } ]
01AC } Ch7 ]
01AD } ]
01AE } Dust ]
01AF } ]
01B0 } Ch1 ]
01B1 } ]
01B2 } Ch2 ]
01B3 } ]
01B4 } Ch3 ] x Minute response
01B5 } ]
01B6 } Ch4 ]
01B7 } ]
01B8 } Ch5 ]
01B9 } ]
01BA } Ch6 ]
01BB } ]
01BC } Ch7 ]
01BD } ]
01BE } Dust ]
01BF } ]
OPS. 080 78
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
**********************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM01C0
Location Description
01C0 } Ch1 ]
01C1 } ]
01C2 } Ch2 ]
01C3 } ]
01C4 } Ch3 ] 3min (Analyser response)
01C5 } ]
01C6 } Ch4 ]
01C7 } ]
01C8 } Ch5 ]
01C9 } ]
01CA } Ch6 ]
01CB } ]
01CC } Ch7 ]
01CD } ]
01CE } Dust ]
01CF } ]
01D0 } Ch1 ]
01D1 } ]
01D2 } Ch2 ]
01D3 } ]
01D4 } Ch3 ] x Minute response
01D5 } ]
01D6 } Ch4 ]
01D7 } ]
01D8 } Ch5 ]
01D9 } ]
01DA } Ch6 ]
01DB } ]
01DC } Ch7 ]
01DD } ]
01DE } Dust ]
01DF } ]
OPS. 080 79
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
**********************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM01E0
Location Description
OPS. 080 80
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
**********************************************************************
Model: SCU smartcem Software ID: D07-019A Module: MM0100
Location Description
OPS. 080 81
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM0120
Location Description
OPS. 080 82
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM0140
Location Description
0140 } x sec }
0141 } }
0142 } y min }
0143 } } Flow m/s(*10)
0144 } z hour }
0145 } }
0146 } d day }
0147 } }
0148 } x sec }
0149 } }
014A } y min }
014B } } Flow m^3/s(*10)
014C } z hour }
014D } }
014E } d day }
014F } }
0150
0151
0152
0153
0154
0155
0156
0157
0158
0159
015A Data Valid
015B Calibration in progress
015C Plant Status
015D Head identifier 06= Vcem0100
015E Reserved for SIU comms validation 00 = o.k., FF = fail
015F
OPS. 080 83
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM0160
Location Description
0160 } Ch1 ]
0161 } ]
0162 } Ch2 ]
0163 } ]
0164 } Ch3 ]
0165 } ] Analogue input data
0166 } Ch4 ]
0167 } ]
0168 } Ch5 ]
0169 } ]
016A } Ch6 ]
016B } ]
016C } Ch7 ]
016D } ]
016E } Ch8 ]
016F } ]
0170 Ch1 ]
0171 Ch2 ]
0172 Ch3 ]Logic input data
0173 Ch4 ]
0174 Ch5 ]
0175 Ch6 ]
0176 Ch7 ]
0177 Ch8 ]
0178
0179
017A Data Valid
017B Calibration in progress
017C Plant Status
017D Head identifier 07= Icem0100
017E Reserved for SIU comms validation 00 = o.k., FF = fail
017F
OPS. 080 84
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM0180
Location Description
0180 } Ch1 ]
0181 } ]
0182 } Ch2 ]
0183 } ]
0184 } Ch3 ] 3min (Analyser response)
0185 } ]
0186 } Ch4 ]
0187 } ]
0188 } Ch5 ]
0189 } ]
018A } Ch6 ]
018B } ]
018C } Ch7 ]
018D } ]
018E } Opacity ]
018F } ]
0190 } Ch1 ]
0191 } ]
0192 } Ch2 ]
0193 } ]
0194 } Ch3 ] x Minute response
0195 } ]
0196 } Ch4 ]
0197 } ]
0198 } Ch5 ]
0199 } ]
019A } Ch6 ]
019B } ]
019C } Ch7 ]
019D } ]
019E } Opacity ]
019F } ]
OPS. 080 85
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM01A0
Location Description
01A0 } Ch1 ]
01A1 } ]
01A2 } Ch2 ]
01A3 } ]
01A4 } Ch3 ] 3min (Analyser response)
01A5 } ]
01A6 } Ch4 ]
01A7 } ]
01A8 } Ch5 ]
01A9 } ]
01AA } Ch6 ]
01AB } ]
01AC } Ch7 ]
01AD } ]
01AE } Dust ]
01AF } ]
01B0 } Ch1 ]
01B1 } ]
01B2 } Ch2 ]
01B3 } ]
01B4 } Ch3 ] x Minute response
01B5 } ]
01B6 } Ch4 ]
01B7 } ]
01B8 } Ch5 ]
01B9 } ]
01BA } Ch6 ]
01BB } ]
01BC } Ch7 ]
01BD } ]
01BE } Dust ]
01BF } ]
OPS. 080 86
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM01C0
Location Description
01C0 } Ch1 ]
01C1 } ]
01C2 } Ch2 ]
01C3 } ]
01C4 } Ch3 ] 3min (Analyser response)
01C5 } ]
01C6 } Ch4 ]
01C7 } ]
01C8 } Ch5 ]
01C9 } ]
01CA } Ch6 ]
01CB } ]
01CC } Ch7 ]
01CD } ]
01CE } Dust ]
01CF } ]
01D0 } Ch1 ]
01D1 } ]
01D2 } Ch2 ]
01D3 } ]
01D4 } Ch3 ] x Minute response
01D5 } ]
01D6 } Ch4 ]
01D7 } ]
01D8 } Ch5 ]
01D9 } ]
01DA } Ch6 ]
01DB } ]
01DC } Ch7 ]
01DD } ]
01DE } Dust ]
01DF } ]
OPS. 080 87
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM01C0
Location Description
01C0 } Ch1 ]
01C1 } ]
01C2 } Ch2 ]
01C3 } ]
01C4 } Ch3 ] 3min (Analyser response)
01C5 } ]
01C6 } Ch4 ]
01C7 } ]
01C8 } Ch5 ]
01C9 } ]
01CA } Ch6 ]
01CB } ]
01CC } Ch7 ]
01CD } ]
01CE } Dust ]
01CF } ]
01D0 } Ch1 ]
01D1 } ]
01D2 } Ch2 ]
01D3 } ]
01D4 } Ch3 ] x Minute response
01D5 } ]
01D6 } Ch4 ]
01D7 } ]
01D8 } Ch5 ]
01D9 } ]
01DA } Ch6 ]
01DB } ]
01DC } Ch7 ]
01DD } ]
01DE } Dust ]
01DF } ]
OPS. 080 88
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM01E0
Location Description
OPS. 080 89
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM7E00
Location Description
OPS. 080 90
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model:SCU smartcem Software ID: D07-019A Module: MM7EE0
Location Description
7EE0
7EE1
7EE2
7EE3
7EE4
7EE5
7EE6
7EE7
7EE8
7EE9
7EEA
7EEB
7EEC
7EED
7EEE
7EEF
7EF0
7EF1
7EF2
7EF3
7EF4
7EF5
7EF6
7EF7
7EF8 Ch.1 definition
7EF9 Ch.2 definition
7EFA Ch.3 definition
7EFB Ch.4 definition
7EFC Ch.5 definition
7EFD Ch.6 definition
7EFE Ch.7 definition
7EFF
OPS. 080 91
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM7F00
Location Description
7F00
7F01 NO/NOx flag (00=NO, 01=NOx) NOvpm, NOorNOx mg/m3, mg/Nm3 & mass
emissions
7F02 } NO2 % (*10) [used for NOx calculations when
7F03 } NO2 ch. not present]
7F04 Plant status off (01=zero, 00=live) vpm, mg/m3, mg/Nm3 & mass emission outputs
7F05
7F06 O2/CO2 Normalisation flag (00=O2, 01=CO2)
7F07 O2/CO2 dry/wet flag (00=DRY, 01=WET)
7F08 } Temperature }
7F09 } }
7F0A } Oxygen %(*10) } Normalisation
7F0B } } Standard levels
7F0C } Pressure }
7F0D } }
7F0E Water Vapour } (Water Vapour wet/dry flag)
7F0F }
7F10 } Dust factor A }
7F11 } } Dust calculated as [Aext'n + B]ext'n
7F12 } Dust factor B }
7F13 } }
7F14 } Cross Sectional Area m2 (*100)
7F15 } for volumetric flow
7F16
7F17
7F18
7F19
7F1A
7F1B
7F1C
7F1D
7F1E
7F1F Reference EEROM Location (01 = SET DEFAULT VALUES AT POWER UP)
OPS. 080 92
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM7F20
Location Description
7F20 } Divisor ]
7F21 } ] Mass flow ch1 = mg/m3 * vol. flow * Multiplier
7F22 } Multiplier ] ---------
7F23 } ] Divisor
7F24 } Divisor ]
7F25 } ]Mass flow ch2
7F26 } Multiplier ]
7F27 } ]
7F28 } Divisor ]
7F29 } ] Mass flow ch3
7F2A } Multiplier ]
7F2B } ]
7F2C } Divisor ]
7F2D } ]Mass flow ch4
7F2E } Multiplier ]
7F2F } ]
7F30 } Divisor ]
7F31 } ] Mass flow ch5
7F32 } Multiplier ]
7F33 } ]
7F34 } Divisor ]
7F35 } ]Mass flow ch6
7F36 } Multiplier ]
7F37 } ]
7F38 } Divisor ]
7F39 } ] Mass flow ch7
7F3A } Multiplier ]
7F3B } ]
7F3C } Divisor ]
7F3D } ]Mass flow ch8
7F3E } Multiplier ]
7F3F } ]
OPS. 080 93
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM7F40
Location Description
OPS. 080 94
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM7F60
Location Description
OPS. 080 95
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM7F80
Location Description
OPS. 080 96
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM7FA0
Location Description
OPS. 080 97
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM7FC0
Location Description
OPS. 080 98
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
******************************************************************************
Model: SCU SmartCem Software ID: D07-019A Module: MM7FE0
Location Description
OPS. 080 99
Issue : B
Revision :
Date : September 2002
Doc i/d : 0080/6
CODEL
List of Figures