0% found this document useful (0 votes)
87 views2 pages

Reliable UPS for Critical Systems

The Ablerex RS series on-line UPS provides reliable backup power for critical systems. It uses digital control technology to provide clean power from both its inputs and batteries. Key features include a wide input voltage range, pure sine wave output, and internal batteries that provide backup times of 10-30 minutes depending on the load. The RS series comes in 1000VA, 2000VA and 3000VA models and includes protections such as overload control, short circuit protection, and over temperature shutdown.

Uploaded by

cuma mencoba
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
87 views2 pages

Reliable UPS for Critical Systems

The Ablerex RS series on-line UPS provides reliable backup power for critical systems. It uses digital control technology to provide clean power from both its inputs and batteries. Key features include a wide input voltage range, pure sine wave output, and internal batteries that provide backup times of 10-30 minutes depending on the load. The RS series comes in 1000VA, 2000VA and 3000VA models and includes protections such as overload control, short circuit protection, and over temperature shutdown.

Uploaded by

cuma mencoba
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Ablerex RS Series On-line UPS

The Ablerex RS series on-line double conversion UPS with full-time


digital single processor control technology is the cost-effective solution
for mission critical users who demand high reliability and performance
from a UPS.

• Advanced Digital Control Technology


• Programmable Parameter Setting
• Unity Input Power Factor
• Wide Input Voltage/Frequency Window
• Optional Power Shedding
• Emergency Shutdown Control through EPO
• Optional Powerful Charger
• Extended Runtime Capability
• Matching Battery Cabinet
Ablerex RS On-line UPS Technical Specifications
MODEL ITEM RS 1K RS 2K RS 3K
CAPACITY VA/W 1000VA/800W 2000VA/1600W 3000VA/2400W
110Vac/140Vac/160Vac-300Vac
Voltage Range
(Based on load percentage 0%~25% / 25%~50% / 50%~100%)
INPUT Frequency Range 45Hz ~ 65Hz
Phase Single phase with ground
Power Factor  0.99 (with full linear load)
Voltage 230V, adjustable to 200/208/220/230/240
Voltage Regulation   1% until low battery warning
Frequency (Synchronized Range) 3Hz or 1Hz (selectable)
OUTPUT Frequency (Battery mode) 50Hz/60Hz  0.1% unless synchronized to line
Current Crest Ratio 3:1 (acceptable)
Harmonic Distortion < 3% (at full load) ; < 6% (at full non-linear load)
Output Waveform Pure sine wave
<105% continuous, >106%~120% for 30 seconds transfer to bypass,
Line mode / Battery mode >121%~150% for 10 seconds transfer to bypass, >150% for immediately
OVERLOAD transfer to bypass, Buzzer continuously alarms.
<105% continuous, >106%~120% for 250 seconds shuts down, >121%~130%
CAPACITY for 125 seconds shuts down, >131%~135% for 50 seconds shuts down,
Bypass mode
>136%~145% for 20 seconds shuts down, >146%~187% for 5~0.32 seconds
shut down, >188% for 0.16 seconds shuts down, Buzzer continuously alarm
OVERALL EFFICIENCY  88%
Number of batteries 3 4 6
Battery type 12V/9AH (Sealed, non-spillage, maintenance-free, lead acid)
Rated Battery Voltage 24Vdc 48Vdc 72Vdc
INTERNAL
Backup time (half load/full load) 10 ~ 30 minutes depending on loads
BATTERY
Recharge time (to 80%)  5 hours
Floating Charging Voltage 27.3Vdc  0.5V 54.6Vdc  0.5V 82.0Vdc  0.5V
Bulk Charging Voltage 30.0Vdc  0.5V 60.0Vdc  0.5V 90.0Vdc  0.5V
TRANSFER TIME AC to DC 0ms
DC START Yes
SELF DIAGNOSTICS By button of the panel or Software Control
Load Level/Battery Level/ Battery Mode/ Normal Mode/ Bypass Mode/ Self-
Standard LED
Test/ Weak/Bad Battery/ Site Wiring Fault/ Fault/ Overload
FRONT PANEL
Optional LED Programmable Outlet 1 / Programmable Outlet 2
Button (ON/Alarm Silence Button)/ OFF Button/ (Test/Level Button)
Battery Mode Sounding once every 1.5 seconds
Low Battery Sounding once every 0.2 seconds
AUDIBLE ALARM Overload Sounding once every 3 seconds
Normal alarm Sounding once every 3 seconds
Fault Continuously Sounding
Bypass mode: FUSE,
Short Circuit Normal Mode: Output Breaker/Electronic Circuit,
Battery Mode: Output Breaker/Electronic circuit
PROTECTION Battery Advance Battery Discharge Management
EPO UPS shuts down immediately
Normal mode: Transfer to Bypass Mode,
Over Temperature
Battery Mode: UPS shuts down immediately
Dimensions (H  W  D in mm) 220  144  360 322  152  438 322  190  438
PHYSICAL Weight (kg) 12 22 27
Outlet (3) 10A, IEC 320-C13 (6) 10A, IEC 320-C13 (6) 10A, IEC 320-C13
Operation Temperature 0-40C
ENVIRONMENT Noise Level <50dBA
Relative Humidity 0 to 90% (Without condensation)
Standards USB port
INTERFACE Optional Dry contact, RS232, 2nd USB, SNMP/Web Card
Compatible platforms Microsoft Window series, Linux
Safety IEC/EN 62040-1-1
Performance IEC/EN 62040-3
STANDARDS AND
IEC/EN 62040-2 class A, FCC Part 15 Subpart B class A, IEC/EN55011,
CERTIFICATIONS EMC
CISPR 11, IEC 61000-4-2/-3/-4/-5, IEC 61000-2-2, IEC 61000-3-2/-3
Markings CE, FCC