Instruction Manual: Sync-Check Relay BE1-25
Instruction Manual: Sync-Check Relay BE1-25
FOR
SYNC-CHECK RELAY
BE1-25
Publication: 9170200990
Revision: R 09/07
INTRODUCTION
This instruction manual provides information about the operation and installation of the BE1-25 Sync-
Check relay. To accomplish this, the following information is provided:
WARNING!
To avoid personal injury or equipment damage, only qualified personnel should
perform the procedures in this manual.
NOTE
Be sure that the relay is hard-wired to earth ground with no smaller than 12 AWG
copper wire attached to the ground terminal on the rear of the unit case. When
the relay is configured in a system with other devices, it is recommended to use a
separate lead to the ground bus from each unit.
Printed in USA
September 2007
CONFIDENTIAL INFORMATION
of Basler Electric, Highland Illinois, USA. It is loaned for confidential use, subject
to return on request, and with the mutual understanding that it will not be used in
any manner detrimental to the interest of Basler Electric.
It is not the intention of this manual to cover all details and variations in equipment, nor does this manual
provide data for every possible contingency regarding installation or operation. The availability and design
of all features and options are subject to modification without notice. Should further information be
required, contact Basler Electric.
BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND IL 62249 USA
http://www.basler.com, [email protected]
PHONE +1 618.654.2341 FAX +1 618.654.2351
ii BE1-25 Introduction 9170200990 Rev R
REVISION HISTORY
The following information provides a historical summary of the changes made to the BE1-25 instruction
manual (9170200990). Revisions are listed in reverse chronological order.
Manual
Revision and Date Change
R, 09/07 • Moved content of Section 6, Maintenance to Section 4.
• Added manual part number and revision to all footers.
• Updated power supply burden data in Section 1.
• Updated Target Indicator description in Section 3.
P, 11/06 • Updated Output Specs in Section 1.
• Added footnote to Figures 1-2 and 1-3.
• Updated drawings of case cover in Section 4, Installation.
• Updated front panel drawing in Section 2, Controls and Indicators.
• Moved manual Revision History to the front of manual.
• Updated drawing on front cover.
N, 08/02 • Updated drawings in the manual to label terminal 15 (COM) as Vctrl.
• Corrected various minor errors throughout the manual.
M, 02/01 • Changed the Specifications, illustrations, and the descriptions
throughout the manual for the minimum voltage required to operate
the sync-check function.
• Corrected Figure 1-6, Style Chart.
• Added contact-sensing burden and enhanced Surge Withstand
Capability description.
• Added new covers information.
• Changed Section 5, Testing, to reflect the minimum voltage
requirements for sync-check function.
L, 08/98 • Added Power Supply information to Section 3 and added new wide
range power supply information to Section 1.
• Corrected Style Chart by changing Power Supply Type T from 230
Vac to 240 Vac.
• Moved Testing information from Section 4 to new Section 5, Testing.
• Added new outline dimensions to include all options (S1 Case,
Double-Ended, Semi-Flush, and Projection Mounting).
• Corrected ground symbol in Figure 4-7, Internal Diagram.
• Updated front cover and Manual Change information.
K, 12/97 • Deleted the reference to Service Manual 9170200620 on page 1-1.
• Corrected an error found on page 1-11 in Minimum Voltage
Requirement from “45 ±2 Vac” to “80 Vac”.
• Updated front cover and Manual Change information.
J, 10/97 • Added three new types (A, B, & C) to Option 2. This included new
paragraphs describing Average Detectors.
H, 01/96 • Corrected power supply type P, voltage input, and range from Vdc to
Vac.
• Minor page layout changes developed from using a word processor
application upgrade.
G, 01/95 • Reformatted instruction manual as Windows Help file for electronic
documentation.
WARNING!
To avoid personal injury or equipment damage, only qualified personnel should perform
the procedures presented in these instructions.
These instructions may be used in place of all earlier editions. For change information, see Revision
History in the manual Introduction.
It is not the intention of these instructions to cover all details and variations in equipment, nor does this
manual provide data for every possible contingency regarding installation or operation. The availability
and design of all features and options are subject to modification without notice. Should further
information be required, contact Customer Service, Basler Electric Company, Highland, IL.
DESCRIPTION
The BE1-25 is a solid-state synchronism check relay designed to permit breaker closure when the
desired maximum phase angle conditions have held for a specified minimum time. The maximum
allowable phase angle and time delay requirements can be set on front panel thumbwheel switches. Five
voltage measuring options are available that identify significant line and bus voltage conditions, and this
information is used to influence the relay output.
APPLICATION
BE1-25 Sync-Check Relays are recommended for situations that require verification of synchronism prior
to closing a circuit breaker. Typical applications are:
SYNC-CHECK FUNCTION
NOTE
Voltage sensing circuits are guaranteed to operate at a minimum voltage of 60 volts.
They are guaranteed not to operate at voltages less than 20 volts. Some units may
operate at voltages in between these two levels because of the individual characteristics
of specific components. Minimum voltage detection is usually in the range of 45 to 55
volts.
CONTACT SENSING
To control operation of the relay, an input from the breaker auxiliary 52b contact is required to signal the
breaker status. If the breaker is open, the relay is enabled to perform its function. When the breaker
closes, the 52b input changes state and causes the relay to terminate its close signal.
Two configurations of the 52b contact sensing input are available to provide additional flexibility for the
protection circuit designer:
• Isolated contact sensing monitors a current supplied by the relay through an isolated contact.
• Non-isolated contact sensing monitors the presence of voltage at its input due to the closure of a
contact.
See Figure 4-10 for typical control circuit connections for each configuration. Also, see Figure 4-11 if a
Type T power supply has been selected.
Mode Switches
Two Mode switches are located on the Voltage Monitor card. Mode Switch No. 1 serves the bus Voltage
Monitor function. Mode Switch No. 2 serves the line Voltage Monitor function. Mode switch positions are
as follows:
NORMAL Mode (Up) - allows measuring elements to establish live and dead reference levels for
the input level.
NOT-OV Mode (Down) - allows measuring elements to establish live and Not-Overvoltage
reference levels for the input level.
When a Mode Switch is in the NORMAL Mode position (Up), a dead level is defined as a monitored
voltage level below the DEAD reference setting. See Figure 1-1 for voltage monitor acceptance zones. A
live level is defined as a monitored voltage above the LIVE reference setting.
When a Mode Switch is in the NOT-OV Mode position (Down), a dead level is defined as a monitored
voltage less than the LIVE reference setting, and a live level is defined as a monitored voltage greater
than the LIVE reference setting, but less than the NOT-OV setting. (An input is considered over-voltage
when it exceeds the NOT-OV reference setting.)
It is permissible to operate the line input in either the same mode or a different mode than the bus input.
This flexibility allows the BE1-25 to be used, for example, to close a generator breaker onto a dead bus,
or to prevent closure if the generator and/or bus voltage is too high.
See Table 2-1, callout R, for a complete description and precautions on setting the Mode Switches. The
location of the switches is shown in Figure 2-2. Also, see Condition and Mode Switches in Section 5.
LIVE 3
LB ADJ 50V
=35V
BUS VOLTAGE 10V (MIN)
NOTES:
1 SYNC RELAY CONTACTS 3 60V FIXED MINIMUM VOLTAGE 4 OV EXCEEDED, SYNC-CHECK
CLOSED BY VOLTAGE MONITOR LIMIT (LIVE LINE/LIVE BUS LOGIC NOT ENABLED (SETTING
LOGIC CONDITION SYNC-CHECK MODE SWITCH NO. 1 TO ON
FUNCTION ONLY) AND CONDITION SWITCH NO. 1
2 SYNC-CHECK LOGIC ENABLED TO ON PERMITS OV)
Condition Switches
Five Condition Switches are located on the Voltage Monitor Card, each with two positions to select ON
(Down) and OFF (Up). When ON, Condition Switch No. 1 programs the relay to require recognition that
the line and bus are not in an overvoltage condition (NOT OV) before the SYNC output is allowed.
Condition Switches No. 2 through No. 5 modify the voltage monitor response according to a programmed
set of external conditions. The possible external conditions for each of these four switches are:
Voltage Difference
A voltage monitor is available that checks the phasor or average voltage difference between the two
inputs. This can be used to prevent the closure of a generator breaker if the voltage difference is too
great (even if the phase angle and voltage level monitoring circuits indicate that proper closing conditions
are otherwise present).
The voltage difference option (included with option 2-A, 2-B, 2-C, 2-R, 2-T or 2-U) is typically used to
reduce the amount of possible system shock or transients when closing a breaker. This option compares
the voltage between line and bus against a selected limit, and initiates either an enable or an inhibit signal
for the sync-check logic, thereby narrowing the voltage across the breaker contacts (as compared to a
simple sync-check acting alone). Figure 1-2 shows closing zones obtained by combining phasor voltage
difference, phase angle limit, and line and bus live/dead voltage limits. Figure 1-3 shows closing zones
obtained by combining average voltage difference, phase angle limit, and line and bus live/dead voltage
9170200990 Rev R BE1-25 General Information 1-3
limits. If a separate Voltage Monitor relay is supplied (Output option G or H), the NO contact must be in
series with the SYNC relay contact to perform the LL/LB and line not-overvoltage/bus not-overvoltage
enabling functions in Figure 1-2.
1
ΔV = (V L2 + V B2 − 2 ⋅ V L ⋅ VB ⋅ cos θ ) 2 (1)
When VL is tangent to the voltage difference circle, the ΔV phasor is perpendicular to VL at the phase
angle limit. Accordingly, the voltage difference or the phase angle can be calculated by equations 2 and
3, respectively.
ΔV = VB sinθ (2)
ΔV
θ = sin −1 (3)
VB
where:
ΔV = Voltage Difference
VL = Line Voltage
VB = Bus Voltage
θ = Phase Angle
Note that the point where VL is tangent to the voltage difference circle represents the most extreme
condition of θ for a closure. Assuming that a constant voltage difference exists, the following condition is
valid: If the magnitude of the line voltage decreases, the phase angle must also decrease to allow sync-
acceptance. Therefore, the minimum line voltage possible for sync-acceptance occurs at zero phase
angle.
∗ Lines apply only if using the NOT-OV mode setting. When operating in NORMAL mode, the 135V
(MAX) line applies as an upper limit.
P0004-37
VL
VB
P0004-39
Output Relay
The Voltage Monitor output relay option G or H provides additional supervision of the breaker closing
circuit, or provides an indication of the existing voltage conditions for the supervisory control system.
When a Voltage Monitor output relay is installed, the SYNC relay is no longer directly operable by voltage
monitor logic. However, the live line/live bus condition may be utilized to enable the Sync-Check function.
Detailed instructions and precautions for setting the Mode switches and Condition switches are provided
in Table 2-1, callouts R and S. The location of the switches is shown in Figure 2-2.
Voltage sensing connections are shown in Figure 4-8.
Expandable Window
An expandable window (option 9 in the second position of the Style Number) is available to enable a local
operator (through a switch) or a remote dispatcher (through the supervisory control system) to expand the
preset phase angle window by a programmed ratio.
Under normal conditions, the phase angle setting is determined by the maximum angular difference that
has been calculated as suitable to meet the expected load flow of the total system. However, under
emergency conditions, the load flow throughout the system may result in excessive phase angle
separation across the opened breaker.
In order to reestablish load on a previously faulted line quickly, it may be necessary to expand the
allowable phase window. With this option, closing a contact input to the relay expands the preset phase
setting by a programmed multiple of 2 or 3 (according to the position of a jumper on the circuit card).
This option is not suggested for use in generator applications for the following reason: The phase angle
setting for a generator breaker is determined by the maximum phase difference that can be tolerated by
the generator when connected to the system. An excessive angle can result in excessive mechanical
forces in the generator and associated mountings.
Internal connections for the expandable window are shown in Figure 4-7; control circuit connections are
in Figures 4-10 and 4-11.
BE1-25 M
MODEL NO.
NOTES:
Voltage and Phase Sensing Nominally rated at 60 hertz with a range of 45 to 65 hertz at a
maximum burden of 1 VA per phase to 125% of nominal voltage.
Maximum continuous voltage rating is 160% of nominal.
Power Supply One of the four types of power supplies listed in Table 1-1 may be
selected to provide internal relay operating power.
Input Voltage
Type Burden at Nominal
Nominal Range
∗ Type R power supply may require 14 Vdc to begin operation. Once operating, the voltage may be
reduced to 12 Vdc.
Resistive
120 Vac Make, break, and carry 7 Aac continuously.
250 Vdc Make and carry 30 Adc for 0.2 seconds, carry 7 Adc continuously,
break 0.3 Adc.
500 Vdc Make and carry 15Adc for 0.2 s, carry 7 Adc continuously, break
0.3 Adc
Inductive
120 Vac, 125 Vdc, Break 0.3 A, (L/R = 0.04).
250 Vdc
Target Indicator The target indicator may be either internally operated or current
operated (operated by a minimum of 0.2 A through the output trip
circuit). When the target is current operated, the sync output circuit
must be limited to 30 A for 1 second, 7 A for 2 minutes, and 3 A
continuously.
Phase Angle
Selection Accuracy ± 0.5° or ± 5.0% of the front panel setting for degrees, whichever is
greater, for a nominal input frequency of 50/60 hertz, a sensing
input range of 80 to 135 volts, and at 25°C.
Timing Accuracy at 25°C Maximum of 25 milliseconds or 5% of the front panel setting for
time whichever is greater, for a nominal input frequency of 50/60
hertz at 25°C.
TIME Delay Accuracy ±10 milliseconds or ±2%, whichever is greater, of the time delay at
(Overall) 25°C, over the full temperature, voltage, and frequency ranges.
Accuracy Voltage difference setpoint does not vary more than 0.5 V or 5%,
whichever is greater, from a reference measurement at 25°C, with
nominal input frequency, and variation of temperature or voltage
inputs over their specified operating range. This setpoint does not
vary more than 3% from a reading at 25°C over the limited range
of +15 to +40°C.
Accuracy The line and bus voltage setpoints do not vary more than 3% from
a reference measurement at 25°C, with nominal input frequency,
and with temperature and voltage inputs within specified operating
range. Setpoints do not vary more than 1% from a reading at 25°C
over the limited temperature range of +15 to +40°C.
In accordance with IEC 255-5 and IEEE C37.90, one minute dielectric
Isolation (high potential) tests as follows:
All circuits to ground: 2,121 Vdc
Input to output circuits: 1,500 Vac or 2,121 Vdc
GOST-R Certification GOST-R certified No. POCC US.ME05.B03391; complies with the
relevant standards of Gosstandart of Russia. Issued by accredited
certification body POCC RU.0001.11ME05.
A
B
P C
O
D
N E
M F
J H
P0046-04
A SYNC Indicator Red LED lights when an in-sync condition has been of
sufficient duration to match the TIME DELAY setting.
Lighting of the LED coincides with closure of the Sync
Output contacts. The LED extinguishes when 52b opens
or the in-sync condition ceases.
B TIME DELAY Selector Thumbwheel switches establish the time delay between
sensing the desired in-sync condition and closing the
Sync Output contact. Time delay is in units of seconds or
of cycles, according to the option selected.
NOTE
A setting of 00 will inhibit closing of the SYNC
output.
C POWER Indicator LED lights to indicate that the relay power supply is
functioning properly.
E ΔV Indicator Red LED lights when the difference between the bus and
line voltage is less than the ΔV setting.
ΔV Adjustment Continuously adjustable from 1 to 135 Vac. Adjustment is
by small screwdriver through an access hole in the front
panel. CW rotation increases the voltage difference
setting.
F LL Indicator Red LED lights when the line voltage exceeds the
reference voltage established by the LL setting.
LL Adjustment Continuously adjustable from 10 to 135 Vac. Adjustment
is by small screwdriver through an access hole in the front
panel. CW rotation increases the voltage setting.
Red LED lights when the line voltage is less than the
reference voltage established by the DL/NOT OV setting
that defines a dead line.
Red LED lights when the line voltage does not exceed the
reference voltage established by the DL/NOT OV setting
that defines an overvoltage condition.
K Target Indicator (Optional) Electronically latching red indicator illuminates when the
Sync Output relay is or was energized.
L LB Indicator Red LED lights when bus voltage exceeds the reference
voltage established by the LB setting that defines a live
bus condition.
Red LED lights when the bus voltage is less than the
reference voltage established by the DB/NOT OV setting
that defines a dead bus condition.
Red LED lights when the bus voltage does not exceed the
reference voltage established by the DB/NOT OV setting
that defines an overvoltage condition.
P PHASE ANGLE Indicator Red LED lights when the phase angle is within the limits
established by the adjacent PHASE ANGLE Selector.
Q Switchable jumper for Position of jumper in Figure 2-2 controls the width of the
EXPAND option expanded phase angle window as a multiple of the
PHASE ANGLE setting. The two positions are X2 and X3.
S CONDITION Switches
CAUTION
If relay has Output Option E or F:
Condition Switch No. 2 (LL-LB) must be Up
(OFF) when output option E or F is selected.
Otherwise, sync outputs will occur under live
line/live bus conditions without benefit of the
Sync-Check function. No switch or contact
should be connected to the LL-LB input
terminal in this case.
CAUTION
If relay has Output Option G or H:
Condition Switch No. 2 (LL-LB) may be Down
(ON) only when output option G or H has been
selected and the Voltage Monitor Output
contacts do not by-pass the Sync-Check
contact. Use of the external LL-LB switch (if
installed) is similarly limited.
FUNCTIONAL DESCRIPTION
Figure 3-1 is a block diagram that illustrates the BE1-25 Sync-Check Relay circuit functions described in
the following paragraphs.
Step-Down Transformers
Standard system transformers with a 120-volt secondary provide line and bus voltages to the sensing
transformer of the BE1-25 Sync-Check Relay. Internal sensing transformers isolate the relay from the
system and step down the voltage to internal circuit levels.
Comparator
The binary number representing phase difference is compared with the setting of the PHASE ANGLE
thumbwheel switches. If the detected phase difference is less than the setting of the switches, the time
delay is started and the PHASE ANGLE LED is illuminated.
Timer
The time delay timer clock is controlled by the TIME DELAY multiplier switch on the front panel.
The timer is enabled when:
1. Phase angle is less than the set limit.
2. Minimum line and bus voltages are present.
3. 52b contact is closed.
4. Voltage difference (ΔV) is within set limits (if option is selected).
5. A live-line and live-bus condition is present (if the Voltage Monitor option is selected).
When the time delay reaches the count entered by the TIME DELAY select switches, the SYNC output is
energized, the SYNC LED is turned ON, and the target (if selected) turns red. The SYNC LED is turned
OFF as soon as any of the five above listed enables are removed. Generally, this occurs when the circuit
breaker closes.
JUMPER
EXPAND ON PCB
PHASE AUX.
ISOLATION AND
ANGLE SYNC.
OPTION OUTPUT
MINIMUM
VOLTAGE SYNC-CHECK CIRCUITRY
DETECTION VOLTAGE MONITOR OPTIONS .
LL LB IF MODE 1:
. .
(LL OV)(LB OV) IF MODE 2
52b ISOLATION PEAK OR AVG LB
DETECTOR
ALTERNATE
FILTER
PATHS
PEAK OR AVG DB OR BOV
DEPENDING
DETECTOR
PEAK OR AVG V ON OUTPUT
OPTIONAL DETECTOR VOLTAGE OPTION
PEAK OR AVG LL MONITOR
EXTERNAL
DETECTOR SELECTION
CONTACTS VOLT.
FILTER LOGIC MONITOR
LB PEAK OR AVG DL OR LOV
DETECTOR
ACCEPT
DB OR BOV
VOLTAGE
FRONT PANEL SETTINGS MONITOR
OUTPUT
LL MODE
SWITCHES
ISOLATION
DL OR LOV
CONDITION
D1058-04.vsd SWITCHES
01-30-01
Power Supply
Operating power for the relay circuitry is supplied by a wide range, electrically isolated, low-burden power
supply. Power supply operating power is not polarity sensitive. The front panel power LED and power
supply status output indicate when the power supply is operating. Power supply specifications are listed
in Table 1-1.
Filters
Input voltages from bus and line are filtered and applied to the peak detectors or average detector
circuitry.
Selection Logic
Voltage monitor selection logic is controlled by Mode and Condition switches or External Condition
Switches to produce the Voltage Monitor output.
Another output from the voltage monitor selection logic serves as an additional qualifier for the timer in
the sync output circuit. The specific conditions being monitored depend upon whether NORMAL or NOT
OV operation is used. Live line and live bus is monitored if NORMAL Mode is selected. Live line, live bus,
and Not Overvoltage is monitored if NOT OV Mode is selected.
Detailed instructions and precautions for programming the Mode and Condition switches are provided in
Table 2-1, callouts R and S. The location of the switches is shown in Figure 2-2.
Target Indicator
A target indicator is an optional component selected when a relay is ordered. The electronically latched
and reset target consists of a red LED indicator located on the relay front panel. A latched target is reset
by operating the target reset switch on the front panel. If relay operating power is lost, an illuminated
(latched) target is extinguished. When relay operating power is restored, the previously latched target is
restored to its latched state.
A relay can be equipped with either an internally operated target or a current operated target.
CAUTION
When the connection plugs are removed, the relay is disconnected from the
operating circuit and will not provide system protection. Always be sure that
external operating (monitored) conditions are stable before removing a relay for
inspection, test, or service.
NOTE
Be sure that the relay is hard-wired to earth ground with no smaller than 12 AWG
copper wire attached to the ground terminal on the rear of the case. When the
relay is configured in a system with other devices, it is recommended to use a
separate lead to the ground bus from each device.
MOUNTING
Relay
Because the relay is of solid-state design, it does not have to be mounted vertically. Any convenient
mounting angle may be chosen. Relay outline dimensions and panel drilling diagrams are supplied at the
end of this section.
Resistor Module
When the condition and mode switching of the Voltage Monitor option is controlled by external contacts
(option 2-C, 2-U, or 2-V), a voltage dropping Resistor Module is bolted to the rear of the relay (Figure
4-9). If the relay is to be projection mounted (Figure 4-3), it will be necessary to first remove the module
when mounting the relay, then reattach it so that the mounting panel lies between the relay and module.
In planning the installation, reserve a clear space directly behind the relay or behind the mounting panel if
projection mounted, since the Resistor Module will give off some heat during use.
P0002-12
01-31-01
DETAIL A-A
P0002-17
01-30-01
8.25
8.63 (209.6)
(219.1)
4.13
4.31
(104.8)
(109.5)
19 11 1.47
.69
(37.3)
20 12 (17.5)
1.00
.25
(25.4)
(6.4)
4.28
(108.7)
3.20 1.63
(81.3) (41.4)
1.16
(29.5)
.68
(17.3) 1.16
(29.5)
3.20
(81.3)
2.28 1.63
(57.9) (41.4)
.63 (16.0) DIA.
4.28 .50 3 PLACES
(108.7) (12.7)
TYP.
9 1 1.47
.69
(17.5) (37.3)
10 2
1.00
.25
(25.4) 1
.75 (19.1) DIA. (6.4)
2.63
20 PLACES
(66.8)
5.25 D1427-05
(133.4) 01-30-01
Notes:
1 Optional rectangular cutout may replace the ten drilled
holes.
CONNECTIONS
Be sure to check the model and style number of a relay before connecting and energizing the relay.
Incorrect wiring may result in damage to the relay. Except where noted, connections should be made with
wire no smaller than 14 AWG.
Typical internal connections are shown in Figure 4-7. Typical external connections are shown in Figures
4-8 through 4-11.
20 18 16 14 12
Vctrl
TERMINAL 19
WILL VARY NON-
ISOL.
DEPENDING AUX. SYNC CONT.
ON OPTIONS OUT SENS. J1
OR
P.S.S.
ISOL.
COM. TO CONT.
EXPAND OPTO-ISOL. SENS.
EXTERNAL
CASE GROUND
TERMINAL
INTERNAL
CIRCUITRY
LINE BUS
EXTERNAL CONTACT
INPUTS FROM
RESISTOR MODULE
VOLTAGE
MONITOR
OUT
TARGET
POWER SYNC
SUPPLY OUT
9 7 5 3 1
COM COM
10 8 6 4 2
D2819-03
LINE BUS 08-29-02
19 17 15 13 11
20 18 16 14 12
RESISTOR
MODULE
9 7 5 3 1
10 8 6 4 2
BE1-25
D999-005
3-10-92
MAINTENANCE
BE1-25 relays require no preventative maintenance other than a periodic operational check. If the relay
fails to function properly, contact Technical Sales Support at Basler Electric to coordinate repairs.
STORAGE
This protective relay contains aluminum electrolytic capacitors which generally have a life expectancy in
excess of 10 years at storage temperatures less than 40°C (104°F). Typically, the life expectancy of a
capacitor is cut in half for every 10°C rise in temperature. Storage life can be extended if, at one year
intervals, power is applied to the relay for a period of 30 minutes.
SWITCH SETTINGS
0.2 0.02
80
0.1 0.01
0.09 0.009 40
0.08 0.008
0.07 0.007
0.06 0.006
0.05 0.005
20
0.04 0.004
0.03 0.003
10
0.02 0.002
5 10 15 20 25
MULTIPLIER SWITCH IN "X1.0" POSITION
Figure 5-1. Maximum Slip Frequency versus Time Delay and Phase Angle Settings
Preliminary Settings
(a) All contact-sensing inputs are open circuited.
(b) All Condition Switches and Mode Switches are UP.
(c) Some styles of relay are equipped with multiturn pots accessible through holes in the front panel.
All such controls should be turned fully CCW (to their minimum settings) except the ΔV control,
which is turned fully CW.
(d) Adjust bus and line sensing input voltages to 95 Vac with zero phase difference.
(e) Apply power to the relay.
(f) If equipped with power supply status output (option 3-6), verify that the power supply status
output contacts are open.
(g) Remove input power and verify that the status contacts close.
(h) Apply power to the relay.
NOTE
A 00 setting of either control must inhibit the Sync-Check function.
If target option B (current operated target) is present, check that targets operate at
closure of the sync contacts. (Requires a minimum of 0.2 A in the output circuit.)
Step 1. Confirm proper sync-check operation at selected PHASE ANGLE settings with TIME DELAY set
at minimum (for convenience). Check that go/no-go operation is within specs.
NOTE
When making this test, observe that the PHASE ANGLE LED is turned ON during the
delay period, and that the SYNC LED flashes when the output contacts close. (Both
LEDs go out as soon as the 52b input is open.)
If auxiliary contacts are supplied, check for proper switching action as relay cycles.
Step 2. With line and bus inputs in phase, check for proper operation of timer, using a time delay of 9.9
seconds, and again at 99 seconds (multiplier switch at 0.1 and at 1.0 respectively). (Close and
open the 52b input to begin and terminate the timing cycle.) Check that accuracy of timing cycle
is within specs.
Step 3. Check that operation of the sync function is inhibited during low voltage conditions of line or bus.
(a) Lower line and bus sensing input to 60 Vac and repeat Step 1. SYNC output should not be
inhibited.
(b) Lower the line sensing inputs to 20 Vac. Attempt Step 1. SYNC function is inhibited and
PHASE ANGLE LED should not turn ON.
(c) Return the line input to 60 Vac and lower the bus input to 20 Vac. Attempt Step 1. Sync
function is inhibited and PHASE ANGLE LED should not turn ON.
It is not necessary to determine the exact voltage threshold at which inhibition occurs in order to confirm
proper operation of this circuit.
NOTE
Steps 4 through 8 check for proper operation of line and bus Voltage Monitor (options 2-
A, 2-C, 2-R, 2-S, 2-U, or 2-V). If these options are not present, proceed to step 7.
Step 4. Verify that the voltage monitor controls operate over the specified range as follows.
(a) Rotate the LL and LB controls (front panel) fully CW; rotate the DL/NOT overvoltage and
DB/NOT overvoltage controls fully CCW.
(b) Adjust line and bus sensing inputs to 135 Vac.
(c) Slowly rotate the LL and LB controls CCW until LEDs turn ON. This should occur only a few
turns from the maximum (fully CW) position.
(d) Adjust line and bus sensing inputs to 10 Vac.
(e) Rotate the LL and LB controls CCW until their indicators LEDs turn ON. This should occur
only a few turns from the minimum (fully CCW) position.
(f) With input voltages remaining at 10 Vac, rotate the DL/NOT overvoltage and DB/NOT
overvoltage controls CW until their LEDs just light. Both adjustments should require only a
few turns from the minimum (fully CCW) position.
(g) Return line and bus sensing inputs to 135 Vac. (Both LEDs of step (f) must now be OFF.)
(h) Again rotate the DL/NOT overvoltage and DB/NOT overvoltage controls CW until the LEDs
just light. Both adjustments should be near their maximum (fully CW) limits.
Step 5. Test NORMAL Mode operation of the line and bus voltage monitor as follows. (Proceed to step 6
if the NORMAL Mode is not used.)
(a) Adjust the following front panel controls by applying the voltages listed below, adjusting each
control to the threshold where its LED just lights. (Reference callouts L, N, F, and G of Figure
2-1.)
LB: Adjust to 80 Vac.
DB/NOT OV: Adjust to 30 Vac.
LL: Adjust to 80 Vac.
DL/NOT OV: Adjust to 30 Vac.
(b) If the relay is not equipped with a separate relay for Voltage Monitor (output options G and
H), set TIME DELAY to 99 seconds. This allows the convenience of using in-phase voltages
for testing non-synchronous functions (without unwanted SYNC contact closures).
(c) Apply simulated line and bus voltages, adjusted to check the bus and line voltage criteria
given in Table 5-1. To be valid, an output must occur immediately after line and bus voltages
are applied.
NOTE
In some units, both the internal Condition Switches and the external condition sensing
inputs are present and in parallel. Take care that only one input method is utilized when
testing the relay, and (most importantly) after the relay is installed.
Condition Switch
1 Up
2 Up
3 Up
4 Up
5 Up
Mode Switch
1 Up
2 Up
Output* only when bus input voltage is greater than 80 volts and line is less than 30 volts.
Condition Switch
1 Up
2 Up
3 Down
4 Up
5 Up
Mode Switch
1 Up
2 Up
Output∗ only when bus input voltage is less than 30 volts and line is greater than 80 volts.
Condition Switch
1 Up
2 Up
9170200990 Rev R BE1-25 Testing 5-5
3 Up
4 Down
5 Up
Mode Switch
1 Up
2 Up
Output∗ only when bus and line input voltages are less than 30 volts.
Condition Switch
1 Up
2 Up
3 Up
4 Up
5 Down
Mode Switch
1 Up
2 Up
Output∗ only when bus and line input voltages are greater than 80 volts.
Condition Switch
1 Up
2 Down†
3 Up
4 Up
5 Up
Mode Switch
1 Up
2 Up
∗ Contact is SYNC output for output option E or F. Voltage Monitor output for output option G or H.
† The only valid use for the LB-LL Condition Switch No. 2 Down is when there is an independent output
relay for the Voltage Monitor output options G and H.
If the delta voltage option is present, it is factory set to 20 volts. (The timed SYNC output is inhibited if the
voltage difference between the line and the bus is greater than 20 volts.)
CAUTION
Condition Switch No. 2, shown in Figure 2-2, must be OFF (Up) when output
option E or F is selected. Otherwise, SYNC outputs will occur under live line/live
bus conditions without benefit of the Sync-Check function.
NOT OV Testing
Step 6. Test the NOT OV Mode of the Voltage Monitor as follows. (Proceed to step 7 if this mode is not
used.)
(a) Adjust the following front panel controls by applying the voltages stated below, adjusting each
control to the threshold where its LED indicator just turns ON. (Reference callouts L, N, F,
and G of Figure 2-1).
LB: Adjust to 80 Vac.
DB/NOT OV: Adjust to 120 Vac.
LL: Adjust to 80 Vac.
DL/NOT OV: Adjust to 120 Vac.
5-6 BE1-25 Testing 9170200990 Rev R
(b) Set TIME DELAY to 99 seconds. This allows the convenience of using in-phase voltages for
testing non-synchronous functions (without unwanted SYNC outputs).
(c) Apply simulated line and bus voltages adjusted to check the bus and line voltage criteria
given in Table 5-2. To be valid, an output must occur immediately after line and bus voltages
are applied.
Step 7. If the voltage difference option is furnished, check for proper enabling of the Sync-Check output
contacts when the voltage differential between line and bus is within selected ΔV settings.
Step 8. If the expand phase angle option is furnished, check that the phase window widens by a factor of
2 or 3 (according to the position of the jumper on the Sync-Check PC board) when the expand
phase input terminal is closed.
No output∗ throughout voltage range. (Normal SYNC output function still operates. SYNC output occurs
after 99 seconds time delay if the line and bus voltages are greater than 60 Vac. This 60 Vac
corresponds to the minimum voltage requirement for the sync-check function, not the LL and LB settings.
For the following tests, if your unit has a minimum voltage requirement of less than 60 Vac, use a voltage
that is appropriate for your unit.
Condition Switch
1 Up
2 Up
3 Up
4 Up
5 Up
Mode Switch†
1 Down
2 Down
Output∗ only when bus input voltage is greater than 60 volts but less than 120 volts, and line is less than
60 volts.
Condition Switch
1 Up
2 Up
3 Down
4 Up
5 Up
Mode Switch†
1 Down
2 Down
Output∗ only when bus input voltage is less than 60 volts and line is greater than 60 volts but less than
120 volts.
Condition Switch
1 Up
2 Up
3 Up
4 Down
5 Up
Condition Switch
1 Up
2 Up
3 Up
4 Up
5 Down
Mode Switch†
1 Down
2 Down
Output∗ only when bus and line input voltages are greater than 60 volts but less than 120 volts.
Condition Switch
1 Up
2 Down‡
3 Up
4 Up
5 Up
Mode Switch†
1 Down
2 Down
No output throughout voltage range. (Normal SYNC function still operates with the additional NOT
overvoltage constraint. Output occurs after 99 seconds time delay if the line and bus voltages are greater
than 60 Vac and less than the NOT overvoltage setting of 120 Vac.)
Condition Switch
1 Down
2 Up
3 Up
4 Up
5 Up
Mode Switch†
1 Down
2 Down