Code of Practice Hardware For Fire and Escape Doors
Code of Practice Hardware For Fire and Escape Doors
Issue No.4
November 2012
This page is intentionally left blank
Index Page i
Section 1 Introduction
1.0 General 3
1.1 Scope 3
1.2 Terminology 3
1.3 Commentary 3
1.4 Relevant legislation 8
1.5 Documentation 12
Section 2 Hinges
2.1 Introduction 19
2.2 Critical Recommendations 19
2.3 Commentary 21
ISBN 0 9521642 2 1
© Guild of Architectural Ironmongers and the Door and Hardware Federation June 2006 - 2012
Permission to reproduce extracts from British Standards is granted by BSI under Licence No.
2009ET0032. Copyright subsists in all BSI publications. British Standards can be obtained in PDF
or hard copy formats from the BSI online shop: www.bsigroup.com/Shop or by contacting BSI
Customer Services for hard copies only:
Tel: +44 (0)20 8996 9001, Email: [email protected].
Foreword Page 1
The Code is advisory, and compliance does not imply immunity from
any legal requirement nor does it necessarily satisfy any special
conditions which might be required by insurance companies or
regulatory authorities.
A combined team from the DHF and the GAl has been responsible for
this document. Technical enquiries should be directed to the GAI or
DHF at the addresses given below:
DHF
42 Heath Street
Tamworth
Staffordshire
B79 7JH
Tel: 01827 52337
Fax: 01827 310827
E-mail: [email protected]
Website: www.dhfonline.org.uk
GAl
BPF House,
6 Bath Place,
Rivington Street,
London
EC2A 3JE
Tel: 020 7033 2480
Fax: 020 7033 2486
E-mail: [email protected]
Website: www.gai.org.uk
Section 1: Introduction Page 3
1.1 Scope
This Code applies to building hardware for fire-resisting doors and
doorsets, and escape doors. The following are taken into account:
1.2 Terminology
Terminology used in this Code of Practice reflects common usage as
far as possible. Where appropriate, terminology has been taken from
the current BS EN standards for building hardware.
1.3 Commentary
Fire-resisting doors
• BS 476:22, or
• BS EN 1634-1.
Time in Minutes
However the deadbolt is not thrown and the spring bolt may be wired
back so that they play no part in holding the door closed. The door
manufacturer is then able to test two points simultaneously:
• the door can perform its fire-resisting function without a latch or bolt
(for unlatched applications relying on a door closer)
• locks of similar dimensions and materials can be fitted without
compromising the door's fire resistance.
"Integrity" does not include passage of smoke, and during the early
stages of a timber door fire test, copious amounts of smoke are pushed
through the gaps between the door and frame, and between the
meeting stiles on pairs of doors, in the upper area. This is due to the
positive pressure in this area of the door. Where doors have intumescent
seals fitted, and these have activated and expanded in the gaps around
the door(s) and frame, the smoke penetration is reduced to almost zero,
until the door assembly reaches the end of its ability to withstand fire
attack, and new gaps open, due to warping of the door, or burn-through.
The results of this small-scale test regime may be used for hardware to be
used on doors of similar construction, which were tested to BS EN 1634-1.
Code of Practice: Hardware for Fire and Escape Doors Page 6 Section 1: Introduction
Without smoke seals, smoke passes around fire doors in the early stages
of a fire - see unsealed right hand door
The report generated after testing will indicate the total length of
interruptions in the perimeter smoke seal due to building hardware
such as hinges and lock strikes. Therefore the specifier of building
hardware for a smoke door must ensure that the fittings selected will
not create a greater total length of interruptions in the seal.
Example: if the tested doorset’s frame-fixed smoke seal was interrupted by:
3 x hinges @ 100 mm height = 300 mm
I x strike plate @ 220 mm height = 220 mm
Total length of interruptions = 520 mm
• pivots or hinges - these attach the door onto the frame, and hinges
might also help to stop it bowing
• a door closing device - e.g. an overhead door closer or floor spring
ensures that the door closes reliably and stays shut
• and/or a latch/lock - in some cases, a latch or lock takes on the role
of holding the door shut (in lieu of the door closing device).
These items must be carefully selected to ensure that they will
perform their role satisfactorily. Most other items of building hardware
on the door perform a function not directly associated with its fire
performance ("non-essential"), but they must in no way impede or
reduce the door's ability to withstand fire attack for the specified
time. This also requires careful selection. Too often, holes are drilled
through timber fire doors, and large metal components are attached,
with no thought as to the consequences.
Door hardware that has been included in successful fire tests has reached
one goal, but there is an additional goal - durability. When fire tested, the
door, the seals and hardware are brand new, and no significant cycling
(opening and closing movements) takes place before the test.
Code of Practice: Hardware for Fire and Escape Doors Page 8 Section 1: Introduction
Those items performing a role essential to the successful operation of
the fire-resisting doors - hinges, closing devices, latches or locks -
should be chosen for their ability to cope with the type of use to which
the door will be put. If hinges collapse, a door closer weakens, or a
latch wears badly, it is unlikely that the door will maintain its essential
self-closing function. This, of course, will defeat the main purpose of
the fire door, and the safety of people and property is put at risk.
Emergency
• Locked doors on
BS EN 179 1 April 2002 escape routes
Exit Hardware
• Fire / smoke doors
Panic
• Locked doors on
BS EN 1125 1 April 2002 escape routes
Exit Hardware
• Fire / smoke doors
• Locked doors on
Single Axis Hinges BS EN 1935 1 Dec. 2002 escape routes
• Fire / smoke doors
Controlled Door
BS EN 1154 1 Oct. 2003 • Fire / smoke doors
Closing Devices
Electrically powered
BS EN 1155 1 Oct. 2003 • Fire / smoke doors
Hold Open Devices
This list is not comprehensive, but gives an insight into the wide-
ranging responsibilities which have been transferred from other agencies,
such as the Fire Service, to building owners and operators. Users of this
Code of Practice will find its guidance on suitable products, the
standards to which they should conform, and the recommendations on
their maintenance, of great help in fulfilling responsibilities they might
have in connection with this legislation. (See also Section 13:
Maintenance: Fire and Escape Door Hardware.)
1.5 Documentation
The following documents are considered acceptable as evidence of
suitability of building hardware for incorporation into a fire-resisting
doorset or door assembly:
• third party certification of the building hardware
• fire-resisting doorsets’ third party certification data sheet
• fire test reports or
• assessment by competent authority.
Fire test reports are complex technical documents and should only
be used by those who are competent to interpret what is reported
in the document.
Code of Practice: Hardware for Fire and Escape Doors Page 14 Section 1: Introduction
It is easy for the uninitiated to overlook a vital aspect of the test
which limits the field of application of the result. For example, a
closer tested on a door which was latched closed is not proven as
suitable for the same door in unlatched condition.
1 .5.5 Assessments
These are usually written in much more user-friendly language than
fire test reports. They are based on test evidence, and the assessor's
experience.
1 - Category of use
Grade 1 - Light duty
Grade 2 - Medium duty
Grade 3 - Heavy duty
Grade 4 - Severe duty
2 - Durability
(Out of possible grades 1-8, only 3,4 & 7 are used in this standard)
3 - Door size/mass
Grade 1 - 20 kg
Grade 2 - 40 kg
Grade 3 - 60 kg
Grade 4 - 80 kg
Grade 5 - 100 kg
Grade 6 - 120 kg
Grade 7 - 60 kg
4 - Fire resistance
Grade 0 - not approved for use on fire / smoke door assemblies
Grade A - suitable for smoke door assemblies - subject to test evidence
Grade B - suitable for fire and smoke door assemblies - based on a test
in accordance with BS EN 1634-1
Code of Practice: Hardware for Fire and Escape Doors Page 16 Section 1: Introduction
5 - Safety in use
Grade 1 - safe (only acceptable grade)
6 - Corrosion resistance
Based on the grades given in BS EN 1670
Grade 0 - none
Grade 1 - mild
Grade 2 - moderate
Grade 3 - high
Grade 4 - very high
Grade 5 - extremely high
7 - Security
Grade 0 - not suitable for burglar-resistant doors
Grade 1 - suitable for burglar-resistant doors, subject to test evidence
Certain products may carry additional classification digits for
parameters specific to those devices.
British Standards for products outside the scope of the BS ENs might
not cover all of these categories. Reference must be made to each
standard with which a product claims compliance.
At the same time, where escape route doors are part of the final exit
from a building, there will be some additional requirements for
security of the door against intrusion and burglary. In this case the
hinges should be of a design so that they cannot be removed or
parted whilst the door is closed, ensuring that the building and its
contents are secured against unauthorised entry.
Where escape route doors are part of the fire compartmentation of the
building, there will be additional requirements to ensure that the hinges
fitted do not compromise the fire-resisting performance of the doors.
2.2.1
If placed on the market after 1 July 2013, the chosen hinge:
2.2.3
The strength and features must be correct for the size of door and
mass to which it is to be fitted, bearing in mind:
• the application of the door (main entrance, toilet lobby, duct door),
• position of door stop if being used (position on floor or wall in
relation to width of door)
• whether subject to factors such as heavy traffic use, abusive
treatment
• whether or not a door closer is being used (with or without
backcheck)
• size (height and width) and mass (weight) of the door number and
position of hinges
• whether the door is on an accessible route and therefore needs to
satisfy Part M of the Building Regulations (see Section 11 for details).
2.2.4
A regular program of maintenance must be undertaken to ensure that
the correct operational performance of the hinge is maintained for the
life of the building. (see Section 13).
2.2.5
Rising butt hinges are NOT recommended for use on fire-resisting
doors (See 2.3.6).
2.2.6
Spring hinges are NOT recommended for use on fire-resisting doors
(see 2.3.8).
Section 2: Hinges Page 21
2.2.8
Hinges for use on final exit escape doors should have a corrosion
resistance of not less than Grade 3 of BS EN 1670.
2.2.9
CE Marked hinges should be marked according to clause ZA.3 of
BS EN 1935.
2.3 Commentary
2.3.2 Sizes
Hinges are available in a range of sizes, which relate to the mass and
size of the door. These are set out in Table 1 of BS EN 1935, which
is shown below:
Clearly, an important factor is the size of the hinge with respect to the
door mass.
Code of Practice: Hardware for Fire and Escape Doors Page 22 Section 2: Hinges
Due to tooling costs and similar considerations, variations of hinge sizes
and fixing methods are not easily accommodated on a steel door. Steel
door manufacturers generally provide their own steel hinges, which
otherwise comply with these requirements, as part of the fire-resisting
steel doorset and these are covered by evidence of performance.
2.3.3 Torque
The torque between the two hinge leaves is important. Limits of this
torque are set down in BS EN 1935; the low torque requirement of
the hinge is necessary to allow the door closing device to overcome
the resistance of the latch bolt and/or seal pressure. The requirements
range between 2 Nm and 4 Nm dependent on the grade of hinge
from 7 to 14. Hinges fitted on fire-resisting doors that are on
accessible routes should have the lowest possible torque. (For more
details see Section 11).
Closed Open
b) The closing force exerted by rising butt hinges is extremely low and
will not overcome air pressure differences or resistance from latches,
seals or carpets that might be fitted, and therefore they cannot be
considered as reliable door closing devices. (See 3.3.9).
Code of Practice: Hardware for Fire and Escape Doors Page 24 Section 2: Hinges
2.3.7 Lift-off, Loose Pin and Journal Supported Hinges
Only hinges which require a special tool to separate the hinge leaves
when the door is in the closed position may be used (this prevents
the fire-resisting door from being removed by unauthorised persons).
Lift-off hinge
For steel doors, hinges should be fixed with machine screws which
are screwed into steel reinforcing plates provided in the door and
the frame.
www.dhfonline.org.uk www.gai.org.uk
Section 3: Door Closing Devices Page 27
• close the door leaf reliably from any angle to which it has been opened
• overcome the resistance of a latch or any seals when fitted.
For the purpose of this Code of Practice door closing mechanisms are
divided into the following categories:
Note: This list does not imply suitability of any device for fire door use
- see 3.2 and 3.3 for further information.
*Dwellinghouses and flats granted planning permission before April 2007 fall under
the recommendations of Approved Document B 2000 edition, which required any
internal fire doors to be self-closing. This requirement will continue for such
buildings, and self-closing devices should still be provided on such internal domestic
fire doors in any refurbishment. In these circumstances, uncontrolled closers are
permitted, including rising butt hinges. Dwellinghouses and flats granted planning
permission after 5 April 2007 fall under the recommendations of Approved Document
B 2006 edition. In this case, any dwellinghouses and flats fitted with hard-wired
smoke sensors may have internal fire doors without self-closing devices. However, the
front door to a flat, and the door to any integral garage must be fitted with a self-
closing device which complies with BS EN 1154 or BS EN 1155.
Code of Practice: Hardware for Fire and Escape Doors Page 28 Section 3: Door Closing Devices
3.2 Critical Recommendations
3.2.1
If placed on the market after 1 July 2013, the door closing device
and its accessories:
3.2.2
The product and any accessories must have demonstrated their
suitability for the intended purpose, by inclusion in satisfactory fire
tests to BS EN 1634-1 or BS EN 1634-2, on a type of door and
configuration in which will be used. This evidence should be
provided by an approved third party certification or testing body.
(See 1.5 Documentation).
3.2.3
The strength and features of the control must be correct for the size
of door to which it is fitted, bearing in mind:
3.2.5
Concealed overhead controls should NOT be used unless they are
provided with any specially designed and proven intumescent
protection (see 3.3.7) which might be stipulated in the fire test
report or field of application data sheet.
3.2.6
For floor springs, strap accessories are preferred (see 3.3.10).
3.2.7
Spring hinges, which are purely spring urged and do not control the
closing speed, are unable to comply with BS EN 1154 and therefore
should NOT be used for fire doors (see section 3.3.8).
3.2.8
Rising butt hinges are NOT recommended for use on fire doors.
(See 2.3.6 and 3.3.9).
3.2.9
Manually operated mechanical hold-open devices (i.e. mechanisms which
must be released manually) SHOULD NOT BE USED ON FIRE DOORS.
(See 3.3.2).
3.2.10
The automation of fire-resisting doors must not detract from their
essential primary function as a fire door. The device should meet all
critical criteria applicable to self-closing devices.
3.2.11
A regular programme of maintenance must be undertaken to ensure
that the correct operational performance is maintained for the life of
the building. (See Section 13).
Code of Practice: Hardware for Fire and Escape Doors Page 30 Section 3: Door Closing Devices
3.3 Commentary
3.3.1 General
The Building Regulations 1991 Approved Document B 2000 Edition
requires that all fire-resisting doors (with the exception of locked
cupboard/duct doors and internal domestic doors) be fitted with an
appropriate self-closing device.
BS EN 1154 states that door closers of less than power size 3 are not
considered suitable for fire doors due to their low closing moments,
especially beyond 90°. It also requires that power adjustable closers
should be capable of adjustment to at least power size 3, and that for
such closers the installation instructions shall include precise
instructions to the installer to ensure that the door closer is adjusted
on site to size 3 or more. (Care should be taken to differentiate
between variable power adjustable closers and template adjustable,
where the closer remains dependent on the template fixing position).
The connection between the door leaf and frame is created by a pair
of folding arms or a single arm guided in a channel.
Mounting options
Because these closers are mortised into the leaf, it is also important
to check that doors are suitable to accommodate the closers and that
the installation of the closers will not be a possible cause of burn-
through and integrity failure.
Section 3: Door Closing Devices Page 37
The closing force exerted by such a device is extremely low and will
not overcome air pressure differences or resistance from latches, seals
or carpets that might be fitted, and therefore they cannot be
considered as reliable door closing devices. Whilst such devices are
still permitted in dwellings and flats covered by Approved Document
B (2000 edition) for certain domestic applications only, they are NOT
recommended for any fire door application by this Code of Practice.
(See also 2.3.6).
Section 3: Door Closing Devices Page 39
As the floor spring and its associated pivots are responsible for
holding the door in position, high melting point metals for the
structural components will usually be required. Although the box
containing the closer mechanism is one of the largest items of
hardware, it is set into the threshold of the doorway and so, with the
exception of the cover plate, is protected by the floor screed. The
performance of the closer is aided during fire attack by the slight
negative pressure at floor level, which is drawing cold air from the
unexposed side of the construction, across the cover plate, so helping
to keep this cool.
This fitting is installed centrally within the thickness of the bottom rail
and is concealed. This fitting has shown itself to be most successful as
an item of fire door hardware for, like the closing control, its position
within the door leaf is the least onerous in terms of exposure. Some
designs require the addition of intumescent protection against the
effects of heat reflection from the cover plate and this should be stated
in the fire test evidence.
Code of Practice: Hardware for Fire and Escape Doors Page 40 Section 3: Door Closing Devices
3.3.10.2 Double Action Shoe
Whilst this performs the same function as the strap, it is constructed
with side and heel walls which wrap around the heel profile of the
door and is commonly made in brass. One sidewall is, therefore,
exposed to flame, and conduction of heat via the walls to the
unexposed face is likely to cause failure of integrity in timber doors
under fire conditions. Some manufacturers are able to solve these
problems by careful design and/or the addition of intumescent
protection, and thus achieve satisfactory fire test evidence.
• the upper part housing the pivot pin, which is retractable to assist
installation, mortised into the underside of the head frame,
• the lower part containing a bearing or bush for the pivot pin,
morticed centrally into the thickness of the door top rail.
Top Centre
Top
Centre
Covers
Single Action Bottom Strap
Strap Cover
Cement Box
Section 3: Door Closing Devices Page 41
Note: with these last three items, where they have a limited offset, it
is necessary to notch away the door and frame locally, to provide
clearance for the housing. This practice could lead to integrity failure
in timber doors, and it is therefore important to check that the fire
test evidence is relevant to the intended door application.
5mm offset strap showing notch required in the frame and door heel
Code of Practice: Hardware for Fire and Escape Doors Page 42 Section 3: Door Closing Devices
3.3.11 Automatic Swing Door Operators
3.3.11.1
Automatic swing door operators generally look like a larger version of
a manual door closing device and are fitted in a similar way. However,
there are safety considerations that are detailed in BS 7036. (see
also 3.2.2)
3.3.11.2
The automatic mechanism should be capable of being interfaced with
the fire alarm system, thereby causing the doors to cease automatic
opening in the event of an emergency triggering the alarm system.
3.3.11.3
Automatic mechanisms normally power open, and close under spring
pressure. Consideration should be given to external forces such as
wind pressure in the same way as for manual devices.
3.3.11.4
Any powered doorset is regarded as "machinery" as defined in the
Supply of Machinery (Safety) Regulations 2008 and these regulations
require that the complete assembly be covered by a declaration of
conformity issued under this legislation; the assembled doorset must
also bear the CE marking specified in the regulations. The person
issuing the declaration is also required to keep a technical
construction file for inspection by the authorities.
www.dhfonline.org.uk www.gai.org.uk
Section 4: Electrically Powered Hold Open Devices Page 43
Depending upon the intended use of the door, there are two basic
functions available:
• Hold open: This function holds the door leaf in an open position
for as long as the device is energised, thus permitting free passage
through the door. When triggered by the fire/smoke alarm system,
local detector control, local pushbutton or by power failure, the
device releases the door leaf and allows it to close under the control
of a door closing device. With power subsequently restored, the leaf
will again be held, once it has been returned to the hold open
position. These devices are usually used on cross-corridor doors and
circulation routes.
• Free-swing: After priming, by moving the door leaf to the fully open
position, this function prevents the door closing mechanism from re-
closing the leaf, but enables the leaf itself to be moved freely
without the need for the user to overcome any force from the closer.
In effect, the door leaf will then behave as though there were no
closing mechanism fitted. When triggered by the fire/smoke alarm
system, local detector control, local pushbutton or by power failure,
the device releases the closer mechanism, allowing it to close the
door leaf in a controlled manner from whatever position it was in at
the time. With power subsequently restored, the leaf will again
achieve this free-swing function once it has been returned to the
fully open position. These devices are usually used on doors opening
into individual rooms and are not recommended for cross-corridor
doors or circulation routes.
Code of Practice: Hardware for Fire and Escape Doors Page 44 Section 4: Electrically Powered Hold Open Devices
It can be seen that the use of these devices will make access around
a building much easier, particularly for the young, elderly, disabled or
those manipulating trolleys etc, without compromising the fire
compartmentation function of the fire-resisting doors to which they
are fitted.
4.2.1
Manually operated mechanical hold open devices (i.e. mechanisms
which must be released manually) SHOULD NOT BE USED ON FIRE
DOORS UNDER ANY CIRCUMSTANCES.
4.2.2
Low voltage (24/12 V dc) electrically-powered hold open devices and
their accessories should be:
4.2.3
The product and any accessories should have demonstrated their
suitability for the intended purpose, by inclusion in satisfactory fire
tests to BS EN 1634-1 or BS EN 1634-2, on a type of door assembly
and configuration with which it is proposed to be used. This evidence
should be provided by an approved third party certification or testing
body. (See 1.5).
Section 4: Electrically Powered Hold Open Devices Page 45
4.2.5
For separate hold open devices, the holding power and manual
release force must be correct for the size of door and power size to
which they are to be fitted, bearing in mind:
4.2.6
Separate hold open devices should be installed such that they are in
the same horizontal plane as the closing device to minimise any
twisting or distortion of the door leaf. (See also 4.3.2).
4.2.7
Holes and apertures for the cables that provide electrical power to
door- or frame-mounted devices must be protected to maintain the
fire integrity of the doors. This might require specially designed and
proven intumescent protection (see 4.3.5).
4.2.8
A regular programme of maintenance must be undertaken to ensure
that the correct operational performance is maintained for the life of
the building. (See Section 13).
Code of Practice: Hardware for Fire and Escape Doors Page 46 Section 4: Electrically Powered Hold Open Devices
4.3 Commentary
4.3.1 General
The Building Regulations 2010 Approved Document B 2006 Edition
allows self-closing fire-resisting doors to be held open by electrically
powered hold open devices actuated by an automatic fire detection
and alarm system, in those situations where a normal self-closing
device would be considered a hindrance to the normal approved use
of the building.
The following extract from BS EN 1155 shows the range of hold open
power sizes and related maximum recommended door leaf widths,
together with some of the relevant test parameters:
Hold open Max. door Test door Overload test Max. test door
power size leaf width mass (kg) drop weight friction (Nm)
3 950 60 15 0.3
4 1100 80 18 0.4
Table 1 BS EN 1155
Section 4: Electrically Powered Hold Open Devices Page 47
It is important that the holding force of any separate hold open device
is higher than the closing force exerted by the door closing mechanism.
If the holding force is not strong enough, the closer will tend to pull the
door leaf from the held position and hence close the door. Whilst this
does not in itself compromise the fire performance of the door, it will be
an annoyance to the building users, who might respond by wedging the
door open to overcome this "nuisance closing".
If the holding force is too strong, the users might have difficulty in
mechanically pulling the door leaf from the hold open position.
It is vital that these hold open devices are able to release reliably in
the case of fire. BS EN 1155 contains durability requirements and
other performance tests to ensure that release will always occur, even
when subject to variations of voltage supply.
The effective holding force available will depend upon the mounting
position of the armature relative to its distance from the hinges and the
power size of the door closer fitted. It is therefore important that the
installation instructions are closely followed to avoid "nuisance closing".
Code of Practice: Hardware for Fire and Escape Doors Page 48 Section 4: Electrically Powered Hold Open Devices
Some separate hold open devices are battery operated rather than
hard wired. They work from an acoustic signal, or a radio
transmission. They are attached to the bottom of the door and look
rather like traditional foot-operated door holders. The acoustic type
relies on the high level of sound from the fire alarm to initiate
releasing the door. They are not suitable for very noisy environments
where a false release might be frequently triggered. For noisy areas,
a similar product that works off a radio signal is available. There are
limits with both types as to the effective distances between the
transmitter and receiving units.
At present, these types of unit are considered suitable only for low
risk situations. Guidance on acceptable locations for their use is
given in BS 7273-4 Code of practice for the operation of fire
protection measures: Part 4: Actuation of release mechanisms for
doors. It is recommended that only those products CE marked to
BS EN 1155 be fitted to fire doors.
Section 4: Electrically Powered Hold Open Devices Page 49
Other types operate directly on the closer arms and do not suffer from
"creep". BS EN 1155 permits a maximum "creep" of only 2° over a
period of 48 hours. Irrespective of the type of device used, it is
important that the manufacturer’s recommendations for routine checks
and maintenance are followed, and it is is often a requirement to ensure
that all door holding devices are released at the end of each working day.
Some types are used for pairs of doors where the two door closing
devices are linked by arms to a common track, which runs across the
transom for the full width of both door leaves. In these circumstances
this additional mass of metal can act as a heat sink and cause local
charring of the frame or leaf in this vulnerable area, unless additional
protection such as an intumescent gasket is fitted. It is important
with all such devices to ensure that any protection recommended or
supplied by the manufacturer is fitted during installation. The fire test
evidence should be examined to make sure that it is relevant to the
intended application.
Code of Practice: Hardware for Fire and Escape Doors Page 50 Section 4: Electrically Powered Hold Open Devices
4.3.4 Devices Incorporated into an Overhead Closing Mechanism
with Integral Smoke Detector
Where devices incorporate their own smoke detection elements, it is
particularly important to follow the installation instructions to ensure
the operation of the detector is not impaired by incorrect mounting.
Conductor hinges
4.3.5
For further information see also the Best Practice Guides:
www.dhfonline.org.uk www.gai.org.uk
Section 5: Door Co-ordinator Devices Page 53
• close the door leaf reliably from any angle to which it has been opened
• overcome the resistance of a latch or any seals when fitted.
For the purpose of this Code of Practice door co-ordinator devices are
divided into the following categories:
Note: This list does not imply suitability of any particular device for
fire door use - see 5.2 and 5.3 for further information.
5.2.1
The door co-ordinator device and its accessories should be:
5.2.3
The strength and features of the co-ordinator must be correct for the
size of door to which it is to be fitted, bearing in mind:
• the application to the door,
• whether subject to other factors such as air pressure, draughts,
heavy traffic use,
• abusive treatment, use by elderly, infirm or disabled,
• whether smoke or other seals are fitted to the doors.
5.2.4
Concealed overhead co-ordinators should NOT be used on timber
doors unless they are provided with specially designed and proven
intumescent protection (see 5.3.1).
5.2.5
Door or frame preparation in timber doorsets for mortised components
must be protected to maintain the fire integrity of the doorset.
This might require specially designed and proven intumescent
protection. (see 5.3.5).
5.2.6
Co-ordinators incorporated with electrical hold-open devices should
comply additionally with the recommendations of 4.2 of this Code of
Practice.
5.2.7
A regular programme of maintenance must be undertaken to ensure
that correct operational performance is maintained for the life of the
building. (See Section 13).
Section 5: Door Co-ordinator Devices Page 55
5.3.1 General
The Building Regulations 2010 Approved Document B 2006 Edition
require that all fire doors (with the exception of locked
cupboard/duct doors and internal domestic doors) be fitted with an
appropriate self-closing device. This applies equally to pairs of doors
(double doors) with rebated meeting edges and therefore requires the
use of a door co-ordinating device for these doors.
Table 1 BS EN 1158
From the above table it can be seen that co-ordinator sizes are related
to the door leaf width and the mass of the door to be controlled, in
exactly the same manner as door closing devices (see Section 3.3.1,
Table from BS EN 1154). This is important not only to ensure that the
co-ordinator size is matched with the power size of the door closers
that are to be fitted, but also to make sure that the co-ordinator is
able to withstand the normal forces and mechanical stresses
experienced in daily use.
Code of Practice: Hardware for Fire and Escape Doors Page 56 Section 5: Door Co-ordinator Devices
Smoke seals can sometimes prevent the door closer from fully closing
the door, considerable force being required to deflect or compress the
seal, particularly if they are not correctly installed and maintained.
Very careful consideration should be given to these issues when
specifying door co-ordinators that incorporate closing controls to
ensure that extra spring strength is not applied just to overcome poor
seal installation or performance.
They consist of two door closing devices (one for each door leaf) and
a common track assembly or concealed cable which connects the two
closers and provides the co-ordinating action.
Code of Practice: Hardware for Fire and Escape Doors Page 58 Section 5: Door Co-ordinator Devices
For overhead, surface fixed co-ordinators, the track assembly is
usually fixed to the underside of the transom, so the mass of metal
could be a source of integrity failure in timber doors under fire
conditions and it will almost certainly require the use of intumescent
material to protect the transom and adjacent door leaves in this area.
Some versions also provide smoke detectors built into the co-ordinator
assembly and with these devices it is essential to have a regular
maintenance programme to ensure that the detectors are kept clean
and all parts remain in good operational order.
Other versions use closers concealed in the door leaves, with the track
assembly concealed in the transom. As so much timber is removed when
installing these devices, it is absolutely imperative to ensure that all
intumescent protection recommended or supplied by the manufacturer is
fitted during installation. The fire test report should be examined closely
to ensure that it covers the particular application envisaged.
With all of these devices it is most important to check that the fire
test evidence is appropriate to the particular application for which it
is intended to be used, and that any intumescent protection
recommended is actually fitted during installation. A thorough
inspection of the installation is also recommended.
www.dhfonline.org.uk www.gai.org.uk
Code of Practice: Hardware for Fire and Escape Doors Page 60 Section 6: Lock & Latches
6.1 Introduction
In order to provide an effective barrier to a fully developed fire, a door
has to remain closed within the frame.
For the purpose of this Code of Practice locks and latches are divided
into the following categories:
• Roller catches
• Rim latches
• Mortice latches
• Mortice locks, rim locks and deadlocks
• Bored-in knobsets
Section 6: Lock & Latches Page 61
6.2.1
If placed on the market after 1 July 2013, the lock or latch:
• must be CE marked to BS EN 12209,
• and preferably, should be provided with additional product
certification by an approved third party certification body.
6.2.2
The lock or latch must have demonstrated its suitability for the
intended purpose by inclusion in satisfactory fire tests to
BS EN 1634-1 or BS EN 1634-2, on a type of door and configuration
in which it is proposed to be used. This evidence should be provided
by an approved third party certification or testing body
(see 1.5 Documentation).
6.2.3
Locks and latches with low melting point (less than 800°C, or 900ºC
for steel doors over 90 minutes resistance) components, which are
critical to the retention of the door in the closed position, should NOT
be used unless proven by specific tests.
6.2.4
According to Approved Document B Vol.2 2006, locked doors on
escape routes should be openable by one hand operation.
(See Section 12 for further information.)
6.2.5
A regular programme of maintenance must be undertaken to ensure
that the correct operational performance is maintained for the life of
the building (see Section 13).
6.2.6
To reduce the removal of timber from doors, the locks and latches
should be as small as is practicable.
Code of Practice: Hardware for Fire and Escape Doors Page 62 Section 6: Lock & Latches
6.3 Commentary
6.3.1 General
The addition of a lock or latch to a fire-resisting door might reduce
the fire performance of the door.
6.3.1.1
Removal of significant sections of the door. The fitting of a lock or a
latch (particularly a mortice device) entails removing wood from the
fire-resisting timber door so reducing the material which provides fire
protection and insulation.
The reduction in the amount of wood in the stile or rail can also
impair the stability of the door, leaving it less able to resist distortion
caused by the heat of a fully developed fire.
Steel doors are normally of hollow construction and voids for mortice
locks do not generally create a risk of integrity failure. However hollow
steel doors should be constructed with a lock reinforcing support to
ensure that the lock case:
Section 6: Lock & Latches Page 63
Where high melting point metals are used, and where these remain in
position for the duration of the fire exposure, it is particularly
important to keep through fixings as small as possible. By the use of
clearance holes, items such as spindles and cylinders should not
come directly into contact with the door's combustible facings. As
stated earlier, these clearances must not be so large as to become an
integrity risk in themselves.
Code of Practice: Hardware for Fire and Escape Doors Page 64 Section 6: Lock & Latches
Fixings and clearance holes must be as per the manufacturer’s fitting
instructions, to ensure that the fire resistance of the door is no less
than when tested.
Where the latch case and keeps are fixed to the protected side of a
timber door, zinc cases and keeps fitted with brass or steel bolts have
been shown to perform satisfactorily. Cast iron lock cases and keeps
fitted with a steel bolt have also been shown to maintain their
retaining action when fitted on either side of a fire-resisting door.
Section 6: Lock & Latches Page 65
Mortise latch
All of these factors could affect the fire integrity of the door and in
some cases might require the use of intumescent protection supplied
by the lock manufacturer.
Code of Practice: Hardware for Fire and Escape Doors Page 66 Section 6: Lock & Latches
To ensure the fire performance is maintained, it is recommended that
documentary evidence of satisfactory testing for the specific door
intended be checked before specifying the building hardware.
Doors with rebated meeting stiles and forend conversion units also
require the use of a door co-ordinator (if a door closer is fitted) so
that the leaves close in the correct order.
The door co-ordinator itself can affect the fire performance of the
doors (see Section 5).
As locks are generally larger than latches, the amount of wood removed
in fixing and the extra amount of metal introduced can make the
reduction in fire integrity that much greater. In all cases documentary
evidence of the suitability of the fittings for the specific door intended
should be checked to ensure that the fire integrity of the door
is maintained.
Section 6: Lock & Latches Page 67
Mortise deadlock
Cylinder knobset
Code of Practice: Hardware for Fire and Escape Doors Page 68 Section 6: Lock & Latches
6.3.7 Push button (digital) locks
Many push button (digital) locks require a large hole to be made in
the door in order to accommodate the mechanism and through
fixings. This is likely to reduce the fire resistance of the door,
especially if the lock incorporates electronic components and
batteries. Where test evidence supports the ability of a push button
lock to satisfy the integrity requirements of a fire door, they can be
used on fire doors of similar construction. Any intumescent
protection used during the test must be replicated on site.
6.3.8 Cylinders
In some of the devices referred to in 6.3.2 - 6.3.6, the locking mechanism
is operated by a cylinder which can be removed from the device.
www.dhfonline.org.uk www.gai.org.uk
Section 7: Door Furniture Page 69
7.2.1
Lever handles and knobs should comply fully with:
7.2.2
All door furniture should have demonstrated its suitability for the
intended purpose, by inclusion in satisfactory fire tests to BS 476:22,
BS EN 1634-1 or BS EN 1634-2, on a type of door and configuration
on which it is proposed to be used. This evidence should be provided
by an approved third party certification or testing body
(see 1.5 Documentation).
7.2.3
On timber doors the absolute minimum amount of wood should be
removed in order to reduce the risk of fire or smoke penetration
through the door.
Code of Practice: Hardware for Fire and Escape Doors Page 70 Section 7: Door Furniture
7.2.4
The use of intumescent sleeves around the fixing holes is always
recommended for timber doors and might be a requirement of the
applicable fire performance assessment schedule in some cases.
7.3 Commentary
7.3.1
The material used in the construction of lever handles, knobs and pull
handles/protection plates has not been found to greatly affect the fire
performance of the timber doors to which they are fitted. Therefore it
is not possible to state that any material is better than another in this
regard. For metal doors, steel-cored plastic handles should not be
fitted to the unexposed face without supporting test evidence.
Experience has shown that such fittings are susceptible to melting
and ignition of the plastic on the unexposed face of the door.
7.3.2
The durability of the fixings for lever handles will have a considerable
bearing on the effective life of the products and the eventual safety of
the occupants. Therefore when considering the selection of these
items, preference should be given to those that can demonstrate
compliance with the higher durability levels contained in
BS EN 1906. Where lever handles and knobs are used on self-closing
doors, a minimum category of use classification (first digit) of Grade
3 is recommended, as this will better withstand the opposing forces
exerted by the closing device. Such products are likely to have:
Pull handles
7.3.4
Pull handles should use bolt-through fixings, rather than face-fixed
screws, as these will prove more durable. The heads of the fixing
bolts should be protected by a push plate or rose.
7.3.5
Door protection (kick) plates fitted at the bottom of the door have
not been shown to have any effect on the fire performance of
timber doors.
7.3.6
Push plates of conventional sizes, which can be screwed or
adhesive-fixed, can also be specified without problems.
7.3.7
Where entrance doors also fulfill fire and smoke protection functions,
they should use items of building hardware which follow the guidance
given above.
7.3.8
For ease of use it is preferable that lever handles are fitted rather
than knobs. (See BS 8300).
Code of Practice: Hardware for Fire and Escape Doors Page 72 Section 7: Door Furniture
7.3.9
Wherever possible the fixing of a letter plate to a fire-resisting door
should be avoided. Prime consideration should be given to installing
the letter plate elsewhere. Both free standing and wall mounted
postal boxes are available as an alternative.
7.3.10
The materials from which door viewers are made will affect the
performance of the door. Plastic lenses might melt very quickly
leaving a hole large enough to cause early integrity failure. The same
situation might arise with plastic or low melting point alloy casings.
On the other hand, substantial steel or brass casings might also
increase the risk of early integrity failure by rapid heat transfer
through the thickness of the leaf of a timber door. As with all items of
fire-resisting door hardware, on timber doors it is essential that the
hole cut in the door to fit the device should be as small as is
practically possible. It follows that door viewers should not be fitted
to timber or steel fire doors unless the door viewer model is supported
by evidence of fire performance in a door of the relevant material.
www.dhfonline.org.uk www.gai.org.uk
Section 8: Door Bolts Page 73
For the purpose of this Code of Practice door bolts are divided into
two categories:
Note: This does not imply suitability of any device for fire door use.
8.2.1
The door bolt, keep and fixings should comply fully with:
8.2.2
The door bolt, keep and fixings should have demonstrated their
suitability for the intended purpose, by inclusion in satisfactory fire
tests to BS 476:22, BS EN 1634-1 or BS EN 1634-2, on a type of
door and configuration in which it is proposed to use them. This
evidence should be provided by an approved third party certification
or testing body. (See 1.5 Documentation).
8.2.3
Bolts should NOT be fitted to single leaf door assemblies on escape
routes without prior consultation with appropriate fire authorities, and
a full risk assessment by the Responsible Person under the RRO.
Code of Practice: Hardware for Fire and Escape Doors Page 74 Section 8: Door Bolts
8.2.4
The size, strength and type of door bolt must be correct for the door
to which it is fitted, bearing in mind:
Where pairs of timber or steel doors are limited to latched and bolted
test evidence, the engagement of the bolt in the frame and at the
floor should not be less than that supported by the evidence.
8.2.5
A regular programme of maintenance must be undertaken, to ensure
that the correct function is maintained for the life of the building.
(See Section 13)
8.3 Commentary
8.3.1 General
Door bolts are available in a range of sizes and types, all of which
are potentially suitable for use on fire-resisting doors. In addition to
fire-resisting requirements, BS EN 12051 also details graded
requirements and tests for:
• durability,
• safety in use,
• corrosion resistance,
• security,
• ability to resist abuse forces
Any deviation from the above in a timber door will require test
evidence or assessment to validate the application.
www.dhfonline.org.uk www.gai.org.uk
Section 9: Fire & Smoke Seals Page 77
9.2.4
Because intumescent materials vary in their characteristics, it is
recommended that manufacturers or specialist intumescent
distributors are consulted before final specification. Door leaves are
manufactured from a variety of core materials which affects the
choice of intumescents likely to be suitable. Specifiers should
consult the details offered by the door core manufacturer and stay
within that guidance.
9.3 Commentary
9.3.1
Intumescent materials other than edge strips are used on fire-
resisting doors. For example, thin sheet material can provide
insulation and protection:
9.3.2
Intumescent pads can protect hinge positions. Various thicknesses
are available e.g. 0.5 mm, 1 mm and 2 mm, all of which will offer
protection to a greater or lesser degree. Check that practical
requirements fall in line with test evidence.
Section 9: Fire & Smoke Seals Page 79
10 mm x 4 mm 15 mm x 4 mm
20 mm x 4 mm 25 mm x 4 mm
10 mm x 2 mm 10 mm x 3 mm 12 mm x 4 mm
30 mm x 4 mm 35 mm x 4 mm 38 mm x 4 mm
Code of Practice: Hardware for Fire and Escape Doors Page 80 Section 9: Fire & Smoke Seals
These latter sizes have their place in the industry, but they are less
widely used. Trade literature and websites relating to intumescent
material have a wealth of information for those wishing to increase
their knowledge of the wide range of variants.
9.5.1
There are three recognised types of intumescent material used for
door seals:
• Exfoliating Graphite
• Mono-ammonium Phosphate
• Hydrated Sodium Silicate
Fire safety signs are divided into five categories but within the scope
of this Code of Practice only two designations of sign are required
according to the location of the sign and the purpose of the door.
The need for any sign within the building environment will be
determined by the enforcing authority and/or the process of a formal
risk assessment.
The use, application and correct position of the fire safety signs can
make a major contribution to the effectiveness of good Fire Safety
Management.
These are not attached to the door but fixed above the door aperture
as part of Escape Route Signing. BS 5499:4: 2000 Safety signs,
including fire safety signs - Code of Practice for Escape Route Signing
provides guidance on the correct provision of signage for such routes.
The fixing height for FIRE EXIT signs is also given in
BS 5499:4.
10.2.1
All signs, whether ESCAPE ROUTE SIGNS or MANDATORY FIRE
SAFETY NOTICES are required to comply with SI 341 The Health
& Safety (Safety Signs and Signals) Regulations 1996.
10.2.2
BS 5499:4: 2000 Safety signs, including fire safety signs – Code of
Practice for escape route signing and 5499:5: 2002 Signs with specific
safety meanings or BS ISO 7010 Registered safety signs satisfy these
requirements. Used in conjunction with a formal risk assessment,
these signs will satisfy all requirements under Building, and Health
and Safety Regulations and Legislation.
10.2.3
Signs with specific safety meanings in the form of three dimensional
arrows or appropriate designated signs with supplementary text e.g.
"Push bar to open", "Push pad to open", are required to be displayed
where panic or emergency exit devices claim compliance with
BS EN 1125: 1998 Building hardware - Panic exit devices operated by
a horizontal bar - Requirements and test methods or
BS EN 179: 1998 Building hardware -Emergency exit devices operated
by a lever handle or push pad - Requirements and test methods.
10.2.4
It is recommended that signs for all equipment, including fire
equipment signs, required to ensure safe, efficient and effective
egress, are adequately conspicuous and readily visible.
Code of Practice: Hardware for Fire and Escape Doors Page 86 Section 10: Fire Safety Signs
10.3 Commentary
10.3.1
Exit signs above doors or indicating exit routes should be provided
where they will help people to find a safe escape route. Signs on exit
routes should have directional arrows according to the route to be
taken. These signs are square or oblong, green background with white
lettering. Signs should not be fixed to doors or positioned where they
might be obscured by opened doors. Signs above doors or open
spaces should be mounted between 2000 mm and 2500 mm from
floor level. When positioned on walls they should be mounted
between 1700 mm and 2000 mm from floor level. The use of arrows
should correctly indicate the direction of travel leading to a place of
safety. (See BS 5499:4: 2000 Code of Practice for escape route
signing for further guidance).
10.3.2
The Building Regulations 2010 Approved Document B 2006 Edition
(5.37) recommends that every escape route (other than those in
ordinary use) should be distinctively and conspicuously marked by
emergency exit sign(s) of adequate size complying with the Health
and Safety (Safety Signs and Signals) Regulations 1996. In general,
signs containing symbols or pictograms which conform to
BS 5499:4: 2000 and BS 5499:5: 2002 or BS ISO 7010 satisfy
these requirements. In some buildings, additional signs might be
needed to meet requirements under other legislation.
10.3.3
Although Approved Document B 2006 edition states a requirement
for marking it does not set out any specific guidance as to the
frequency or definitive location of the safe condition signs. This is left
to the discretion and interpretation of persons responsible for the
safety of the building through Risk Assessment. Advice on fire safety
signs, including emergency escape signs, is given in an HSE
publication: Safety Signs and Signals; Guidance on Regulations, and
BS 5499:4: 2000.
Section 10: Fire Safety Signs Page 87
EEC Directive
(to be withdrawn in 2013) BS ISO 7010
10.3.5
Mandatory notices to BS 5499:5: 2002 are required on all doors
which are designated as fire-resisting. These signs are circular in
shape, have a blue background with white lettering. Self-colour
aluminium or satin stainless steel might be used as the lettering
within the blue background but no other combinations are permitted.
No supplementary signs are normally required.
10.3.6
Approved Document B 2006 edition (Appendix B.8) of the Building
Regulations 2010 for England and Wales recommends that all fire-
resisting doors should be marked with the appropriate fire safety
(mandatory) notice complying with BS 5499:5: 2002 according to
whether the door is to be:
10.3.7
For Scotland the requirements are stated in the Technical Handbooks
for compliance with the Building Standards (Scotland) Regulations
2009:Section 2.
10.3.8
BS 9999:2008 (10.4.4) recommends that where the risk
assessment identifies a need for a fire sign, such signs should be
displayed prominently, conspicuously and appropriately. It further
recommends that the location of all fire safety signs be recorded in
the fire safety manual.
10.3.9
Guidance is given in BS 5499:4 stating that:
"In order to ensure that occupants within a building are aware of their
immediate escape route it is advised that the Exit or Fire Exit can be
seen. If this is not possible then a sign or series of signs with a
directional arrow will provide guidance to the final Exit or Fire Exit."
Acceptable signs
Section 10: Fire Safety Signs Page 89
10.3.11
For sliding doors the appropriate sign with text "Slide door to open" should
be displayed. The arrow should show the direction of "Slide to open".
10.3.12
Where there is a danger that a door designated as a fire exit might
become obstructed because its importance as a fire safety measure is
not appreciated, e.g. a final exit door opening out from the face of the
building in a secluded area, or a seldom used intercommunicating
door between rooms or occupancies, a conspicuous "FIRE ESCAPE -
KEEP CLEAR" notice should be displayed on the appropriate face of
the door. This is a mandatory sign and requires white lettering on a
blue background.
Code of Practice: Hardware for Fire and Escape Doors Page 90 Section 10: Fire Safety Signs
10.3.13
Fire fighting equipment location signs, and prohibition signs should
be considered at the same time as escape route and mandatory signs.
Hazard signs might require consideration after occupation of the
building.
10.5 Maintenance
Any damaged, worn or missing signs should be replaced immediately.
• prevention of fire,
• escape from fire,
• suppression of fire,
• confinement of fire,
• communication of fire safety management,
• communication of the emergency plan,
• education and training of building occupants.
• Prohibition sign
Safety sign that indicates that a specific behaviour is forbidden.
Comprising a red circular band with diagonal cross bar on a white
background, the symbol within the circle to be black denoting the
forbidden activity.
• Hazard sign
Safety sign that gives warning of a hazard. Comprising a yellow
triangle with black border and symbol within the yellow area
denoting the designated hazard.
• Mandatory sign/notice
Safety sign or notice that indicates that a specific course of action
is to be taken. Comprising a blue circle with white symbol or
lettering denoting the safety requirement.
Section 10: Fire Safety Signs Page 91
• Supplementary sign
Sign that is supportive of a safety sign by providing additional
clarification. This sign may comprise text or an arrow. When used
with a safety sign it becomes part of the safety sign
For details of safety colours and contrast colours for safety signs,
geometric shapes and graphical symbols refer to BS ISO 3864-1: 2011.
Code of Practice: Hardware for Fire and Escape Doors Page 92 Section 11: Fire-resisting Doors on Accessible Routes
The publication of Approved Document M: 2004 (ADM) in support of
the Building Regulations (England and Wales): 2000, recommends
specific performance levels for all doors on accessible routes in all
non-domestic buildings.
Note: the opening force stated in ADM 3.10.a relates to the force
required at the opening position between 30° and 60°.
Low opening forces help many in the community to have easy access
through fire doors
Code of Practice: Hardware for Fire and Escape Doors Page 96 Section 12: Panic & Emergency Exit Devices
12.1 Introduction
Experience relating to escape from buildings and general safety has
shown the importance of fitting doors on escape routes with suitable
exit devices to enable the occupants of the building to escape quickly
and easily in the case of fire or some other emergency. Factors to
consider include:
For the purpose of this Code of Practice therefore, exit door hardware
is divided into the following categories:
• Panic exit devices (for use where panic situations may be envisaged),
• Emergency exit devices (for use by trained personnel where panic
situations are not envisaged),
• Exit devices for use on fire-resisting doors,
• Accessories for exit devices.
Note: This list does not imply suitability of any device for fire or
escape door use - see Section 12.3 for further information.
Section 12: Panic & Emergency Exit Devices Page 97
12.2.1.1
The device and its accessories must be chosen taking account of the
type of user:
• devices placed on the market after 1 July 2013 and intended for use
by the general public must be CE Marked to BS EN 1125 - Panic
exit devices operated by a horizontal bar, and preferably provided
with additional product certification by an approved third party
certification body. (See 1.5 Documentation).
• devices placed on the market after 1 July 2013 for use by trained
personnel must be CE Marked to BS EN 179 - Emergency exit devices
operated by a lever handle or push-pad, and preferably provided with
additional product certification by an approved third party certification
body. (See 1.5 Documentation).
12.2.1.2
Devices for use on pairs of doors should have been specifically tested
and approved for that purpose. (See 12.3.3.2).
12.2.1.3
Standard projection exit devices should be used where there is
restricted width for escape, or where the exit doors cannot open
beyond 90°.
12.2.1.4
Care should be taken that hinges and any seals are correctly fitted
so that the escape doors are able to open freely once the exit device
is operated.
12.2.1.5
A regular programme of maintenance must be undertaken to ensure
that the correct operational performance is maintained for the life
of the building. (See Section 13).
12.2.1.6
No additional security devices should ever be fitted to escape route
doors unless specifically included in the Fire Risk Assessment.
(See 12.3.4).
Code of Practice: Hardware for Fire and Escape Doors Page 98 Section 12: Panic & Emergency Exit Devices
12.2.2
Additional recommendations for devices for fire door use
12.2.2.1
The exit device and any accessories should have demonstrated their
ability to be suitable for the intended purpose, by inclusion in
satisfactory fire tests to BS EN 1634-1 or BS EN 1634-2, on the type
of timber or steel doorset and configuration in which it is proposed to
be used. This evidence should be provided by an approved third party
certification or testing body. (See 1.5 Documentation).
12.2.2.2
Devices for use on pairs of doors should have been specifically
fire tested on an appropriate set of double doors and approved for
that purpose. (See 12.3.3.2).
12.2.2.3
The exit device should not include any dogging mechanism unless its
use is proven by fire test evidence on self-closing unlatched fire
doors. (See 12.3.3.1).
12.3 Commentary
12.3.1 General
The Building Regulations (England & Wales) 2010 Approved Document B
2006 Edition requires that all doors on escape routes be fitted with
escape hardware that is simple to operate and does not require
specialist knowledge or tools for its operation (e.g. panic bars).
It is important that any panic exit device is able to operate safely for
a realistic lifetime, and tests are included in BS EN 1125 to verify
the durability of the product. Two categories of durability are
recognised:
If the escape door to which the panic device is fitted is also used
during the day as a normal access door, it is important to ensure that
the panic device is proven for at least 200 000 cycles (Grade 7).
Panic devices are classified according to the amount that they project
from the door face. When the door is in the open position at around 90°,
any projection of the panic device effectively reduces the clear escape
width of the opening. It is therefore important that a standard projection
device (100 mm or less) is chosen where the door might only be able to
open to around 90°, in order to maintain a clear opening width. "Large
projection" describes devices up to 150 mm projection.
If the escape door to which the exit device is fitted is also used
during the day as a normal access door, it is important to ensure that
the exit device is proven for at least 200 000 cycles (Grade 7).
12.3.3.1 Dogging
Dogging is a method of holding the bolt(s) of the exit device in a
withdrawn state, for easy passage through the door. Where the door
relies on the provision of a bolt for its fire resistance rating, then
devices with a dogging feature should never be used. However,
dogging may be permitted where the fire test evidence has been
obtained from unlatched fire doors, as these tests will have proved
that the self-closing device fitted to that particular door is capable of
maintaining the closed position without any help from a bolt.
For safety and reliability reasons, the traditional UK double panic bolt
consisting of a single bolt and slave arm connected by bevelled plugs,
is not permitted by BS EN 1125. For rebated pairs of doors, this
product is now usually replaced by a panic latch on the first opening
leaf and a panic bolt on the second opening leaf. More sophisticated
multiple locking devices are also available. In all cases the
manufacturer’s installation instructions should be followed closely,
particularly where supplementary intumescent protection is required
to achieve the correct fire rating.
Section 12: Panic & Emergency Exit Devices Page 103
For these cases there are additional security measures that can be
taken to enhance the physical security of the building, without
compromising the ability of people to escape during an emergency.
Where necessary, such measures should always be discussed with
local building and fire authorities and will generally be determined
on a building occupancy and risk assessment basis.
In all cases it is essential that the escape function of the door be not
compromised at any time while the building is occupied.
In particular, any additional dead bolt locking used must still enable
the exit device to comply with the release requirements of
BS EN 1125 or BS EN 179. If delayed egress devices are to be used,
they must be designed such that after the delay period approved by
the building authority, the door will automatically be released. In the
case of genuine emergency, such as a fire alarm or power failure, the
door must be released immediately.
12.3.5.1
Outside access devices (OADs): These devices are used to enable
authorised access from the opposite side to the escape direction, and
can consist of a cylinder, lever/knob or keypad assembly. All are
connected to the operating mechanism or bolt(s) of the exit device in
some way, either through a mechanical link or an electrical connection.
www.dhfonline.org.uk www.gai.org.uk
Code of Practice: Hardware for Fire and Escape Doors Page 106 Section 13: Maintenance of Building Hardware
13.1 Introduction
Building Regulation 39 (previously Regulation 16), Building Regulations
2010, England and Wales, requires information on the fire safety
measures in a building to be passed to the Responsible Person on
completion or occupation of the building, so that these measures
might be operated and maintained in a satisfactory way. This should
include information on the installation, adjustment (where
appropriate), operation and maintenance of essential hardware on fire
and escape doors. These documents should be consulted and their
recommendations followed. Older buildings might not have such a file
of information available. In such cases, the following details may
assist the Responsible Person in fulfilling their duties with regard to
the functioning of their fire and escape route doors.
13.1.1
Doors designated as:
must be periodically inspected to make sure that they meet the same
standards as when they were originally installed and commissioned.
13.1.2
Much will depend on the general use to which the door is normally
put. A door that is only used as an emergency exit might never be
opened and will need periodic inspection and minor adjustment,
whilst a door that is used as a staff entrance or "smoke-break" exit
door will need more frequent inspections and maintenance.
13.1.3
The Regulatory Reform (Fire Safety) Order (RRO) for England and Wales
and a similar Order for Scotland place the responsibility for Fire Safety
Duties and general fire precautions on the building owner or his
representative and the appointed "responsible person" nominated as
being the person ultimately responsible as defined in the RRO.
Recommendations on the frequency of inspections are included in the
Guides prepared for the “Responsible Person” in respect of the RRO for
England and Wales. These are available on the CLG website. All
premises are subject to a suitable system of maintenance. "Suitable"
means, among other things:
13.1.5
Building controllers may thus include such inspections in their
regular fire drills and routine fire precaution inspections.
13.2.1
The Management should include requirements on the competence of
people employed to assist in health and safety matters, including
maintenance. It is important to employ properly trained personnel.
(See 13.1.4 above.)
13.2.2
For the doors to work efficiently, regular and programmed
maintenance must be carried out to all parts of the door. Work should
be undertaken only by persons experienced in this type of work.
If outside contractors are used, they should sign the maintenance log
maintained by the company.
13.2.3
A maintenance log should be kept and all doors given a unique number.
13.2.4
The maintenance period should be appropriate for the building; for high
life risk, such as hospitals, schools, retired persons' accommodation,
this may be monthly. Other buildings with low life risk may be annually.
Refer to the RRO Guide appropriate to the type of building.
13.2.5
The maintenance and replacement of components to maintain the
correct performance of the door for the full life of the building is
thus essential.
Code of Practice: Hardware for Fire and Escape Doors Page 108 Section 13: Maintenance of Building Hardware
13.3 Commentary
13.3.1 General
The most important factor is that these devices are designed to protect
human life against fire and to ensure people can safely exit a building.
Nothing must be done or neglected that could compromise this.
Building Regulations, and to some degree fire regulations, provide
general guidance on the type of products to be used. If not already
included in the building's "Regulation 38" file (England & Wales),
recommendations on the inspection and maintenance for each specific
device and each part should be obtained from manufacturers and used
against all such parts fitted to each door.
The types and uses of doors are many and each door will need to be
treated as the situation dictates. The geographical location will also
dictate the frequency and type of maintenance; wet salty areas will
need special consideration. Wind-blown debris and illicit dumping of
rubbish could render an emergency exit sealed. Doors used as staff
"smoke break" exits will be subject to higher wear factors than those
limited to occasional use.
Internal fire and smoke-resisting doors are at least as important as the
final exit door, although it is unlikely they will have the same hardware
as the final exit. However, hinges, closers, co-ordinators and seals all
have as much importance. The incorrect closing action of such doors
might cause serious injury to the building occupants who are more
likely to use these doors in the course of the normal day. They are
often subject to a higher degree of wear than final exit doors.
Vandalism and attempted forced entry will cause damage to external
doors, as well as misuse by building occupants. Only regular periodic
inspection will pick up these faults.
External doors will also need inspecting during seasonal changes to
ensure continuing functionality.
Only parts of equal or a better standard should be fitted as running
replacements or additions to fire/smoke and final exit doors; anything
less could invalidate fire certificates and breach the building owner’s
responsibility to keep the doors in safe working order. If there
is concern about suitability of replacements, test evidence from
a competent authority should be obtained.
13.3.2 Hinges
Bear the mass of the door, the whole load being applied to just two
or more metal pivot devices. They should be checked for wear in the
pivot pin. Also ensure that the fixing screws are tight and all are
effectively holding. Light lubrication might be required by local
conditions. Hinges on doors in frequent use will wear quicker than
those only opened for inspection or access to service ducts etc.
Section 13: Maintenance of Building Hardware Page 109
Each type and make of closer will need servicing in differing ways but
pivoting arms and terminal fixings should be checked for tightness
and lubrication added as appropriate. Terminal fixings into the door
and frame are subject to stress and should be carefully checked.
13.3.6 Co-ordinators
These devices are used to close rebated sets of doors in the correct
order to provide an effective seal. The maintenance schedule should
include a check to ensure that each part is securely located and the
screw fixings are tight. Any pivoting parts should be checked for wear
and any protruding arms checked for straightness. The function
should be checked over the full range of door openings and all parts
lubricated as required.
13.3.8 Seals
Smoke and fire seals should be examined to ensure they are
unbroken and secure in the door; that the gap in the door has not
moved out of tolerance or the door moved out of square so as to
prevent an effective seal. Worn or damaged seals must be replaced
with the appropriate product.
13.3.10
In almost all cases, the installed products will have been
supplied complete with fixing instructions and the correct
maintenance data sheets. It is important that these documents
are retained by the Building Manager and used as the basis
of the maintenance schedule.
Code of Practice: Hardware for Fire and Escape Doors Page 112 Section 14: Product Standards and Definitions
14.1 Standards
In order to help users, almost all of these standards use the same
simple categorisation system. Although some products have extra
categories, the first seven digits generally (but not always) relate to the
same performances. These are fully described in Section 1, Page 15.
14.1.2
From 1 July 2013, any product which can be CE marked against a BS EN
(European standard published as a BS) must be so CE marked, in order to
comply with the Construction Products Regulation. The following European
product Standards have been published as British Standards:
BS 476:22: 1987
Fire tests on building materials and structures -
Methods for determination of the fire resistance of non-Ioadbearing
elements of construction.
BS 476:31.1: 1983
Fire tests on building materials and structures -
Methods of measuring smoke penetration through doorsets and shutter
assemblies: measurement under ambient temperature conditions.
BS 7273-4: 2007
Code of Practice for the operation of fire protection measures -
Activition of release mechanisms of doors.
BS 8214: 2008
Code of Practice for Fire door assemblies with non-metallic leaves.
BS 5499:4: 2000
Safety signs, including fire safety signs
Code of Practice for Escape Route Signing.
BS 7036: 1996
Parts 1 - 5
Code of Practice for safety at powered doors for pedestrian use.
Code of Practice: Hardware for Fire and Escape Doors Page 114 Section 14: Product Standards and Definitions
BS 8424: 2004
Building hardware. Pull handles. Requirements and test methods.
BS 9999: 2008
Code of Practice for fire safety in the design, management and use
of buildings.
BS EN 1634-1:2008
Fire resistance tests for door and shutter assemblies.
BS EN 1634-2:2008
Fire resistance and smoke control tests for door, shutter and open-
able window assemblies and elements of building hardware. Fire
resistance characterisation test for elements of building hardware.
BS EN 1634-3:2004
Fire resistance tests for door and shutter assemblies. Smoke control
doors and shutters.
14.2 Definitions
Accessible route
Any route that is used to approach, or move around or within
a building, and is accessible to disabled people.
Closing moment
Torque (Nm) generated by a door closing device which acts upon the
door leaf during the closing operation.
Cylinder
Key operated device containing differs, usually separate from, but
engaging with, its associated lock or latch.
Deadbolt
Bolt that is operated in both directions by a key, handle and/or
thumb turn.
Deadlock
Lock that contains only a deadbolt.
Dogging mechanism
Mechanism fitted to an emergency/panic device for holding the bolt
head(s) in the withdrawn position until manually or electronically reset.
Final exit
An exit from a building where people can continue to disperse in
safety and where they are no longer in danger from fire and/or smoke.
Fire door
A door leaf, frame, all hardware and any fire/smoke seals, supplied
as a doorset by one legal entity, or supplied as components from
separate sources for assembly on site.
Fire integrity
Measure of the ability of a specified door to resist and thus contain
the effects of fire for a recognised period of time. (Usually expressed
in minutes - e.g. FD60 or E60 implies a doorset capable of
withstanding exposure to fire test for at least 60 minutes).
Latch bolt
Moving part of a latch that engages the locking plate.
Mortise latch
Latch for fixing in a mortise, usually in the closing edge of a door leaf
or window.
Mortise lock
Lock for fixing in a mortise, usually in the closing edge of a door leaf
or window.
Rim lock
Lock for fixing on the face of a door leaf.
Tubular latch
Mortise latch, which has a case shaped to fit into a cylindrical mortise.
Code of Practice: Hardware for Fire and Escape Doors Page 116 Section 14: Product Standards and Definitions
14.3 Abbreviations
CEN
European Committee for Standardization
EN
Euronorm (European standard)
FDIS
Fire Door Inspection Scheme
This page is intentionally left blank
DHF
42 Heath Street
Tamworth
Staffordshire
B79 7JH
Tel: 01827 52337
Fax: 01827 310827
E-mail: [email protected]
Website: www.dhfonline.org.uk
GAl
BPF House,
6 Bath Place,
Rivington Street,
London
EC2A 3JE
Tel: 020 7033 2480
Fax: 020 7033 2486
E-mail: [email protected]
Website: www.gai.org.uk