RS-485 2X22/7 AWG SF/UTP PVC Low Temperature
Part Number: 9FY9F1L101
Applications: RS-485, Fixed or portable installations, CAN Bus communication,
High Noise Environments, Outdoor, Harsh Environments
General Construction: The cable contains one twisted pair, cabled together with filler
elements, overall shielded with aluminum-foil and a TC braid.
Outer FR-PVC low temperature jacket make the cable suitable for
low temperature harsh environment installations.
Outer Jacket Material: UV resistant FR-PVC
Outer Diameter: 5.8 mm nom.
Weight: 39 kg/km
Design & Materials
Conductor Material: Annealed Tinned Copper
Conductor Size: 22 AWG
Conductor Construction: Stranded
Insulation Material: Cellular PO
Insulation O.D.: 1.62 mm nom.
Insulation O.D.: 0.064 in.
Conductor Color Code: Blue X White
Overall Shield Design: 100% Coverage
Overall Shield Material: Aluminum/Polyester Foil
Overall Foil Shield: Yes
Overall Braid Shield: Yes
Overall Braid Material: Annealed Tinned Copper
Braid Coverage: 80 % nom.
Overall Drain-wire Material: Annealed Tinned Copper
Overall Drain-wire size: 24 AWG
Overall Drain-wire Construction: Stranded
Total number of conductors: 2
Outer Diameter: 0.228 in.
Outer Jacket Color: Black
Weight: 26 lb/1000'
Marking: Per request, Teldor Standard
Standards
Applicable Standards: RoHS 3 2015/863/EU
Flammability Rating: IEC 60332-1, IEC 60332-3 , UL 1581 VW-1
P/N: 9FY9F1L101 1/2
Performance
Frequency Range: 1 - 10 MHz
Impedance: 120 Ω
Attenuation: 1.8 dB/100m @1 MHz 3.3 dB/100m @ 4 MHz
Capacitance: 42 pF/m
Velocity of Propagation: 75 % nom.
Dielectric Strength: 1500 V/minute
Dielectric Strength to Shield: 1000 V/minute
Min. Bend Radius: 35 mm
Max. Operating Temperature: +85 °C
Min. Operating Temperature: -45 °C
UV Resistance: Yes
Prepared By Revised By Version Num Modified on
Jacob Ben Ary Ofer Solter 2.5 07-01-2016
Teldor Cables & Systems Ltd. ("Teldor") reserves the right to make changes to the products described in this catalog without prior
notice. Teldor does not assume any liability which may occur due to the use of the products described herein. Drawings may not be to
scale and are provided for general and informational purposes only. The information contained in this catalog is the proprietary property
of Teldor, and may not be used, reproduced or disclosed to others, in whole or in part, without the written authorization of Teldor.
Teldor Cables & Systems Ltd. - Ein-Dor, 1933500 ISRAEL Tel: +972 4 6770555 Fax: +972 4 6770650
P/N: 9FY9F1L101 2/2