0% found this document useful (0 votes)
432 views

PSV Report Blocked

This document provides a sizing report for pressure relief valves (PSVs) on inlet separators at an energy plant. It outlines the design basis, calculation method, and results. The key findings are: 1) PSV-10310 and PSV-10311, which protect an inlet separator, require 0.785 square inch orifices to safely relieve 64,123 pounds per hour under blocked discharge conditions. 2) PSV-1223, which protects another inlet separator, requires a 2.853 square inch orifice to relieve 140,471 pounds per hour during an instrument failure scenario. 3) Attachment sheets provide full calculation details for PSV sizing.

Uploaded by

Elias Elias
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
432 views

PSV Report Blocked

This document provides a sizing report for pressure relief valves (PSVs) on inlet separators at an energy plant. It outlines the design basis, calculation method, and results. The key findings are: 1) PSV-10310 and PSV-10311, which protect an inlet separator, require 0.785 square inch orifices to safely relieve 64,123 pounds per hour under blocked discharge conditions. 2) PSV-1223, which protects another inlet separator, requires a 2.853 square inch orifice to relieve 140,471 pounds per hour during an instrument failure scenario. 3) Attachment sheets provide full calculation details for PSV sizing.

Uploaded by

Elias Elias
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 5

ENERGY EQUITY EPIC

DOC. NO. REV.


EE-PR-CAL-004 A
Calculation
DATE: August 31, 2021 SHEET: 1 OF 5

PSV SIZING
REPORT
(BLOCKED OUTLET CASE)

ENERGY EQUITY EPIC (SENGKANG) Pty. Ltd.

CPP & PMS PLANT MODIFICATION PROJECT

RE DATE PAGE DESCRIPTION PREP’ CHK’D APP’D COMP


A 31-Aug-21 5 ISSUED FOR REVIEW AHS DNS
ENERGY EQUITY EPIC CPP & PMS Plant Modification Project

TABLE OF CONTENT

Page

1. INTRODUCTION.......................................................................................................2

2. DESIGN BASIS......................................................................................................... 3

3. DESIGN METHOD.....................................................................................................3

4. SUMMARY OF RESULT...........................................................................................4

5. REFERENCE............................................................................................................. 4

ATTACHMENT:
A. PSV-10310 CALCULATION SHEET
B. PSV-10311 CALCULATION SHEET
C. PSV-1223 CALCULATION SHEET

PSV SIZING REPORT (Blocked Discharge) Page 2 of 5


ENERGY EQUITY EPIC CPP & PMS Plant Modification Project

1.0 INTRODUCTION

The aims of this calculation are determine the recommended Pressure Relief Valves
(PSV) size for inlet separator (V-103) at Central Processing Plant (CPP) and inlet
separator (V-122) Patila Metering System (PMS).

2.0 DESIGN BASIS

The following basis was applied:


1. PSV loads for blocked outlet case were based on rates as shown on Process Flow
Diagrams.
2. PSV-1223 load (instrument failure case) were based on restriction orifice calculation.
3. PSV load for PSV 10310 and PSV-10311 is 49505 lb/hr.
4. PSV load for PSV-1223 is 71 mmscfd or 132226 lb/hr

3.0 DESIGN METHOD

Orifice Size calculation

The following formula will be used for blocked outlet case.

W Z T
a 
C  P1  Kd  Kb M

Where:

W = Relief Load, Lb/hr


P1 = Relieving pressure, psia
C = Coefficient, Table. 9 API 520
Kd = constant, 0.975 per API 520
Kb = constant, 1 per API 520
Z = Compressibility factor
T = relieving temperature
M = molecular weight
a = orifice area, in2

4.0 SUMMARY OF THE CALCULATION RESULT

PSV SIZING REPORT (Blocked Discharge) Page 3 of 5


ENERGY EQUITY EPIC CPP & PMS Plant Modification Project

Refer to Attachment for Calculation of Design Result

Vessel “Full-open” PSV Orifice Orifice Lead and Tail


PSV No. Case
No. Relief Rate Area Designation Pipe Size
LB/HR IN2 IN
Blocked
V-103 PSV-10310 64123 0.785 H 2-600# X 3-150#
Discharge
Blocked
V-103 PSV-10311 64123 0.785 H 2-600# X 3-150#
Discharge
Instrument
V-122 PSV-1223 140471 2.853 L 4-300# X 6-150#
Failure

The Complete calculation result is provided in Attachment Calculation Sheet

5.0 REFERENCE

1. Perry, Robert. H, "Perry's Chemical Engineering Handbooks", 5 th edition.


2. Gas Processors Supplier Association “Engineering Data Book”, Vol. 1.
3. API Recommended Practice 520, 4th edition

PSV SIZING REPORT (Blocked Discharge) Page 4 of 5


ENERGY EQUITY EPIC CPP & PMS Plant Modification Project

Attachment Calculation Sheet


 PSV-10310 Calculation Sheet
 PSV-10311 Calculation Sheet
 PSV-1223 Calculation Sheet

PSV SIZING REPORT (Blocked Discharge) Page 5 of 5

You might also like