0% found this document useful (0 votes)
232 views3 pages

CXW02-80-298Y Compressor Specs

This document provides technical specifications for a CXW02-80-298Y compressor. It has 2 rotors, a nominal motor power of 80HP/60kW, and can operate between 30-70Hz. Additional details include compressor dimensions, sound levels, materials, and optional accessories like valves, filters, and dampers. Pressure and electrical ratings are listed, along with lubricant type and specifications. Dimensional drawings show the compressor connections and components.

Uploaded by

woalid hossen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
232 views3 pages

CXW02-80-298Y Compressor Specs

This document provides technical specifications for a CXW02-80-298Y compressor. It has 2 rotors, a nominal motor power of 80HP/60kW, and can operate between 30-70Hz. Additional details include compressor dimensions, sound levels, materials, and optional accessories like valves, filters, and dampers. Pressure and electrical ratings are listed, along with lubricant type and specifications. Dimensional drawings show the compressor connections and components.

Uploaded by

woalid hossen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

CXW02-80-298Y

Data sheets
For standard refrigerants > CXW series<br>

Technical data:
Rotors # 2
Displacement @ 50 Hz m3/h [50Hz] 298
Displacement @ 60 Hz m3/h [60Hz] 358
Compressor version[1] 2
Nominal Motor power HP 80
Nominal Motor power kW 60
400 (+/-10%) V/3/50Hz
Motor voltage at 50 Hz[2] V/ph/Hz
PWS
460 (+/-10%) V/3/60Hz
Motor voltage at 60 Hz[2] V/ph/Hz
PWS
PWS partition 50-50
Capacity control (CC) step % 100-75-50-25
Capacity control (CC) stepless % 100-50
MRA, max operating current at 400V/50Hz and 460V/60Hz A 145
LRA, max starting current at 400V/50Hz and 460V/60Hz, PWS motor A 373
LRA, max starting current at 400V/50Hz and 460V/60Hz, PWS motor-DOL connection A 600
Frequency min Hz 30
Frequency max[3] Hz 70
Control and protection device INT69 FRY
Electric terminal box class protection IP65
Maximum pressure HP bar 30
Maximum pressure LP bar 20.5
Oil type[4] POE 170 cSt
Oil charge l 11
Oil filter Standard; replaceable
Crankcase heater Standard; integrate
Oil level sight glass # 1
Discharge check valve Standard
Safety valve Standard
Maximum oil temperature sensor Standard
Suction bushing (SL) mm mm 80
Suction bushing (SL) inch inch 3" 1/8
Discharge valve (DV) mm mm 54
Discharge valve (DV) inch inch 2" 1/8
Net weight kg 550
Max Length mm 1393
Max Width mm 560
Max Height mm 624
Sound power level (5/50, R407A)[5] dB(A) 87.4
Sound pressure level @ 1m (5/50, R407A)[5] dB(A) 79.4
Compressor body material Cast Iron

[1] Motor version: 1 = high and mid temp. all refrigerants; 2 = low and mid temp. all refrigerants; 3 = mid temp. R134a only
[2] Other motor voltage available on request
[3] Maximum frequency depends on the working conditions: use the FSS.3 (Frascold selection software)
[4] For alternative lubricants refer to bulletin FTEC022
[5] Sound pressure in free field, hemispherical model at 1 meter distance, 50Hz; PWL and SPL in different conditions are available on

FRASCOLD SPA via Barbara Melzi 103/105, IT 20027 Rescaldina MI - +39-0331-742201 email [email protected] web www.frascold.it
CXW02-80-298Y
Data sheets
For standard refrigerants > CXW series<br>

Accessories:
Suction shut-off valve T00SK103900B
Electronic oil level switch (230V) T00WP253
Oil filter clogging differential pressure switch T00W3501122
Oil Flowswitch T00WK1400
Kit with Service valve & muffler for ECO / Liquid injection T00WK1500
Rubber dampers kit T00SK205200
Oil separator Select the model with selection software FSS3
Nipples for oil cooler connection T00WK1450
Bridges for DOL start T00WK1203

FRASCOLD SPA via Barbara Melzi 103/105, IT 20027 Rescaldina MI - +39-0331-742201 email [email protected] web www.frascold.it
CXW02-80-298Y
Data sheets
For standard refrigerants > CXW series<br>

Dimensional drawing: V1 Capacity control valve (Step 1) -


1 Low pressure connection (1) 1/8" NPT V2 Capacity control valve (Step 2) -
2 High pressure connection (2) 1/8" NPT V3 Capacity control valve (Step 3) -
1/4"SAE x 79.4mm -
3 Low pressure connection (3) SV Suction valve (SV)
1/4"SAE 3"1/8
1/4"SAE x SL Suction bushing (SL) -
4 High pressure connection (4)
1/4"SAE
DV Discharge valve (DV) 54mm - 2"1/8
5 Oil charge plug (5) 3/8"GAS
NP Name Plate (NP) -
6 Crankcase heater (6) -
7 Oil level switch connection (7) 3/4"NPT
8 Oil level sight glass (8) -
Connection for filter clogging sensor
9 1/2"GAS
(9)
10 Connection for oil cooler (10) 1/2"NPT
11 Connection for oil drain (11) 1/4"NPT
12 Oil drain valve (12) 1/8" NPT
13 Maximum oil temperature sensor -
Connection for ECO or Liquid
14 Ø1"1/8
injection (14)

FRASCOLD SPA via Barbara Melzi 103/105, IT 20027 Rescaldina MI - +39-0331-742201 email [email protected] web www.frascold.it