0% found this document useful (0 votes)
128 views2 pages

Marathon Gen-744RSL4058 480V 60hz

This document provides submittal data for a Marathon Electric generator model 744RSL4058, including: 1) Key specifications such as a rating of 2060 kW at 480 Volts, 60 Hz, and 0.8 power factor. 2) Test data and results meeting various Mil-Std standards for insulation resistance, voltage regulation, harmonics, and other parameters. 3) Performance characteristics including recovery times for load application and rejection, efficiency curve, and voltage dip with motor starting.

Uploaded by

jesus_rs01
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
128 views2 pages

Marathon Gen-744RSL4058 480V 60hz

This document provides submittal data for a Marathon Electric generator model 744RSL4058, including: 1) Key specifications such as a rating of 2060 kW at 480 Volts, 60 Hz, and 0.8 power factor. 2) Test data and results meeting various Mil-Std standards for insulation resistance, voltage regulation, harmonics, and other parameters. 3) Performance characteristics including recovery times for load application and rejection, efficiency curve, and voltage dip with motor starting.

Uploaded by

jesus_rs01
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

MARATHON ELECTRIC

GENERATORS
TYPICAL SUBMITTAL DATA
MODEL : 744RSL4058
BASE MODEL: 744RSL4058 Winding H-SG740066
Submittal Data: 480 Volts*, 2060 kW, 2575 kVA, 0.8 P.F., 1800 RPM, 60 Hz, 3 Phase 06/25/2008

Kilowatt ratings at 1800 RPM 60 Hertz 4 BARS Standard 3 phase

kW (kVA) 3 Phase 0.8 Power Factor Dripproof or Open Enclosure


Class B Class F Class H
105º C 125º C
80º C 90º C 95º C 105º C 130º C 125º C 150º C
British British
Continuous Lloyds ABS Continuous Standby Continuous Standby
Voltage* Standard Standard
480 1760 (2200) 1910 (2388) 1980 (2475) 2100 (2625) 2100 (2625) 2320 (2900) 2150 (2688) 2270 (2838) 2370 (2963)
460 1730 (2163) 1870 (2338) 1940 (2425) 2050 (2563) 2050 (2563) 2260 (2825) 2200 (2750) 2210 (2763) 2420 (3025)
440 1690 (2113) 1820 (2275) 1880 (2350) 1990 (2488) 1990 (2488) 2180 (2725) 2125 (2656) 2140 (2675) 2340 (2925)
416 1640 (2050) 1760 (2200) 1820 (2275) 1920 (2400) 1920 (2400) 2090 (2613) 2035 (2544) 2050 (2563) 2240 (2800)
380 1550 (1938) 1650 (2063) 1700 (2125) 1790 (2238) 1790 (2238) 1950 (2438) 1910 (2388) 1910 (2388) 2070 (2588)
Rise by resistance method, Mil-Std-705, Method 680.1b. British Standard Rating per BS 5000

Submittal Data: 480 Volts*, 2060 kW, 2575 kVA, 0.8 P.F., 1800 RPM, 60 Hz, 3 Phase STD. CONNECTION
Mil-Std-705B Mil-Std-705B
Method Description Value Method Description Value
301.1b Insulation Resistance >1.5 Meg 505.3b Overspeed 2250 RPM
302.1a High Potential Test 507.1c Phase Sequence CCW-ODE ABC
Main Stator 2000 Volts 508.1c Voltage Balance, L-L or L-N 0.20%
Main Rotor 1500 Volts 601.4a L-L Harmonic Maximum - Total 5.0%
Exciter Stator 1500 Volts (Distortion Factor)
Exciter Rotor 1500 Volts 601.4a L-L Harmonic Maximum - Single 3.0%
PMG Stator 1500 Volts 601.1c Deviation Factor 5.0%
401.1a Stator Resistance, Line to Line --- TIF (1960 Weightings) < 50
High Wye Connection 0.0012 Ohms --- THF (IEC, BS & NEMA Weightings) <2%
Rotor Resistance 1.25 Ohms 652.1a Shaft Current < 0.1 ma
Exciter Stator 22.1 Ohms
Exciter Rotor 0.066 Ohms --- Main Stator Capacitance to ground 0.15 mfd
PMG Stator 2.1 Ohms
410.1a No Load Exciter Field Amps 0.92 A DC
at 480 Volts Line to Line Additional Prototype Mil-Std Methods
420.1a Short Circuit Ratio 0.902 are Available on Request.
421.1a Xd Synchronous Reactance 1.594 pu -- Generator Frame 744
0.143 ohms -- Type MAGNAMAXDVR
422.1a X2 Negative Sequence React. 0.155 pu -- Insulation Class H
0.014 ohms -- Coupling - Single Bearing Flexible
423.1a X0 Zero Sequence Reactance 0.102 pu -- Amortisseur Windings Full
0.009 ohms -- Excitation Ext. Voltage Regulated, Brushless
425.1a X'd Transient Reactance 0.095 pu -- Voltage Regulator DVR2000E
0.009 ohms -- Voltage Regulation 0.25%
426.1a X''d Subtransient Reactance 0.072 pu
0.006 ohms
-- Xq Quadrature Synch. React. 1 pu -- Cooling Air Volume 3000 CFM
0.089 ohms
427.1a T'd Transient Short Circuit -- Heat rejection rate 5164 Btu's/min
Time Constant 0.215 sec.
428.1a T''d Subtransient Short Circuit -- Full load current 3097 amps
Time Constant 0.011 sec.
430.1a T'do Transient Open Circuit -- Minimum Input hp required 2883.1
Time Constant 2.75 sec. Efficiency at rated load : 95.8%
432.1a Ta Short Circuit Time
Constant of Armature Winding 0.031 sec. -- Full load torque 8409 Lb-ft

(3) Excitation support system or PMG required to sustain short circuit currents.
* Voltages refer to wye (star) connection, unless otherwise specified.
MARATHON ELECTRIC
GENERATORS
TYPICAL DYNAMIC CHARACTERISTICS
MODEL : 744RSL4058
BASE MODEL: 744RSL4058 Winding H-SG740066
Submittal Data: 480 Volts*, 2060 kW, 2575 kVA, 0.8 P.F., 1800 RPM, 60 Hz, 3 Phase
Recovery time /

Recovery time /
1 1
sec.

sec.
0 0
0 1000 2000 3000 0 1000 2000 3000

Load application Load rejection


30% 30%

% Voltage Rise
% Voltage Dip

20% 20%

10% 10%

0% 0%
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000
kW kW

Efficiency at rated voltage and frequency vs. load kW


.8 pf 1.0 pf
98.0%
97.0%
96.0%
95.0%
94.0%
93.0%
92.0%
91.0%
90.0%
0 500 1000 1500 2000 2500 3000
kW Output

Voltage dip with motor starting


Percent dip
40%
35%
30%
25%
20%
15%
10%
5%
0%
0 2000 4000 6000 8000 10000 12000 14000 16000
Locked rotor kVA