Lab 5 - Ring AC Distributor
Lab 5 - Ring AC Distributor
Islamabad
Power Distribution and Utilization
EXPERIMENT # 5:
An electric supply system consists of three principal components viz., the power station, the transmission
lines and the distribution system. Electric power distribution is the final stage in the delivery of electric
power; it carries electricity from the transmission system to individual consumers. At the utilization end,
the power is distributed to a large number of small and big consumers through a distribution network.
Distribution consists of two stages i–e primary distribution and secondary distribution. The secondary
distribution system consists of feeders, distributors and service mains. No consumer is given direct
connection from the feeders. Instead, the consumers are connected to the distributors through their service
mains.
1 Feeder
A feeder is a conductor which connects the sub-station (or localised generating station) to the area where
power is to be distributed. Generally, no tappings are taken from the feeder so that current in it remains
the same throughout. The main consideration in the design of a feeder is the current carrying capacity.
Distribution feeder circuits are the connections between the output terminals of a distribution substation
and the input terminals of primary circuits. The distribution feeder circuit conductors leave the substation
from a circuit breaker or circuit recloser via underground cables, called substation exit cables. The
underground cables connect to a nearby overhead primary circuit outside the substation. This eliminates
multiple circuits on the poles adjacent to the substations thereby improving the overall appearance of the
substation.
2 Distributor
A distributor is a conductor from which tappings are taken for supply to the consumers. In Fig. 4.1, AB,
BC, CD and DA are the distributors. The current through a distributor is not constant because tappings
are taken at various places along its length. While designing a distributor, voltage drop along its length is
the main consideration since the statutory limit of voltage variations is ± 6% of rated value at the
consumers’ terminals.
(b) The system is very reliable as each distributor is fed via *two feeders. In the event of fault on any
section of the feeder, the continuity of supply is maintained.
Figure 5.2: line diagram of ring main system for a.c. distribution
4 Case Study:
There are several ways of solving a.c. distribution problems. However, symbolic notation method has
been found to be most convenient for this purpose. In this case study three distributors A B and C are
connected to a feeder in ring main arrangement. Two Loads, each of 100W is used for testing.
Case-2 Case-2
Case -3 Case-3
Case-4 Case-4
Observations
Metering near distributor B Metering near distributor C
Voltage Current P.F Power Power Power Voltage Current P.F Power Power Power
(V) (A) (KVA (KVAr) (KW) (V) (A) (KVA) (KVAr) (KW)
)
Case-1 Case-1
Case-2 Case-2
Case -3 Case-3
Case-4 Case-4